Zone Design Load Summary for 20-24

Project Name: branislav 05.08.2019


Prepared by: Grappa d.o.o. 02:54

0.1 KUHINJA DESIGN COOLING DESIGN HEATING


Jul 1600 Design Heating Day
OA DB / WB 33 C / 21,6 C OA DB / WB -11,7 C / -13 C
Thermostat Setpoint 24,0 C Thermostat Setpoint 20,0 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 175000 sqm 160 - 175000 sqm - -
Wall Transmission 5 sqm 18 - 5 sqm 48 -
Roof Transmission 0 sqm 0 - 0 sqm 0 -
Window Transmission 2 sqm 17 - 2 sqm 78 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 18 sqm 0 - 18 sqm 208 -
Partitions/Ceilings 41 sqm 99 - 41 sqm 171 -
Overhead Lighting 185 W 185 - 0W 0 -
Electric Equipment 2400 W 2400 - 0W 0 -
People 2 160 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3039 120 - 505 0

1.1 KUHINJA DESIGN COOLING DESIGN HEATING


Jul 1500 Design Heating Day
OA DB / WB 33,3 C / 21,7 C OA DB / WB -11,7 C / -13 C
Thermostat Setpoint 24,0 C Thermostat Setpoint 20,0 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 292400 sqm 169 - 292400 sqm - -
Wall Transmission 28 sqm 81 - 28 sqm 260 -
Roof Transmission 0 sqm 0 - 0 sqm 0 -
Window Transmission 3 sqm 29 - 3 sqm 130 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 3 sqm 129 - 3 sqm 111 -
Floor Transmission 14 sqm 32 - 14 sqm 0 -
Partitions/Ceilings 41 sqm 194 - 41 sqm 6 -
Overhead Lighting 201 W 201 - 0W 0 -
Electric Equipment 99 W 99 - 0W 0 -
People 2 160 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1093 180 - 506 0

Block Load 4.15 Page 1 of 2


Zone Design Load Summary for 20-24
Project Name: branislav 05.08.2019
Prepared by: Grappa d.o.o. 02:54

0.7 TERETANA DESIGN COOLING DESIGN HEATING


Jul 1600 Design Heating Day
OA DB / WB 33 C / 21,6 C OA DB / WB -11,7 C / -13 C
Thermostat Setpoint 24,0 C Thermostat Setpoint 20,0 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 0 sqm 0 - 0 sqm - -
Wall Transmission 0 sqm 0 - 0 sqm 0 -
Roof Transmission 42 sqm 221 - 42 sqm 456 -
Window Transmission 0 sqm 0 - 0 sqm 0 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 42 sqm 0 - 42 sqm 0 -
Partitions/Ceilings 98 sqm 18 - 98 sqm 588 -
Overhead Lighting 425 W 425 - 0W 0 -
Electric Equipment 500 W 500 - 0W 0 -
People 4 680 1000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1843 1000 - 1045 0

Block Load 4.15 Page 2 of 2