Research and Design of DC500kV Optical Fiber

Composite Submarine Cable

Wenjie Mei, Wenlin Pan, Tao Chen, Guanghui Song, Jian Di


Department of Research and Development
Hengtong Submarine Power Cable Co., Ltd
Suzhou, Jiangsu Province, China
892897377@qq.com

Abstract - According to the project capacity requirement, and other layers can be designed according to international
the selection of system operating voltage level, the type of and national standards. The optical fiber unit will be put on the
insulation material and the highest operation temperature of suitable position. This article mainly introduces the design
cable, simulation analysis by the current capacity capacity methodology for a project with a scheme of two circuits of DC
finite element software, then get the conductor DC resistance 500kV composite submarine cables with total capacity 2GW
requirements, combined with the need of project laying and maximum operating temperature 70.
environment, get the design of the appropriate conductor and
structure and size finally. Reference to the maximum electric II. CONDUCTOR DESIGN OF DC SUBMARINE CABLE
field strength of the insulating material, design of the Cable conductor can be divided into 4 types, stranded
appropriate insulation layer thickness, make the insulation compacted shaped conductor (sector or tile), stranded
wire core Laplace field strength to meet the insulation compacted circular conductor, Milliken conductor and hollow
requirements, at the same time to ensure the insulation conductor [2]. Milliken conductor is usually made up of 4 or 5
temperature between inside and outside less than 20 at least. segments. Because of the compaction coefficient is normally
The material selection and thickness determination of the below 0.9, the water proof performance is not very good and
other process, must follow the rules of environmental this conductor is always applied to land cable. The hollow
requirements, international and domestic standards, the conductor is usually applied for self-contained oil-filled cable.
thickness is calculated by assuming diameter algorithm, and to For example, SZ stranding will result in large gap between
meet the customers’ needs add the optical fibers in the right wires and poor water-proof performance. Besides, the self-
location of the submarine cable, get the design of DC500kV locking construction is adverse to the production of flexible
large conductor section optical fiber composite DC submarine joint, which is not suitable for XLPE insulated submarine
cable finally. cable at present. For a 500kV large cross-section DC
submarine cable, only compacted circular conductor can be
Index Terms - HVDC; optical composite submarine cable;
abnormal shape wire; insulation thickness applied.
Based on the design conditions, the value of current rating
I. INTRODUCTION is 2000A. After combining the finite element analysis by
Because of the advantage of no limit in transmission simulation software and the national standard [3], the DC
capacity and distance and realizable interconnection between resistance of conductor at 20 is 0.009Ω/km. After analyzing
non-simultaneous networks [1], HVDC system can be widely two design mentality and six design schemes by theoretical
applied in long distance (crossing the sea) power transmission, calculation and CAD simulation, scheme e with a diameter
high-capacity electricity transmission and interconnection 52mm and cross-section 2000mm2 is finally selected. The
between regional networks. When DC submarine cable is detail design of conductor refers to Design and Optimization
integrated with optical fiber cable, the cost of separate of Large Cross-section Conductor in Submarine Cable [4].
installation of optical fiber cable will be saved. Besides, Please see the following table I.
communication, early warning and temperature monitoring TABLE I
which can guarantee submarine cable safe operation will also The Structure Design of Circular Compact Conductor with Abnormal
be realized. Due to the advantages of submarine composite Shape Copper Wire
cable, research and developing of this cable becomes a
tendency. After finite element analysis of current rating by Center Drums /NO. Radius/heig Cross- Width/heigh

simulation software based on the capacity, maximum


operating temperature, rated voltage and environment, the
parameters of conductor will be obtained. Then, the insulation
ht/mm sectional t
submarine cable is bended, twisted or suffered from other
area/mm2
Every layer Design mechanical damage during the laying and operating process,
insulation thickness should be more than 26mm. In
consideration of the accessories requirements, it is
1 1 2.6 21.23 — recommended that the thickness of insulation is 28mm.
Finally, the insulation thickness is derived after a series of
6 6 3.9 18.58 1.667 electrical, mechanical and aging test.

12 10 3.9 20.71 1.648


IV. DESIGN AND SELECTION OF METALLIC SHEATH AND
Copper rod
OUTER SHEATH
with 18 15 3.9 20.18 1.524
diameter
A. Theoretical basis of selection for metallic sheath and
5.2mm outer sheath
24 20 3.9 19.91 1.460
According to third part of TICW7.1~4-2012, lead sheath
30 24 3.9 20.57 1.479 is used as a metallic screen. Extruded outer sheath should be
applied on the lead sheath. There also should be a layer of
36 29 3.9 20.32 1.442
anti-corrosive material on the surface of lead sheath [7]. Type
E lead alloy is an inert material with good creep resistance,
III. DESIGN OF THE INSULATION FOR DC SUBMARINE CABLE high density, good radial water-proof and anti-corrosive
performance that is widely applied in domestic. Lead is also
A. Theoretical basis
the only material that shall be applied as the metallic sheath of
XLPE insulation thickness has a direct influence on the submarine cable, which is stipulated by national standard.
cable quality and service life. At present, the breakdown Bitumen, as an anti-corrosive layer should be coated on the
strength is the main factor affecting the selection of insulation surface of lead sheath by melt casting.
thickness. The thicker the insulation, the more nonuniformed All cables must have outer sheath because it can prevent
the electric field distribution. The thicker the insulation, the the armor from corrosion, abrasion and being locked during
lower the utilization factor. The thicker the insulation, the installation [8]. Thermoplastic compound (such as PVC, PE or
more easily the insulation breakdown. In addition, during the zero halogen material) or elastomer compound (such as
practical operation, the thicker the insulation, the bigger polychloroprene, chlorosulfonated polyethylene or similar
temperature difference it will cause between inside and polymer) can be applied as outer sheath according to specific
outside of insulation. Space charge will be induced and conditions. By comparing the properties of different polymers,
accumulated due to the large temperature difference, as a polyethylene is selected as outer sheath of this DC submarine
result, which cause partial distortion of electrical field and cable because the polyethylene material has a good water-
finally break the insulation. Also, the space charge will induce proof performance and no voltage will be induced on the
water-tree and electrical-tree which will break the insulation sheath. Based on the manufacturing technology, MDPE is
down after they grow up to a certain extent. The thinner the finally selected as the outer sheath.
insulation, the large laplace stress it will cause. When the large B. Design of semi-conductive water blocking tape
laplace stress exceeds the maximum allowable value of the
Semi-conductive water blocking tape is applied on the
insulation, the insulation will breakdown as well [5].
insulation screen, which is used not only to prevent the water
According to the GB/T 22078.2, the conductor screen which
penetration along the cable but also to prevent the core from
approximate thickness is 2.5mm consists of semi-conductive
being damaged by high temperature during the insulation
tape and extruding semi-conductive layer which approximate
extruding process. After overall consideration, two layers of
thickness is 2.0mm [6]. Considering the margin of current
semi-conductive water blocking tapes are applied to keep
rating for system, the value 2100A is appropriate. The
electrical touch between the insulation screen and metallic
maximum normal operating temperature is 70 for the screen. The size of water blocking tape is 0.5mm in thickness
conductor insulated by the material LS4258DCE from and 80mm in width. The overlap is not less than 15% of the
borealis. In the DC system, the maximum electric stress which width. After tested during practical manufacturing process, it
the insulation can withstand is 30kV/mm. The temperature can totally meet the requirements of water-proof and core
difference should not exceed 20 between inside and outside protection.
of the insulation according to the design experience. Based on
these parameters, the appropriate insulation thickness can be C. Calculation of metallic sheath thickness
calculated. The calculation of fictitious diameter D refers to the annex
B. The insulation thickness for DC submarine cable A [9] in standard GB/T 12706.3 and technical specification of
Through the theoretical calculation, the insulation National Cable Quality Supervision and Inspection Center
thickness of DC 500kV submarine cable is 26mm. However, [13]. The thickness of longitudinal water-proof layer can be
due to the large cross-section and great weight of conductor, neglected. However, the biggest cross-section area of
the stress and strain on the insulation will increase when the conductor which can be found in annex A is 1600mm2. For
conductor with cross-section area 2000mm2, the fictitious VI. DESIGN OF INNER BEDDING
diameter is 52mm.
Big crushing pressure will be caused on the optical fiber
The diameter over insulation core D and the nominal unit due to the steel wires when the cable is stretched. It is
thickness of lead sheath T1 can be calculated as follows: necessary to design a layer of Polypropylene yarn under the
steel wire armor as cushion. At the same time, to prevent the
D=dL+2ti+3.0 3-1 Polypropylene yarn embedded in the layer of optical fiber
T1=0.03D+1.1 3-2 unit, two layers of binder tapes are applied with 0.2mm in
where dL—fictitious diameter of conductormm thickness. The diameter of Polypropylene yarn is usually
2.0mm.
ti —nominal thickness of insulationmm
T1—thickness of lead sheathmm VII. DESIGN OF ARMOR AND OUTER SERVING
Set the value of dL=52.0mm and the diameter over A. Material and diameter of armor
insulation core can be obtained from the formula 3-1,
D=111mm. According to TICW 7.3-2012 and GB/T 3082, galvanized
Based on the above formula 3-2, the thickness of lead steel wires are applied as armor materials. Taking
sheath is 4.4mm after correction. consideration of necessary tensile strength during installation
D. Calculation of outer sheath thickness and manufacturing technology, a layer of galvanized steel
wires with diameter 6.0mm are selected as the armor of 500kV
The calculation of fictitious diameter D1 refers to the DC submarine cable, which is also the many years of
formula in annex A of standard GB/T 12706.3. manufacturing experience in submarine cable for Hengtong
D1  D  2 T1 Submarine Power Cable Co., Ltd.
(3-3) B. Material and diameter of outer serving
T2  0.03D1  0.6
During the transportation of submarine cable, the outer
where D1—fictitious diameter over lead sheathmm serving over the armor is used to protect it from damage.
T2—thickness of outer sheathmm According to TICW 7.3-2012, the outer serving of submarine
Based on the above formula 3-3, the thickness of outer cable is always a layer of fiber materials with approximate
sheath is 4.2mm after correction. thickness 4mm. In this design, two layers of polypropylene
V. DESIGN OF OPTICAL FIBER UNIT yarns which are applied on the steel wire armor, is used not
only to reduce the corrosive speed of the steel wire but also to
During the power transmission process, it is always protect the steel wire from damage. To keep the polypropylene
accompanied with the requirement of communication for yarns bonded together, bitumen with a thickness 0.5mm is
submarine cable. At present, because the power grid is not coated both on the steel wire and first layer of polypropylene
smart enough, it is possible that a massive power outage which yarn. The thickness of every layer of polypropylene yarn is
also last for a long time will occur if the fault location 2.0mm, which meets the requirement in TICW7.3-2012. At
couldnt be found in time. In this condition, the sensing last, we get the construction of 500kV DC submarine cable,
technology of optical fibers is required to locate the fault. which cross-sectional drawing is in Appendix-A.
With this technology, the integrated optical fiber unit can VIII. CONCLUSION
monitor the temperature around the position where it is and
Circular compacted conductor with shaped wires have
then deduce the conductor temperature by software. The
many advantages, such as high compaction coefficient, good
whole cable can be monitored all the time and it is reminded
water-proof performance and low requirement on frame type
to adjust the operational parameters of cable in time. As a
stranding machine. It is superior to the circular conductor with
result, the faults can be prevented and reduced. In conclusion,
circular wires on manufacture and design. The length of lay
an optical fiber composite submarine cable should be designed
has no effect on conductor with circular wires. However, the
not only to meet the requirement of communication, early
influence of length of lay on conductor with shaped wires
warning and temperature monitoring, but also saves the
need further research.
installation cost of communication cable.
The thickness of insulation in this design mainly takes
In this design, optical fiber cable is placed on the plastic
considerations of the breakdown level of material, technology
sheath. The type and number of optical fiber cable is selected
level of accessory and limit of materials. There are many other
according to customers requirements. Based on the
factors which can’t be considered at present and will be
production capacity of optical fiber cable manufacturer and researched during the production of flexible joint, voltage test
submarine cable manufacturer, optical fiber cable is placed and simulate operation after the cable is finished. In addition,
between PE tubes. The diameter of PE tube and optical fiber finite element can also be used to test whether this cable meets
cable is 6mm and 4.8mm respectively, which makes the the long-time operation requirement.
external force mainly act on the PE tube and prevents optical
fiber cable from damage. This DC 500kV, 2000mm2 submarine cable, where
circular compacted conductor with shaped wires firstly
applied, the calculation of insulation thickness and electrical
stress and the theoretical basis of remaining layer design can
be used for reference to other DC submarine cable with other
size.
ACKNOWLEDGMENT
Thank you for Hengtong Submarine Power Cable Co.,
Ltd give me a chance to do this work, and also thank you Mr
Pan’s help during I design the cable conductor. My colleague
also give me lots advises when I need them.
REFERENCES
[1] Chen zheng-zheng,Zhao Jiang-kang, Study on the Nanoparticle
modification of working temperature and breakdown characteristics for
insulation materials in DC cables[J],High Voltage Engineering ,2015, 41
41214-1227.
[2] Qiao Yue-chun, Li Jie-hao, Design of wire and cable structure[M] ,China
Electric Power Pressed2011:18-19.
[3] General Administration of quality supervision inspection and quarantine
of the people`s republic of China GB/T 3956-2008  Cable
conductor ,State Standard of the People's Republic of China,China
Electric Power Pressed,2009-11-01.
[4] Mei Wen-jie,Yang Hong-liang, Li Chun-mei, Design of Special-shaped
single wire circular compact condcutor for high-voltage DC undersea
cable [J]  Optical Fiber & Electric and Their Applications  2016
613-15.
[5] Zheng Xiao-quan,Xie An-sheng,Li Sheng-tao, Electrical branches
developed inside and outside the XLPE cable insulation[J]  ACTA
Physica sinica , 2007,569:5494-5501.
[6] General Administration of quality supervision inspection and quarantine
of the people`s republic of China ,.GB/T22078-2008  XLPE insulated
power cables of rated voltage 500kV (Um=550kV) and their
accessories ,State Standard of the People's Republic of China, China
Electric Power Pressed,2009-11-01.
[7] General Administration of quality supervision inspection and quarantine
of the people`s republic of China ,TICW7.1~4-2012,Technical
specification for extruded insulated power cable system for rated voltage,
rated voltage 500kV and below,2012-7-30.
[8] Qiao Yue-chun, Li Jie-hao, Design of wire and cable structure[M] ,China
Electric Power Pressed2011:39-42.
[9] General Administration of Quality Supervision and Quarantine of the
people  s Republic of China. GB/T12706.3-2008. Natioal Standard of
Peoples Republic of China. Beijing: China Standard press.2009-11-01.
Appendix-A

Fig.1 DC500kV submarine optical composite cable DC-HYJQ41-F 500kV 1×2000mm2+12B1

TABLE II
Structure chart of DC500kV submarine optical composite cable DC-HYJQ41-F 500kV 1×2000mm2+12B1

NO. structure Description thickness /mm Outside diameter /mm

1 Conductor Diameter of conductor Φ52.0 52.0±0.5

Semi-conductive banging water blocking tape 1×0.3 /


Semi-conductive blocking

2 tape
Semi-conductive polyester tape 1×0.2 /

Conductor screen Conductor screen 2.0 /

3 XLPE insulation XLPE Insulation 28.0 /

4 Insulation screen Insulation screen 1.5 116.0±1.5

5 Water blocking Semi-conductive water blocking 2×0.5 /

6 Lead alloy Lead alloy sheath 4.4 /

7 Over sheath PE outer sheath 4.2 136.2±2.5

8 Lap covering Non-woven fabrics 1×0.2

9 PE tube PE tube Φ6.0 /

10 Optical unit Fiber optic cable Φ4.8 /

11 Inner layer Non-woven fabrics and PP rope 2×0.2+Φ2.0

12 Metal armoring Galvanized wire Φ6.0 /

13 Outer layer PP rope 4.0 173.4±4.0


Appendix-B

Fig.2 HOUC-2 LW 20G652D+4G651/0.3Submarine Optical fiber cable

TABLE III
Structure Chart of HOUC-2 LW 20G652D+4G651/0.3Submarine Optical Fiber Cable

Items Physical Characteristics Unit Nominal Value

Fiber No.
24

FIMT Thickness mm
0.2

FIMT O.D. mm
Structure& Parameter 2.4

mm
PE Sheath Thickness 1.5

mm
Cable O.D. Φ5.4

Minimum Breaking Load,(UTS) N


300

Nominal Transient Tensile Load,NTTS N


210

Nominal Operating Tensile Load, NOTS N


100

Nominal Permanent Tensile Load,NPTS N


70

m
Minimum Bending Radius, installation 0.75

m
Nominal Specification Minimum Bending Radius, handling/coiling 0.50

Operating Temperature Range °C -10 to +40

Handling Temperature Range °C -15 to +45

Storage Temperature Range °C -30 to +60

Weight in air, approximately


kg/km 31.6
Weight
Weight in seawater, approximately
kg/km 8.2