Air System Sizing Summary for SplitSystem

Project Name: Clinique Beni Mellal 09/20/2016


Prepared by: CLIM CONSULT 10:35

Air System Information


Air System Name: SplitSystem Number of zones: 1
Air System Type: Single Zone CAV Floor Area: 33,6 sqm
Location: Béni Mellal, Morocco

Sizing Calculation Information


Calculation Months: Jan to Dec Calculation method: Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load: 3,2 kW Load occurs at: Jul 1500
Total coil load: 3,2 kW OA DB / WB: 43,0/23,1
Sensible coil load: 2,8 kW Entering DB / WB: 28,0/18,8
Coil airflow: 181 L/s Leaving DB / WB: 14,4/13,6
Sensible heat ratio: 0,888 Coil ADP: 12,9 C
Area per unit load: 10,6 sqm/kW Bypass Factor: 0,100
Load per unit area: 94,0 W/sqm Resulting RH: 60 %
Design supply temp: 14,4 C

Central Heating Coil Sizing Data


Max coil load: 1,2 kW Load occurs at: Des Htg
Coil airflow: 181 L/s Ent DB / Lvg DB: 15,5/21,2
Load per unit area: 34,8 W/sqm

Supply Fan Sizing Data


Actual max airflow: 181 L/s Fan motor BHP: 0,00 BHP
Standard airflow: 171 L/s Fan motor kW: 0,00 kW
Actual max airflow per unit area: 5,40 L/(s-sqm) Fan static: 0,00 Pa

Outdoor Ventilation Air Data


Design airflow: 50 L/s Airflow per person: 8,30 L/s/person
Airflow per unit floor area: 1,48 L/(s-sqm)

Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Administration 1,6 181 Jul 1700 0,0 33,6 5,40

Block Load 4.15 Page 1 of 3


System Design Load Summary for SplitSystem
Project Name: Clinique Beni Mellal 09/20/2016
Prepared by: CLIM CONSULT 10:35

DESIGN COOLING DESIGN HEATING


Jul 1500 Design Heating Day
OA DB / WB 43 C / 23,1 C OA DB / WB 1 C / -2,1 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 0 sqm 0 - 0 sqm - -
Wall Transmission 0 sqm 0 - 0 sqm 0 -
Roof Transmission 0 sqm 0 - 0 sqm 0 -
Window Transmission 0 sqm 0 - 0 sqm 0 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 0 sqm 0 - 0 sqm 0 -
Partitions/Ceilings 108 sqm 408 - 108 sqm 0 -
Overhead Lighting 840 W 769 - 0W 0 -
Electric Equipment 0W 0 - 0W 0 -
People 6 340 360 0 0 0
Infiltration - 29 0 - 27 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>>Total Zone Loads - 1546 360 - 27 0
Thermostat and Pulldown Adjustment - 85 0 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 50 L/s 1176 -7 50 L/s 1138 0
Supply Fan Load 181 L/s 0 - 181 L/s 0 -
>> Total System Loads - 2807 353 - 1170 0
Central Cooling Coil - 2807 353 - 0 0
Central Heating Coil - 0 - - 1170 -
>> Total Coil Loads - 2807 353 - 1170 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 3


System PsychrometricsforSplitSystem
Project Name: Clinique Beni Mellal 09/20/2016
Prepared by: CLIM CONSULT 10:35

Location: Béni Mellal, Morocco


Altitude: 468,0 m
Data for: Jul DESIGN COOLING DAY, 1500

1. Outdoor Air
0,020
2. Mixed Air
3.CentralCoolingCoilOutlet
4. Supply Fan Outlet 0,018
5. Room Air

0,016

0,014

Specific Humidity ( kg/kg )


0,012
5 2 1
4
3 0,010

0,008

0,006

0,004

0,002

0,000
0 10 20 30 40
Temperature (C)

Block Load 4.15 Page 3 of 3