You are on page 1of 5

Chapter C28

WIND LOADS ON BUILDINGS – MWFRS


(ENVELOPE PROCEDURE)

The Envelope Procedure is the former “low-rise each wind direction range. The end zone creates the
buildings” provision in Method 2 of ASCE 7-05 for required structural actions in the end frame or bracing.
MWFRS. The simplified method in this chapter is Note also that for all roof slopes, all eight load cases
derived from the MWFRS provisions of Method 1 in must be considered individually to determine the
ASCE 7-05 for simple diaphragm buildings up to 60 critical loading for a given structural assemblage or
ft in height. component thereof. Special attention should be given
to roof members, such as trusses, which meet the
definition of MWFRS but are not part of the lateral
resisting system. When such members span at least
PART 1: ENCLOSED AND PARTIALLY from the eave to the ridge or support members
ENCLOSED LOW-RISE BUILDINGS spanning at least from eave to ridge, they are not
required to be designed for the higher end zone loads
C28.3.1 Velocity Pressure Exposure Coefficient
under MWFRS. The interior zone loads should be
See commentary to Section C27.3.1.
applied. This is due to the enveloped nature of the
loads for roof members.
C28.3.2 Velocity Pressure To develop the appropriate “pseudo” values of
See commentary to Section C27.3.2. (GCpf), investigators at the University of Western
Loads on Main Wind-Force Resisting Systems: Ontario (Davenport et al. 1978) used an approach that
The pressure coefficients for MWFRS are basically consisted essentially of permitting the building model
separated into two categories: to rotate in the wind tunnel through a full 360° while
simultaneously monitoring the loading conditions on
1. Directional Procedure for buildings of all heights
each of the surfaces (Fig. C28.4-1). Both Exposures B
(Fig. 27.4-1) as specified in Chapter 27 for
and C were considered. Using influence coefficients
buildings meeting the requirements specified
for rigid frames, it was possible to spatially average
therein.
and time average the surface pressures to ascertain the
2. Envelope Procedure for low-rise buildings
maximum induced external force components to be
(Fig. 28.4-1) as specified in Chapter 28 for
resisted. More specifically, the following structural
buildings meeting the requirements specified
actions were evaluated:
therein.
1. Total uplift.
In generating these coefficients, two distinctly
2. Total horizontal shear.
different approaches were used. For the pressure
3. Bending moment at knees (two-hinged frame).
coefficients given in Fig. 27.4-1, the more traditional
4. Bending moment at knees (three-hinged frame).
approach was followed and the pressure coefficients
5. Bending moment at ridge (two-hinged frame).
reflect the actual loading on each surface of the
building as a function of wind direction, namely, The next step involved developing sets of
winds perpendicular or parallel to the ridge line. “pseudo” pressure coefficients to generate loading
For low-rise buildings, however, the values of conditions that would envelop the maximum induced
(GCpf) represent “pseudo” loading conditions that, force components to be resisted for all possible wind
when applied to the building, envelop the desired directions and exposures. Note, for example, that the
structural actions (bending moment, shear, thrust) wind azimuth producing the maximum bending
independent of wind direction. To capture all appro- moment at the knee would not necessarily produce the
priate structural actions, the building must be designed maximum total uplift. The maximum induced external
for all wind directions by considering in turn each force components determined for each of the preced-
corner of the building as the windward or reference ing five categories were used to develop the coeffi-
corner shown in the eight sketches of Fig. 28.4-1. At cients. The end result was a set of coefficients that
each corner, two load patterns are applied, one for represent fictitious loading conditions but that

557
CHAPTER C28 WIND LOADS ON BUILDINGS – MWFRS (ENVELOPE PROCEDURE)

FIGURE C28.4-1 Unsteady Wind Loads on Low Buildings for Given Wind Direction (After Ellingwood 1982).

conservatively envelop the maximum induced force on a low-rise building with a 4:12 pitched gable roof
components (bending moment, shear, and thrust) to be and the resulting wind-induced forces on its MWFRS.
resisted, independent of wind direction. Two different MWFRS were evaluated. One consisted
The original set of coefficients was generated for of shear walls and roof trusses at different spacings.
the framing of conventional pre-engineered buildings, The other had moment-resisting frames in one
that is, single-story moment-resisting frames in one of direction, positioned at the same spacings as the roof
the principal directions and bracing in the other trusses, and diagonal wind bracing in the other
principal direction. The approach was later extended direction. Wind tunnel tests were conducted for both
to single-story moment-resisting frames with interior Exposures B and C. The findings of this study showed
columns (Kavanagh et al. 1983). that the (GCpf) values of Fig. 28.4-1 provided satisfac-
Subsequent wind tunnel studies (Isyumov and tory estimates of the wind forces for both types of
Case 1995) have shown that the (GCpf) values of Fig. structural systems. This work confirms the validity
28.4-1 are also applicable to low-rise buildings with of Fig. 28.4-1, which reflects the combined action of
structural systems other than moment-resisting frames. wind pressures on different external surfaces of a
That work examined the instantaneous wind pressures building and thus takes advantage of spatial averaging.

558
MINIMUM DESIGN LOADS

In the original wind tunnel experiments, both B low buildings, the effect of the increased intensity of
and C exposure terrains were checked. In these early turbulence in rougher terrain (i.e., Exposure A or B
experiments, Exposure B did not include nearby vs. C) increases the local pressure coefficients.
buildings. In general, the force components, bending Beginning in ASCE 7-98 the effect of the increased
moments, and so forth were found comparable in turbulence intensity on the loads is treated with the
both exposures, although (GCpf) values associated truncated profile. Using this approach, the actual
with Exposure B terrain would be higher than that for building exposure is used and the profile truncation
Exposure C terrain because of reduced velocity corrects for the underestimate in the loads that would
pressure in Exposure B terrain. The (GCpf) values be obtained otherwise.
given in Figs. 28.4-1, 30.4-1, 30.4-2A, 30.4-2B, Figure 28.4-1 is most appropriate for low
30.4-2C, 30.4-3, 30.4-4, 30.4-5A, 30.4-5B, and 30.4-6 buildings with width greater than twice their height
are derived from wind tunnel studies modeled with and a mean roof height that does not exceed 33 ft
Exposure C terrain. However, they may also be used (10 m). The original database included low buildings
in other exposures when the velocity pressure repre- with width no greater than five times their eave
senting the appropriate exposure is used. height, and eave height did not exceed 33 ft (10 m).
In comprehensive wind tunnel studies conducted In the absence of more appropriate data, Fig. 28.4-1
by Ho at the University of Western Ontario (1992), it may also be used for buildings with mean roof
was determined that when low buildings (h < 60 ft) height that does not exceed the least horizontal
are embedded in suburban terrain (Exposure B, which dimension and is less than or equal to 60 ft (18 m).
included nearby buildings), the pressures in most Beyond these extended limits, Fig. 27.4-1 should
cases are lower than those currently used in existing be used.
standards and codes, although the values show a very All the research used to develop and refine the
large scatter because of high turbulence and many low-rise building method for MWFRS loads was done
variables. The results seem to indicate that some on gable-roofed buildings. In the absence of research
reduction in pressures for buildings located in on hip-roofed buildings, the committee has developed
Exposure B is justified. The Task Committee on Wind a rational method of applying Fig. 28.4-1 to hip roofs
Loads believes it is desirable to design buildings for based on its collective experience, intuition, and
the exposure conditions consistent with the exposure judgment. This suggested method is presented in
designations defined in the standard. In the case of Fig. C28.4-2.

Notes:
1. Adapt the loadings shown in Figure 28.4-1 for hip roofed buildings as shown above. For a given hip roof pitch use the roof coefficients from the Case A table
for both Load Case A and Load Case B.

2. The total horizontal shear shall not be less than that determined by neglecting the wind forces on roof surfaces.

FIGURE C28.4-2 Hip Roofed Low-Rise Buildings.

559
CHAPTER C28 WIND LOADS ON BUILDINGS – MWFRS (ENVELOPE PROCEDURE)

Research (Isyumov 1982 and Isyumov and Case of the wall. Horizontal roof pressures are the net sum
2000) indicated that the low-rise method alone of the windward and leeward pressures on vertical
underestimates the amount of torsion caused by wind projection of the roof. Vertical roof pressures are the
loads. In ASCE 7-02, Note 5 was added to Fig. 28.4-1 net sum of the external and internal pressures on the
to account for this torsional effect and has been horizontal projection of the roof.
carried forward through subsequent editions. The Note that for the MWFRS in a diaphragm
reduction in loading on only 50 percent of the building, the internal pressure cancels for loads on the
building results in a torsional load case without an walls and for the horizontal component of loads on
increase in the predicted base shear for the building. the roof. This is true because when wind forces are
The provision will have little or no effect on the transferred by horizontal diaphragms (e.g., floors and
design of MWFRS that have well-distributed resis- roofs) to the vertical elements of the MWFRS (e.g.,
tance. However, it will impact the design of systems shear walls, X-bracing, or moment frames), the
with centralized resistance, such as a single core in collection of wind forces from windward and leeward
the center of the building. An illustration of the intent sides of the building occurs in the horizontal dia-
of the note on two of the eight load patterns is shown phragms. Once transferred into the horizontal dia-
in Fig. 28.4-1. All eight patterns should be modified phragms by the vertically spanning wall systems, the
in this way as a separate set of load conditions in wind forces become a net horizontal wind force that is
addition to the eight basic patterns. delivered to the lateral force resisting elements of the
Internal pressure coefficients (GCpi) to be used for MWFRS. There should be no structural separations in
loads on MWFRS are given in Table 26.11-1. The the diaphragms. Additionally, there should be no girts
internal pressure load can be critical in one-story or other horizontal members that transmit significant
moment-resisting frames and in the top story of a wind loads directly to vertical frame members of the
building where the MWFRS consists of moment- MWFRS in the direction under consideration. The
resisting frames. Loading cases with positive and equal and opposite internal pressures on the walls
negative internal pressures should be considered. The cancel each other in the horizontal diaphragm. This
internal pressure load cancels out in the determination simplified approach of the Envelope Procedure
of total lateral load and base shear. The designer can combines the windward and leeward pressures into a
use judgment in the use of internal pressure loading net horizontal wind pressure, with the internal
for the MWFRS of high-rise buildings. pressures canceled. The user is cautioned to consider
the precise application of windward and leeward wall
C28.4.4 Minimum Design Wind Loading loads to members of the roof diaphragm where
This section specifies a minimum wind load to be openings may exist and where particular members,
applied horizontally on the entire vertical projection such as drag struts, are designed. The design of the
of the building as shown in Fig. C27.4-1. This load roof members of the MWFRS for vertical loads is
case is to be applied as a separate load case in influenced by internal pressures. The maximum uplift,
addition to the normal load cases specified in other which is controlled by Load Case B, is produced by a
portions of this chapter. positive internal pressure. At a roof slope of approxi-
mately 28° and above the windward roof pressure
becomes positive and a negative internal pressure
PART 2: ENCLOSED SIMPLE DIAPHRAGM used in Load Case 2 in the table may produce a
LOW-RISE BUILDINGS controlling case. From 25° to 45°, both positive and
negative internal pressure cases (Load Cases 1 and 2,
This simplified approach of the Envelope Procedure is respectively) must be checked for the roof.
for the relatively common low-rise (h ≤ 60 ft) For the designer to use this method for the design
regular-shaped, simple diaphragm building case (see of the MWFRS, the building must conform to all of
definitions for “simple diaphragm building” and the requirements listed in Section 26.8.2; otherwise
“regular-shaped building”) where pressures for the the Directional Procedure, Part 1 of the Envelope
roof and walls can be selected directly from a table. Procedure, or the Wind Tunnel Procedure must be
Figure 28.6-1 provides the design pressures for used. This method is based on Part 1 of the Envelope
MWFRS for the specified conditions. Values are Procedure, as shown in Fig. 28.4-1, for a specific
provided for enclosed buildings only ((GCpi) = ±0.18). group of buildings (simple diaphragm buildings).
Horizontal wall pressures are the net sum of the However, the torsional loading from Fig. 28.4-1 is
windward and leeward pressures on vertical projection deemed to be too complicated for a simplified

560
MINIMUM DESIGN LOADS

method. The last requirement in Section 28.6.2 be checked for the various separately acting (not
prevents the use of this method for buildings with simultaneous) component and cladding load cases.
lateral systems that are sensitive to torsional wind Main wind-force resisting roof members spanning
loading. at least from the eave to the ridge or supporting
Note 5 of Fig. 28.4-1 identifies several building members spanning at least from eave to ridge are not
types that are known to be insensitive to torsion and required to be designed for the higher end zone loads.
may therefore be designed using the provisions of The interior zone loads should be applied. This is
Section 28.6. Additionally, buildings whose lateral due to the enveloped nature of the loads for roof
resistance in each principal direction is provided by members.
two shear walls, braced frames, or moment frames
that are spaced apart a distance not less than 75
percent of the width of the building measured normal REFERENCES
to the orthogonal wind direction, and other building
types and element arrangements described in Section Davenport, A. G., Surry, D., and Stathopoulos, T.
27.6.1 or 27.6.2 are also insensitive to torsion. This (1978). Wind loads on low-rise buildings, Final
property could be demonstrated by designing the Report on Phase III, BLWT-SS4, University of
building using Part 1 of Chapter 28, Fig. 28.4-1, and Western Ontario, London, Ontario, Canada.
showing that the torsion load cases defined in Note 5 Davenport, A. G., Grimmond, C. S. B., Oke, T.
do not govern the design of any of the lateral resisting R., and Wieringa, J. (2000). “Estimating the
elements. Alternatively, it can be demonstrated within roughness of cities and sheltered country.” Preprint of
the context of Part 2 of Chapter 28 by defining torsion the 12th AMS Conference on Applied Climatology,
load cases based on the loads in Fig. 28.6-1 and 96–99.
reducing the pressures on one-half of the building by Ho, E. (1992). “Variability of low building wind
75 percent, as described in Fig. 28.4-1, Note 5. If lands.” Doctoral Dissertation, University of Western
none of the lateral elements are governed by these Ontario, London, Ontario, Canada.
torsion cases, then the building can be designed using Isyumov, N. (1983). “Wind induced torque on
Part 2 of Chapter 28; otherwise the building must be square and rectangular building shapes.” J. Wind
designed using Part 1 of Chapter 27 or Part 1 of Engrg. Industrial Aerodynamics, 13, 183–186.
Chapter 28. Isyumov, N., and Case, P. (1995). Evaluation
Values are tabulated for Exposure B at h = 30 ft, of structural wind loads for low-rise buildings
and Kzt = 1.0. Multiplying factors are provided for contained in ASCE standard 7-1995, University of
other exposures and heights. The following values Western Ontario, London, Ontario, Canada,
have been used in preparation of the figures: BLWT-SS17-1995.
Isyumov, N., and Case, P. C. (2000). “Wind-
h = 30 ft Exposure B Kz = 0.70
induced torsional loads and responses of buildings.”
Kd = 0.85 Kzt = 1.0
In Advanced technology in structural engineering,
(GCpi) = ± 0.18 (enclosed building)
P. E. Mohamad Elgaaly, ed., American Society of
Pressure coefficients are from Fig. 28.4-1. Civil Engineers, Reston, Va.
Wall elements resisting two or more simultaneous Isyumov, N., Mikitiuk, M., Case, P., Lythe, G.,
wind-induced structural actions (e.g., bending, uplift, and Welburn, A. (2003). “Predictions of wind loads
or shear) should be designed for the interaction of the and responses from simulated tropical storm
wind loads as part of the MWFRS. The horizontal passages,” Proceedings of the 11th International
loads in Fig. 28.6-1 are the sum of the windward and Conference on Wind Engineering, D. A. Smith and
leeward pressures and are therefore not applicable as C. W. Letchford, eds.
individual wall pressures for the interaction load Kavanagh, K. T., Surry, D., Stathopoulos, T., and
cases. Design wind pressures, ps for zones A and C, Davenport, A. G. (1983). “Wind loads on low-rise
should be multiplied by +0.85 for use on windward buildings.” University of Western Ontario, London,
walls and by –0.70 for use on leeward walls (the plus Ontario, Canada, Phase IV, BLWT-SS14.
sign signifies pressures acting toward the wall Krayer, W. R., and Marshall, R. D. (1992). “Gust
surface). For side walls, ps for zone C multiplied by factors applied to hurricane winds.” Bull. American
–0.65 should be used. These wall elements must also Meteorological Soc., 73, 613–617.

561

You might also like