Voltage Drop Analysis

FCPS-24S8 Notification Appliance Circuit (3.0 amps)


Notification Appliances - NAC #2
Source Voltage: 19.20 VDC Terminal Voltage

Protected Premises: GRUPO INMOBILIARIO EMG, S.A. DE C.V. Date: 30/03/2021


Address: Carretera Federal México-Puebla Km.126.5 Col.Momoxpan City: Puebla
State: San Pedro Cholula Zip: 72760 Note:

Prepared By: PROSISA IMC DE MÉXICO S.A. de C.V. Phone: 58221061


Address: Av.Ingenieros militares 105 City: México
State: México Zip: 54913

Current Distance (Feet) Circuit Voltage @ Each Device


(amps)
Device # Part Number Between Total 10 AWG 12 AWG 14 AWG 16 AWG 18 AWG
1 P2RL30 0.1160 141 141 18.92 18.76 18.50 18.08 17.42
2 P2RL30 0.1160 129 270 18.71 18.41 17.95 17.20 16.03
3 P2RL30 0.1160 129 399 18.52 18.12 17.49 16.47 14.86
4 P2RL30 0.1160 189 588 18.31 17.78 16.95 15.61 13.50
5 P2RL30 0.1160 100 688 18.23 17.65 16.73 15.27 12.96
6 P2RL30 0.1160 149 837 18.14 17.52 16.52 14.93 12.42
7 P2RL30 0.1160 4 841 18.14 17.51 16.52 14.93 12.41
Total Current: 0.8120 % Voltage Drop: 5.50 8.78 13.96 22.24 35.34

Go Go Go No Go No Go

Strikethrough indicates a value below the device's minimum voltage at indicated location and wire gauge.
These calculations assume a worst-case source voltage as measured by UL with the batteries depleted to 20.4 volts. Under AC
power and for most of the drain cycle of the batteries, the circuit voltages will be substantially higher and thus, would
support a greater number of devices. A device's minimum operating voltage is derived from the UL-requirement that it
operate within a Regulated Voltage Range (16VDC - 33VDC).