www.tyco-fire.com
Contacts
Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General having nominal K-factors of 14.0 and
16.8. This feature offers flexibility when
Description sizing system piping, as well as possi-
bly reducing or eliminating the need for
TYCO Model ESFR-25 Pendent Sprin- a system fire pump.
klers are Early Suppression, Fast Also, Model ESFR-25 Sprinklers permit
Response (ESFR) sprinklers having a use of a maximum deflector-to-ceiling
nominal K-factor of 25.2 (Ref. Figure 1). distance of 18 inches (460 mm) versus
They are suppression-mode sprinklers 14 inches (356 mm). Additionally, a
that are especially advantageous as a storage arrangement of 40 ft. (12,2
means of eliminating the use of in-rack m) with a ceiling height of 45 ft. (13,7
sprinklers when protecting high-piled m) does not require in-rack sprinklers
storage. as do other ESFR Sprinklers having
The Model ESFR-25 Sprinklers are pri- nominal K-factors of 14.0 and 16.8.
marily used for ceiling-only sprinkler The Model ESFR-25 Sprinklers are
protection of (but not limited to) the fol- listed by Underwriters Laboratories
lowing storage applications: (UL) for specific applications with a lines. The general guidelines in this
• most encapsulated or non-encap- maximum storage height of 43 ft. (13,1 data sheet are not intended to provide
sulated common materials including m) with a maximum ceiling height of 48 complete installation criteria.
cartoned, unexpanded plastics ft. (14,6 m) without the requirement for
7 1" NPT
Components: 8 1-13/16"
9/16" (46,0 mm)
1 - Frame
(14,3 mm)
2 - Deflector
9 NOMINAL
3 - Compression MAKE-IN
Screw
4 - Hook 6
5 - Strut
6 - Link Assembly 3-13/16"
5 (96,8 mm) THERMAL
7 - Button SENSING
8 - Sealing ELEMENT
Assembly
4
9 - Ejection Spring WRENCH
FLATS
3
2
TEMPERATURE
RATING
2" (50,8 mm)
FIGURE 1
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE
TABLE A
MODEL ESFR-25 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TFP312
Page 3 of 4
Ordering
of normal position in any way. Replace
damaged sprinklers.