Abstract - According to the project capacity requirement, and other layers can be designed according to international
the selection of system operating voltage level, the type of and national standards. The optical fiber unit will be put on the
insulation material and the highest operation temperature of suitable position. This article mainly introduces the design
cable, simulation analysis by the current capacity capacity methodology for a project with a scheme of two circuits of DC
finite element software, then get the conductor DC resistance 500kV composite submarine cables with total capacity 2GW
requirements, combined with the need of project laying and maximum operating temperature 70.
environment, get the design of the appropriate conductor and
structure and size finally. Reference to the maximum electric II. CONDUCTOR DESIGN OF DC SUBMARINE CABLE
field strength of the insulating material, design of the Cable conductor can be divided into 4 types, stranded
appropriate insulation layer thickness, make the insulation compacted shaped conductor (sector or tile), stranded
wire core Laplace field strength to meet the insulation compacted circular conductor, Milliken conductor and hollow
requirements, at the same time to ensure the insulation conductor [2]. Milliken conductor is usually made up of 4 or 5
temperature between inside and outside less than 20 at least. segments. Because of the compaction coefficient is normally
The material selection and thickness determination of the below 0.9, the water proof performance is not very good and
other process, must follow the rules of environmental this conductor is always applied to land cable. The hollow
requirements, international and domestic standards, the conductor is usually applied for self-contained oil-filled cable.
thickness is calculated by assuming diameter algorithm, and to For example, SZ stranding will result in large gap between
meet the customers’ needs add the optical fibers in the right wires and poor water-proof performance. Besides, the self-
location of the submarine cable, get the design of DC500kV locking construction is adverse to the production of flexible
large conductor section optical fiber composite DC submarine joint, which is not suitable for XLPE insulated submarine
cable finally. cable at present. For a 500kV large cross-section DC
submarine cable, only compacted circular conductor can be
Index Terms - HVDC; optical composite submarine cable;
abnormal shape wire; insulation thickness applied.
Based on the design conditions, the value of current rating
I. INTRODUCTION is 2000A. After combining the finite element analysis by
Because of the advantage of no limit in transmission simulation software and the national standard [3], the DC
capacity and distance and realizable interconnection between resistance of conductor at 20 is 0.009Ω/km. After analyzing
non-simultaneous networks [1], HVDC system can be widely two design mentality and six design schemes by theoretical
applied in long distance (crossing the sea) power transmission, calculation and CAD simulation, scheme e with a diameter
high-capacity electricity transmission and interconnection 52mm and cross-section 2000mm2 is finally selected. The
between regional networks. When DC submarine cable is detail design of conductor refers to Design and Optimization
integrated with optical fiber cable, the cost of separate of Large Cross-section Conductor in Submarine Cable [4].
installation of optical fiber cable will be saved. Besides, Please see the following table I.
communication, early warning and temperature monitoring TABLE I
which can guarantee submarine cable safe operation will also The Structure Design of Circular Compact Conductor with Abnormal
be realized. Due to the advantages of submarine composite Shape Copper Wire
cable, research and developing of this cable becomes a
tendency. After finite element analysis of current rating by Center Drums /NO. Radius/heig Cross- Width/heigh
TABLE II
Structure chart of DC500kV submarine optical composite cable DC-HYJQ41-F 500kV 1×2000mm2+12B1
2 tape
Semi-conductive polyester tape 1×0.2 /
TABLE III
Structure Chart of HOUC-2 LW 20G652D+4G651/0.3Submarine Optical Fiber Cable
Fiber No.
24
FIMT Thickness mm
0.2
FIMT O.D. mm
Structure& Parameter 2.4
mm
PE Sheath Thickness 1.5
mm
Cable O.D. Φ5.4
m
Minimum Bending Radius, installation 0.75
m
Nominal Specification Minimum Bending Radius, handling/coiling 0.50