Worldwide

www.tyco-fire.com
Contacts

Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General having nominal K-factors of 14.0 and
16.8. This feature offers flexibility when
Description sizing system piping, as well as possi-
bly reducing or eliminating the need for
TYCO Model ESFR-25 Pendent Sprin- a system fire pump.
klers are Early Suppression, Fast Also, Model ESFR-25 Sprinklers permit
Response (ESFR) sprinklers having a use of a maximum deflector-to-ceiling
nominal K-factor of 25.2 (Ref. Figure 1). distance of 18 inches (460 mm) versus
They are suppression-mode sprinklers 14 inches (356 mm). Additionally, a
that are especially advantageous as a storage arrangement of 40 ft. (12,2
means of eliminating the use of in-rack m) with a ceiling height of 45 ft. (13,7
sprinklers when protecting high-piled m) does not require in-rack sprinklers
storage. as do other ESFR Sprinklers having
The Model ESFR-25 Sprinklers are pri- nominal K-factors of 14.0 and 16.8.
marily used for ceiling-only sprinkler The Model ESFR-25 Sprinklers are
protection of (but not limited to) the fol- listed by Underwriters Laboratories
lowing storage applications: (UL) for specific applications with a lines. The general guidelines in this
• most encapsulated or non-encap- maximum storage height of 43 ft. (13,1 data sheet are not intended to provide
sulated common materials including m) with a maximum ceiling height of 48 complete installation criteria.
cartoned, unexpanded plastics ft. (14,6 m) without the requirement for

• uncartoned (exposed) expanded


in-rack sprinklers. Refer to the Specific
Application Listing (UL) for the design Sprinkler
plastics in accordance with NFPA 13
and FM Global standards
criteria.
Applications for the TYCO ESFR Sprin-
Identification
• some storage arrangements of rub-
ber tires, roll paper, flammable liq-
klers are expanding beyond currently
recognized installation standards. For
Number (SIN)
uids, aerosols, and automotive information on research fire tests (e.g., TY9226
components with flammable liquids and aerosols) TY9226 is a re-designation for Central
For more specific criteria, refer to Table that may be acceptable to an author- SIN 9226, Gem SIN G8441, and Star
A as well as the applicable design ity having jurisdiction, contact Tyco Fire SIN S8010.
standard. Protection Products (TFPP) Technical
The Model ESFR-25 Pendent Sprin-
Services.
Technical
klers provide the system designer
with hydraulic and sprinkler place-
NOTICE
The Model ESFR-25 Sprinklers
Data
ment options not presently available to
the traditional ESFR sprinklers having described herein must be installed Approvals
and maintained in compliance with this UL and C-UL Listed
nominal K-factors of 14.0 and 16.8. In FM Approved
particular, the Model ESFR-25 Sprin- document, as well as with the applica-
ble standards of the National Fire Pro- VdS Approved
kler has been designed to operate at NYC Approved under MEA 356-01-E
substantially lower-end head pres- tection Association (NFPA), in addition
LPCB Certified (Cert. Nos. 094b and 007l)
sures, as compared to ESFR Sprinklers to the standards of any authorities
CE Certified (Certificate of Conformity
having jurisdiction (e.g., FM Global). 1725-CPD-H0010)
Failure to do so may impair the perfor-
mance of these devices. Maximum Working Pressure
IMPORTANT 175 psi (12,1 bar)
Always refer to Technical Data The owner is responsible for main-
Sheet TFP700 for the “INSTALLER taining their fire protection system Pipe Thread Connections
WARNING” that provides cautions and devices in proper operating con- 1 Inch NPT or ISO 7-R 1
with respect to handling and instal- dition. Contact the installing contrac- Discharge Coefficient
lation of sprinkler systems and com- tor or product manufacturer with any K=25.2 gpm/psi½ (362,9 lpm/bar½)
ponents. Improper handling and questions.
installation can permanently damage Temperature Ratings
In all cases, the appropriate NFPA or 165°F (74°C) and 212°F (100°C)
a sprinkler system or its compo- FM Global installation standard, or
nents and cause the sprinkler to fail other applicable standard, must be Finish
to operate in a fire situation or cause referenced to ensure applicability and Natural Brass
it to operate prematurely. to obtain complete installation guide-

Page 1 of 4 JULY 2016 TFP312


TFP312
Page 2 of 4

7 1" NPT

Components: 8 1-13/16"
9/16" (46,0 mm)
1 - Frame
(14,3 mm)
2 - Deflector
9 NOMINAL
3 - Compression MAKE-IN
Screw
4 - Hook 6
5 - Strut
6 - Link Assembly 3-13/16"
5 (96,8 mm) THERMAL
7 - Button SENSING
8 - Sealing ELEMENT
Assembly
4
9 - Ejection Spring WRENCH
FLATS
3

2
TEMPERATURE
RATING
2" (50,8 mm)
FIGURE 1
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE

Storage Type NFPA FM Global

Open Frame (i.e., no solid shelves) Refer to NFPA 13 Refer to FM Global


Single, Double, Multiple-Row, or Portable Rack Storage of Chapters 16 and 17 2-0 and 8-9
Class I-IV and Group A or B Plastics

Solid Pile or Palletized Storage of Refer to NFPA 13 Refer to FM Global


Class I-IV and Group A or B Plastics Chapters 14 and 15 2-0 and 8-9

Refer to NFPA 13 Refer to FM Global


Idle Pallet Storage Chapter 12 2-0, 8-9, and 8-24

Refer to NFPA 13 Refer to FM Global


Rubber Tire Storage Chapter 18 2-0 and 8-3

Roll Paper Storage Refer to NFPA 13 Refer to FM Global 8-21


(Refer to the Standard) Chapter 19

Flammable/Ignitable Liquid Storage Refer to NFPA 30 Refer to FM Global 7-29


(Refer to the Standard)

Aerosol Storage Refer to NFPA 30B Refer to FM Global 7-31


(Refer to the Standard)

Automotive Components in Portable Racks Refer to NFPA 13 N/A


(Control mode only; refer to the Standard) Chapter 20

N/A – Not Applicable

TABLE A
MODEL ESFR-25 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TFP312
Page 3 of 4

Physical Characteristics System Type Sprinkler Position


Frame ���������������������������������������������������������Brass Wet Pipe Pendent:
Deflector ���������������������������������������������������Bronze Frame arms aligned with pipe
Compression Screw �������������������� Stainless Steel Roof Construction Deflectors parallel with ceiling or roof
Hook ��������������������������������������������������������MONEL Unobstructed or obstructed con-
Strut ���������������������������������������������������������MONEL struction (e.g., smooth ceiling, bar System Type
Link Assembly ��������������������������������Solder, Nickel
Button ���������������������������������������������������������Brass joists, beam and girder, and so forth). Wet Pipe only
Sealing Assembly. . Beryllium Nickel w/TEFLON Where the depths of the solid struc-
Maximum Area of Coverage
Ejection Spring ������������������������������������ INCONEL tural members (e.g., beams and stem)
100 ft² (9,3 m²)
exceed 12 inches (302 mm), install
Operation ESFR Sprinklers in each channel
formed by the structural members.
In some cases, the installation stan-
dards permit a greater coverage area.
The fusible link assembly is com- Ceiling Slope Minimum Area of Coverage
prised of two link halves that are joined Maximum 2 inch rise for 12 inch run 64 ft² (5,8 m²) according to NFPA 13
together by a thin layer of solder. When (16.7%)
the rated temperature is reached, the Maximum Slope Ceiling
solder melts and the two link halves Maximum Coverage Area 2 inch rise for 12 inch run (16.7%)
separate, activating the sprinkler and 100 ft² (9,3 m²)
Maximum Spacing
flowing water. In some cases, the installation stan- 10 feet (3,1 m)
dards permit a greater coverage area.
Design Minimum Coverage Area
In some cases, the installation stan-
dards permit a greater spacing.
Criteria 64 ft² (5,8 m²) per
NFPA 13 / FM Global 2-0 Minimum Spacing
8 feet (2,4 m)
The following general guidelines pro- Maximum Spacing
vided for the TYCO Model ESFR-25 Temperature Rating
12 feet (3,7 m) for building heights up to
Pendent Sprinklers can be used for a 165°F (74°C) and 212°F (100°C)
30 feet (9,1 m)
quick reference. Deflector Distance from Walls
10 feet (3,1 m) for building heights
The National Fire Protection Associa- greater than 30 feet (9,1 m). Minimum of 4 inches (102 mm) from
tion (NFPA) and FM Global (FM Approv- walls but no more than 1/2 the allow-
als) provide installation standards that In some cases, installation standards able distance permitted between
must be used to properly design an permit a greater spacing. sprinklers
automatic sprinkler system utilizing Minimum Spacing Deflector to Top of Storage
Early Suppression, Fast Response 8 feet (2,4 m) Minimum of 36 inches (914 mm)
(ESFR) Sprinklers. The guidelines pro-
vided by NFPA and FM Global may Minimum Clearance to Commodity Deflector-to-Ceiling Distance
differ. Consequently, the appropri- 36 inches (914 mm) 6 to 14 inches (152 to 356 mm)
ate standard must be used for a given NFPA Maximum Ceiling Height
installation. Deflector-to-Ceiling Distance 48 feet (14,6 m)
In all cases, the appropriate NFPA or 6 to 18 inches (152 to 457 mm)
Maximum Storage Height
FM Global installation standard must FM Global 43 feet (13,1 m)
be referenced to ensure applicabil- Centerline of Thermal Sensing
ity and to obtain complete installation Storage Arrangement
Element-to-Ceiling Distance
guidelines. Palletized, solid piled, open frame,
Refer to FM Global 2-0 for Storage single row, or double row
The following general guidelines are not Sprinklers.
intended to provide complete installa- Commodity
tion criteria.
Specific Class I-IV; Cartoned, unexpanded
plastic
In addition to this technical data sheet,
the following data sheets describe
other TYCO ESFR Sprinklers:
Application Sprinkler System Design
NFPA 13 for ESFR Sprinklers based
• TFP315 Listing (UL) upon 45 psi (3,1 bar) design pressure,
Model ESFR-17 (TY7226) 169 gpm (640 lpm) with 12 sprinkler
TYCO Model ESFR-25 Pendent Sprin- remote area
K=16.8 Pendent Sprinkler klers are listed by Underwriters Labo-
• TFP316 ratories (UL) for Specific Applications Minimum Aisle Width
Model ESFR-17 (TY7126) with a ceiling height greater than 5 feet (1,5 m)
K=16.8 Upright Sprinkler 45 ft. (13,7 m) up to and includ-
ing 48 ft. (14,6 m), and a storage
• TFP317 arrangement up to and including
Model ESFR-17 (TY7223) 43 ft. (13,1 m), the following guide-
K=16.8 Pendent Sprinkler line are provided for the TYCO Model
• TFP318 ESFR-25 Pendent Sprinklers:
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
• TFP319
Model ESFR-14 (TY6236)
K=14.0 Pendent Sprinkler
TFP312
Page 4 of 4

Step 4. After installation, inspect the


Link Assembly of each Model ESFR-25 Limited
"FITTING SIDE"
TOWARDS SPRINKLER
Pendent Sprinkler for damage. In par-
ticular, verify that the Link Assembly Warranty
FITTING and Hook are positioned as illustrated
For warranty terms and conditions, visit
in Figure 1, and that the Link Assem-
www.tyco-fire.com.
bly is not bent, creased, or forced out

Ordering
of normal position in any way. Replace
damaged sprinklers.

Care and Procedure


WRENCH
RECESS
Maintenance Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and part number
TYCO Model ESFR-25 Early Suppres-
(P/N).
sion, Fast Response 25.2K Pendent
FIGURE 2 Sprinklers must be maintained and ser- Sprinkler Assemblies
W-TYPE 1 viced in accordance with this section. Specify: Model ESFR-25 Early Sup-
SPRINKLER WRENCH Before closing a fire protection system pression, Fast Response 25.2K
main control valve for maintenance Pendent Sprinklers (TY9226), (specify
temperature rating), with Natural Brass
Installation work on the fire protection system that
it controls, permission to shut down the finish, P/N (specify):
TYCO Model ESFR-25 Early Suppres- affected fire protection system must be 165°F (74°C) . . . . . . . . . . . . . . . . . . 58-441-1-165
obtained from the proper authorities 212°F (100°C) . . . . . . . . . . . . . . . . . 58-441-1-214
sion, Fast Response 25.2K Pendent
Sprinklers must be installed in accor- and notify all personnel who may be Special Order
dance with this section. affected by this action. Sprinkler Assemblies with
Sprinklers which are found to be ISO 7-1 Thread Connection
General Instructions Specify: Model ESFR-25, Early Sup-
Damage to the fusible Link Assem- leaking or exhibiting visible signs of
corrosion must be replaced. pression, Fast Response 25.2K
bly during installation can be avoided Pendent Sprinklers (TY9226) with
by handling the sprinkler by the frame Automatic sprinklers must never be ISO 7-1 thread connection, (specify
arms only (i.e., do not apply pressure painted, plated, coated, or other- temperature rating), with Natural Brass
to the fusible Link Assembly), and by wise altered after leaving the factory. finish, P/N (specify):
using the appropriate sprinkler wrench. Modified sprinklers must be replaced.
Failure to do so can lead to an unstable Sprinklers that have been exposed to 165°F (74°C) . . . . . . . . . . . . . . . . . 58-442-1-165
212°F (100°C) . . . . . . . . . . . . . . . . 58-442-1-214
link assembly and premature activation corrosive products of combustion, but
of the sprinkler. Damaged sprinklers have not operated, should be replaced Sprinkler Wrench
must be replaced. if they cannot be completely cleaned Specify: W-Type 1 Sprinkler Wrench,
A leak-tight 1 inch NPT sprinkler joint by wiping the sprinkler with a cloth or P/N 56-872-1-025
should be obtained by applying a min- by brushing it with a soft bristle brush.
imum-to-maximum torque of 20 to 30 Care must be exercised to avoid
lbs.-ft. (26,8 to 40,2 Nm). Higher levels damage to the sprinklers before,
of torque can distort the sprinkler inlet during, and after installation. Sprin-
with consequent leakage or impairment klers damaged by dropping, striking,
of the sprinkler. wrench twist/slippage, or the like, must
Note: Install the Model ESFR-25 be replaced. Also, replace any sprin-
Pendent Sprinkler in the pendent posi- kler that has a cracked bulb or that has
tion (Ref. Figure 2). lost liquid from its bulb (Ref. Installa-
tion section).
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into The owner is responsible for the
the sprinkler fitting. Do not apply pres- inspection, testing, and maintenance of
sure to the Link Assembly, and handle their fire protection system and devices
the Model ESFR-25 Pendent Sprinkler in compliance with this document, as
only by the Frame arms. well as with the applicable standards
of the National Fire Protection Asso-
Step 2. Wrench-tighten the Model ciation (e.g., NFPA 25), in addition to
ESFR-25 Pendent Sprinkler using only the standards of any authorities having
the W-Type 1 Sprinkler Wrench (Ref. jurisdiction. Contact the installing con-
Figure 2) and by fully engaging (seating) tractor or product manufacturer with
the wrench on the sprinkler wrench any questions.
flats (Ref. Figure 1).
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.