Systems Operation
EMCP4.3/4.4
Media Number -UENR1210-05 Publication Date -01/03/2017 Date Updated -09/03/2017

i03883415

Event Viewing
SMCS - 4490

The EMCP 4 shows previous and current events from both the EMCP and external modules.
These events are organized into logs for each physical EMCP 4 module.

The logs include the following:

STATUS EVENTS - Recent event history

GENSET CONTROL - Events for the EMCP 4 GSC

ENGINE CONTROL - Events for a primary CAN data link compatible engine ECM

DIGITAL AVR - Events for the Cat Digital Voltage Regulator (CDVR)

THERMOCOUPLE - Events for the thermocouple module

EXTERNAL I/O - Events for the discrete input/output (DIO) module

RTD MODULE - Events for the resistive temperature device (RTD) module

SCR MODULE - Events for engine after treatment systems

The generator set control log stores events that are generated by the EMCP 4. Any other event is
stored within the module that generated the event. Even if the EMCP annunciates an event, that
does not mean that the EMCP logs that event. The event may be within the log of another module.

Each log is visible only if the module is connected to the appropriate data link. The module must
be connected to either the primary data link or the accessory data link. The module must be
communicating with the EMCP 4.

The list of event logs can be viewed by pressing the "Event Log" key or via the "VIEW" submenu.
Select the log that you wish to view and press the "OK" key to view the events.

The EMCP 4 supports more than one instance of some of the above modules. Those modules are
uniquely identified with a number at the end of the log name.

https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sis... 05/10/2021
Media Search - UENR1210 - EMCP4.3/4.4 Page 2 of 2

The module number is software-configured, and is called the "ECU INSTANCE NUMBER". The
ECU instance number can be viewed and modified by the Caterpillar service tool.

An event in the EMCP 4 generator set control log can be in one of three states:

• Present

• Active

• Inactive

Table 1 explains the different states.

Table 1
This state is only applicable to the generator set control log. Present means that the
condition that caused the event is still present. The condition must be addressed
Present before the event can be reset.
This state only applies to Genset Control events. Other modules will not have
present in logs.
The event was previously in a "Present" state, but event is no longer present. The
event has been latched by the event system and needs to be reset before the engine
can be restarted.
Within the generator set control log, the condition that caused the event is still
affecting the system, but may be reset. Warning type events automatically reset
when the condition that caused the event is resolved and will never be active.
Active Within any log other than the generator set control log, the condition that caused the
event is affecting the system. The event may, or may not, be resettable. If the "Reset
All" command fails to reset the event, then this event is still occurring. The event
must be resolved before the event can be reset.
Many events go from present to active when the engine is shut down and may
reoccur once the engine starts running again. Further action may be required to
resolve the issue.
The event has happened at some time in the past but is no longer affecting the
Inactive
system. Inactive events are stored for historical purposes only.