France Paratonnerres
*Non-contractual pictures
General information about lightning
Formation of or the arrival of a storm cloud creates an electric field between the cloud and the ground. This
electric field increases up to values of 10 kV/m, thus initiating creation of corona discharges from irregularities
on the ground or from metal structures (projections).
Lightning between the cloud and the ground is composed of both downward leaders and upward leaders.
The negative downward leader (most frequent case), starts within the negative masses of the cloud.
This leader then propagates downward in a succession of intermittent steps (contrary to the positive leader
which travels without stepping) of about ten metres and with pauses of 40 à 100 µs between steps.
As the leader progresses, one can see numerous forks pointing downwards.
6
General information about lightning
When the electrostatic field is over the dielectric limits of the air (variable depending on humidity and atmos-
pheric pressure), a lightning discharge is produced and accompanied by a sound wave: thunder (produced
by the sudden dilatation of air over-heated by the electric arc).
The manufacture of lightning risk protection implicates assessing geographic and climatic conditions to deter-
mine the level of exposure to the structure which is to be protected.
• The keraunic level Nk : It expresses the mean annual value of the number of days with storms (days when
thunder can be heard in a specific place).
• Density of strike Ng : It indicates the mean value of the number of lightning strikes noted per year
and per km².
In France, the number of lightning strikes hitting the ground is about a million a year
Although the probability of being hit by lightning is about one in a million, damage caused by lightning per
year represents:
• 10 to 30 deaths
• 100 persons struck by lightning
• 20 000 animals hit by lightning
• 20 000 lightning accidents due to lightning, including 15 000 fires
• 50 000 electrical junction boxes destroyed
• 250 steeples destroyed
• 1 billion euros
7
General information about lightning
To reduce and to protect from these different effects (both direct and indirect), it is necessary to have a state-
of-the-art Installation for External Lightning Protection System (ELPS) and Interior Lightning Protection System
(ILPS), with particular care taken in earthing and interconnections with the conducting elements running along-
side the down conductors poles and the electric masses of the installation.
8
General information about lightning
Ng = Nk
10
At proximity of an
Type of situation Nk ≤ 25 Nk >25
installation of the first column
Building equipped with an air terminal Type 1 Type 1 Compulsory Not compulsory
Safety risk for people Not compulsory Type 1 or 2 Compulsory Not compulsory
Installing a protection system against overvoltages enables to reduce the probabilities of accidents causes by
constraints or overvoltages to an acceptable level, thus providing a safe environment for people or property.
When a surge protector device system is not compulsory, a Lightning Risk Analysis can be carried out to justify
its installation or not, if costs of material involved and its unavailability are vital to the installation.
9
General information about lightning
The map divides France into 5 areas. Each area is then divided into 3 different sites
Protected site : hollow area surrounded by hills and therefore protected from winds coming from all directions.
Normal site : wide plain or plateau with few differences in gradient with slopes below 10%.
Exposed site : near the sea: the coast in general (about 6 kms), tops of cliffs, islands or narrow peninsulas.
Inland : narrow valleys where the wind sweeps through; isolated or high mountains and certain mountain passes
Area Site Normal pressure (Pa) Extreme pressure (Pa) Normal speed (km/h) Extreme speed (km/h)
Exposed
10
General information about lightning
> Regulations
Lightning protection is a domain which is regulated by a large number of standards to which France Paratonnerres
adheres to when developing or marketing its many products.
This standard describes the set up regulations for the protection of structures and open zones against direct lightning
strikes by Early Streamer Emission (E.S.E.) Air Terminal.
It gives the rules relative to conception, manufacture, verification and maintenance of installations made using E.S.E.
Air Terminals.
This standard basically describes the E.S.E. Air Terminal product and gives test procedures to be carried out
This standard is applicable to all electrical installations with a power supply of below or equal to 1000V alternative
current and to 1500V continuous current.
This document lists the rules for design and creation of electrical installations which are to be applied to ensure
correct working conditions and safety.
Articles 443 and 534.1 describe more particularly protection measures against voltage and electromagnetic va-
riations.
- EN 61643-11 : Low voltage surge protector devices – surge protector devices connected to low voltage distri-
bution networks – Requirements and tests :
– Exigence et essais :
This standard describes the requirements and tests enabling characterisation of surge protector devices connected
to low voltage distribution networks.
This series of standards is a « product » standard describing the technical characteristics which the various compo-
nents for protection against lightning have to respect. The series is divided into 7 standardised volumes for different
products:
• IEC 62561-5/EN 50164-5 : Requirements for earth electrode inspection housings and earth electrode seals
11
General information about lightning
> Regulations
- EN 62305 : Protection against lightning :
This series of standards is divided into 4 volumes and first explains the general principles of lightning, then a gives
a method for the evaluation of risks. The third volume describes the rules for the installation of lightning protection
systems protecting people and buildings; the final volume proposes protection measures to reduce the risks of
network and communication failure:
This document is a guide offering a simplified method to analyse lightning risks. The method is inspired from the
full lightning risk analysis described in EN 62305-2. The method is described as being simplified because it only
contains a limited number of parameters compared to the full method. It is therefore only applicable for structures
where:
This document is a guide describing the rules for installing photovoltaic generators connected to the low voltage
public distribution network and not designed to work autonomously.
It also gives the rules for the installation of AC and DC surge protector devices providing protection for overcurrents
and overvoltages.
- UTE C 15-443 : Protection of low voltage electrical installations against overvoltages of atmospheric origin
or due to manoeuvres. Choice and installation of surge protector devices.
This practical guide indicates conditions relative to the choice and the implementation of surge protector devices in
low voltage installations. It details and completes articles 443 and 534.1 of standard NF C 15-100.
12
France Paratonnerres
13
France Paratonnerres
France Paratonnerres is a 100% French company, based in the Ester Technopole site in Limoges.
(1h by plane from Paris)
In 2014, France Paratonnerres has 40 years of research in laboratories and field experiences, of developpe-
ment and of production of high technology devices in lightning protection
Its equipments are installed in more than 70 countries in more than one thousand of sites, with a field expe-
rience of the most liability, thanks to its technologic choice.
Our company is registered and certified by Bureau Veritas, according to the ISO 9001 2008 Version.
Our procedures, our products and our staff are certified and authorized with respect to the requirements of
the QUALIFOUDRE certification (approved by the ministry)
14
France Paratonnerres
Our research and Development department is composed of a multidisciplinary team with Doctors in
electromagnetic compatibility, doctors in micro-electronic, electromechanic ingeniers, specialized technicians, issued
from CNRS research laboratory, and prestigious high school, with permanent know-how transfer for 40 years.
Our concept of sustainable quality assurance leans known a policy of reliability and refusal of the obsolescence
scheduled of the products. In this strategy, we associate our suppliers, our scientific and industrial partners in the
eco-conception of our systems, and the durability of our products.
We have in permanence, 4 experts involved in standardization in national, European and international com-
mittee.
They participate to all the lightning thematic works of the WG (Working Group), Workshop and Maintenance
Team (MT) and are present to a large majority of the meeting in lightning.
This expertise is available to help you for defining your strategic, statutory and economic orientations.
France Paratonnerres also participates regularly at various congress and lightning conference all over the
world.
15
France Paratonnerres
• the same interlocutor, trilingual with a pointed follow-up of your commercial and technical projects
• An answering time, lower than 24h for your consultation
• A deadline of load from 24 to 48 hours for all your orders
16
France Paratonnerres
Our services
France Paratonnerres / Our services
The IONEXPERT 3000® enables quickly and easily to determine the Protection Level required, in order to protect
efficiently, and according the standard a site.
Moreover, this software gives a Quick Technical Study of the site and quick view of the protection radius of the air
terminals.
18
France Paratonnerres / Our services
A version of this tool can be obtained online from the company by simple request.
http://www.france-paratonnerres.com
• Geographical situation
• Location factor
• Dimensions
• Specific danger
• Fire risk
To know if, when an external and internal lightning protection system is present, (according to the four levels of pro-
tection available), the building is or is not protected. The software programme identifies the level of risk depending
on the characteristics of the building and compares it to a tolerated risk level.
Once the protection level has been chosen the Design Office will establish a technical study with the type of protec-
tion to be installed.
France Paratonnerres certified Qualifoudre by INERIS, is committed to carrying out studies in conformity to stan-
dard NF IEC/EN 62305-2.
Our Design Office is qualified for all types of Lightning Risk Analysis (LRA) and Technical Studies (TS).
The Design Office can manage both :
• Analyses considered complex as described in standard EN 62305-2 or NF C 17-102.
• Simpler analyses as in the practical guide NF C 17-108.
Lightning Risk Analysis cannot be prescribed and does not quantify the materials implemented for proposed solu-
tions. These elements are defined by the technical study depending on the protection measures chosen.
Complex Lightning Risk Analysis is managed according to the risk evaluation method as described in standard
EN 62305-2 and in accordance to the Annex A of the NFC 17-102 Standard Edition 2011.
Risk evaluation enables the selection of values in consideration of elements in the building which needs protecting.
These values will be included in the calculations to find the best level of protection to implement.
19
France Paratonnerres / Our services
The Lightning
Phenomenon Installers
Standards regarding
MODULE 1 Protection against Lightning Protection
Distributors None
(1 day) Lightning
Establishing protection
Architects
Demonstration on site
Effects of lightning
Standards Engineers
and Regulations
Lightning Technicians
Lightning Risk Analysis Electrotechnical and
MODULE 2 Analysis and Detailed
protection set up Building & Public Works
(2 days) knowledge
Case studies Maintenance engineers
Protection systems
Installers
Setting up protection
20
France Paratonnerres / Our services
In France, the law decree of October 11th, 1983 forbids the use of radioactive elements
in lightning protection
> Installations
Our teams are qualified to intervene on all types of site, from simple to complex cases classified environmentally
protected sites (I.C.P.E.), in accordance with our Qualifoudre approval delivered by INERIS.
France Paratonnerres can also use the services of partners who are qualified to work on electrical installations,
drive aerial work platforms, drill bore-holes, carry out levelling work and so on in order to complete certain instal-
lations.
A certificate of conformity to standards can be remitted after work has been carried out.
21
France Paratonnerres / Our services
France Paratonnerres ensures maintenance and bringing installations into compliance in accordance to standards :
• The state and the quality of fixing elements of down conductors, from air terminal systems to earthing
• Conformity of surge protection devices (state, section…)
• Electrical continuity of such devices, where they are placed and how they are routed, notably those with
electrical interconnections.
• The conformity to regulations and the distance of security required.
• Resistance values of earthing terminals.
• All equipotentiality connections
• Existence, state and conformity of the surge protector device installation.
22
France Paratonnerres / Our services
23
France Paratonnerres / Our services
24
France Paratonnerres / Our services
■ Pylon
25
France Paratonnerres / Our services
26
Early Streamer
Emision Air-Terminal
The IONIFLASH MACH®
technology
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
A complete and well scaled range from 15 to 60 µs of Early Streamer Emission times,
in order to answer in the most adapted way to each needs
Mach NG60
Mach NG45
Mach NG30
Mach NG25
Mach NG15
Mach NG15 Mach NG25 Mach NG30 Mach NG45 Mach NG60
A high level of early streamer emission time Δt 55 µs 78 µs 87 µs 114 µs 135 µs
28
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
This is when the corona discharge effect takes place, changing suddenly from a position at the tip to an
upward leader.
These positive upward leaders suddenly move in the direction of the downward leader. One of the leaders, the
closest or the one which has started earlier or the one which has travelled the faster, enters into contact with
the downward leader. Then, the ionised air channel is in connection with both the ground and the cloud, and
the return stroke can take place, engendering a high lightning current of many kA.
The air terminal IONIFLASH MACH® is a device for lightning protection with a spherical metal part fixed to the
top. This sphere is insulated from the rod by a ring made from a material with very high electrical insulation
properties.
When a storm comes, the external electrode (sphere) charges under the influence of the electric field until the
potential reaches a critical value from which a spark appears between the exterior electrode and the tip of the
central electrode. The tip enables plasma to be created close by the tip.
The plasma, in association with the intense electric field created close by the tip, constitutes the first stage of
development of an upward leader.
The spark produced at the top of the IONIFLASH MACH® air terminal will initiate the advance of the discharge,
engendering an upward leader moving in the direction of the downward leader.
29
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
A complete sequence of tests is defined in order to confront the IONIFLASH MACH® to the whole parameters
it will meet in natural condition
Marking tests
Efficiency measurements
In addition, the materials used to make IONIFLASH MACH® have been selected for their resistance to both
corrosion and very high temperatures.
The IONIFLASH MACH® ESE air-terminals have passed the complete sequence of tests of the NFC 17-102
standard (2011). Some tests have been realized in a more severe way than required in order to warranty the
most important liability to our products.
Moreover, the good insulation of the IONIFLASH MACH® has been tested in rain condition with respect to the
IEC 60060-1 standard.
30
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
• Mechanical tests
The continuous axis of the ESE IONIFLASH MACH® through which
the lightning current passes, presents a minimal section of 200 mm ²
according to the requirements of this tests.
• Environmental tests
The IONIFLASH MACH® have passed the environmental tests:
- Salt mist treatment with a severity of level 2 according to the
EN 60068-2-52.
- Humid sulphurous treatment with a 7 cycles sequence according to the
EN ISO 6988.
The pollution generated by the test sequence is superficial and doesn’t disturb the functioning
of the IONIFLASH MACH®.
• Electrical tests
The IONIFLASH MACH®, range has been tested in lightning attachment impact with a 10/350 µs waveform
at 100 kA and passes the test requirements.
• Efficiency tests
Le ESE IONIFLASH MACH® is design to reduce the average statistical time
associated with the initiating of the upward streamer. This ESE presents
an advanced time in comparison with a simple reference rod (PTS) tested
in the same conditions. This gain is evaluated in high voltage labora-
tory
31
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
Mach NG15 Mach NG25 Mach NG30 Mach NG45 Mach NG60
Average reference time of
252 252 186 186 199
breakdown <T’PTS> (µs)
Average reference time of
Results on the 222 213 150 138 140
breakdown <T’PDA> (µs)
experimental
<T’PTS> - <T’PDA> 30 39 34 46 59
waveform
in laboratory Standard deviation PTS (µs) 40 40 43 43 62
<T’PTS> (µs)
Standard deviation σPDA (µs) 31 25 32 19 18
σPDA
k= 0.61 0.76 0,74 0,44 0,29
σPTS
During efficiency test, in different high voltage laboratories, the IONIFLASH MACH® air-terminal have obtai-
ned excellent breakdown time <T’> with very low standard deviation in comparison with the simple reference
rod.
The IONIFLASH MACH® ESE are very well insulated and their working
isn’t disturb by the rain pollution.
Tests have been performed according to IEC 60060-1 standard protocol. The insulation is greater
than 97 %.
32
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
Thus, the protection of our IONIFLASH MACH®, for a surface to be protected, depends on the lightning level of
protection determined by the lightning risk evaluation (EN 62305-2), on the height of the tip of the air terminal
and on the early streamer emission time (∆T)
• The IONIFLASH MACH® has been tested strictly in respect of the procedures defined in the NFC 17-102 in :
- AMPERE CNRS (National Scientific Research Center) Laboratory in LYON (France)
- Laboratoire de Génie Electrique in PAU (under bailiff’s control)
- SHANGHAÏ JIAO TONG Laboratroy (China)
- Laboratoire CPRI Bangalore (India)
- GERAC Laboratory of LIMOGES (France)
- LCIE Central Laboratory of FONTENAY UAX ROSES (France)
• TESTED IN COMPLIANCE WITH STANDARDS NFC 17-102 2nd edition September 2011, UNE 21186 Annex C,
EN 50164, EN62305 and NP4426
In situ test FT / Puy Beaubier Site – Alt. 879m – June 1987 to June 1988
Hertzian pylon of 70m installed on very impacted site.
The IONIFLASH IF1 and a simple rod were installed at both side of the
pylon at the same high.
The results were several impacts on the IONIFLASH and none on the Simple rod.
33
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
Rp(5)
Rp (h) = h x for 2 ≤ h ≤ 5m (2)
5
r (m)
- 20m for protection level I
- 30m for protection level II
- 45m for protection level III
- 60m for protection level IV
∆(m) = ∆T x 106
The experience shows that ∆ efficiency is obtained during the evaluation tests of the E.S.E. air-terminal.
34
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
%
Tip height in meters security
2 3 4 5 6 10 15 20 30 45 60
MODELS
IONIFLASH MACH NG 15 73% 13 19 25 32 32 34 35 35 34 24
MODELS
IONIFLASH MACH NG 15 73% 15 22 30 37 38 40 42 44 45 42 34
MODELS
IONIFLASH MACH NG 15 73% 18 27 36 45 46 49 52 55 58 60 58
MODELS
IONIFLASH MACH NG 15 73% 20 31 41 51 52 56 60 63 69 73 75
IONIFLASH MACH NG 60 56% 43 64 85 107 107 109 111 113 116 119 120
35
Early Streamer Emission Air Terminals / IONIFLASH MACH® Technology
For most of the case, the angle of protection method is suited. The angle of protection is constant for heights
h lower than 2 m
In comparison with the IONIFLASH MACH ESE, the table below indicates the protection radius (Rp), versus the
height of the simple air-terminal and gives the protected volume.
3 7 7 10 13
4 8 9 13 15
5 8 10 13 16
6 9 11 14 17
8 10 12 16 19
10 10 14 18 21
20 8 15 22 27
30 12 23 30
45 19 31
60 25
36
Our Products
for the direct lightning
Protection
Our products / Protection against direct effects of lightning
38
Our products / Protection against direct effects of lightning
Emission Time
Ref Description Material Weight
measured weighted
90160 MACH NG 60 Stainless steel 316 L 135 µs 60 2,2 kg
90145 MACH NG 45 Stainless steel 316 L 114 µs 45 2,1 kg
90130 MACH NG 30 Stainless steel 316 L 87 µs 30 2 kg
90325 MACH NG 25 Stainless steel 316 L 78 µs 25 1,9 kg
90315 MACH NG 15 Stainless steel 316 L 55 µs 15 1,8 kg
39
Our products / Protection against direct effects of lightning
Height : 2 m
[ Very early streamer emission of the leader. Emission at the right time
Advanced Time
Ref Designation Material Weight
Measured Weighted
90316 MACH NG 15 S/s copper bonded 316 L 55 µs 15 1,8 kg
90131 MACH NG 30 S/s copper bonded 316 L 87 µs 30 2 kg
41
Our products / Protection against direct effects of lightning
• 17001/17002
Ref. 17001
300
Ø 18
Ø M10 prof. : 25 mm
• 10013/10014/10017
Ref. 10013/10014
Ref. 10017
Ref 30002
Fastening Parallel
Counter 2-999999
Function mode Electromechanic
Range of detection 1 kA - 100 kA (8/20 µs)
Size 52 x 50x 30 mm
Weight 100 g
Protection index IP66
Operation
Placed directly on the lightning conductor, this meter uses fields shone by the current
of lightning to activate an electromechanic meter.
Connection
This counter is installed just in contact of the lightning conductor (round Ø 8
to 10mm, flat 30x2 or 30x3mm) above the inspection joint, and at 2 meters
behind the ground (NF C 17-102).
Fastening
The fastening is made on the counter with the stamped stainless steel plate
Thanks to its light weight, the product can simply be supported be the lightning
conductor.
43
Our products / Protection against direct effects of lightning
Ref 30001
Fastening system Parrallel
Counter 0-999999
Function mode Electronic
Detection range 1 kA - 100 kA
Dimensions 65 x 50 x 45 mm
Weight 140 g
44
Our products / Protection against direct effects of lightning
This lightning counter impact enables to count and registered the Platinum of fixation
lightning events captured by the Lightning Protection System.
The 30003 counter enables to know exactly the date and time of
the lightning events. It can keep in memory the last 500 impacts.
Those informations can be very usefull to realize the maintenance
and verification of the Lightning Protection System after an impact
Its fucntionning has been validated in laboratory.
It is able to register all events from 1kA to 100 kA, as well for positive
and negative lightning strokes.
Conductor
counter
Ref 30 003
Fastening system Parallel
Memory Until 500 events
Function mode Electronic
Detection range 1 kA (8/20µs) / 100 kA (10/350µs)
Dimensions 100 x 100 x 75 mm
Weight 0.6 kg
Protection Index IK08 IP66/67
45
Our products / Protection against direct effects of lightning
[ In order to receive the 1st extended mast collar, the pole is drilled.
Ø 38
Ø 30
10
Ø M6
Ø 25
Diameter Ø 8,5
Ref Material Length Weight
Inside / outside Ø 30
46
Our products / Protection against direct effects of lightning
Ø 38
Ø 30
10
Ø M6
3400
Ø 25
Ø 30
Ref Material Length Diameter inside Weight
Ø 8,5 ■
11047 S/s 304 L 4m 25 mm 10 kg
The Extension
Transition piece between Air Terminal and the pole (Ref11042 to 11048).
[ Ideal for fastening of the connection collar for conductors
(Ref. 15301) Equipped of a threaded system and of a security screw.
2 plats
200
Ø 33,7 (Ref. 11037)
Ø 42,4 (Ref. 11039)
Ø 48,3 (Ref. 11041)
2000
IONIFLASH MACH
ESE
Pole
Ref. 11042
Ref. 11043
Ref. 11044
Ref. 11045
Collar for
extended mast
Ref. 90005
maximal height : 7,40 m
1st mast
Ref. 11037
Collar for
extended mast
Ref. 90045
2nd mast
Ref. 11039
Collar for
extended mast
Ref. 90046
3rd mast
Ref. 11041
49
Our products / Protection against direct effects of lightning
[ The 17013 reference is the ideal solution for fixing the capture
point on metallic structure
4 x Ø M8
Ø M10
Cheville
Ø 17
Ø M10
4 x Ø M8
50
Our products / Protection against direct effects of lightning
300
8
28 2 x Ø M10 x 60
55
35
■ Universal clamp
Universal clamp for fixing air terminal brackets on all types of
elements.
56
65
49
Ø 14,5
2 x Ø M12
112
51
Our products / Protection against direct effects of lightning
110
8 55
28
200 (Ref.12012/12013)
300 (Ref.12022/12023)
263 (Ref.12012/12013)
363 (Ref.12022/12023)
2 x Ø 11,5
2 x Ø M10 x 60
Ref Material Profil shift Height of support Packaging Weight 35
130
12012 Galvanized Steel 200 mm <4m 2 2,58 kg 170
110 110
55 55
8
28 28
260 (Ref.12014/12015)
350 (Ref.12020/12021)
52
Our products / Protection against direct effects of lightning
55
8
28
110
2 x Ø M10 x 60
Ref Material Profil shift Height of support Packaging Weight
35
12016 Galvanized Steel 150 mm <4m 2 2,50 kg
12028 Galvanized Steel 150 mm <8m 3 3,75 kg
■ Lateral clamp
These lateral clamps are used to fix air terminals to flat elements.
28
55
110
110
2 x Ø M10 x 60
Ref Material Profil shift Height of support Packaging Weight
35
53
Our products / Protection against direct effects of lightning
• 12017
available on request
Air-terminal
Ref Designation Material Footing Weight
maximum height
Bolted
12017 Galvanized 0,75 m 8 2,58 kg
Tripod
■ Screwing clamp
Fixing brackets for air terminals directly into masonry.
55
8
28
220
320
110
2 x Ø M10 x 60
35
54
Our products / Protection against direct effects of lightning
[ The tile must be installed with the cone, delivered with a cone. (réf. 12114)
Ø 63
Ø 35
300
Ø 40
Ø 45
120
400
125
125
■ Anchor bolt
These anchor bolts are used to fix Air Terminals directly on wood
frames.
Ø 24,8 Ø 14,9
425 (Ref.90079)
1410 (Ref.90080)
55
Our products / Protection against direct effects of lightning
■ Aluminum
Aluminum strips for use as down-conductors for earthing of Air
Terminals.
56
Our products / Protection against direct effects of lightning
■ Flat Steel
Steel strips for use as down-conductors for earthing of Air
terminals.
Galvanized
13010 30 mm 3,5 mm 30 m roll 0,833 kg /m
Steel
57
Our products / Protection against direct effects of lightning
■ Stranded copper
Copper cable for use as an earthing conductor.
58
Our products / Protection against direct effects of lightning
[These clamps are fixed with special masonry lead peg (ref.14004)
(See accessories)
Ref A B
B
14001 31 36,5
14003 31 56
14005 3 35
25 2,5
Ref Designation Material Length Weight To use with
14001 Clamp 30 Galvanized Steel 30 mm 25 g Plate 30 x 2 mm2
Ø8
14003 Clamp 50 Galvanized Steel 50 mm 17 g Plate 30 x 2 mm2
57
59
Our products / Protection against direct effects of lightning
ØM5
65 65
100
200
ep.0,80
12
60
Our products / Protection against direct effects of lightning
Ø7
19
Ref. 14000
30
200
14034 Fastening strap Copper 100 mm 54 g Plate or round conductor ep : 2
Tinplated
14000 Rein for slate 200 mm 58 g Plate conductor
copper
■ Straps ride
For fixing flat conductors. Protects the conductor against damage
170
45
Ref. 14009
12
0
2xØ4
Ref Designation Matière Dimensions Poids A utiliser avec
0
14010 Ruberalu Ruberalu 170 x 45 mm 35 g Rivets
0
Stainless
14015 S/s 304 L 35 x 10 mm 3g 14012 or 14013
Steel clip
62
Our products / Protection against direct effects of lightning
65
9
ØM5
Ø 12
Ø4
Ø5
65
Ref Designation Material Dimensions Weight
14031 Stainless steel clip Stainless Steel 20 x 22 x 35 mm 25 g
■ Swivel orientable
Fasteners which can be swivelled for any type of conductor on roof
frames.
2xØM5
2
2xØM5
63
Our products / Protection against direct effects of lightning
■ Stands off
Fixing flat or round conductors on flat waterproof roofs.
64
Our products / Protection against direct effects of lightning
4 x Ø M5
65
Our products / Protection against direct effects of lightning
Connection Flat/Round :
to assemble a flat conductor to a round conductor.
Connection Round/Round :
to assemble two round conductors
4xØM8
Ref. 15103/15104
4xØM8
66
Our products / Protection against direct effects of lightning
Connection Flat/Round :
to assemble a flat conductor to a round conductor.
Connection Round/Round :
to assemble two round conductors
4xØM8
4xØM8
67
Our products / Protection against direct effects of lightning
68
Our products / Protection against direct effects of lightning
55
Ref. 15301 Ref. 15303 Ref. 15305
4xØM8
Ref. 15302/15306
• 15302/15306
69
Our products / Protection against direct effects of lightning
2xØM6 ØM7
For tightening
of the conductor
For fixing
on the building
■ Protection sheath
Mechanical protection of flat or round conductors for down-conductors
Supplied with 3 fixation collars in stainless steel
40
200
ep : 2
70
Our products / Protection against direct effects of lightning
■ Earth connectors
Connector for several earthing conductors, for “crow-foot“
branched earth .Only for plate conductors.
■ Signaling plate
Signalling plate indicating presence of Air Terminal earthing.
(Supplied with ankles and screw)
71
Our products / Protection against direct effects of lightning
16106 2000
16108 Earth rod Stainless Steel 16 mm 1m 1,4 kg
■ Coupling sleeve
Coupling sleeve to join two earth rods
Driving tip to insert rod without damaging it
Ø 20
Ø 16,5
72
Our products / Protection against direct effects of lightning
ØM8
Ref. 16126
Ref. 16121 Ref. 16126 Ø M10 x 20
40,5
26
16121 Round collar Brass 40 x 22 mm Round conductor 76 g
0
20 31,5
16126 Round collar 2 Brass 40 x 22 mm Plate conductor 120 g 42
4xØM8
Ref. 16125
73
Our products / Protection against direct effects of lightning
■ Enhancing compound
TERRAGONIX ADVANTAGES :
- Permanent contact with the earth conductor
➢ - Expansion of granules all around the conductor
➢ - No alteration of earth resistance value. The water streaming
won’t damage the earth system
➢ - Great stability of the earth value
74
Our products / Protection against direct effects of lightning
■ Equipotentiality bars
Earthing interconnections.
Allows deconnection for separate earthing measurements.
Ref. 16143
• 16143/16144
55
8xØ8 5
Ref. 16144
• 80020
55
5
12 x Ø 8
Ref. 80020
2 x Ø M6
75
Our products / Protection against direct effects of lightning
• 23503/20002
Nominal Maximal
Nominal
Ref Name discharge discharge Weight
voltage
current current
Equipotentiality
23503 350 V 10 kA 25 kA 410 g
spark gap
76
Our Products
for the indirect lightning
Protection
Our Products for the indirect lightning protection
■ Monobloc SPD – 25 kA
High impulsed current: 25 kA.
Direct and indirect protection of 1 and 3-phase power supply network
installations for areas with high risk of lightning strikes
(high keraunic level).
Equipped with a remote and optical fault indicator contact.
78
Our Products for the indirect lightning protection
79
Our Products for the indirect lightning protection
80
Our Products for the indirect lightning protection
■ Multipolar SPD – 40 kA
Discharge currents of 40 kA.
Primary protection (in common and differential mode) of 1 or
3-phase power supply network installations situated in exposed
areas (high keraunic level) or as a complement to type 1 SPD.
Equipped with a remote and optical fault indicator contact.
81
Our Products for the indirect lightning protection
■ Multipolar SPD – 15 kA
Discharge currents of 15 kA.
Primary protection of 1-phase power supply installations situated
in exposed areas (high keraunic level) or as a complement to type 1 SPD.
Equipped with a remote and optical fault indicator contact.
82
Our Products for the indirect lightning protection
Max
Nominal Level of
Max discharge
Module discharge protection Replacement
Ref voltage current
Network current In Up under In plug
Uc Imax
(L-N-N-PE) (L-N-N-PE)
(L-N-N-PE)
23301 4 3* L + N diff 335 VAC 10/40 kA 5/20 kA 1,1/1,2 kV 23303 (Phase)
Max Nominal
Level of protection Replacement
Ref Application discharge discharge
Up under In plug
current Imp current In
23401 RTC/ADSL 185 VDC 10 kA 5 kA Non
removable
23402 Numéris 7 VDC 10 kA 5 kA
23414 RTC/ADSL 185 VDC 10 kA 5 kA 20403
23415 Numéris +-7 VDC 10 kA 5 kA 23404
83
Our Products for the indirect lightning protection
■ Multipolar class II – 40 kA
Maximum impulsed current: 40 kA.
Direct and indirect protection of photovoltaic and wind generator
installations situated in high risk areas of lightning strikes.
(high keraunic level).
Equipped with a remote and optical fault indicator contact.
84
Our Products for the indirect lightning protection
Nominal
Max
Max dis- Level of
discharge
Ref Application voltage charge protection Weight
current
Uc current Up under In
Imax
In
Indirect earthing
23503 of separate 350 V 100 kA 10 kA 25 kA 410 g
system
Indirect
20002 connection of 200 VDC 25 kA 120 g
roof support
■ Coordination coil – 15 µH
Coordination coils, to make the coordination between 2 consecutive
Surge Protection Devices when the length of conduction is very
high.
85
Our Products for the indirect lightning protection
Ref
Please consult us
Various models available
Please consult us
■ Circuit Breakers
Ref
Please consult us
Various models available
Please consult us
86
Our Products for the indirect lightning protection
No
Keraunic Level
No Air-terminal presence ?
Nk>25 ?
SPD non mandatory at the
begining of the installation
Yes
Yes
LV supply network
No Connect a Class II SPD at the origin of the installation
Globally burried ?
Network Pole number Surge Protective Device
2 (Mono) 23 206 23 212 23 106
Yes TT - TN
3 (Tri) 23 205 23 216
(Uc = 335 V)
4 (Tri + N) 23 204 23 218
SPD non mandatory at the 2 (Mono) 23 203
begining of the installation IT
3 (Tri) 23 202
(Uc = 440 V)
4 (Tri + N) 23 201
87
Our Products for the indirect lightning protection
L1
L2 3 Phase + neutral
L3
N
d1
d2
Circuit breaker
SPD
d3
Earthing
d1 + d2 +d3 < 50 cm
88
Testing apparatus
and Accessories
Testing apparatus and accessories
Auto-
Ref Power supply Dimensions Weight
nomy
■ Geiger counter
Light and easy to use, this Geiger counter detects radioactive air
terminals over several metres as well as any other radioactive
element.
Measure of Beta particles, X and Gamma rays.
- Technical characteristics:
Range of measure: de 5 à 999 Rem/h ou de 0,05 à 9,99 Sv/h
Bêta rays : 350 keV à 1,5 MeV
Gamma rays : 0,1 à 1,25 MeV
Power supply: 2x1,5 V batteries (LR03 included)
X rays
90 g
30041 Geiger counter Gamma rays 150 x 60 mm
(without batteries)
Bêta particles
90
Testing apparatus and accessories
When the risk level is overpass, the storm alert is signalized with
a contact, a beep and a fast blinking.
91
Testing apparatus and accessories
By its design, its use allows to carry out reliable tests of functioning
in total security.
*This high voltage test bench allows to control and to guarantee the well
functioning of the IONIFLASH MACH® NG with the following
checkings:
[ Insulation Test (Ω) : Check the well insulation of the different parts
of the ESE air terminal.
[ High Voltage test (HV): Check the well functioning of the early
streamer emission internal device of the air terminal under
high voltage (200 000 Volts).
92
Testing apparatus and accessories
> Accessories
■ Hooping buckles
Fixing Air Terminals with hooping buckles especially for chimneys.
■ Hooping buckles
Fixing Air Terminals with hooping buckles.
93
Testing apparatus and accessories
> Accessories
■ Hoop mounting device
Hoop mounting device
■ Aluminothermic welding
The aluminothermic welding system Calweld® Multi, is simple and
adaptable to ensure earthing circuit connections
Please consult us
94
Testing apparatus and accessories
> Accessories
■ Bolt
Zinc coated steel bolt with antimony lead expansion peg
95
Testing apparatus and accessories
> Accessories
■ Roof ornements
Different sized rooster ornaments to fix on steeples
• 18101/18102/18105/18106/18108
■ Sheath
Sheath with ball bearing on bronze pebble.
• 18020
Ref. 18020
96
Certifications and References
97
Certifications and References
MàJ 09/06/2011
ATTESTATION DE CONFORMITE
EN CONFORMITÉ AVEC LES NORMES :
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
d’isolement en conditions de pluie : > 97 %.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
d’isolement en conditions de pluie : > 97 %.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
EN CONFORMITÉ AVEC LES NORMES :
ATTESTATION DE CONFORMITE
MàJ 09/06/2011
98
and
Certifications et References
Références
Qualifoudre Certification
> Certification Qualifoudre
MàJ 09/06/2011
ATTESTATION DE CONFORMITE
EN CONFORMITÉ AVEC LES NORMES :
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
d’isolement en conditions de pluie : > 97 %.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
d’isolement en conditions de pluie : > 97 %.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
EN CONFORMITÉ AVEC LES NORMES :
ATTESTATION DE CONFORMITE
MàJ 09/06/2011
99
Certifications and References
Perimeter IONIFLASH MACH (in Teq CO2) IONIFLASH MACH + Accessories (in Teq CO2)
Life cycle 31 37
Global 50 58
ATTESTATION DE CONFORMITE
IONIFLASH new NFC 17-102 STANDARD of September 2011
ATTESTATION DE CONFORMITE IONIFLASH 213
Tests on the IONIFLASH MACH NG45
Applicant : FRANCE
Contact :
Contact
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
Thomas AKA : thomas.aka@ec-lyon.fr Thomas AKA : thomas.aka@ec-lyon.fr
MEILLEURE EMPREINTE CARBONE : certifiée par – VERTEEGO MEILLEURE: Temps EMPREINTE CARBONE :certifiés, certifiée par VERTEE
Results :
NFC 17-102 UNE 21186 – NP 4426 d’avance à l’amorçage
Tél : +33 (0) 4 72 18 60 99 Fax : +33 (0) 4 78 43 37 17 http://www.ampere-lab.fr Tél : +33 (0) 4 72 18 60 99 Fax : +33 (0) 4 78 43 37 17 http://www.ampere-lab.fr
NFC 17-102 – UNE 21186 – NP
4426 : Temps d’avance à l’amorçage certifiés, Voltage E
suivant Tests Laboratoire Officiel
obtained for the
normalized Shanghaï Jiao Tong – Chine.
curve of
switching
EN
Average 50164-1:
EN CONFORMITÉ AVEC LES NORMES :
impulse test,
Tenue en courant 100 kA classe N/H certifié suivant Tests
Time on which
Laboratoires GERAC (Cofrac), selon < 0,8 norme IEC-60-1 et IEC 1083-1.
50 corresponds to
strikes the average Reference t
E.S.E Simple
(µs) Time (kV) Time (µs) (µs) T <T E.S.E Simple Rod Rod
IONIFLASH
onNFC
The tests the IONIFLASH17-102 MACH NG60 – UNE air terminal21186
have shown – an Early
ATTESTATION DE CONFORMITE Streamer Emission vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
(ESE) greater than 60 µs (135,0 µs) but FRANCE Paratonnerres
decided to weight to 60 µs according to the NF C 17-102 Standard.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
d’isolement en conditions de pluie : > 97 %.
MàJ 09/06/2011
NFC 17-102 et UNE of High VoltageCertificat
Head 21186: de Rayon de Protection.
Thomas AKA Ph.D.
Test Center
9001.
Contact :
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
Ampère – Ecole Centrale de Lyon – 36, avenue Guy de Collongue - 69134 Ecully cedex – France
Tél : +33 (0) 4 72 18 60 99 Fax : +33 (0) 4 78 43 37 17 http://www.ampere-lab.fr
0 101
101
MàJ 09/06/2011
Certifications et
andRéférences
References
IONIFLASH
> Tests MACH
selon NF C 17-102
®
TestsEdition
according to the NFC 17-102 (2011)
2011
■ 100 kA test according to the EN50164
■ Essai à 100 kA suivant EN 50164 Essai à 100 kA suivant EN 50164
MàJ 09/06/2011
ATTESTATION DE CONFORMITE
EN CONFORMITÉ AVEC LES NORMES :
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
MàJ 09/06/2011
102 102
MàJ 09/06/2011
MàJ 09/06/2011
Certifications et
andRéférences
References
IONIFLASH
> Test MACH® Tests
supplémentaire selonaccording to the
NF C 17-102 NFC 17-102
Edition 2011 (2011)
d’isolement en conditions de pluie : > 97 %.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
CERTIFICATE
vieillissement Laboratoire LCIE – Fontenay aux Roses – France. Of OPERATION in RAIN CONDITIONS
ATTESTATION DE CONFORMITE
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de According to the IEC 60060-1 STANDARD
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine. EN CONFORMITÉ AVEC
Applicant: FRANCE PARATONNERRES
LES NORMES :
Date: 29th April 2010
NFC 17-102
Input Voltage – UNE
DRY condition 21186 – NP
RAIN condition 4426in %: Temps d’avance à l’amorçage certifiés,
Insulation
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
ATTESTATION DE CONFORMITE
The tests realized
onNFC 17-102 MACH
the IONIFLASH – UNE 21186Emission
Early Streamer – NP (ESE)4426
air- :
terminal have shown vieillissement Laboratoire
insulation greater than LCIE
97% according – Fontenay
to the IEC 60060-1 aux
Roses – France.
standard.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
d’isolement en conditions de pluie : > 97 %.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre
Thomas AKA
et BUREAU VERITAS – ISO 9001.
Head of High Voltage Test Center
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
Contact :
Thomas AKA: thomas.aka@ec-lyon.fr
d’isolement en conditions de pluie : > 97 %. d’isolement en conditions de pluie : > 97 %.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
ATTESTATION
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de DE CONFORMITE ATTESTATION DE CONFORMITE
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1. Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
EN CONFORMITÉ AVEC LES NORMES :
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine. EN CONFORMITÉ AVEC LES NORMES :
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés, NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier). suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier). NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amor
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés, suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés, MàJ huissier). suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (so
MàJ 09/06/2011
09/06/2011
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés, NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amor
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN CONFORMITÉ AVEC LES NORMES : suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN CONFORMITÉ AVEC LES NORMES :
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
EN 50164-1: Tenue en courant 100 kA classe N/H certifié
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1. Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
ATTESTATION DE CONFORMITE NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de NFC 17-102 – UNE 21186 – NP 4426 : Tests environneme
ATTESTATION DE CONFORMITE
vieillissement Laboratoire LCIE – Fontenay aux Roses – France. vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoir
d’isolement en conditions de pluie : > 97 %. d’isolement en conditions de pluie : > 97 %.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001. Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
103
11
/06/20 09
104 MàJ 104
EGO
r VERTE
ifiée pa
E : cert 01.
RBON ISO 90
TE CA
PREIN R ITAS –
L E U RE EM AU VE ti o n .
t BURE te c
MEIL udre e de Pro
Qualifo Rayon t
ation icat de ertifica
ire – C
Certific 8 6 : Certif to
. Labora
NE 211
> 97 % et en
02 et U :
r sites
C 17-1 e pluie u
NF de
ions d nt menés s
condit e
rance. mentaux et
ses – F e
M
ent en sts d’isolem
solem
’i e a y aux RoàJ 09/06/2011 nvironn e
d : T n
te
n ts
s
e
60060-1
IE – Fo 26 : T
IEC
toire LC NP 44
-1.
Tests
t Lab ora 21186 –
semen N E C 1083 s uivant
U
vieillis 0 2 – C -6 0-1 et IE if ié
C 17-1 IE /H cert
NF ATT norme sse N
MEIL (C E
MàJ 09/06/2011 ofracST ATION D
), selon 100 kA cla
e . c ertifiés
,
toires G
ERAC en courant E CON
FO
LEUR – Chin l’amorçage
E E o Tong sier).
M haï Jia ance à
RMITE
PREIN us huis ,
AU (so ge certifiés
N et P a
RMITÉ
rtificati BONE EN 5 Officiel 4426 : Temp
on :c e oratoire P
Q rt AVEC
u a li if ié e sts Lab 86 – N CEH
T LYO ce à l’amorç
fo e 1
p T 1
LES N
u
d
O
re CNRS
d’avan
02 et U
s –
ERNIT
u iv U
N
FA Labora – NP 4
NE 21
a
E
1 S
ts
n
8 – s
t 2
6
T 1
:
e 1
C 21186
s 8
t TISeO
d’is n
ts 6
o e a E
rt 9
L –
if iv 0 N
a
u
N
ic
b
s 1 .
o
a –0U
N ra
t
F
d
to
e
R 7-102
NnFde Protecti
NRS C ps d’avanc
men
e 6 N
t m É
O : e
e IT
ff
n EN ic
ERT
Temps
NF ssement La
iel S
bo NFORM t PAU rçage certifié
h
és sur O
50164-1
C 17-1
(sous h
d’avan
L : T
angha RMITE
0
ab e ï J
c e
fiée
o ra n u e
ia
à uissier) s,
EN C sites et en
par VITE
to o T l’ . ONFO
2 – U ratoire LCIE –
ir e o
n
N
n
La
e
F 001.
b :
s
E
9
o amorç
G c
ra
E o
2 1 to certi FORM
R g – Ch
N
A C n t e.
BO age cTeION DE C
1
186 – ontenay aux ire – C
R o ert A
(Cofrac ura TA rtifiés,
RN
00kAin
TTEESINTTE t e IE r
P P
C
REA
-6 0
50164-1 ERAC (Cofr e sts enviro . EA
: ac nnR EM t BU n de
vieillis -102 – UN
-1 etIE certifié e –
a
n
Rayo
E 211 toir
semen A
C 1083 suiv
86 -1
t Te
Tenue en ), selon norm
e tL T a .
LEU ementaux foudre e
b ts
su ora
s
t de
–
c MEIL
o T
iv o IE li e t b
ra
a u
N
a
C
E
ra d
rtifiés
n -6 e
Qua tifica
toSirT
P 442
IEC
eA LCIE 6
S:
t 100
6
0-1 et IE
: E
%
–
: Cer
0 T
NF nt Tests Lab k C tion . et enL
0 T M
C o
A 6 7
I
a age ce r).
e R
8
1
O
9
60-1 sts O
7 1
l’amorç
c
sie
-1
N
la
: NFonte
>
d n
tif8i3c-1
T S
.
D L E
E 21
02 – U ratoire Officie sse N Ce1r0 sitesce ta
EN C E ironn ance à U (sous huis
ie :ssur
s d’av A
NE 21 é
/H cert .
ONF’isolement en ests d’isolem
suivant
ifié CayOaNux Roses –eFnvIT AeVmEeCnta certifié
Tests 186 – l Shanghaï J et UN sde plu Fran nnemen
ia -10s2u
N
rancÉ
n men ses –
NF L a b P 4 ORM
o T condit 1 7 iva ent me
n
io
t
e.
ro ux et
né orçage
o 4 o t it : Temp T LYON et P
ions d 4426
FOORNFORM
N s
n C
H m
g T d x Ro
F d M
C 1 rato 26 envi
s
7 F e men
e E
– n
u N
-1 : s e
p r I
o ts l
lu E C
0 T
2 e m C 17 ITÉ AV
-1 0 2
nc
ie : sC it T E 8 6 – NeP S e à l’a
e
e
d’iso
>
– UNE ires Officiels ps d’a ChineN. ay au Tests
nt s nten :
t UENC
2 t o
E
1
s 6 ’avanc e.
1 F .
2E
8
mp s d in
e 97 %. es et en Lab – UNE 211 Officiels CNR
L 1S 2 e
o s h
1 N 0 to
ir e : T – C
83-1
NFCCe 17 C
ir 6 Te
6 – NP CNRS C E H vance à l’aiso leme-1:T
C 17-1 ra rato
T
b
eo–
EN CO
ReM
IE – NP 442
e LC
-1a0ti2 86:O
ific
rtE NF La
d’ mo 0
suiv rtific suivant
4426 :
o–n Sat d sts
Certif6ic – NP 442 haï Jiao Tong
NFORM 0a6g0e ce t IEC 10 rtifié s
ertifié
ITÉ A Temps L YON et PA EC 6rç
d ’a IU rtifiéboratoir 186 – EEGO
6 0-1 e ce
118 at l Shang
(s
V
- H
ie
v
UNE 2
/
E o
N ant Tests UQNuEali2foud : eRayonde suivant Te
N/H c
a
re
C
ic
u
1 P
C
–
n N
FMC L a 1 8 e ro
te
0 2 O ff
b 6 tB c -1 ir e lasse
s hm
83-1.
nt La sU,NEe p2a1r VERT
E1IL o U ti 7
c
ce à l’
to
LES N
r – R o1
ifié
a E n A
t o N
.
k
e IE classe
AU abora IEC 10
amorç e uisesier)c
NFC
norm
ir P L
t
ORME
e
illiasgs E2 : –.ert n
ts
S e .
0
4 s
i e A
-1
N
R
. e
: 1
4 VE 0
v k
IT
suivan 7L-1E0U2R–E EMP - c
Te
1
R es O nt 100
e in
U 2 t -6
0
t A
rt
C
0
6 ra
or
T f
9lo
e ic – u
: et
c),Ose
IS
CCAR1B7O ifiés, aIS 100 – Ch
O n co rme IE
TE F l’am
sts L NE 21E1INTEfC Tem S 90
suiv0an
abor
MPREIN N AieRlsBC RC
1 ntaux
EN ps d
EA
nneme
IT(ACSof–r courant Tong ance à
NRES: C ’ . :Tenueeac),selon no
-1
URE E AU VR . Jiao v U (
5
E
L atoire 86 – NP ON ceErtifié
O H e a van 50164
A C (Cofr
enviro
t BURE s GE
ts
e en tection nghaï
f T R
e
f E s
MEIL a p
G T e
par VERTEEGO h
icie 4426 Lpar VEce àEN
MEILLEURE EMPREINTE CARBONE : certifiée
ce.
Lab 0164-1: m
o : s
s d’a N et PA m
n
S
Y
udre e e
l
atoir
r l T ’ ra
r Tenu de Pro
T
n l T
a e a F
o
S
:
e
:
ON RTEE
y
–
ie
to ir n h m Gmratoire 4426 : s
A ic 6 O at à l’a
a e
Qualifo
e p e s
T
s n s t r ç o
T
g PLaboOo a R
h – NP
64a-t1de Ra
x
T eLrtYific
G ue ATTE e d g – Cer
Labo 01ic HC ance
E n S 6
e Off NP 442
ESTAT
A nay au
Ce5rtif
ratoir – d’av
Certification Qualifoudre et BUREAU VERITAS – ISO 9001. T oraRStoC
r E 2118 oratoire
ireE –ps
RAC (Co couT 21186E:N Labo . 186 LaCbN ATTESTATION DE onteCONFORMITE
ION DE Certification
IO aï Jiao on’avance à AU (sous hece –tifiUéN
NFC en Lab
CO
ests > 97 % E 21 l’am s, ire LCIE – F
N
frac) rant 10 N DE CTO es et
, -10u2issie
F
0 Ng – C
O et eniels 26 : Tem
17- 1 se lo k FO hin e F Corç17 a r) orato ur sit
RM02 et UNE 44
R
ptluTie : – UNur sitess Offic
0 n A . N g
s e
2 M
divean
n IT e ent La.b
FC 17-1 ITE
Evieilli
N s – o r c l a E m enés s
et de
s m t
NFC 17-102 et UNE 21186: Certificat de Rayon Nde ce.
C O Nem F U N e s s e ie illissemcertif i e n 7 %.
Protection. conditionsu Ce1n7t-1m0e2nésaboratoir 86 – NFP
O eR n t
M LIT E I E C v 21o é s, d’isolem 9
1ses – ran nementaux
ie : >
IE n
-60-1 N/H c ction.
ent en sts d’isoNleFm t Tests L NaE
e
’isolem
abÉorAVE21186 : Te a n n a Uy ux R enviro :
e Prote
d’isolement en conditions de C 60
pluie : > 97 %. d atoir C LE – iv et IE : Tests itions de plu
60060-1 Fo0n2te–
d’i s
060-
1 e LC S NONP C 10 rtifié Csu60060-1
IE n cond R ayon d
Tests RMES
I R iv
suC
o
l e N
m F : T E – 4 4
S EN 83 -
CONFORMITÉ 1 n n t
teAVEC e : a t de .
L IE 1–7-1NP 4426 :
d’isolement menés sur
sites IEC et en Laboratoire
IEC 60060-1: Tests NFC
rato–ireCertificat
S NO
eC 2:6 : E
n 17-1ests FontME . ’isoleam Certific O 9001
L
Tes LES NORMES ests
e T d
d n t
83-1.
2 s
nt Labo 186 – 1 C 0
– a
2 1
y
E
U’iso 21186: AS – IS
C
N
V
UNE
lisseme
FC suivatnet n c0
Te ondit NEle2m 11e aux R ests en et UNE VERIT
vieil
s
ts io 8
n6t o vi
ivant T MITE
r
02–
La – s e o
-1 ITÉ A IEC-60-1 et IE certifié su
17-1 m
–Fontenay Roses
aux
b ns N n UREAU
vieillissement Laboratoire LCIE
0
o P s 17-102
–17France.
B
e
N ra d e C TEEGO
OR
2 t
N/H
F n 4 – e F e
ORM rm
C toe
C
é 4 F N17-102 – UNE 21186 – NP 4426 : Temps d’avance àRl’amorçage certifi
e
m
F
ir
s
re VE
N
e1t7U epsluO elon no
ONF ONF
NFC 17-102 – UNE 21186 – NP 4426 C -1N02 ranc nNFC
ieffic s s2u6r : Tem e enta alifoud
:Tests environnementaux Cet), sde A clas
er t
: ie> ls s
it p s d u x Officiels CNRS TifLYON
iée par et PAU (sous huissier)
EN ofrac
e ’a
100 k
9C7N on Qu
e Laboratoires EE: cHert
DE C certifiés,
ificasuivant Te E 2–11U 8N6E NC
AC(C
e.N
R vanc.e suivant Tests
tio sts : C21186 %RS C sE et
E Ch
à rtifictatid
ourant
n L H e e e
c
a
rçage
n l’ C ARBO
g
b T
TinIO o
a
n
Q o m
T o –A
LY o
toires G en
u LO
o
– TNP E C4426 : Temps d’avance à l’amorçage certifi
T à l’am ier).
M ratoeirretifica– NP 4426 .
S
: abNo r e NFC rçage– UNE 21186
E
EILL EN 50 alifoudr Offict ie atoPirAU 17-102
Labora 64-1: Tenue hanghaï Jia
01 1083-1. dle S certifEié MsPREIN
URE
Laboratoire , Officiel Shanghaï Jiao Tong – Chine.
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et 5IEC
Rhaayno Temps d’a e – (sTests
EUR iel S
ApTsT d’avance AU (sous huisesrtifiés,
164-1: e et
La E b E T e n B gnhaï
d J vanc suivant MCo EuILsLhEu
e is
e Offic 6 : Tem
o ia
N et P
e
age c
u
2
ra Mto e P o
EN 50164-1: Tenue en courant 100 kA classe Tests
eU
EN N/H certifié osuivant
nRE ro
a b ratoir NP 44 T LYO l’ amorç
PirReEs IG cA tT
ec
–
ong – C e à l’a H
morçartificat sier).
E à
NE R ou UV h
e
ra t
C c
T A nE i o
Tests L
.
21186
(C n . ineEN 50164-1:
ge cert
Tenue
CNRS d’avan
suivant
E CCAR
ifiés, en courant 100 kA classe N/H certifié suivant Te
– UNE
ac), se tRI1T0A0S –kA c
Officiels Temps
:
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine. 7-102
BoOfrN s 6
ss
NF 2
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 1 E : c lon norme ISO la
C 17 orato ire NP 44
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance àTel’amorçage e r
sts Lab
ti fi IE 900 e N/H
C -6 0
certifiés,
1186 –
vieil lis -102 – UN
E ée p -11e. t IE certifié su
C
UNE 2
sem iva
suivant
en t ar V E 1 0 8 3 nt T
L -1 e
suivant Tests Laboratoires Officiels CNRS C E H T LYON -102 –(sous huissier).
sts
17PAU
RTE
C et
aborato 21186 – N
NF P EG NFC . 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et
S:
IEC
ire LCIE
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés, ORME
600 – Fonte 4426 : Tests Ovieillissement Laboratoire LCIE – Fontenay aux Roses – France.
LES N
n a e
C
y n
E
d’isole 60-1: Tests
m d’i
ITÉ AV a ux Ros v iron nem
es – F ra e n ta u
NFORM
ent en conditiosolement me
n nceIEC. 60060-1: x eTests menés sur sites et en Laboratoire – Certifi
EN CO
NF t de d’isolement
EN CONFORMITÉ AVEC LES NORMES :
RMITE C 17-1 ns de
02 pluie : és sur sites
et U N E >9 7 % et e n d’isolement en conditions de pluie : > 97 %.
. L
CONFO
2 a b
DE
Ce 1186: C
ATION oratoire
rtificati ertifica
T
o t – Cert
n Q u d e R a NFC 17-102 etifUNE
ic a t 21186: Certificat de Rayon de Protection.
ATTES
alifoud yon de
MEIL re et B Protec
tion.
LEURE UREAU
E
M P
V E R Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
ATTESTATION DE CONFORMITE
IT
REINT
E C A R
AS – IS
O 9 0
BO N E 01. àJ 09/06/
: certifié MMEILLEURE
2011 EMPREINTE CARBONE : certifiée par VERTEEGO
e par V
ERTEE G O
> Rapports
Inspectiond’inspection
reports
MàJ
09 /06/20
11
Certifications et
andRéférences
References
MàJ 09/06/2011
MàJ 09
/06/ 2011
Certifications and References
MàJ 09/06/2011
ATTESTATION DE CONFORMITE
EN CONFORMITÉ AVEC LES NORMES :
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
d’isolement en conditions de pluie : > 97 %.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
d’isolement en conditions de pluie : > 97 %.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
EN CONFORMITÉ AVEC LES NORMES :
ATTESTATION DE CONFORMITE
MàJ 09/06/2011
105
Certifications and References
MàJ 09/06/2011
ATTESTATION DE CONFORMITE
EN CONFORMITÉ AVEC LES NORMES :
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
d’isolement en conditions de pluie : > 97 %.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
d’isolement en conditions de pluie : > 97 %.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
EN CONFORMITÉ AVEC LES NORMES :
ATTESTATION DE CONFORMITE
106
Certifications and References
MàJ 09/06/2011
ATTESTATION DE CONFORMITE
EN CONFORMITÉ AVEC LES NORMES :
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
d’isolement en conditions de pluie : > 97 %.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
Certification Qualifoudre et BUREAU VERITAS – ISO 9001.
NFC 17-102 et UNE 21186: Certificat de Rayon de Protection.
MEILLEURE EMPREINTE CARBONE : certifiée par VERTEEGO
d’isolement en conditions de pluie : > 97 %.
IEC 60060-1: Tests d’isolement menés sur sites et en Laboratoire – Certificat
vieillissement Laboratoire LCIE – Fontenay aux Roses – France.
NFC 17-102 – UNE 21186 – NP 4426 : Tests environnementaux et de
Laboratoires GERAC (Cofrac), selon norme IEC-60-1 et IEC 1083-1.
EN 50164-1: Tenue en courant 100 kA classe N/H certifié suivant Tests
suivant Tests Laboratoire Officiel Shanghaï Jiao Tong – Chine.
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
suivant Tests Laboratoires Officiels CNRS C E H T LYON et PAU (sous huissier).
NFC 17-102 – UNE 21186 – NP 4426 : Temps d’avance à l’amorçage certifiés,
EN CONFORMITÉ AVEC LES NORMES :
ATTESTATION DE CONFORMITE
107
Certifications and References
Chenonceau - Castle
Taïwan - Palace
Calenzana - Church
108
Certifications and References
La Villeneuve - House
109
Certifications and References
Cableship
Cableship
Paris - Necker Hospital
Solar Field
110
Certifications and References
Paris - Disneyland
111
Certifications and References
Emergency centre
Herment - Mast
Shanghaï China - Radio Telescope
112
Certifications and References
113
Certifications and References