You are on page 1of 4

BOQ FOR ELECTRICAL WORK OF SWAMI TOWER Project.

Note: Use of Flexible conduits & Elbows in Circuit wiring is not allowed except in exceptional
site conditions with the approval of Engineer / Architect and All wiring laying in the MS/PVC
conduit strickly follow IE( Indian Electricity) rules and IE(Indian Electricity) rules follow in all
items of project. Proper ferrules, lux, thimble to be done in all cabling and wiring from both
load/source end.
S.No. DESCRIPTION QTY UNIT RATE AMOUNT
1 ELECTRICAL WIRING

Providing & fixing POINT WIRING for Ceiling and wall lights, Ceiling fan, wall fan, exhaust fan,
Plug points Bell points. The item includes Circuit wiring from DB to the switch board with 3x2.5
Sq.MM PVC insulated copper conductor single core multistrended wire for Phase, Neutral &
Earth (P+N+E) in appropriate size 20/25mm dia of 16 SWG wall thickness, MS medium
conduits ( stove enamelled regid steel conduit) ISI mark (IS :9537), point wiring to be with
3x1.5 Sq.MM PVC insulated copper conductor with all necessary accessories, such as saddles
etc. on surface or embedded in wall, chasing the walls and making the surface neat
afterwards. Item includes 6 AMP switch, socket, etc. PHILIPS ELITE , MK / NORTH
WEST & ANCHOR ROMA, with all base plates, covering plate Metal box of same make etc.
complete. (EACH Circuit to take NOT MORE than 7-8 points) Flexible conduits & Elbows are
not allowed. Flexible conduit use it must be joined by gland and check

Providing and fixing point wiring with same specifications as MAIN point wiring above but One
a) 876 Nos.
point controlled by one switch.(i.e. inclusive of mains wiring).

Providing and fixing point wiring with same specifications as MAIN point wiring above but 2
b) 798 Nos
points to be controlled by one switch.(i.e. inclusive of mains wiring).

Providing and fixing point wiring with same specifications as MAIN point wiring above but for
c) 192 Nos.
one Exhaust fan point

6/16 AMP power point with 3x 2.5 sq.mm. wire and 20 mm dia. 16 swg stove enameled
g) rigid steel conduits with 1x 5pin 6/16 Amp socket outlet. No extra cost for wiring and conduits is 480 Nos.
payable (i.e. inclusive of mains wiring).

20 AMP power point with 3x 4 sq.mm. wire and 20 mm dia. 16 swg stove enameled rigid
steel conduits with 1x 5pin 20 Amp socket outlet. No extra cost for wiring and conduits is 257 Nos.
payable (i.e. inclusive of mains wiring).

32 AMP power point with 3x 4 sq.mm. wire and 20 mm dia. 16 swg stove enameled rigid
steel conduits with 1x 5pin 20 Amp socket outlet. No extra cost for wiring and conduits is 51 Nos.
payable (i.e. inclusive of mains wiring).

Call bell point with call bell with 3x1.5 sq.mm. wire and 20 mm dia. 16 swg stove enameled
i) rigid steel conduits. No extra cost for wiring and conduits is payable (i.e. inclusive of mains 28 Nos.
wiring).

2 A.C. point

Supply, Installation, commissioning & Testing of the surface / recess mounting A.C. point as
per above point wiring with 3x 4 sq.mm. PVC wiring in M.S. Conduit pipe, etc. with the
followings : 32 A D.P.,1 way switch with neon with plate and box.- 1 set
204 Nos.
25 A & 10 A Twin socket with plate and box.- 1 Set. i/c electrical connections and making good
all the damages, painting, cleaning the site etc complete as required as per site requirement
and as directed.(i.e. inclusive of mains wiring).

4 TELEPHONE POINT

Supplying and fixing of krone telephone tag block, suitable for the multi core telephone
cable and shall accommodate tin-plated phosphor bronze connectors, the connectors shall
splice unskinned cables up to 0.61 mm dia and shall be terminate both incoming and out going
i)
lines, the tag blocks shall be mounted inside, water proof box and locking arrangement and
shall be fully accessibIe.The item is inclusive of providing and fixing of boxes in surface /
recessed system etc complete as required.

a. 20 Pair Tag Box


1 Nos

ii) Supplying, Installation, testing and commissioning of the telephone point with the followings -

Two pair, 0.50 mm dia. telephone cable tinned copper conductor, P.V.C. insulated and
a.
sheathed , fire retarding, anti termite, colour coded twisted pairs and rip cord.

1200 Mtrs.

Double outlet with shutter modular type Telephone Outlets ( RJ – 11 )


b.
with suitable size M.S./ PVC modular boxes complete as req.
24 Nos.

Supplying, Laying / Fixing of the following size conduit with conduit accessories like bend /
junction box / fan box etc on surface / recessed manner and making and making good all the
iii) damages, painting, cleaning the site etc complete as required as per site requirement and as
directed.

Page 1 of 4
iii)
S.No. DESCRIPTION QTY UNIT RATE AMOUNT

a. 20 mm dia.1.6 mm wall thickness rigid PVC conduits. 3000 Mtrs

b. 25 mm dia.1.6 mm wall thickness rigid PVC conduits. 3000 Mtrs.

8 DISTRIBUTION BOARDS All MCB to be "C" series

Supply, installation, commissioning & Testing of the surface/recess mounting following ways
MCB DB's 230/415 Volts on surface/recessed, complete with tinned copper Busbar, Neutral
Bar, Earth Bar, Din Bar detachable gland plate, interconnection and making good all the
damages, painting, cleaning the site etc complete as required as per site requirement and as
directed.

LIGHT DISTRIBUTION BOARD :


A.
a.
1 no. TPN MCB DB 4 way ( 4 + 12 ways ) 28 Nos

b. 1 no TPN MCB 63 amp.

c. 12 nos SP MCB 10 amp.

6 nos SP MCB 16 amp.


4 nos SP MCB 25 amp.

B. POWER DISTRIBUTION BOARD :

1 no. TPN MCB DB 4 way ( 4 + 12 ways )


2 Nos
1 no TPN MCB 63 amp.
12 nos SP MCB 20/32 amp.

9 LAN - ( LOCAL AREA NETWORKING ) FOR COMPUTERS :

Supply and laying of Four Pair UTP CAT 6 LAN cables in existing PVC Conduit / Floor trunking
c 1440 Mtrs.
with RJ-45 connector if required as per requirement.

Supply and fixing of modular type Information Outlets with suitable size M.S./ PVC modular
d
boxes complete with insulation displacement connectors etc suitable for CAT 6 UTP Cabling.

11 CABLING

Supplying, unloading, storing , laying, testing and commissioning of following sizes of PVC
/XLPE insulated (heavy duty)AI./ following sizes of PVC / XLPE insulated (Heavy duty) Al / Cu
conductor armored cables suitable for working voltage up to armored cables suitable for
working voltage upto and including 1100 volts ,laid and tied on existing overhead cables trays
or laid and tied over MS supports in Volts , laid and tied on existing overhead cable trays; or
laid and tied over s in masonry trenches including providing MS including providing MS
supports and clamps for fixing to supports ; or buried in ground complete as required as
specifications required and as per specifications.

a) 3.5 Core, 150 sq.mm Al. Cable.(main cable) 100 RM

b) 4.0 Core, 25 sq.mm Al. Cable.(Power DB) 100 RM

c) 5.0 Core, 10 sq. mm Cu. Cable.(Light DB) 1200 RM

12 CABLE END TERMINATION : ( 1100 V Gr.Cable )

Termination of the following sizes ( 4 / 3.5 core ) of XLPE insulated Aluminum conductor
cable. Including providing terminal lugs single compression gland, crimping the joints,
20 Nos
insulation tape effecting terminal connections to the equipment complete as required Up to 150
sq mm

Termination of the following sizes ( 4 / 3.5 core ) of XLPE insulated Aluminum conductor
cable. Including providing terminal lugs single compression gland, crimping the joints,
20 Nos
insulation tape effecting terminal connections to the equipment complete as required Up to 25
sq mm

ELECTRICAL FAN AND FITTINGS

LED LIGHT FITTINGS

Page 2 of 4
S.No. DESCRIPTION QTY UNIT RATE AMOUNT

Fixing,commissioning & testing of ceiling mounted Environment Friendly , Energy Efficient


16
,decorative Square & Round molded body Ceiling Mounted LED light Fixture.

9 W-LED Light Fixture 313 Nos.


12 W- LED Light Fixture Down Lighter 287 Nos.

18 L E D TUBE LIGHT

Supply, fixing, commissioning & testing of ceiling/wall mounted Environment Friendly , Energy
Efficient ,decorative Ultra Slim Linear light Fixture with extruded Aluminum heat Sink with
class I electrical safety, complete as required.

20 W LED 4’0” Tube Light 27 Nos.


36 W LED 4’0” Tube Light 66 Nos.
20 G.I.PLATE EARTH STATION :

Preparation of the Plate Earth Station: (as per IS:3043)

Excavation of rocky earth, soft murrum, hard murrum etc and back
filling with black cotton soil for the earth station, the earth pit size is
1000 mm x 1000 mm x 2500 mm deep.

S/F of G.I. plate of size 600 x 600 x 6.0 mm thick.

fixing 50 mm x 6 mm, 3 mtrs G.I, strips from G.I.plate to earth terminal


including brazing / welding at plate etc.

Supplying and laying in position 19 mm, 2 mtrs G.I. `B' class pipe for
watering.with reducer/funnel with mesh.

S/F of the following in the earth station.


75 Kg. Charcoal.
15 Kg. Original Salt.
Black Cotton soil

Construction of earth pit chamber including necessary brick work


concrete, plastering, S/F of C.I. Cover of size 12" x 12" complete as per
site req. 4 No.

21 COPPER PLATE EARTH STATION :

Preparation of the Plate Earth Station: (as per IS:3043)

Excavation of rocky earth, soft murrum, hard murrum etc and back
filling with black cotton soil for the earth station, the earth pit size is
1000 mm x 1000 mm x 2500 mm deep.

S/F of Copper plate of size 600 x 600 x 3.0 mm thick.

fixing 50 mm x 6 mm, 3 mtrs Copper strips from G.I.plate to earth


terminal including brazing / welding at plate etc.

Supplying and laying in position 19 mm, 2 mtrs G.I. `B' class pipe for
watering.with reducer/funnel with mesh.

S/F of the following in the earth station.


75 Kg. Charcoal.
15 Kg. Original Salt.
Black Cotton soil

Construction of earth pit chamber including necessary brick work


concrete, plastering, S/F of C.I. Cover of size 12" x 12" complete as per

Page 3 of 4
S.No. DESCRIPTION QTY UNIT RATE AMOUNT
site req. 1 No.

22 i) Providing and fixing Copper / GI strip as per specification complete


including connection to earth electrode revetting / sweating / soldering,
burying 15 cms below in all types of soil / rocks etc complete as
required.

a G.I.Strip 25 X 5 mm 100 Mtrs.


b G.I.Strip 50 X 6 mm 50
Mtrs.
c Copper Strip 25 X 5 mm 50

d Copper Strip 50 X 6 mm 50 Mtrs.


ii) Supply and laying of following size hot dip G.I.wire from earth terminal
at earth station to earth bus-bar / pole etc.or with the Cable on wall /
150 mm below ground level ,wherever required as per site condition.

a 6 SWG G.I.Wire 0 Mtrs.


b 10 SWG G.I.Wire 0 Mtrs.

23 Supply and laying of 16 sqmm PVC insulated copper wire in 15 mm


G.I. pipe including accessories complete as required. 0 RM

GRAND TOTAL

Page 4 of 4