Air System Sizing Summary for DefaultSystem

Project Name: USINE ZENATA-CASABLANCA 04/12/2021


Prepared by: Ingénieur Mouad MELLOUKI 08:41

Air System Information


Air System Name:................................. DefaultSystem Number of zones: ....................................................... 1
Air System Type: .............................. Single Zone CAV Floor Area: ........................................................... 125,0 sqm
Location: ................................... Casablanca, Morocco

Sizing Calculation Information


Calculation Months: .....................................Jan to Dec Calculation method: ........... Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load: ....................................................... 12,9 kW Load occurs at: ............................................... Jul 2000
Total coil load: ....................................................... 12,9 kW OA DB / WB:.................................................. 27,0/21,5
Sensible coil load:.................................................. 10,4 kW Entering DB / WB:.......................................... 24,5/18,4
Coil airflow: ............................................................. 882 L/s Leaving DB / WB: .......................................... 14,6/14,0
Sensible heat ratio: ...............................................0,810 Coil ADP: ............................................................... 13,5 C
Area per unit load: ................................................... 9,7 sqm/kW Bypass Factor: ..................................................... 0,100
Load per unit area: ...............................................103,2 W/sqm Resulting RH: ........................................................... 54 %
Design supply temp: .............................................. 14,4 C

Central Heating Coil Sizing Data


Max coil load: .......................................................... 7,0 kW Load occurs at: ................................................ Des Htg
Coil airflow: ............................................................. 882 L/s Ent DB / Lvg DB:............................................ 18,8/25,4
Load per unit area: ................................................ 55,8 W/sqm
Supply Fan Sizing Data
Actual max airflow: ................................................. 882 L/s Fan motor BHP: ..................................................... 0,00 BHP
Standard airflow:..................................................... 875 L/s Fan motor kW: ....................................................... 0,00 kW
Actual max airflow per unit area: ............................ 7,05 L/(s-sqm) Fan static: .............................................................. 0,00 Pa

Outdoor Ventilation Air Data


Design airflow: ........................................................ 133 L/s Airflow per person: ................................................. 8,30 L/s/person
Airflow per unit floor area: ...................................... 1,06 L/(s-sqm)
Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Plateau Bureau ETG 10,0 882 Jul 2100 4,3 125,0 7,05

Block Load 4.15 Page 1 of 8


System Design Load Summary for DefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

DESIGN COOLING DESIGN HEATING


Jul 2000 Design Heating Day
OA DB / WB 27 C / 21,5 C OA DB / WB 5,6 C / 1,8 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 0 sqm 0 - 0 sqm - -
Wall Transmission 95 sqm 960 - 95 sqm 2078 -
Roof Transmission 125 sqm 4185 - 125 sqm 2214 -
Window Transmission 0 sqm 0 - 0 sqm 0 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 0 sqm 0 - 0 sqm 0 -
Partitions/Ceilings 22 sqm 0 - 22 sqm 0 -
Overhead Lighting 3125 W 3125 - 0W 0 -
Electric Equipment 500 W 500 - 0W 0 -
People 16 1149 961 0 0 0
Infiltration - 8 22 - 37 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>>Total Zone Loads - 9926 983 - 4329 0
Thermostat and Pulldown Adjustment - 44 0 - 149 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 133 L/s 478 1468 133 L/s 2491 0
Supply Fan Load 882 L/s 0 - 882 L/s 0 -
>> Total System Loads - 10448 2452 - 6969 0
Central Cooling Coil - 10448 2452 - 0 0
Central Heating Coil - 0 - - 6969 -
>> Total Coil Loads - 10448 2452 - 6969 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 8


System PsychrometricsforDefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

L o c a t i o n : C a s a b l a n c a , M o r o c c o
A l t i t u d e : 6 1 , 9 m
D a t a f o r : J u l D E S I G N C O O L I N G D A Y , 2 0 0 0
0 , 0 2 0
1 . O u t d o o r A ir
2 . M ix e d A ir
3 . C e n t r a l C o o l
in g C o il O u t le t
4 . S u p p ly F a n O u t le t 0 , 0 1 8
5 . R o o m A ir

0 , 0 1 6

0 , 0 1 4

S p e c if ic
1

0 , 0 1 2
2
4
3
5 0 , 0 1 0

H u m id it y
0 , 0 0 8

0 , 0 0 6

0 , 0 0 4

(
0 , 0 0 2

kg/ kg
0 , 0 0 0
0 1 0 2 0 3 0
T e m p e r a t u r e ( C )

)
Block Load 4.15 Page 3 of 8
Ventilation Sizing Summary for DefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

Summary
Ventilation Sizing Method: .................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate: ................................................................... 133 L/s

Space Ventilation Analysis Table

Space Name Floor Area Maximum Maximum Required Required Required Required Uncorrected
sqm Occupants Supply Air Outside Air Outside Air Outside Air Outside Air Outdoor Air
L/s L/s/person L/(s-sqm) L/s (% of supply) L/s
Plateau Bureau ETG 125,0 16,0 881,8 8,30 0,00 0,0 0,0 132,8
Totals 881,8 132,8

Block Load 4.15 Page 4 of 8


Hourly Air System Design Day Loads for DefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

DESIGN MONTH:Jul
Hour OA SUPPLY CENTRAL CENTRAL CENTRAL PREHEAT TERMINAL TERMINAL
TEMP C AIRFLOW COOLING COOLING HEATING COIL kW COOLING HEATING
L/s SENSIBLE TOTAL kW COIL kW COILS kW COILS kW
kW
0000 25,3 882 10,0 12,4 0,0 0,0 0,0 0,0
0100 25,0 882 9,8 12,1 0,0 0,0 0,0 0,0
0200 24,7 882 9,6 12,0 0,0 0,0 0,0 0,0
0300 24,5 882 9,4 11,6 0,0 0,0 0,0 0,0
0400 24,4 882 9,1 11,3 0,0 0,0 0,0 0,0
0500 24,3 882 8,6 10,6 0,0 0,0 0,0 0,0
0600 24,4 882 8,7 10,8 0,0 0,0 0,0 0,0
0700 24,7 882 8,7 10,8 0,0 0,0 0,0 0,0
0800 25,2 882 8,3 10,2 0,0 0,0 0,0 0,0
0900 25,8 882 8,2 10,0 0,0 0,0 0,0 0,0
1000 26,6 882 8,7 10,7 0,0 0,0 0,0 0,0
1100 27,5 882 8,4 10,2 0,0 0,0 0,0 0,0
1200 28,3 882 9,0 11,0 0,0 0,0 0,0 0,0
1300 28,9 882 8,8 10,7 0,0 0,0 0,0 0,0
1400 29,3 882 9,0 10,9 0,0 0,0 0,0 0,0
1500 29,4 882 9,6 11,7 0,0 0,0 0,0 0,0
1600 29,3 882 9,5 11,6 0,0 0,0 0,0 0,0
1700 28,9 882 10,1 12,3 0,0 0,0 0,0 0,0
1800 28,4 882 10,3 12,7 0,0 0,0 0,0 0,0
1900 27,7 882 10,3 12,7 0,0 0,0 0,0 0,0
2000 27,0 882 10,4 12,9 0,0 0,0 0,0 0,0
2100 26,5 882 10,1 12,5 0,0 0,0 0,0 0,0
2200 26,0 882 10,1 12,5 0,0 0,0 0,0 0,0
2300 25,6 882 10,0 12,3 0,0 0,0 0,0 0,0
Loads calculated using Transfer Function Method

Block Load 4.15 Page 5 of 8


Hourly Zone Loads for DefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

ZONE: Plateau Bureau ETG


DESIGN MONTH: Jul
Hour OA TEMP C ZONE TEMP RH (%) ZONE ZONE TERMINAL TERMINAL ZONE
C AIRFLOW SENSIBLE COOLING HEATING HEATING
L/s LOAD W COIL W COIL W UNIT W
0000 25,3 24,1 55,0 881,8 9723,3 0,0 0,0 0,0
0100 25,0 24,1 56,0 881,8 9566,6 0,0 0,0 0,0
0200 24,7 24,0 56,0 881,8 9395,6 0,0 0,0 0,0
0300 24,6 24,0 57,0 881,8 9216,8 0,0 0,0 0,0
0400 24,4 24,1 58,0 881,8 9034,4 0,0 0,0 0,0
0500 24,3 24,2 60,0 881,8 8851,0 0,0 0,0 0,0
0600 24,4 24,1 59,0 881,8 8668,7 0,0 0,0 0,0
0700 24,7 24,0 59,0 881,8 8489,5 0,0 0,0 0,0
0800 25,2 24,2 61,0 881,8 8321,8 0,0 0,0 0,0
0900 25,8 24,2 62,0 881,8 8185,4 0,0 0,0 0,0
1000 26,6 23,9 60,0 881,8 8104,2 0,0 0,0 0,0
1100 27,4 24,2 62,0 881,8 8095,0 0,0 0,0 0,0
1200 28,3 23,9 60,0 881,8 8164,0 0,0 0,0 0,0
1300 28,9 24,2 61,0 881,8 8307,5 0,0 0,0 0,0
1400 29,3 24,2 61,0 881,8 8513,9 0,0 0,0 0,0
1500 29,4 24,1 59,0 881,8 8766,1 0,0 0,0 0,0
1600 29,3 24,2 59,0 881,8 9043,5 0,0 0,0 0,0
1700 28,9 24,1 57,0 881,8 9322,8 0,0 0,0 0,0
1800 28,4 24,1 55,0 881,8 9578,7 0,0 0,0 0,0
1900 27,7 24,1 55,0 881,8 9787,3 0,0 0,0 0,0
2000 27,1 24,1 54,0 881,8 9926,4 0,0 0,0 0,0
2100 26,5 24,2 55,0 881,8 9979,7 0,0 0,0 0,0
2200 25,9 24,1 55,0 881,8 9949,2 0,0 0,0 0,0
2300 25,6 24,2 55,0 881,8 9856,6 0,0 0,0 0,0
Loads calculated using Transfer Function Method

Block Load 4.15 Page 6 of 8


System Psychrometrics Table for DefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

DESIGN COOLING DAY, Jul 2000

TABLE 1: SYSTEM DATA

Component Location Dry-Bulb Specific Airflow L/s Sensible Latent Heat


Temp C Humidity Heat W W
kg/kg
Ventilation Air Inlet 27,1 0,01398 133 478 1468
Vent - Return Mixing Outlet 24,5 0,01077 882 - -
Central Cooling Coil Outlet 14,6 0,00982 882 10448 2452
Central Heating Coil Outlet 14,6 0,00982 882 0 -
Supply Fan Outlet 14,6 0,00982 882 0 -
Zone Air - 24,1 0,01020 882 9971 983
Return Plenum Outlet 24,1 0,01020 882 0 -

Site Altitude = 61,9 m


Air Density x Heat Capacity x Conversion Factor = 1,1984 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor = 2926,0 W/(L/s)

TABLE 2: ZONE DATA

Zone Name Zone T-stat Mode Zone Temp Zone Airflow Reheat Coil
Sensible C L/s Load W
Load W
Plateau Bureau ETG 9926 Cooling 24,1 882 0

Block Load 4.15 Page 7 of 8


System Psychrometrics Table for DefaultSystem
Project Name: USINE ZENATA-CASABLANCA 04/12/2021
Prepared by: MOUAD FREELANCE 08:41

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Component Location Dry-Bulb Specific Airflow L/s Sensible Latent Heat


Temp C Humidity Heat W W
kg/kg
Ventilation Air Inlet 5,6 0,00284 133 -2491 0
Vent - Return Mixing Outlet 18,8 0,00284 882 - -
Central Cooling Coil Outlet 18,8 0,00284 882 0 0
Central Heating Coil Outlet 25,4 0,00284 882 6969 -
Supply Fan Outlet 25,4 0,00284 882 0 -
Zone Air - 21,2 0,00284 882 -4478 0
Return Plenum Outlet 21,2 0,00284 882 0 -

Site Altitude = 61,9 m


Air Density x Heat Capacity x Conversion Factor = 1,1984 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor = 2926,0 W/(L/s)

TABLE 2: ZONE DATA

Zone Name Zone T-stat Mode Zone Temp Zone Airflow Reheat Coil
Sensible C L/s Load W
Load W
Plateau Bureau ETG -4329 Deadband 21,2 882 0