You are on page 1of 323

Room Checksums

By Trane
T1- hop ke hoach

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.55 0.19 13.97 Partition/Door -0.39 -0.39 0.00 Diffuser 156 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 156 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 156 47
Infiltration 0.26 0.26 13.07 0.06 4.41 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.45 0.00 0.45 22.61 0.25 18.38 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.07 0.21 15.44 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.34 0 0 17.09 0.18 13.24 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 33.67 0.67 49.26 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 63.82 1.06 77.94 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.68 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 12.56 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.01 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.02 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 11.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.40 2.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 78.68
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.63
W/m² 94.00 -27.80
Grand Total ==> 1.72 -0.04 1.99 100.00 1.36 100.00 Grand Total ==> -0.39 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.98 1.46 156 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.98 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 1 of 323
Room Checksums
By Trane
T1- khoa cap cuu ban dau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.00 0.00 2.00 26.28 2.06 40.08 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.12 0.00 0.12 1.58 0.13 2.53 Glass/Door Cond -0.04 -0.04 1.69
Cooling Heating
Wall Cond 0.26 0.11 0.37 4.86 0.27 5.25 Wall Cond -0.03 -0.05 2.12
Partition/Door 0.19 0.19 2.50 0.19 3.70 Partition/Door -0.26 -0.26 11.02 Diffuser 522 157
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 522 157
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 522 157
Infiltration 0.82 0.82 10.78 0.18 3.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.39 0.11 3.50 45.99 2.83 55.06 Sub Total ==> -0.33 -0.35 14.83 Nom Vent 95 0
AHU Vent 95 0
Internal Loads Internal Loads Infil 19 0
Lights 0.62 0.15 0.77 10.12 0.62 12.06 Lights 0.00 0.00 0.00 MinStop/Rh 157 157
People 1.61 0 2 21.16 0.81 15.76 People 0.00 0 0.00 Return 541 157
Misc 0.59 0.00 0.59 7.75 0.59 11.48 Misc 0.00 0.00 0.00 Exhaust 114 0
Sub Total ==> 2.82 0.15 2.97 39.03 2.02 39.30 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.29 -0.29 0.00 0.00 0.29 5.64 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.28 16.82 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.33 -0.33 -4.34 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.19 2.50 RA Preheat Diff. -1.00 42.37 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.01 42.80 % OA 18.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.65 2.29
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 68.65
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.98
W/m² 111.35 -19.73
Grand Total ==> 6.50 -0.36 7.61 100.00 5.14 100.00 Grand Total ==> -0.34 -2.36 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.61 5.30 513 26.6 19.9 11.9 15.8 15.8 11.3 Floor 68 Main Htg -1.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 29 9 31 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 2 of 323
Room Checksums
By Trane
T1- khu giuong benh+hanh lang tham

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.38 0.38 3.44 0.38 6.01 Partition/Door -0.51 -0.51 16.89 Diffuser 644 193
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 644 193
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 644 193
Infiltration 2.16 2.16 19.53 0.47 7.44 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.54 0.00 2.54 22.97 0.85 13.45 Sub Total ==> -0.51 -0.51 16.89 Nom Vent 109 0
AHU Vent 109 0
Internal Loads Internal Loads Infil 50 0
Lights 1.73 0.43 2.16 19.53 1.73 27.37 Lights 0.00 0.00 0.00 MinStop/Rh 193 193
People 4.48 0 4 40.51 2.35 37.18 People 0.00 0 0.00 Return 694 193
Misc 0.63 0.00 0.63 5.70 0.63 9.97 Misc 0.00 0.00 0.00 Exhaust 158 0
Sub Total ==> 6.84 0.43 7.27 65.73 4.71 74.53 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.76 -0.76 0.00 0.00 0.76 12.03 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.47 13.29 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.46 -0.46 -4.16 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.24 2.17 RA Preheat Diff. -1.24 41.06 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.25 41.39 % OA 16.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.66 Lps/m² 3.56 1.07
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 16.36
W/m² 61.11 -9.78
Grand Total ==> 10.14 -0.79 11.06 100.00 6.32 100.00 Grand Total ==> -0.52 -3.02 100.00 No. People 36

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.07 6.23 642 26.6 19.9 11.9 15.8 15.2 10.6 Floor 181 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 58 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.07 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 3 of 323
Room Checksums
By Trane
T1- phong bac si

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.10 0.10 6.13 0.10 8.55 Partition/Door -0.19 -0.19 0.00 Diffuser 111 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 111 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 111 33
Infiltration 0.20 0.20 12.27 0.05 4.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.30 0.00 0.30 18.40 0.15 12.82 Sub Total ==> -0.19 -0.19 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 5 0
Lights 0.16 0.04 0.20 12.27 0.16 13.68 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.26 0 0 15.95 0.14 11.97 People 0.00 0 0.00 Return 115 33
Misc 0.67 0.00 0.67 41.10 0.67 57.26 Misc 0.00 0.00 0.00 Exhaust 19 0
Sub Total ==> 1.09 0.04 1.13 69.33 0.97 82.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 4.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 12.27 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.45 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 12.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.70 2.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 67.90
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.14
W/m² 98.61 -23.44
Grand Total ==> 1.44 -0.05 1.63 100.00 1.17 100.00 Grand Total ==> -0.19 -0.58 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.63 1.21 110 26.8 20.3 12.4 16.3 16.3 11.7 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.63 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 4 of 323
Room Checksums
By Trane
T1- phong noi soi khi phe quan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.55 0.15 0.70 31.39 0.55 35.48 Wall Cond -0.05 -0.07 3.24
Partition/Door -0.59 -0.59 -26.46 -0.59 -38.06 Partition/Door -1.49 -1.49 68.98 Diffuser 158 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 158 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 158 47
Infiltration 0.11 0.11 4.93 0.03 1.94 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.07 0.15 0.22 9.87 -0.01 -0.65 Sub Total ==> -1.54 -1.56 72.22 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.87 0.22 1.09 48.88 0.87 56.13 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.23 0 0 10.31 0.12 7.74 People 0.00 0 0.00 Return 161 47
Misc 0.52 0.00 0.52 23.32 0.52 33.55 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 1.62 0.22 1.84 82.51 1.51 97.42 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.23 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 7.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -2.24 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.69 RA Preheat Diff. -0.30 13.89 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 14.35 % OA 8.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.46 Lps/m² 13.74 4.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 70.87
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.16
W/m² 193.74 -160.89
Grand Total ==> 1.74 0.27 2.23 100.00 1.55 100.00 Grand Total ==> -1.54 -2.16 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.23 1.94 158 26.6 19.6 11.6 15.8 15.8 11.3 Floor 12 Main Htg -1.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 170 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.23 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 26 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 5 of 323
Room Checksums
By Trane
T1- Phong rua tiet trung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.85 0.24 1.09 40.52 0.85 44.50 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 194 58
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 194 58
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 194 58
Infiltration 0.19 0.19 7.06 0.05 2.62 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.04 0.24 1.28 47.58 0.90 47.12 Sub Total ==> -0.06 -0.08 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 4 0
Lights 0.19 0.05 0.24 8.92 0.19 9.95 Lights 0.00 0.00 0.00 MinStop/Rh 58 58
People 0.39 0 0 14.50 0.21 10.99 People 0.00 0 0.00 Return 198 58
Misc 0.52 0.00 0.52 19.33 0.52 27.23 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.10 0.05 1.15 42.75 0.92 48.17 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 10.04 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -2.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.60 RA Preheat Diff. -0.37 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.38 0.00 % OA 11.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 9.95 2.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.99
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.24
W/m² 138.11 -22.40
Grand Total ==> 2.23 0.12 2.69 100.00 1.91 100.00 Grand Total ==> -0.06 -0.82 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.69 2.21 194 26.6 19.7 11.7 15.8 15.8 11.3 Floor 20 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 6 of 323
Room Checksums
By Trane
T1- phong truc theo doi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 3.70 0.06 5.31 Partition/Door -0.13 -0.13 0.00 Diffuser 102 31
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 102 31
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 102 31
Infiltration 0.21 0.21 12.96 0.05 4.42 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 16.67 0.11 9.73 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 15 0
AHU Vent 15 0
Internal Loads Internal Loads Infil 5 0
Lights 0.16 0.04 0.20 12.35 0.16 14.16 Lights 0.00 0.00 0.00 MinStop/Rh 31 31
People 0.27 0 0 16.67 0.15 13.27 People 0.00 0 0.00 Return 107 31
Misc 0.67 0.00 0.67 41.36 0.67 59.29 Misc 0.00 0.00 0.00 Exhaust 19 0
Sub Total ==> 1.10 0.04 1.14 70.37 0.98 86.73 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.54 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 12.35 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.85 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 14.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.05 1.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 63.40
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.47
W/m² 95.43 -19.26
Grand Total ==> 1.41 -0.03 1.62 100.00 1.13 100.00 Grand Total ==> -0.13 -0.53 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.19 102 26.7 20.3 12.5 15.8 15.8 11.3 Floor 17 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 7 of 323
Room Checksums
By Trane
T1- phong XN X quang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.41 0.12 0.53 25.48 0.41 27.70 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.09 0.09 4.33 0.09 6.08 Partition/Door -0.13 -0.13 0.00 Diffuser 152 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 152 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 152 46
Infiltration 0.16 0.16 7.69 0.04 2.70 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.66 0.12 0.78 37.50 0.54 36.49 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 4 0
Lights 0.17 0.04 0.21 10.10 0.17 11.49 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.34 0 0 16.35 0.18 12.16 People 0.00 0 0.00 Return 155 46
Misc 0.52 0.00 0.52 25.00 0.52 35.14 Misc 0.00 0.00 0.00 Exhaust 22 0
Sub Total ==> 1.03 0.04 1.07 51.44 0.87 58.78 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 4.73 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.24 11.54 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -3.37 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.88 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.29 0.00 % OA 12.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.98 2.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.05
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.14
W/m² 122.84 -26.63
Grand Total ==> 1.76 0.02 2.08 100.00 1.48 100.00 Grand Total ==> -0.16 -0.74 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.08 1.66 152 26.7 19.8 11.7 15.8 15.8 11.3 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.08 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 8 of 323
Room Checksums
By Trane
T1- phong y ta

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.10 0.10 6.13 0.10 8.55 Partition/Door -0.19 -0.19 0.00 Diffuser 111 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 111 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 111 33
Infiltration 0.20 0.20 12.27 0.05 4.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.30 0.00 0.30 18.40 0.15 12.82 Sub Total ==> -0.19 -0.19 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 5 0
Lights 0.16 0.04 0.20 12.27 0.16 13.68 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.26 0 0 15.95 0.14 11.97 People 0.00 0 0.00 Return 115 33
Misc 0.67 0.00 0.67 41.10 0.67 57.26 Misc 0.00 0.00 0.00 Exhaust 19 0
Sub Total ==> 1.09 0.04 1.13 69.33 0.97 82.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 4.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 12.27 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.45 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 12.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.70 2.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 67.90
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.14
W/m² 98.61 -23.44
Grand Total ==> 1.44 -0.05 1.63 100.00 1.17 100.00 Grand Total ==> -0.19 -0.58 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.63 1.21 110 26.8 20.3 12.4 16.3 16.3 11.7 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.63 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 9 of 323
Room Checksums
By Trane
T1-chup CT scanner 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.51 0.51 14.49 0.51 24.40 Partition/Door -0.68 -0.68 45.95 Diffuser 226 68
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 226 68
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 226 68
Infiltration 0.28 0.28 7.95 0.10 4.78 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.79 0.00 0.79 22.44 0.61 29.19 Sub Total ==> -0.68 -0.68 45.95 Nom Vent 41 0
AHU Vent 41 0
Internal Loads Internal Loads Infil 8 0
Lights 0.25 0.06 0.31 8.81 0.36 17.22 Lights 0.00 0.00 0.00 MinStop/Rh 68 68
People 0.72 0 1 20.45 0.41 19.62 People 0.00 0 0.00 Return 234 68
Misc 0.41 0.00 0.41 11.65 0.54 25.84 Misc 0.00 0.00 0.00 Exhaust 50 0
Sub Total ==> 1.38 0.06 1.44 40.91 1.31 62.68 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.16 -0.16 0.00 0.00 0.17 8.13 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.41 40.06 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.19 -0.19 -5.40 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 1.99 RA Preheat Diff. -0.40 27.03 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.40 27.03 % OA 22.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.08 1.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 64.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.55
W/m² 94.73 -28.94
Grand Total ==> 2.33 -0.29 3.52 100.00 2.09 100.00 Grand Total ==> -0.68 -1.48 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.53 1.55 178 26.3 21.2 13.8 16.3 16.1 11.4 Floor 37 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 77 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.53 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 10 of 323
Room Checksums
By Trane
T1-chup MRI

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.85 0.24 1.09 24.22 0.85 28.52 Wall Cond -0.06 -0.08 4.71
Partition/Door 0.37 0.37 8.22 0.37 12.42 Partition/Door -0.50 -0.50 29.41 Diffuser 322 97
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 322 97
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 322 97
Infiltration 0.44 0.44 9.78 0.11 3.69 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.66 0.24 1.90 42.22 1.33 44.63 Sub Total ==> -0.56 -0.58 34.12 Nom Vent 50 0
AHU Vent 50 0
Internal Loads Internal Loads Infil 10 0
Lights 0.44 0.11 0.55 12.22 0.44 14.77 Lights 0.00 0.00 0.00 MinStop/Rh 97 97
People 0.90 0 1 20.00 0.48 16.11 People 0.00 0 0.00 Return 332 97
Misc 0.52 0.00 0.52 11.56 0.52 17.45 Misc 0.00 0.00 0.00 Exhaust 59 0
Sub Total ==> 1.86 0.11 1.97 43.78 1.44 48.32 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.21 -0.21 0.00 0.00 0.21 7.05 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.70 15.56 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.19 -0.19 -4.22 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 2.67 RA Preheat Diff. -0.56 32.94 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.57 33.53 % OA 15.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.59 Lps/m² 7.23 2.17
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.91
W/m² 100.89 -25.26
Grand Total ==> 3.73 -0.05 4.50 100.00 2.98 100.00 Grand Total ==> -0.56 -1.70 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.50 3.31 322 26.8 19.9 11.8 16.3 16.2 11.5 Floor 45 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 56 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.50 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 11 of 323
Room Checksums
By Trane
T1-dieu tri huu khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 12.84 0.19 17.76 Partition/Door -0.25 -0.25 0.00 Diffuser 110 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 110 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 110 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 18.92 0.22 20.56 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.61 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 29.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.33 2.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.01
W/m² 124.82 -39.18
Grand Total ==> 1.12 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.25 -0.67 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.47 0.87 92 26.8 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.47 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 12 of 323
Room Checksums
By Trane
T1-dieu tri ngoai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.32 0.32 19.75 0.32 26.67 Partition/Door -0.42 -0.42 0.00 Diffuser 123 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 123 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 123 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 25.31 0.35 29.17 Sub Total ==> -0.42 -0.42 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 27.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 13.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.46 3.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.15 -55.88
Grand Total ==> 1.25 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.42 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.01 105 26.8 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 13 of 323
Room Checksums
By Trane
T1-dieu tri noi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 12.84 0.19 17.76 Partition/Door -0.25 -0.25 0.00 Diffuser 110 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 110 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 110 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 18.92 0.22 20.56 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.61 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 29.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.33 2.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.01
W/m² 124.82 -39.18
Grand Total ==> 1.12 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.25 -0.67 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.47 0.87 92 26.8 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.47 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 14 of 323
Room Checksums
By Trane
T1-dieu tri noi 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.49 0.00 0.49 22.79 0.53 29.61 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 2.79 0.05 2.79 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.17 0.06 0.23 10.70 0.16 8.94 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 8.84 0.19 10.61 Partition/Door -0.25 -0.25 0.00 Diffuser 183 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 183 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 183 55
Infiltration 0.11 0.11 5.12 0.03 1.68 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.02 0.06 1.08 50.23 0.96 53.63 Sub Total ==> -0.28 -0.29 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 6.98 0.12 6.70 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.24 0 0 11.16 0.13 7.26 People 0.00 0 0.00 Return 185 55
Misc 0.52 0.00 0.52 24.19 0.52 29.05 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.88 0.03 0.91 42.33 0.77 43.02 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 3.35 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.15 6.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.79 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.26 RA Preheat Diff. -0.35 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.47 4.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.22
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.51
W/m² 181.45 -53.64
Grand Total ==> 1.96 -0.03 2.15 100.00 1.79 100.00 Grand Total ==> -0.28 -0.98 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.14 1.87 182 27.0 19.8 11.5 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 15 of 323
Room Checksums
By Trane
T1-dieu tri vo khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.49 0.00 0.49 22.79 0.53 29.61 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 2.79 0.05 2.79 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.17 0.06 0.23 10.70 0.16 8.94 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 8.84 0.19 10.61 Partition/Door -0.25 -0.25 0.00 Diffuser 183 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 183 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 183 55
Infiltration 0.11 0.11 5.12 0.03 1.68 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.02 0.06 1.08 50.23 0.96 53.63 Sub Total ==> -0.28 -0.29 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 6.98 0.12 6.70 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.24 0 0 11.16 0.13 7.26 People 0.00 0 0.00 Return 185 55
Misc 0.52 0.00 0.52 24.19 0.52 29.05 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.88 0.03 0.91 42.33 0.77 43.02 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 3.35 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.15 6.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.79 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.26 RA Preheat Diff. -0.35 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.47 4.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.22
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.51
W/m² 181.45 -53.64
Grand Total ==> 1.96 -0.03 2.15 100.00 1.79 100.00 Grand Total ==> -0.28 -0.98 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.14 1.87 182 27.0 19.8 11.5 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 16 of 323
Room Checksums
By Trane
T1-doi nguoi nha benh nhan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.37 0.45 1.82 29.74 1.37 47.24 Wall Cond -0.16 -0.21 13.82
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door -0.52 -0.52 34.21 Diffuser 214 64
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 214 64
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 214 64
Infiltration 0.46 0.46 7.52 0.09 3.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.83 0.45 2.28 37.25 1.46 50.34 Sub Total ==> -0.68 -0.73 48.03 Nom Vent 104 0
AHU Vent 104 0
Internal Loads Internal Loads Infil 12 0
Lights 0.44 0.11 0.55 8.99 0.44 15.17 Lights 0.00 0.00 0.00 MinStop/Rh 64 64
People 1.91 0 2 31.21 1.04 35.86 People 0.00 0 0.00 Return 227 64
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 116 0
Sub Total ==> 2.35 0.11 2.46 40.20 1.48 51.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.04 0.04 0.00 0.00 -0.04 -1.38 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.22 19.93 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.08 0.08 1.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 1.31 RA Preheat Diff. -0.41 26.97 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.42 27.63 % OA 48.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.04 -2.63 Lps/m² 4.80 1.44
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 34.95
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.28
W/m² 137.34 -24.63
Grand Total ==> 4.14 0.68 6.12 100.00 2.90 100.00 Grand Total ==> -0.68 -1.52 100.00 No. People 15

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 6.13 3.81 214 27.3 22.2 14.9 15.8 14.8 10.2 Floor 45 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 6.13 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 80 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 17 of 323
Room Checksums
By Trane
T1-giao ban dao tao

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.26 0.26 10.79 0.26 15.76 Partition/Door -0.52 -0.52 47.27 Diffuser 150 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 150 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 150 45
Infiltration 0.35 0.35 14.52 0.09 5.45 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.61 0.00 0.61 25.31 0.35 21.21 Sub Total ==> -0.52 -0.52 47.27 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 8 0
Lights 0.28 0.07 0.35 14.52 0.28 16.97 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.46 0 0 19.09 0.25 15.15 People 0.00 0 0.00 Return 158 45
Misc 0.67 0.00 0.67 27.80 0.67 40.61 Misc 0.00 0.00 0.00 Exhaust 33 0
Sub Total ==> 1.41 0.07 1.48 61.41 1.20 72.73 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 6.06 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.34 14.11 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -3.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.49 RA Preheat Diff. -0.29 26.36 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.29 26.36 % OA 16.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 5.22 1.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 62.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.93
W/m² 83.75 -28.01
Grand Total ==> 2.12 -0.11 2.41 100.00 1.65 100.00 Grand Total ==> -0.52 -1.10 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.41 1.71 150 27.2 20.6 12.5 15.9 15.9 11.4 Floor 29 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.41 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 18 of 323
Room Checksums
By Trane
T1-hanh chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.32 0.10 0.42 23.73 0.32 24.43 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.05 0.05 2.82 0.05 3.82 Partition/Door -0.10 -0.10 0.00 Diffuser 151 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 151 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 151 45
Infiltration 0.13 0.13 7.34 0.03 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.50 0.10 0.60 33.90 0.40 30.53 Sub Total ==> -0.12 -0.13 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 7.91 0.11 8.40 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.19 0 0 10.73 0.10 7.63 People 0.00 0 0.00 Return 154 45
Misc 0.67 0.00 0.67 37.85 0.67 51.15 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.97 0.03 1.00 56.50 0.88 67.18 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 2.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 7.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.39 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 6.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.04 3.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.56
W/m² 152.40 -27.29
Grand Total ==> 1.50 0.08 1.77 100.00 1.31 100.00 Grand Total ==> -0.12 -0.50 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.77 1.49 151 26.4 20.1 12.2 17.7 17.0 12.0 Floor 12 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 12 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 19 of 323
Room Checksums
By Trane
T1-hanh lang 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.26 0.00 0.26 1.24 0.27 2.80 Glass/Door Cond -0.07 -0.07 2.42
Cooling Heating
Wall Cond 0.02 0.26 0.28 1.33 0.02 0.21 Wall Cond 0.00 -0.03 1.04
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door -0.65 -0.65 22.49 Diffuser 857 257
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 857 257
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 857 257
Infiltration 2.96 2.96 14.07 0.59 6.12 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.24 0.26 3.50 16.63 0.88 9.13 Sub Total ==> -0.72 -0.75 25.95 Nom Vent 156 0
AHU Vent 156 0
Internal Loads Internal Loads Infil 76 0
Lights 2.78 0.69 3.47 16.49 2.78 28.84 Lights 0.00 0.00 0.00 MinStop/Rh 257 257
People 11.74 0 12 55.80 6.31 65.46 People 0.00 0 0.00 Return 934 257
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 232 0
Sub Total ==> 14.52 0.69 15.21 72.29 9.09 94.29 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.34 0.34 0.00 0.00 -0.33 -3.42 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.83 8.70 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.19 0.19 0.90 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.31 1.47 RA Preheat Diff. -1.05 36.33 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.07 37.02 % OA 18.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.69 Lps/m² 3.08 0.93
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 40.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 13.20
W/m² 75.69 -6.56
Grand Total ==> 17.42 1.48 21.04 100.00 9.64 100.00 Grand Total ==> -0.75 -2.89 100.00 No. People 93

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 21.05 11.59 854 26.6 21.5 14.0 17.7 15.0 9.7 Floor 278 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 74 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 21.05 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 52 39 74 Opt Vent 0.0 0 0.0 0.0
Ext Door 39 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 20 of 323
Room Checksums
By Trane
T1-hanh lang 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.51 0.48 1.99 1.95 1.59 3.21 Wall Cond -0.15 -0.19 1.32
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door -0.13 -0.13 0.90 Diffuser 3,688 1,106
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 3,688 1,106
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,688 1,106
Infiltration 14.24 14.24 13.98 2.87 5.79 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 15.75 0.48 16.23 15.94 4.46 9.00 Sub Total ==> -0.28 -0.32 2.22 Nom Vent 760 0
AHU Vent 760 0
Internal Loads Internal Loads Infil 373 0
Lights 13.55 3.39 16.94 16.64 13.55 27.34 Lights 0.00 0.00 0.00 MinStop/Rh 1,106 1,106
People 57.32 0 57 56.29 30.81 62.15 People 0.00 0 0.00 Return 4,061 1,106
Misc 0.94 0.00 0.94 0.92 0.94 1.90 Misc 0.00 0.00 0.00 Exhaust 1,133 0
Sub Total ==> 71.81 3.39 75.20 73.85 45.30 91.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.20 0.20 0.00 0.00 -0.19 -0.38 Ceiling Load -0.05 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 8.94 8.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.11 0.11 0.11 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 1.35 1.33 RA Preheat Diff. -7.01 48.68 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -7.04 48.89 % OA 20.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.03 0.21 Lps/m² 2.72 0.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 36.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 13.33
W/m² 75.00 -5.42
Grand Total ==> 87.36 4.18 101.83 100.00 49.57 100.00 Grand Total ==> -0.33 -14.40 100.00 No. People 452

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 101.82 56.27 3,672 27.2 21.7 14.1 15.9 14.4 9.7 Floor 1,357 Main Htg -7.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 101.82 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 74 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -7.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 21 of 323
Room Checksums
By Trane
T1-hanh lang 3-1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 16 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.26 0.41 1.67 3.66 1.43 7.19 Wall Cond -0.15 -0.19 0.75
Partition/Door -2.70 -2.70 -5.91 -2.70 -13.57 Partition/Door -19.71 -19.71 77.84 Diffuser 1,535 460
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,535 460
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,535 460
Infiltration 8.78 8.78 19.22 1.69 8.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.34 0.41 7.75 16.96 0.42 2.11 Sub Total ==> -19.86 -19.90 78.59 Nom Vent 448 0
AHU Vent 448 0
Internal Loads Internal Loads Infil 220 0
Lights 7.90 1.98 9.88 21.62 7.90 39.72 Lights 0.00 0.00 0.00 MinStop/Rh 460 460
People 20.58 0 21 45.04 11.21 56.36 People 0.00 0 0.00 Return 1,755 460
Misc 0.96 0.00 0.96 2.10 0.96 4.83 Misc 0.00 0.00 0.00 Exhaust 668 0
Sub Total ==> 29.44 1.98 31.42 68.77 20.07 100.90 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.63 0.63 0.00 0.00 -0.60 -3.02 Ceiling Load -0.05 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 5.60 12.26 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.36 0.36 0.79 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.56 1.23 RA Preheat Diff. -2.69 10.62 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -2.71 10.70 % OA 29.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.08 Lps/m² 1.92 0.58
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 33.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 17.51
W/m² 57.08 -28.25
Grand Total ==> 36.15 3.38 45.69 100.00 19.89 100.00 Grand Total ==> -19.91 -25.32 100.00 No. People 160

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 45.69 24.41 1,523 27.1 21.8 14.4 16.3 13.9 9.0 Floor 800 Main Htg -22.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 2,241 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 45.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 74 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -22.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 22 of 323
Room Checksums
By Trane
T1-hanh lang 3-2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.59 0.52 2.11 4.38 1.59 7.12 Wall Cond -0.15 -0.19 2.88
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,649 495
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,649 495
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,649 495
Infiltration 8.48 8.48 17.60 1.69 7.57 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 10.07 0.52 10.59 21.98 3.28 14.69 Sub Total ==> -0.15 -0.19 2.88 Nom Vent 448 0
AHU Vent 448 0
Internal Loads Internal Loads Infil 220 0
Lights 7.99 2.00 9.99 20.73 7.99 35.78 Lights 0.00 0.00 0.00 MinStop/Rh 495 495
People 20.27 0 20 42.06 10.90 48.81 People 0.00 0 0.00 Return 1,869 495
Misc 0.94 0.00 0.94 1.95 0.94 4.21 Misc 0.00 0.00 0.00 Exhaust 668 0
Sub Total ==> 29.20 2.00 31.20 64.74 19.83 88.80 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.78 0.78 0.00 0.00 -0.78 -3.49 Ceiling Load -0.06 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 5.34 11.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.45 0.45 0.93 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.61 1.27 RA Preheat Diff. -3.17 48.03 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -3.20 48.48 % OA 27.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.04 0.61 Lps/m² 2.06 0.62
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 34.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 16.60
W/m² 60.20 -4.26
Grand Total ==> 38.49 3.75 48.19 100.00 22.33 100.00 Grand Total ==> -0.21 -6.60 100.00 No. People 160

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 48.18 27.35 1,649 26.9 21.7 14.3 15.8 14.0 9.3 Floor 800 Main Htg -3.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 48.18 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 74 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -3.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 23 of 323
Room Checksums
By Trane
T1-hop dieu duong

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.55 0.19 13.97 Partition/Door -0.39 -0.39 0.00 Diffuser 156 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 156 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 156 47
Infiltration 0.26 0.26 13.07 0.06 4.41 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.45 0.00 0.45 22.61 0.25 18.38 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.07 0.21 15.44 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.34 0 0 17.09 0.18 13.24 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 33.67 0.67 49.26 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 63.82 1.06 77.94 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.68 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 12.56 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.01 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.02 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 11.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.40 2.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 78.68
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.63
W/m² 94.00 -27.80
Grand Total ==> 1.72 -0.04 1.99 100.00 1.36 100.00 Grand Total ==> -0.39 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.98 1.46 156 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.98 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 24 of 323
Room Checksums
By Trane
T1-kham ngoai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.32 0.32 19.75 0.32 26.67 Partition/Door -0.42 -0.42 0.00 Diffuser 123 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 123 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 123 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 25.31 0.35 29.17 Sub Total ==> -0.42 -0.42 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 27.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 13.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.46 3.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.15 -55.88
Grand Total ==> 1.25 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.42 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.01 105 26.8 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 25 of 323
Room Checksums
By Trane
T1-kham ngoai 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.32 0.32 19.75 0.32 26.67 Partition/Door -0.42 -0.42 0.00 Diffuser 123 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 123 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 123 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 25.31 0.35 29.17 Sub Total ==> -0.42 -0.42 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 27.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 13.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.46 3.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.15 -55.88
Grand Total ==> 1.25 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.42 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.01 105 26.8 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 26 of 323
Room Checksums
By Trane
T1-kham noi 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.31 0.31 17.71 0.31 24.60 Partition/Door -0.41 -0.41 0.00 Diffuser 129 39
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 129 39
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 129 39
Infiltration 0.10 0.10 5.71 0.04 3.17 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 23.43 0.35 27.78 Sub Total ==> -0.41 -0.41 0.00 Nom Vent 16 0
AHU Vent 16 0
Internal Loads Internal Loads Infil 3 0
Lights 0.10 0.03 0.13 7.43 0.14 11.11 Lights 0.00 0.00 0.00 MinStop/Rh 39 39
People 0.28 0 0 16.00 0.16 12.70 People 0.00 0 0.00 Return 132 39
Misc 0.45 0.00 0.45 25.71 0.54 42.86 Misc 0.00 0.00 0.00 Exhaust 19 0
Sub Total ==> 0.83 0.03 0.86 49.14 0.84 66.67 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 5.56 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.52 29.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -4.57 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.29 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 15.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.20 2.76
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.69
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.01
W/m² 124.72 -46.74
Grand Total ==> 1.31 -0.12 1.75 100.00 1.26 100.00 Grand Total ==> -0.41 -0.90 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.75 1.03 109 26.8 20.7 12.9 15.9 15.9 11.4 Floor 14 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 46 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.75 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 27 of 323
Room Checksums
By Trane
T1-kham noi 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 12.84 0.19 17.76 Partition/Door -0.25 -0.25 0.00 Diffuser 110 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 110 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 110 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 18.92 0.22 20.56 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.61 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 29.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.33 2.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.01
W/m² 124.82 -39.18
Grand Total ==> 1.12 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.25 -0.67 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.47 0.87 92 26.8 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.47 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 28 of 323
Room Checksums
By Trane
T1-kham noi 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.32 0.32 19.75 0.32 26.67 Partition/Door -0.42 -0.42 0.00 Diffuser 123 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 123 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 123 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 25.31 0.35 29.17 Sub Total ==> -0.42 -0.42 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 27.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 13.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.46 3.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.15 -55.88
Grand Total ==> 1.25 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.42 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.01 105 26.8 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 29 of 323
Room Checksums
By Trane
T1-kho sach 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 4.58 0.06 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 95 28
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 95 28
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 95 28
Infiltration 0.13 0.13 9.92 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.19 0.00 0.19 14.50 0.09 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 10.69 0.11 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 28 28
People 0.17 0 0 12.98 0.09 0.00 People 0.00 0 0.00 Return 98 28
Misc 0.67 0.00 0.67 51.15 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.95 0.03 0.98 74.81 0.87 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 9.92 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.29 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 10.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.68 2.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 72.23
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.33
W/m² 120.03 -26.92
Grand Total ==> 1.17 -0.02 1.31 100.00 0.99 100.00 Grand Total ==> -0.13 -0.47 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.31 1.04 94 26.7 20.2 12.3 16.3 16.3 11.7 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.31 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 30 of 323
Room Checksums
By Trane
T1-kho sach 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 4.58 0.06 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 89 27
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 89 27
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 89 27
Infiltration 0.13 0.13 9.92 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.19 0.00 0.19 14.50 0.09 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 10.69 0.11 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 27 27
People 0.17 0 0 12.98 0.09 0.00 People 0.00 0 0.00 Return 92 27
Misc 0.67 0.00 0.67 51.15 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.95 0.03 0.98 74.81 0.87 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 9.92 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.29 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 10.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.20 2.46
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 68.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.33
W/m² 119.92 -27.52
Grand Total ==> 1.17 -0.02 1.31 100.00 0.99 100.00 Grand Total ==> -0.13 -0.47 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.31 1.04 89 26.6 20.2 12.3 15.8 15.8 11.3 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.31 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 31 of 323
Room Checksums
By Trane
T1-khth

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.32 0.10 0.42 23.73 0.32 24.43 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.05 0.05 2.82 0.05 3.82 Partition/Door -0.10 -0.10 0.00 Diffuser 151 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 151 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 151 45
Infiltration 0.13 0.13 7.34 0.03 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.50 0.10 0.60 33.90 0.40 30.53 Sub Total ==> -0.12 -0.13 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 7.91 0.11 8.40 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.19 0 0 10.73 0.10 7.63 People 0.00 0 0.00 Return 154 45
Misc 0.67 0.00 0.67 37.85 0.67 51.15 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.97 0.03 1.00 56.50 0.88 67.18 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 2.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 7.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.39 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 6.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.04 3.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.56
W/m² 152.40 -27.29
Grand Total ==> 1.50 0.08 1.77 100.00 1.31 100.00 Grand Total ==> -0.12 -0.50 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.77 1.49 151 26.4 20.1 12.2 17.7 17.0 12.0 Floor 12 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 12 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 32 of 323
Room Checksums
By Trane
T1-khu vuc tam luu 12 giuong

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 453 136
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 453 136
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 453 136
Infiltration 1.55 1.55 19.11 0.34 7.64 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.55 0.00 1.55 19.11 0.34 7.64 Sub Total ==> 0.00 0.00 0.00 Nom Vent 104 0
AHU Vent 104 0
Internal Loads Internal Loads Infil 36 0
Lights 1.24 0.31 1.55 19.11 1.24 27.87 Lights 0.00 0.00 0.00 MinStop/Rh 136 136
People 3.21 0 3 39.58 1.69 37.98 People 0.00 0 0.00 Return 489 136
Misc 0.63 0.00 0.63 7.77 0.63 14.16 Misc 0.00 0.00 0.00 Exhaust 140 0
Sub Total ==> 5.08 0.31 5.39 66.46 3.56 80.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.55 -0.55 0.00 0.00 0.55 12.36 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.41 17.39 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.41 -0.41 -5.06 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.17 2.10 RA Preheat Diff. -0.87 49.15 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.88 49.72 % OA 23.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 1.13 Lps/m² 3.48 1.05
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 55.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 16.00
W/m² 62.48 -6.83
Grand Total ==> 7.18 -0.65 8.11 100.00 4.45 100.00 Grand Total ==> -0.01 -1.77 100.00 No. People 26

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 8.13 4.42 451 26.6 20.0 12.1 15.8 15.2 10.6 Floor 130 Main Htg -0.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.13 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 33 of 323
Room Checksums
By Trane
T1-lay benh pham

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.32 0.32 19.75 0.32 26.67 Partition/Door -0.42 -0.42 0.00 Diffuser 123 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 123 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 123 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 25.31 0.35 29.17 Sub Total ==> -0.42 -0.42 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 27.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 13.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.46 3.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.15 -55.88
Grand Total ==> 1.25 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.42 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.01 105 26.8 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 34 of 323
Room Checksums
By Trane
T1-nhan vien

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 86 26
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 86 26
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 86 26
Infiltration 0.13 0.13 10.57 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.13 0.00 0.13 10.57 0.03 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 11.38 0.11 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 26 26
People 0.17 0 0 13.82 0.09 0.00 People 0.00 0 0.00 Return 89 26
Misc 0.67 0.00 0.67 54.47 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.95 0.03 0.98 79.67 0.87 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.12 9.76 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -2.44 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.44 RA Preheat Diff. -0.16 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.16 0.00 % OA 10.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.98 2.39
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 70.00
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.77
W/m² 113.93 -15.26
Grand Total ==> 1.12 -0.04 1.23 100.00 0.94 100.00 Grand Total ==> 0.00 -0.32 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.23 0.98 86 27.1 20.4 12.4 15.9 15.9 11.4 Floor 11 Main Htg -0.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 28 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.23 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 35 of 323
Room Checksums
By Trane
T1-nhan vien 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.77 0.13 10.00 Partition/Door -0.26 -0.26 0.00 Diffuser 149 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 149 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 149 45
Infiltration 0.26 0.26 13.54 0.06 4.62 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.39 0.00 0.39 20.31 0.19 14.62 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.54 0.21 16.15 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.34 0 0 17.71 0.18 13.85 People 0.00 0 0.00 Return 155 45
Misc 0.67 0.00 0.67 34.90 0.67 51.54 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 66.15 1.06 81.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.85 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 13.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.60 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 12.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.05 2.11
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.01
W/m² 90.80 -21.22
Grand Total ==> 1.66 -0.04 1.92 100.00 1.30 100.00 Grand Total ==> -0.26 -0.64 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.92 1.39 148 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.92 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 36 of 323
Room Checksums
By Trane
T1-nhan vien 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.77 0.13 10.00 Partition/Door -0.26 -0.26 0.00 Diffuser 149 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 149 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 149 45
Infiltration 0.26 0.26 13.54 0.06 4.62 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.39 0.00 0.39 20.31 0.19 14.62 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.54 0.21 16.15 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.34 0 0 17.71 0.18 13.85 People 0.00 0 0.00 Return 155 45
Misc 0.67 0.00 0.67 34.90 0.67 51.54 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 66.15 1.06 81.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.85 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 13.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.60 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 12.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.05 2.11
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.01
W/m² 90.80 -21.22
Grand Total ==> 1.66 -0.04 1.92 100.00 1.30 100.00 Grand Total ==> -0.26 -0.64 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.92 1.39 148 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.92 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 37 of 323
Room Checksums
By Trane
T1-nhan vien 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.77 0.13 10.00 Partition/Door -0.26 -0.26 0.00 Diffuser 149 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 149 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 149 45
Infiltration 0.26 0.26 13.54 0.06 4.62 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.39 0.00 0.39 20.31 0.19 14.62 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.54 0.21 16.15 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.34 0 0 17.71 0.18 13.85 People 0.00 0 0.00 Return 155 45
Misc 0.67 0.00 0.67 34.90 0.67 51.54 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 66.15 1.06 81.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.85 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 13.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.60 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 12.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.05 2.11
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.01
W/m² 90.80 -21.22
Grand Total ==> 1.66 -0.04 1.92 100.00 1.30 100.00 Grand Total ==> -0.26 -0.64 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.92 1.39 148 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.92 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 38 of 323
Room Checksums
By Trane
T1-nhan vien 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 134 40
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 134 40
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 134 40
Infiltration 0.26 0.26 14.53 0.06 5.13 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.26 0.00 0.26 14.53 0.06 5.13 Sub Total ==> 0.00 0.00 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 14.53 0.21 17.95 Lights 0.00 0.00 0.00 MinStop/Rh 40 40
People 0.34 0 0 18.99 0.18 15.38 People 0.00 0 0.00 Return 140 40
Misc 0.67 0.00 0.67 37.43 0.67 57.26 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 70.95 1.06 90.60 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 4.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 13.97 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.23 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.79 RA Preheat Diff. -0.16 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 13.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 6.35 1.90
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.16
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.84
W/m² 84.39 -8.04
Grand Total ==> 1.53 -0.04 1.79 100.00 1.17 100.00 Grand Total ==> 0.00 -0.34 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.78 1.25 133 26.5 20.3 12.4 17.7 16.8 11.7 Floor 21 Main Htg -0.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.78 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 39 of 323
Room Checksums
By Trane
T1-nhan vien chi dao tuyen

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.93 0.28 1.21 31.84 0.93 36.61 Wall Cond -0.07 -0.09 8.18
Partition/Door 0.15 0.15 3.95 0.15 5.91 Partition/Door -0.30 -0.30 27.27 Diffuser 291 87
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 291 87
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 291 87
Infiltration 0.39 0.39 10.26 0.09 3.54 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.47 0.28 1.75 46.05 1.17 46.06 Sub Total ==> -0.37 -0.39 35.45 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 9 0
Lights 0.33 0.08 0.41 10.79 0.33 12.99 Lights 0.00 0.00 0.00 MinStop/Rh 87 87
People 0.54 0 1 14.21 0.29 11.42 People 0.00 0 0.00 Return 300 87
Misc 0.67 0.00 0.67 17.63 0.67 26.38 Misc 0.00 0.00 0.00 Exhaust 38 0
Sub Total ==> 1.54 0.08 1.62 42.63 1.29 50.79 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 3.15 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.38 10.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -1.58 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.11 2.89 RA Preheat Diff. -0.36 32.73 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.36 32.73 % OA 10.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.91 Lps/m² 8.69 2.61
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.83
W/m² 113.19 -21.85
Grand Total ==> 3.09 0.22 3.80 100.00 2.54 100.00 Grand Total ==> -0.37 -1.10 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.79 2.99 291 26.5 20.2 12.3 17.7 16.8 11.7 Floor 34 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 34 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.79 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 34 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 40 of 323
Room Checksums
By Trane
T1-nhan vien dieu duong

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.58 0.17 0.75 27.37 0.58 30.37 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.13 0.13 4.74 0.13 6.81 Partition/Door -0.26 -0.26 0.00 Diffuser 219 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 219 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 219 66
Infiltration 0.26 0.26 9.49 0.06 3.14 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.97 0.17 1.14 41.61 0.77 40.31 Sub Total ==> -0.32 -0.34 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 10.22 0.22 11.52 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.36 0 0 13.14 0.20 10.47 People 0.00 0 0.00 Return 225 66
Misc 0.67 0.00 0.67 24.45 0.67 35.08 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 47.81 1.09 57.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 2.62 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.12 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.92 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 8.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 9.73 2.92
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.19
W/m² 121.98 -26.43
Grand Total ==> 2.27 0.14 2.74 100.00 1.91 100.00 Grand Total ==> -0.32 -0.87 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.75 2.20 219 26.5 20.1 12.3 17.7 16.9 11.8 Floor 23 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.75 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 41 of 323
Room Checksums
By Trane
T1-nhan vien KHTH

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.60 0.18 0.78 29.00 0.60 31.91 Wall Cond -0.04 -0.06 0.00
Partition/Door 0.10 0.10 3.72 0.10 5.32 Partition/Door -0.19 -0.19 0.00 Diffuser 215 64
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 215 64
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 215 64
Infiltration 0.25 0.25 9.29 0.06 3.19 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.95 0.18 1.13 42.01 0.76 40.43 Sub Total ==> -0.23 -0.25 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 9.67 0.21 11.17 Lights 0.00 0.00 0.00 MinStop/Rh 64 64
People 0.35 0 0 13.01 0.19 10.11 People 0.00 0 0.00 Return 220 64
Misc 0.67 0.00 0.67 24.91 0.67 35.64 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 47.58 1.07 56.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 2.66 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.24 8.92 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.49 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.97 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 8.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.98 2.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.00
W/m² 124.94 -23.47
Grand Total ==> 2.23 0.14 2.69 100.00 1.88 100.00 Grand Total ==> -0.23 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.69 2.17 215 26.5 20.1 12.3 17.7 16.8 11.8 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 22 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 42 of 323
Room Checksums
By Trane
T1-nhan vien quan nhu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.58 0.17 0.75 27.37 0.58 30.37 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.13 0.13 4.74 0.13 6.81 Partition/Door -0.26 -0.26 0.00 Diffuser 219 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 219 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 219 66
Infiltration 0.26 0.26 9.49 0.06 3.14 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.97 0.17 1.14 41.61 0.77 40.31 Sub Total ==> -0.32 -0.34 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 10.22 0.22 11.52 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.36 0 0 13.14 0.20 10.47 People 0.00 0 0.00 Return 225 66
Misc 0.67 0.00 0.67 24.45 0.67 35.08 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 47.81 1.09 57.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 2.62 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.12 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.92 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 8.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 9.73 2.92
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.19
W/m² 121.98 -26.43
Grand Total ==> 2.27 0.14 2.74 100.00 1.91 100.00 Grand Total ==> -0.32 -0.87 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.75 2.20 219 26.5 20.1 12.3 17.7 16.9 11.8 Floor 23 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.75 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 43 of 323
Room Checksums
By Trane
T1-p bac si

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.12 0.12 5.31 0.12 7.95 Partition/Door -0.24 -0.24 0.00 Diffuser 137 41
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 137 41
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 137 41
Infiltration 0.35 0.35 15.49 0.09 5.96 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.47 0.00 0.47 20.80 0.21 13.91 Sub Total ==> -0.24 -0.24 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 8 0
Lights 0.28 0.07 0.35 15.49 0.28 18.54 Lights 0.00 0.00 0.00 MinStop/Rh 41 41
People 0.46 0 0 20.35 0.25 16.56 People 0.00 0 0.00 Return 145 41
Misc 0.67 0.00 0.67 29.65 0.67 44.37 Misc 0.00 0.00 0.00 Exhaust 33 0
Sub Total ==> 1.41 0.07 1.48 65.49 1.20 79.47 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 6.62 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.34 15.04 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -3.54 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.21 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 0.00 % OA 18.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 4.75 1.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 60.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.74
W/m² 78.43 -17.58
Grand Total ==> 1.98 -0.11 2.26 100.00 1.51 100.00 Grand Total ==> -0.24 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.26 1.55 137 27.2 20.6 12.6 15.9 15.9 11.4 Floor 29 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 28 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.26 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 44 of 323
Room Checksums
By Trane
T1-p chuan bi dieu khien 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 7.34 0.19 11.45 Partition/Door -0.37 -0.37 0.00 Diffuser 157 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 157 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 157 47
Infiltration 0.41 0.41 15.83 0.10 6.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 0.00 0.60 23.17 0.29 17.47 Sub Total ==> -0.37 -0.37 0.00 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 9 0
Lights 0.32 0.08 0.40 15.44 0.32 19.28 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.53 0 1 20.46 0.29 17.47 People 0.00 0 0.00 Return 166 47
Misc 0.67 0.00 0.67 25.87 0.67 40.36 Misc 0.00 0.00 0.00 Exhaust 38 0
Sub Total ==> 1.52 0.08 1.60 61.78 1.28 77.11 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 5.42 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.40 15.44 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.70 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.32 RA Preheat Diff. -0.28 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.28 0.00 % OA 18.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 4.75 1.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 61.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.87
W/m² 77.66 -19.63
Grand Total ==> 2.21 -0.08 2.59 100.00 1.66 100.00 Grand Total ==> -0.37 -0.93 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.57 1.73 157 26.9 20.5 12.6 16.3 16.2 11.6 Floor 33 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 42 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.57 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 45 of 323
Room Checksums
By Trane
T1-p chuan bi dieu khien 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 7.34 0.19 11.45 Partition/Door -0.37 -0.37 0.00 Diffuser 157 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 157 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 157 47
Infiltration 0.41 0.41 15.83 0.10 6.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 0.00 0.60 23.17 0.29 17.47 Sub Total ==> -0.37 -0.37 0.00 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 9 0
Lights 0.32 0.08 0.40 15.44 0.32 19.28 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.53 0 1 20.46 0.29 17.47 People 0.00 0 0.00 Return 166 47
Misc 0.67 0.00 0.67 25.87 0.67 40.36 Misc 0.00 0.00 0.00 Exhaust 38 0
Sub Total ==> 1.52 0.08 1.60 61.78 1.28 77.11 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 5.42 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.40 15.44 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.70 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.32 RA Preheat Diff. -0.28 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.28 0.00 % OA 18.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 4.75 1.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 61.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.87
W/m² 77.66 -19.63
Grand Total ==> 2.21 -0.08 2.59 100.00 1.66 100.00 Grand Total ==> -0.37 -0.93 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.57 1.73 157 26.9 20.5 12.6 16.3 16.2 11.6 Floor 33 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 42 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.57 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 46 of 323
Room Checksums
By Trane
T1-p yta ho ly

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 4.48 0.06 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 91 27
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 91 27
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 91 27
Infiltration 0.14 0.14 10.45 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.20 0.00 0.20 14.93 0.09 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 10.45 0.11 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 27 27
People 0.18 0 0 13.43 0.10 0.00 People 0.00 0 0.00 Return 94 27
Misc 0.67 0.00 0.67 50.00 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.96 0.03 0.99 73.88 0.88 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 10.45 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.49 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.24 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.18 0.00 % OA 11.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.88 2.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 67.72
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.59
W/m² 116.32 -26.31
Grand Total ==> 1.19 -0.02 1.34 100.00 1.00 100.00 Grand Total ==> -0.13 -0.48 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.34 1.05 91 26.6 20.2 12.4 15.8 15.8 11.3 Floor 12 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.34 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 47 of 323
Room Checksums
By Trane
T1-phong bac si 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.18 0.00 2.18 52.15 2.18 61.58 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.07 0.00 0.07 1.67 0.07 1.98 Glass/Door Cond -0.04 -0.04 2.82
Cooling Heating
Wall Cond 0.04 0.07 0.11 2.63 0.04 1.13 Wall Cond -0.01 -0.01 0.70
Partition/Door 0.06 0.06 1.44 0.06 1.69 Partition/Door -0.13 -0.13 9.15 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.17 0.17 4.07 0.03 0.85 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.52 0.07 2.59 61.96 2.38 67.23 Sub Total ==> -0.18 -0.18 12.68 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 6.94 0.23 6.50 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.38 0 0 9.09 0.20 5.65 People 0.00 0 0.00 Return 327 96
Misc 0.67 0.00 0.67 16.03 0.67 18.93 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 32.06 1.10 31.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 1.69 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 4.07 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -0.96 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 2.87 RA Preheat Diff. -0.62 43.66 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.62 43.66 % OA 6.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.57 4.07
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.66
W/m² 176.71 -33.45
Grand Total ==> 3.86 0.03 4.18 100.00 3.54 100.00 Grand Total ==> -0.18 -1.42 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.17 3.74 320 26.4 20.0 12.1 15.8 15.8 11.3 Floor 24 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.17 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 9 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 48 of 323
Room Checksums
By Trane
T1-phong bac si 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.18 0.00 2.18 52.15 2.18 61.58 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.07 0.00 0.07 1.67 0.07 1.98 Glass/Door Cond -0.04 -0.04 2.82
Cooling Heating
Wall Cond 0.04 0.07 0.11 2.63 0.04 1.13 Wall Cond -0.01 -0.01 0.70
Partition/Door 0.06 0.06 1.44 0.06 1.69 Partition/Door -0.13 -0.13 9.15 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.17 0.17 4.07 0.03 0.85 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.52 0.07 2.59 61.96 2.38 67.23 Sub Total ==> -0.18 -0.18 12.68 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 6.94 0.23 6.50 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.38 0 0 9.09 0.20 5.65 People 0.00 0 0.00 Return 327 96
Misc 0.67 0.00 0.67 16.03 0.67 18.93 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 32.06 1.10 31.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 1.69 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 4.07 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -0.96 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 2.87 RA Preheat Diff. -0.62 43.66 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.62 43.66 % OA 6.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.57 4.07
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.66
W/m² 176.71 -33.45
Grand Total ==> 3.86 0.03 4.18 100.00 3.54 100.00 Grand Total ==> -0.18 -1.42 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.17 3.74 320 26.4 20.0 12.1 15.8 15.8 11.3 Floor 24 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.17 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 9 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 49 of 323
Room Checksums
By Trane
T1-phong benh nhan hap hoi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 14.07 0.19 18.27 Partition/Door -0.25 -0.25 0.00 Diffuser 112 34
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 112 34
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 112 34
Infiltration 0.08 0.08 5.93 0.03 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 20.00 0.22 21.15 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.07 0.02 0.09 6.67 0.11 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 34 34
People 0.21 0 0 15.56 0.12 11.54 People 0.00 0 0.00 Return 115 34
Misc 0.41 0.00 0.41 30.37 0.54 51.92 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 0.69 0.02 0.71 52.59 0.77 74.04 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 4.81 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.40 29.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -4.44 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.22 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 13.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.30 3.09
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.09
W/m² 123.52 -41.33
Grand Total ==> 1.01 -0.09 1.35 100.00 1.04 100.00 Grand Total ==> -0.25 -0.65 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.35 0.79 87 26.4 20.5 12.8 16.3 16.3 11.7 Floor 11 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.35 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 50 of 323
Room Checksums
By Trane
T1-phong chi dao

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.21 0.21 7.47 0.21 11.86 Partition/Door -0.41 -0.41 40.59 Diffuser 169 51
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 169 51
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 169 51
Infiltration 0.46 0.46 16.37 0.11 6.21 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.67 0.00 0.67 23.84 0.32 18.08 Sub Total ==> -0.41 -0.41 40.59 Nom Vent 32 0
AHU Vent 32 0
Internal Loads Internal Loads Infil 10 0
Lights 0.36 0.09 0.45 16.01 0.36 20.34 Lights 0.00 0.00 0.00 MinStop/Rh 51 51
People 0.59 0 1 21.00 0.32 18.08 People 0.00 0 0.00 Return 179 51
Misc 0.67 0.00 0.67 23.84 0.67 37.85 Misc 0.00 0.00 0.00 Exhaust 43 0
Sub Total ==> 1.62 0.09 1.71 60.85 1.35 76.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 5.65 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 16.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -2.85 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.14 RA Preheat Diff. -0.30 29.70 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 29.70 % OA 19.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 4.54 1.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 60.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 13.27
W/m² 75.31 -19.14
Grand Total ==> 2.39 -0.09 2.81 100.00 1.77 100.00 Grand Total ==> -0.41 -1.01 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.80 1.86 168 26.9 20.5 12.6 16.3 16.1 11.5 Floor 37 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 47 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.80 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 51 of 323
Room Checksums
By Trane
T1-phong chi dao 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.26 0.08 0.34 20.99 0.26 20.97 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.05 0.05 3.09 0.05 4.03 Partition/Door -0.10 -0.10 0.00 Diffuser 143 43
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 143 43
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 143 43
Infiltration 0.10 0.10 6.17 0.02 1.61 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.08 0.49 30.25 0.33 26.61 Sub Total ==> -0.12 -0.13 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 8.64 0.11 8.87 Lights 0.00 0.00 0.00 MinStop/Rh 43 43
People 0.19 0 0 11.73 0.10 8.06 People 0.00 0 0.00 Return 146 43
Misc 0.67 0.00 0.67 41.36 0.67 54.03 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.97 0.03 1.00 61.73 0.88 70.97 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 2.42 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.10 6.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.23 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 3.09 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.18 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 12.29 3.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 87.72
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.14
W/m² 140.02 -26.36
Grand Total ==> 1.41 0.06 1.62 100.00 1.24 100.00 Grand Total ==> -0.12 -0.48 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.62 1.39 143 26.3 20.0 12.2 17.7 17.0 12.0 Floor 12 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 12 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.62 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 52 of 323
Room Checksums
By Trane
T1-phong chieu x quang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.49 0.00 0.49 16.01 0.53 23.04 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.96 0.05 2.17 Glass/Door Cond -0.01 -0.01 0.71
Cooling Heating
Wall Cond 0.19 0.06 0.25 8.17 0.17 7.39 Wall Cond -0.02 -0.03 2.14
Partition/Door 0.35 0.35 11.44 0.35 15.22 Partition/Door -0.47 -0.47 33.57 Diffuser 238 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 238 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 238 71
Infiltration 0.24 0.24 7.84 0.05 2.17 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.33 0.06 1.39 45.42 1.15 50.00 Sub Total ==> -0.50 -0.51 36.43 Nom Vent 27 0
AHU Vent 27 0
Internal Loads Internal Loads Infil 5 0
Lights 0.24 0.06 0.30 9.80 0.24 10.43 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.50 0 1 16.34 0.26 11.30 People 0.00 0 0.00 Return 243 71
Misc 0.52 0.00 0.52 16.99 0.52 22.61 Misc 0.00 0.00 0.00 Exhaust 33 0
Sub Total ==> 1.26 0.06 1.32 43.14 1.02 44.35 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 5.65 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.38 12.42 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -3.92 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 2.94 RA Preheat Diff. -0.45 32.14 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.45 32.14 % OA 11.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.71 Lps/m² 9.62 2.89
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.86
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.10
W/m² 123.46 -38.61
Grand Total ==> 2.72 -0.13 3.06 100.00 2.30 100.00 Grand Total ==> -0.50 -1.40 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.05 2.42 237 27.1 19.9 11.7 15.9 15.9 11.4 Floor 25 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 53 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.05 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 53 of 323
Room Checksums
By Trane
T1-Phong doc xu ly hinh anh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 9.22 0.13 11.93 Partition/Door -0.25 -0.25 0.00 Diffuser 105 31
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 105 31
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 105 31
Infiltration 0.12 0.12 8.51 0.03 2.75 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.25 0.00 0.25 17.73 0.16 14.68 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 10.64 0.12 11.01 Lights 0.00 0.00 0.00 MinStop/Rh 31 31
People 0.20 0 0 14.18 0.11 10.09 People 0.00 0 0.00 Return 108 31
Misc 0.67 0.00 0.67 47.52 0.67 61.47 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.99 0.03 1.02 72.34 0.90 82.57 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.03 2.75 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.12 8.51 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.84 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.33 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.84
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.87
W/m² 112.74 -34.74
Grand Total ==> 1.28 -0.03 1.41 100.00 1.09 100.00 Grand Total ==> -0.25 -0.62 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.42 1.15 105 26.7 20.2 12.3 16.3 16.3 11.7 Floor 13 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.42 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 54 of 323
Room Checksums
By Trane
T1-phong giao ban 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.18 0.00 2.18 52.15 2.18 61.58 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.07 0.00 0.07 1.67 0.07 1.98 Glass/Door Cond -0.04 -0.04 2.82
Cooling Heating
Wall Cond 0.04 0.07 0.11 2.63 0.04 1.13 Wall Cond -0.01 -0.01 0.70
Partition/Door 0.06 0.06 1.44 0.06 1.69 Partition/Door -0.13 -0.13 9.15 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.17 0.17 4.07 0.03 0.85 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.52 0.07 2.59 61.96 2.38 67.23 Sub Total ==> -0.18 -0.18 12.68 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 6.94 0.23 6.50 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.38 0 0 9.09 0.20 5.65 People 0.00 0 0.00 Return 327 96
Misc 0.67 0.00 0.67 16.03 0.67 18.93 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 32.06 1.10 31.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 1.69 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 4.07 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -0.96 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 2.87 RA Preheat Diff. -0.62 43.66 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.62 43.66 % OA 6.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.57 4.07
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.66
W/m² 176.71 -33.45
Grand Total ==> 3.86 0.03 4.18 100.00 3.54 100.00 Grand Total ==> -0.18 -1.42 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.17 3.74 320 26.4 20.0 12.1 15.8 15.8 11.3 Floor 24 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.17 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 9 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 55 of 323
Room Checksums
By Trane
T1-phong hop hau can kt

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.55 0.19 13.97 Partition/Door -0.39 -0.39 0.00 Diffuser 156 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 156 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 156 47
Infiltration 0.26 0.26 13.07 0.06 4.41 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.45 0.00 0.45 22.61 0.25 18.38 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.07 0.21 15.44 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.34 0 0 17.09 0.18 13.24 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 33.67 0.67 49.26 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 63.82 1.06 77.94 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.68 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 12.56 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.01 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.02 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 11.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.40 2.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 78.68
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.63
W/m² 94.00 -27.80
Grand Total ==> 1.72 -0.04 1.99 100.00 1.36 100.00 Grand Total ==> -0.39 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.98 1.46 156 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.98 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 56 of 323
Room Checksums
By Trane
T1-phong kham noi soi 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.28 0.00 0.28 14.21 0.28 17.72 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.54 0.05 3.16 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.19 0.07 0.26 13.20 0.19 12.03 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 9.64 0.19 12.03 Partition/Door -0.26 -0.26 0.00 Diffuser 163 49
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 163 49
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 163 49
Infiltration 0.11 0.11 5.58 0.03 1.90 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.82 0.07 0.89 45.18 0.74 46.84 Sub Total ==> -0.29 -0.30 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 7.61 0.12 7.59 Lights 0.00 0.00 0.00 MinStop/Rh 49 49
People 0.24 0 0 12.18 0.13 8.23 People 0.00 0 0.00 Return 166 49
Misc 0.53 0.00 0.53 26.90 0.53 33.54 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.89 0.03 0.92 46.70 0.78 49.37 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 3.80 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 8.12 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -3.05 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.05 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 13.82 4.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.99
W/m² 166.92 -50.99
Grand Total ==> 1.77 -0.02 1.97 100.00 1.58 100.00 Grand Total ==> -0.29 -0.91 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.97 1.70 163 27.0 19.8 11.6 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.97 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 57 of 323
Room Checksums
By Trane
T1-phong kham noi soi 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.32 0.32 19.75 0.32 26.67 Partition/Door -0.42 -0.42 0.00 Diffuser 123 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 123 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 123 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.41 0.00 0.41 25.31 0.35 29.17 Sub Total ==> -0.42 -0.42 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 27.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 13.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.46 3.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.15 -55.88
Grand Total ==> 1.25 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.42 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 1.01 105 26.8 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 48 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 58 of 323
Room Checksums
By Trane
T1-phong kho phim phan loai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 13.10 0.19 17.59 Partition/Door -0.25 -0.25 0.00 Diffuser 117 35
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 117 35
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 117 35
Infiltration 0.09 0.09 6.21 0.03 2.78 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 19.31 0.22 20.37 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 3 0
Lights 0.08 0.02 0.10 6.90 0.12 11.11 Lights 0.00 0.00 0.00 MinStop/Rh 35 35
People 0.24 0 0 16.55 0.14 12.96 People 0.00 0 0.00 Return 120 35
Misc 0.41 0.00 0.41 28.28 0.54 50.00 Misc 0.00 0.00 0.00 Exhaust 17 0
Sub Total ==> 0.73 0.02 0.75 51.72 0.80 74.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.06 5.56 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 31.03 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -4.14 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.07 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.37 2.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.60
W/m² 116.26 -36.74
Grand Total ==> 1.06 -0.09 1.45 100.00 1.08 100.00 Grand Total ==> -0.25 -0.67 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.45 0.82 91 26.4 20.6 12.9 16.3 16.3 11.7 Floor 13 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.45 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 59 of 323
Room Checksums
By Trane
T1-Phong kt can thiep 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 10 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 24 / 18 OADB: 32 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 179 54
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 179 54
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 179 54
Infiltration 0.12 0.12 6.25 0.05 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.12 0.00 0.12 6.25 0.05 2.86 Sub Total ==> 0.00 0.00 0.00 Nom Vent 27 0
AHU Vent 27 0
Internal Loads Internal Loads Infil 5 0
Lights 0.17 0.04 0.21 10.94 0.19 10.86 Lights 0.00 0.00 0.00 MinStop/Rh 54 54
People 0.45 0 0 23.44 0.25 14.29 People 0.00 0 0.00 Return 184 54
Misc 0.57 0.00 0.57 29.69 0.63 36.00 Misc 0.00 0.00 0.00 Exhaust 32 0
Sub Total ==> 1.19 0.04 1.23 64.06 1.07 61.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 4.57 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.62 32.29 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.55 31.43 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -4.69 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.08 RA Preheat Diff. -0.34 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 15.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.17 2.75
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.92
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.14
W/m² 98.59 -17.85
Grand Total ==> 1.39 -0.13 1.92 100.00 1.75 100.00 Grand Total ==> 0.00 -0.69 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.92 1.04 107 26.3 20.7 13.1 15.8 15.8 11.3 Floor 20 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.92 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 60 of 323
Room Checksums
By Trane
T1-Phong kt can thiep 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.85 0.24 1.09 40.52 0.85 44.50 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 194 58
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 194 58
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 194 58
Infiltration 0.19 0.19 7.06 0.05 2.62 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.04 0.24 1.28 47.58 0.90 47.12 Sub Total ==> -0.06 -0.08 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 4 0
Lights 0.19 0.05 0.24 8.92 0.19 9.95 Lights 0.00 0.00 0.00 MinStop/Rh 58 58
People 0.39 0 0 14.50 0.21 10.99 People 0.00 0 0.00 Return 198 58
Misc 0.52 0.00 0.52 19.33 0.52 27.23 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.10 0.05 1.15 42.75 0.92 48.17 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 10.04 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -2.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.60 RA Preheat Diff. -0.37 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.38 0.00 % OA 11.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 9.95 2.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.99
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.24
W/m² 138.11 -22.40
Grand Total ==> 2.23 0.12 2.69 100.00 1.91 100.00 Grand Total ==> -0.06 -0.82 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.69 2.21 194 26.6 19.7 11.7 15.8 15.8 11.3 Floor 20 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 61 of 323
Room Checksums
By Trane
T1-phong nghi benh nhan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 13.10 0.19 17.59 Partition/Door -0.25 -0.25 0.00 Diffuser 117 35
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 117 35
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 117 35
Infiltration 0.09 0.09 6.21 0.03 2.78 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 19.31 0.22 20.37 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 3 0
Lights 0.08 0.02 0.10 6.90 0.12 11.11 Lights 0.00 0.00 0.00 MinStop/Rh 35 35
People 0.24 0 0 16.55 0.14 12.96 People 0.00 0 0.00 Return 120 35
Misc 0.41 0.00 0.41 28.28 0.54 50.00 Misc 0.00 0.00 0.00 Exhaust 17 0
Sub Total ==> 0.73 0.02 0.75 51.72 0.80 74.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.06 5.56 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 31.03 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -4.14 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.07 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.37 2.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.60
W/m² 116.26 -36.74
Grand Total ==> 1.06 -0.09 1.45 100.00 1.08 100.00 Grand Total ==> -0.25 -0.67 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.45 0.82 91 26.4 20.6 12.9 16.3 16.3 11.7 Floor 13 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.45 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 62 of 323
Room Checksums
By Trane
T1-phong noi soi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 12.84 0.19 17.76 Partition/Door -0.25 -0.25 0.00 Diffuser 110 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 110 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 110 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 18.92 0.22 20.56 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 5.61 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 29.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.33 2.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.01
W/m² 124.82 -39.18
Grand Total ==> 1.12 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.25 -0.67 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.47 0.87 92 26.8 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.47 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 63 of 323
Room Checksums
By Trane
T1-phong rua tiet trung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 32 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.09 0.09 7.09 0.09 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 100 30
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 100 30
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 100 30
Infiltration 0.08 0.08 6.30 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.17 0.00 0.17 13.39 0.12 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 15 0
AHU Vent 15 0
Internal Loads Internal Loads Infil 3 0
Lights 0.08 0.02 0.10 7.87 0.10 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 30 30
People 0.21 0 0 16.54 0.13 0.00 People 0.00 0 0.00 Return 103 30
Misc 0.42 0.00 0.42 33.07 0.59 0.00 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 0.71 0.02 0.73 57.48 0.82 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.05 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.39 30.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -3.94 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.36 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 15.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.20 2.76
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.60
W/m² 116.19 -29.46
Grand Total ==> 0.92 -0.07 1.27 100.00 0.99 100.00 Grand Total ==> -0.13 -0.51 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.27 0.71 74 26.2 20.6 13.0 15.8 15.8 11.3 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.27 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 64 of 323
Room Checksums
By Trane
T1-phong truc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 16.1 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.28 0.08 0.36 15.00 0.32 18.50 Wall Cond -0.03 -0.04 3.85
Partition/Door 0.20 0.20 8.33 0.20 11.56 Partition/Door -0.40 -0.40 38.46 Diffuser 156 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 156 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 156 47
Infiltration 0.25 0.25 10.42 0.04 2.31 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.73 0.08 0.81 33.75 0.56 32.37 Sub Total ==> -0.43 -0.44 42.31 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 12.08 0.23 13.29 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.38 0 0 15.83 0.21 12.14 People 0.00 0 0.00 Return 163 47
Misc 0.67 0.00 0.67 27.92 0.67 38.73 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 55.83 1.11 64.16 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.24 10.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -2.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.50 RA Preheat Diff. -0.30 28.85 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 28.85 % OA 13.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.62 1.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 64.94
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.81
W/m² 101.93 -30.95
Grand Total ==> 2.07 0.03 2.40 100.00 1.73 100.00 Grand Total ==> -0.43 -1.04 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.41 1.85 154 26.6 20.2 12.4 15.8 15.8 11.3 Floor 24 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 45 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.41 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 65 of 323
Room Checksums
By Trane
T1-phong X quang tong hop 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.39 0.39 14.55 0.39 23.21 Partition/Door -0.52 -0.52 44.83 Diffuser 182 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 182 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 182 55
Infiltration 0.20 0.20 7.46 0.07 4.17 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.59 0.00 0.59 22.01 0.46 27.38 Sub Total ==> -0.52 -0.52 44.83 Nom Vent 30 0
AHU Vent 30 0
Internal Loads Internal Loads Infil 6 0
Lights 0.18 0.05 0.23 8.58 0.26 15.48 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.52 0 1 19.40 0.30 17.86 People 0.00 0 0.00 Return 188 55
Misc 0.41 0.00 0.41 15.30 0.54 32.14 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 1.11 0.05 1.16 43.28 1.10 65.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 7.14 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.02 38.06 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.14 -0.14 -5.22 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 1.87 RA Preheat Diff. -0.32 27.59 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 27.59 % OA 20.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.78 2.03
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 67.69
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.98
W/m² 100.14 -31.39
Grand Total ==> 1.82 -0.21 2.68 100.00 1.68 100.00 Grand Total ==> -0.52 -1.16 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.68 1.26 143 26.3 21.0 13.5 16.3 16.1 11.5 Floor 27 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.68 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 66 of 323
Room Checksums
By Trane
T1-phong X quang tong hop 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.39 0.39 14.55 0.39 23.21 Partition/Door -0.52 -0.52 44.83 Diffuser 182 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 182 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 182 55
Infiltration 0.20 0.20 7.46 0.07 4.17 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.59 0.00 0.59 22.01 0.46 27.38 Sub Total ==> -0.52 -0.52 44.83 Nom Vent 30 0
AHU Vent 30 0
Internal Loads Internal Loads Infil 6 0
Lights 0.18 0.05 0.23 8.58 0.26 15.48 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.52 0 1 19.40 0.30 17.86 People 0.00 0 0.00 Return 188 55
Misc 0.41 0.00 0.41 15.30 0.54 32.14 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 1.11 0.05 1.16 43.28 1.10 65.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 7.14 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.02 38.06 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.14 -0.14 -5.22 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 1.87 RA Preheat Diff. -0.32 27.59 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 27.59 % OA 20.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.78 2.03
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 67.69
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.98
W/m² 100.14 -31.39
Grand Total ==> 1.82 -0.21 2.68 100.00 1.68 100.00 Grand Total ==> -0.52 -1.16 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.68 1.26 143 26.3 21.0 13.5 16.3 16.1 11.5 Floor 27 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.68 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 67 of 323
Room Checksums
By Trane
T1-phong X quang tong hop 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 11 Mo/Hr: 9 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 22 OADB: 30 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.03 0.00 2.03 42.03 2.10 54.97 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.15 0.00 0.15 3.11 0.12 3.14 Glass/Door Cond -0.04 -0.04 2.11
Cooling Heating
Wall Cond 0.05 0.06 0.11 2.28 0.04 1.05 Wall Cond -0.01 -0.02 1.05
Partition/Door 0.29 0.29 6.00 0.29 7.59 Partition/Door -0.39 -0.39 20.53 Diffuser 412 124
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 412 124
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 412 124
Infiltration 0.30 0.30 6.21 0.06 1.57 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.82 0.06 2.88 59.63 2.61 68.32 Sub Total ==> -0.44 -0.45 23.68 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 7 0
Lights 0.23 0.06 0.29 6.00 0.23 6.02 Lights 0.00 0.00 0.00 MinStop/Rh 124 124
People 0.61 0 1 12.63 0.30 7.85 People 0.00 0 0.00 Return 420 124
Misc 0.56 0.00 0.56 11.59 0.56 14.66 Misc 0.00 0.00 0.00 Exhaust 45 0
Sub Total ==> 1.40 0.06 1.46 30.23 1.09 28.53 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 3.14 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.48 9.94 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.14 -0.14 -2.90 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.15 3.11 RA Preheat Diff. -0.72 37.89 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.73 38.42 % OA 9.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 15.38 4.61
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.54
W/m² 180.32 -43.47
Grand Total ==> 4.34 -0.14 4.83 100.00 3.82 100.00 Grand Total ==> -0.44 -1.90 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.83 3.98 410 26.6 19.7 11.6 16.3 16.2 11.6 Floor 27 Main Htg -1.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.83 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 16 10 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 68 of 323
Room Checksums
By Trane
T1-quan luc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.32 0.10 0.42 23.73 0.32 24.43 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.05 0.05 2.82 0.05 3.82 Partition/Door -0.10 -0.10 0.00 Diffuser 151 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 151 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 151 45
Infiltration 0.13 0.13 7.34 0.03 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.50 0.10 0.60 33.90 0.40 30.53 Sub Total ==> -0.12 -0.13 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 7.91 0.11 8.40 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.19 0 0 10.73 0.10 7.63 People 0.00 0 0.00 Return 154 45
Misc 0.67 0.00 0.67 37.85 0.67 51.15 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.97 0.03 1.00 56.50 0.88 67.18 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 2.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 7.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.39 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 6.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.04 3.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.56
W/m² 152.40 -27.29
Grand Total ==> 1.50 0.08 1.77 100.00 1.31 100.00 Grand Total ==> -0.12 -0.50 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.77 1.49 151 26.4 20.1 12.2 17.7 17.0 12.0 Floor 12 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 12 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 69 of 323
Room Checksums
By Trane
T1-rua tiet trung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.49 0.00 0.49 22.79 0.53 29.61 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 2.79 0.05 2.79 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.17 0.06 0.23 10.70 0.16 8.94 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 8.84 0.19 10.61 Partition/Door -0.25 -0.25 0.00 Diffuser 183 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 183 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 183 55
Infiltration 0.11 0.11 5.12 0.03 1.68 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.02 0.06 1.08 50.23 0.96 53.63 Sub Total ==> -0.28 -0.29 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 6.98 0.12 6.70 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.24 0 0 11.16 0.13 7.26 People 0.00 0 0.00 Return 185 55
Misc 0.52 0.00 0.52 24.19 0.52 29.05 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.88 0.03 0.91 42.33 0.77 43.02 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 3.35 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.15 6.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.79 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.26 RA Preheat Diff. -0.35 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.47 4.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.22
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.51
W/m² 181.45 -53.64
Grand Total ==> 1.96 -0.03 2.15 100.00 1.79 100.00 Grand Total ==> -0.28 -0.98 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.14 1.87 182 27.0 19.8 11.5 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 70 of 323
Room Checksums
By Trane
T1-sieu am 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 71 of 323
Room Checksums
By Trane
T1-sieu am 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 72 of 323
Room Checksums
By Trane
T1-sieu am 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 73 of 323
Room Checksums
By Trane
T1-sieu am 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 74 of 323
Room Checksums
By Trane
T1-sieu am 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 75 of 323
Room Checksums
By Trane
T1-sieu am 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 76 of 323
Room Checksums
By Trane
T1-sieu am 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.6 21.0
Ra Plenum 26.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.84 0.28 19.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.30 0.05 3.47 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.08 0.30 16.48 0.20 13.89 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.95 0.09 6.25 Partition/Door -0.12 -0.12 0.00 Diffuser 155 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 46
Infiltration 0.10 0.10 5.49 0.03 2.08 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.08 0.82 45.05 0.65 45.14 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 2 0
Lights 0.10 0.02 0.12 6.59 0.10 6.94 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.20 0 0 10.99 0.11 7.64 People 0.00 0 0.00 Return 157 46
Misc 0.52 0.00 0.52 28.57 0.53 36.81 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.82 0.02 0.84 46.15 0.74 51.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.47 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 7.69 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.30 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 15.64 4.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.48
W/m² 182.38 -43.16
Grand Total ==> 1.61 0.01 1.82 100.00 1.44 100.00 Grand Total ==> -0.15 -0.69 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.81 1.56 155 26.7 19.6 11.5 16.3 16.2 11.5 Floor 10 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 77 of 323
Room Checksums
By Trane
T1-tham muu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.32 0.10 0.42 23.73 0.32 24.43 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.05 0.05 2.82 0.05 3.82 Partition/Door -0.10 -0.10 0.00 Diffuser 151 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 151 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 151 45
Infiltration 0.13 0.13 7.34 0.03 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.50 0.10 0.60 33.90 0.40 30.53 Sub Total ==> -0.12 -0.13 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 7.91 0.11 8.40 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.19 0 0 10.73 0.10 7.63 People 0.00 0 0.00 Return 154 45
Misc 0.67 0.00 0.67 37.85 0.67 51.15 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.97 0.03 1.00 56.50 0.88 67.18 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 2.29 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 7.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.39 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 6.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.04 3.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.56
W/m² 152.40 -27.29
Grand Total ==> 1.50 0.08 1.77 100.00 1.31 100.00 Grand Total ==> -0.12 -0.50 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.77 1.49 151 26.4 20.1 12.2 17.7 17.0 12.0 Floor 12 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 12 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 78 of 323
Room Checksums
By Trane
T1-tham muu hau can

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.55 0.19 13.97 Partition/Door -0.39 -0.39 0.00 Diffuser 156 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 156 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 156 47
Infiltration 0.26 0.26 13.07 0.06 4.41 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.45 0.00 0.45 22.61 0.25 18.38 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.07 0.21 15.44 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.34 0 0 17.09 0.18 13.24 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 33.67 0.67 49.26 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.22 0.05 1.27 63.82 1.06 77.94 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.68 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 12.56 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.01 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.02 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 11.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 7.40 2.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 78.68
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.63
W/m² 94.00 -27.80
Grand Total ==> 1.72 -0.04 1.99 100.00 1.36 100.00 Grand Total ==> -0.39 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.98 1.46 156 26.5 20.2 12.4 17.7 16.9 11.8 Floor 21 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.98 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 79 of 323
Room Checksums
By Trane
T1-tra nhan kq

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.12 0.12 5.31 0.12 7.95 Partition/Door -0.24 -0.24 0.00 Diffuser 137 41
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 137 41
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 137 41
Infiltration 0.35 0.35 15.49 0.09 5.96 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.47 0.00 0.47 20.80 0.21 13.91 Sub Total ==> -0.24 -0.24 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 8 0
Lights 0.28 0.07 0.35 15.49 0.28 18.54 Lights 0.00 0.00 0.00 MinStop/Rh 41 41
People 0.46 0 0 20.35 0.25 16.56 People 0.00 0 0.00 Return 145 41
Misc 0.67 0.00 0.67 29.65 0.67 44.37 Misc 0.00 0.00 0.00 Exhaust 33 0
Sub Total ==> 1.41 0.07 1.48 65.49 1.20 79.47 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 6.62 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.34 15.04 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -3.54 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.21 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 0.00 % OA 18.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 4.75 1.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 60.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.74
W/m² 78.43 -17.58
Grand Total ==> 1.98 -0.11 2.26 100.00 1.51 100.00 Grand Total ==> -0.24 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.26 1.55 137 27.2 20.6 12.6 15.9 15.9 11.4 Floor 29 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 28 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.26 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 80 of 323
Room Checksums
By Trane
T1-trb quan nhu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.29 0.08 0.37 19.17 0.29 20.71 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.06 0.06 3.11 0.06 4.29 Partition/Door -0.13 -0.13 0.00 Diffuser 160 48
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 160 48
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 160 48
Infiltration 0.18 0.18 9.33 0.04 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.53 0.08 0.61 31.61 0.39 27.86 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.16 0.04 0.20 10.36 0.16 11.43 Lights 0.00 0.00 0.00 MinStop/Rh 48 48
People 0.25 0 0 12.95 0.14 10.00 People 0.00 0 0.00 Return 165 48
Misc 0.67 0.00 0.67 34.72 0.67 47.86 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.08 0.04 1.12 58.03 0.97 69.29 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.86 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 8.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.55 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.11 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 8.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.14 3.04
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.12
W/m² 123.16 -22.86
Grand Total ==> 1.65 0.05 1.93 100.00 1.40 100.00 Grand Total ==> -0.16 -0.57 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.95 1.57 160 26.5 20.1 12.3 17.7 17.0 11.9 Floor 16 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 81 of 323
Room Checksums
By Trane
T1-tro ly nhan vien cntt

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.60 0.18 0.78 29.00 0.60 31.91 Wall Cond -0.04 -0.06 0.00
Partition/Door 0.10 0.10 3.72 0.10 5.32 Partition/Door -0.19 -0.19 0.00 Diffuser 215 64
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 215 64
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 215 64
Infiltration 0.25 0.25 9.29 0.06 3.19 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.95 0.18 1.13 42.01 0.76 40.43 Sub Total ==> -0.23 -0.25 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 9.67 0.21 11.17 Lights 0.00 0.00 0.00 MinStop/Rh 64 64
People 0.35 0 0 13.01 0.19 10.11 People 0.00 0 0.00 Return 220 64
Misc 0.67 0.00 0.67 24.91 0.67 35.64 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 47.58 1.07 56.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 2.66 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.24 8.92 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.49 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.97 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 8.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.98 2.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.00
W/m² 124.94 -23.47
Grand Total ==> 2.23 0.14 2.69 100.00 1.88 100.00 Grand Total ==> -0.23 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.69 2.17 215 26.5 20.1 12.3 17.7 16.8 11.8 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 22 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 82 of 323
Room Checksums
By Trane
T1-tro ly+nv quan ly

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.74 0.21 0.95 36.82 0.74 39.36 Wall Cond -0.07 -0.09 0.00
Partition/Door 0.07 0.07 2.71 0.07 3.72 Partition/Door -0.15 -0.15 0.00 Diffuser 215 64
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 215 64
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 215 64
Infiltration 0.19 0.19 7.36 0.05 2.66 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.00 0.21 1.21 46.90 0.86 45.74 Sub Total ==> -0.22 -0.24 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 5 0
Lights 0.16 0.04 0.20 7.75 0.16 8.51 Lights 0.00 0.00 0.00 MinStop/Rh 64 64
People 0.27 0 0 10.47 0.15 7.98 People 0.00 0 0.00 Return 220 64
Misc 0.67 0.00 0.67 25.97 0.67 35.64 Misc 0.00 0.00 0.00 Exhaust 19 0
Sub Total ==> 1.10 0.04 1.14 44.19 0.98 52.13 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.13 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.18 6.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.16 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.10 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 6.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.95 3.88
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.81
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.40
W/m² 156.25 -29.49
Grand Total ==> 2.14 0.18 2.58 100.00 1.88 100.00 Grand Total ==> -0.22 -0.76 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.59 2.20 215 26.4 20.1 12.2 17.7 16.9 11.8 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 17 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.59 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 35 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 83 of 323
Room Checksums
By Trane
T1-truong ban dieu duong

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.58 0.17 0.75 31.38 0.58 32.95 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.13 0.13 5.44 0.13 7.39 Partition/Door -0.26 -0.26 0.00 Diffuser 201 60
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 201 60
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 201 60
Infiltration 0.18 0.18 7.53 0.04 2.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.89 0.17 1.06 44.35 0.75 42.61 Sub Total ==> -0.32 -0.34 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.16 0.04 0.20 8.37 0.16 9.09 Lights 0.00 0.00 0.00 MinStop/Rh 60 60
People 0.25 0 0 10.46 0.14 7.95 People 0.00 0 0.00 Return 205 60
Misc 0.67 0.00 0.67 28.03 0.67 38.07 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.08 0.04 1.12 46.86 0.97 55.11 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 7.11 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.26 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.93 RA Preheat Diff. -0.25 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.71 3.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.65
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.58
W/m² 151.87 -36.15
Grand Total ==> 2.01 0.14 2.39 100.00 1.76 100.00 Grand Total ==> -0.32 -0.83 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.40 2.02 201 26.5 20.1 12.2 17.7 16.9 11.9 Floor 16 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.40 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 84 of 323
Room Checksums
By Trane
T1-truong ban doanh trai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.0 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.29 0.08 0.37 19.17 0.29 20.71 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.06 0.06 3.11 0.06 4.29 Partition/Door -0.13 -0.13 0.00 Diffuser 160 48
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 160 48
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 160 48
Infiltration 0.18 0.18 9.33 0.04 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.53 0.08 0.61 31.61 0.39 27.86 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.16 0.04 0.20 10.36 0.16 11.43 Lights 0.00 0.00 0.00 MinStop/Rh 48 48
People 0.25 0 0 12.95 0.14 10.00 People 0.00 0 0.00 Return 165 48
Misc 0.67 0.00 0.67 34.72 0.67 47.86 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.08 0.04 1.12 58.03 0.97 69.29 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.86 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 8.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.55 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.11 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 8.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.14 3.04
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.12
W/m² 123.16 -22.86
Grand Total ==> 1.65 0.05 1.93 100.00 1.40 100.00 Grand Total ==> -0.16 -0.57 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.95 1.57 160 26.5 20.1 12.3 17.7 17.0 11.9 Floor 16 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 85 of 323
Room Checksums
By Trane
T1-truong khoa

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 26.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.43 0.12 0.55 19.23 0.43 21.50 Wall Cond -0.04 -0.06 5.31
Partition/Door 0.19 0.19 6.64 0.19 9.50 Partition/Door -0.38 -0.38 33.63 Diffuser 183 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 183 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 183 55
Infiltration 0.33 0.33 11.54 0.08 4.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.95 0.12 1.07 37.41 0.70 35.00 Sub Total ==> -0.42 -0.44 38.94 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 8 0
Lights 0.28 0.07 0.35 12.24 0.28 14.00 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.46 0 0 16.08 0.25 12.50 People 0.00 0 0.00 Return 191 55
Misc 0.67 0.00 0.67 23.43 0.67 33.50 Misc 0.00 0.00 0.00 Exhaust 33 0
Sub Total ==> 1.41 0.07 1.48 51.75 1.20 60.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 5.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.32 11.19 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -2.80 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.45 RA Preheat Diff. -0.35 30.97 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 30.97 % OA 13.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.88 Lps/m² 6.35 1.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 63.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.02
W/m² 99.72 -26.91
Grand Total ==> 2.46 0.01 2.86 100.00 2.00 100.00 Grand Total ==> -0.42 -1.13 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.87 2.19 183 27.1 20.5 12.4 15.9 15.9 11.4 Floor 29 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 43 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.87 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 22 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 86 of 323
Room Checksums
By Trane
T2- phong hop ban tai chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.12 0.12 6.42 0.12 9.38 Partition/Door -0.24 -0.24 0.00 Diffuser 133 40
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 133 40
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 133 40
Infiltration 0.25 0.25 13.37 0.06 4.69 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.37 0.00 0.37 19.79 0.18 14.06 Sub Total ==> -0.24 -0.24 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 6 0
Lights 0.20 0.05 0.25 13.37 0.20 15.63 Lights 0.00 0.00 0.00 MinStop/Rh 40 40
People 0.33 0 0 17.65 0.18 14.06 People 0.00 0 0.00 Return 139 40
Misc 0.67 0.00 0.67 35.83 0.67 52.34 Misc 0.00 0.00 0.00 Exhaust 24 0
Sub Total ==> 1.20 0.05 1.25 66.84 1.05 82.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 3.91 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.24 12.83 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.14 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.67 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 13.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 6.43 1.93
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.20
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.07
W/m² 90.27 -21.12
Grand Total ==> 1.62 -0.04 1.87 100.00 1.28 100.00 Grand Total ==> -0.24 -0.64 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.87 1.35 133 26.5 20.3 12.4 17.0 16.6 11.7 Floor 21 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 27 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.87 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 87 of 323
Room Checksums
By Trane
T2- phong kiem nghiem

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.07 0.07 4.79 0.07 6.67 Partition/Door -0.14 -0.14 0.00 Diffuser 121 36
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 121 36
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 121 36
Infiltration 0.17 0.17 11.64 0.04 3.81 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.24 0.00 0.24 16.44 0.11 10.48 Sub Total ==> -0.14 -0.14 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 4 0
Lights 0.13 0.03 0.16 10.96 0.13 12.38 Lights 0.00 0.00 0.00 MinStop/Rh 36 36
People 0.21 0 0 14.38 0.12 11.43 People 0.00 0 0.00 Return 125 36
Misc 0.67 0.00 0.67 45.89 0.67 63.81 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 1.01 0.03 1.04 71.23 0.92 87.62 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 1.90 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 10.96 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.37 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.74 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.15 0.00 % OA 9.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.02 2.71
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.15
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.21
W/m² 108.47 -21.19
Grand Total ==> 1.27 -0.01 1.46 100.00 1.05 100.00 Grand Total ==> -0.14 -0.43 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.46 1.12 121 26.2 20.1 12.3 17.8 16.9 11.8 Floor 13 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 16 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 88 of 323
Room Checksums
By Trane
T2-dieu tri da lieu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.73 0.00 0.73 27.34 0.73 33.03 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.11 0.00 0.11 4.12 0.11 4.98 Glass/Door Cond -0.02 -0.02 1.90
Cooling Heating
Wall Cond 0.41 0.13 0.54 20.22 0.41 18.55 Wall Cond -0.05 -0.07 6.67
Partition/Door 0.09 0.09 3.37 0.09 4.07 Partition/Door -0.12 -0.12 11.43 Diffuser 228 69
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 228 69
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 228 69
Infiltration 0.11 0.11 4.12 0.03 1.36 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.45 0.13 1.58 59.18 1.37 61.99 Sub Total ==> -0.19 -0.21 20.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 5.62 0.12 5.43 Lights 0.00 0.00 0.00 MinStop/Rh 69 69
People 0.24 0 0 8.99 0.13 5.88 People 0.00 0 0.00 Return 231 69
Misc 0.52 0.00 0.52 19.48 0.52 23.53 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.88 0.03 0.91 34.08 0.77 34.84 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 3.17 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 5.99 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.25 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.00 RA Preheat Diff. -0.43 40.95 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.43 40.95 % OA 5.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 -1.90 Lps/m² 19.35 5.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.19
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.40
W/m² 226.96 -52.38
Grand Total ==> 2.40 0.03 2.67 100.00 2.21 100.00 Grand Total ==> -0.19 -1.05 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.68 2.40 228 27.2 19.8 11.5 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 13 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.68 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 89 of 323
Room Checksums
By Trane
T2-hanh lang 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.26 0.00 0.26 1.24 0.27 2.81 Glass/Door Cond -0.07 -0.07 2.82
Cooling Heating
Wall Cond 0.02 0.26 0.28 1.33 0.02 0.21 Wall Cond 0.00 -0.03 1.21
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 799 240
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 799 240
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 799 240
Infiltration 2.96 2.96 14.08 0.59 6.13 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.24 0.26 3.50 16.65 0.88 9.15 Sub Total ==> -0.07 -0.10 4.03 Nom Vent 156 0
AHU Vent 156 0
Internal Loads Internal Loads Infil 76 0
Lights 2.78 0.69 3.47 16.51 2.78 28.90 Lights 0.00 0.00 0.00 MinStop/Rh 240 240
People 11.74 0 12 55.85 6.31 65.59 People 0.00 0 0.00 Return 876 240
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 232 0
Sub Total ==> 14.52 0.69 15.21 72.36 9.09 94.49 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.36 0.36 0.00 0.00 -0.35 -3.64 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.82 8.66 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.20 0.20 0.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.29 1.38 RA Preheat Diff. -1.16 46.77 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.19 47.98 % OA 19.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.03 1.21 Lps/m² 2.88 0.86
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 38.01
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 13.22
W/m² 75.59 -4.67
Grand Total ==> 17.40 1.51 21.02 100.00 9.62 100.00 Grand Total ==> -0.11 -2.48 100.00 No. People 93

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 21.02 11.58 796 26.6 21.5 14.1 17.0 14.6 9.4 Floor 278 Main Htg -1.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 21.02 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 52 39 74 Opt Vent 0.0 0 0.0 0.0
Ext Door 39 0 0 Total -1.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 90 of 323
Room Checksums
By Trane
T2-hanh lang 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.48 0.00 0.48 0.76 0.50 1.59 Glass/Door Cond -0.14 -0.14 0.48
Cooling Heating
Wall Cond 0.04 0.42 0.46 0.73 0.04 0.13 Wall Cond -0.01 -0.07 0.24
Partition/Door -1.99 -1.99 -3.16 -1.99 -6.32 Partition/Door -20.09 -20.09 68.78 Diffuser 2,355 706
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,355 706
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,355 706
Infiltration 13.77 13.77 21.88 2.92 9.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 12.30 0.42 12.72 20.21 1.47 4.67 Sub Total ==> -20.24 -20.30 69.50 Nom Vent 141 0
AHU Vent 141 0
Internal Loads Internal Loads Infil 346 0
Lights 12.33 3.08 15.41 24.48 12.33 39.16 Lights 0.00 0.00 0.00 MinStop/Rh 706 706
People 32.23 0 32 51.21 17.49 55.54 People 0.00 0 0.00 Return 2,701 706
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 487 0
Sub Total ==> 44.56 3.08 47.64 75.69 29.82 94.70 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.19 -0.19 0.00 0.00 0.20 0.64 Ceiling Load -0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.77 2.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -0.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.86 1.37 RA Preheat Diff. -4.42 15.13 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -4.45 15.23 % OA 6.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.04 0.14 Lps/m² 1.87 0.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 37.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 19.97
W/m² 50.04 -19.69
Grand Total ==> 57.05 3.26 62.94 100.00 31.49 100.00 Grand Total ==> -20.32 -29.21 100.00 No. People 251

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 62.93 35.77 2,344 27.2 21.4 13.7 15.9 14.3 9.5 Floor 1,257 Main Htg -24.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 2,284 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 62.93 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 108 79 74 Opt Vent 0.0 0 0.0 0.0
Ext Door 79 0 0 Total -24.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 91 of 323
Room Checksums
By Trane
T2-hanh lang 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 447 134
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 447 134
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 447 134
Infiltration 2.22 2.22 18.83 0.44 8.87 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.22 0.00 2.22 18.83 0.44 8.87 Sub Total ==> 0.00 0.00 0.00 Nom Vent 116 0
AHU Vent 116 0
Internal Loads Internal Loads Infil 57 0
Lights 2.07 0.52 2.59 21.97 2.07 41.73 Lights 0.00 0.00 0.00 MinStop/Rh 134 134
People 5.25 0 5 44.53 2.82 56.85 People 0.00 0 0.00 Return 504 134
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 173 0
Sub Total ==> 7.32 0.52 7.84 66.50 4.89 98.59 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.37 0.37 0.00 0.00 -0.37 -7.46 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.35 11.45 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.22 0.22 1.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.16 1.36 RA Preheat Diff. -0.53 48.62 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.54 49.54 % OA 25.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 1.83 Lps/m² 2.16 0.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 37.93
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 17.57
W/m² 56.88 -2.66
Grand Total ==> 9.17 1.11 11.79 100.00 4.96 100.00 Grand Total ==> -0.01 -1.09 100.00 No. People 41

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.78 6.32 445 26.5 21.6 14.3 17.8 14.7 9.2 Floor 207 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.78 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 92 of 323
Room Checksums
By Trane
T2-hanh lang 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 477 143
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 477 143
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 477 143
Infiltration 2.24 2.24 18.84 0.44 8.94 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.24 0.00 2.24 18.84 0.44 8.94 Sub Total ==> 0.00 0.00 0.00 Nom Vent 116 0
AHU Vent 116 0
Internal Loads Internal Loads Infil 57 0
Lights 2.07 0.52 2.59 21.78 2.07 42.07 Lights 0.00 0.00 0.00 MinStop/Rh 143 143
People 5.25 0 5 44.15 2.82 57.32 People 0.00 0 0.00 Return 534 143
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 173 0
Sub Total ==> 7.32 0.52 7.84 65.94 4.89 99.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.41 0.41 0.00 0.00 -0.41 -8.33 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.40 11.77 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.24 0.24 2.02 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.17 1.43 RA Preheat Diff. -0.46 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.46 0.00 % OA 24.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 2.31 0.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 40.14
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 17.42
W/m² 57.39 -2.25
Grand Total ==> 9.15 1.17 11.89 100.00 4.92 100.00 Grand Total ==> 0.00 -0.93 100.00 No. People 41

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.88 6.34 475 26.3 21.5 14.2 18.4 15.0 9.3 Floor 207 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.88 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 93 of 323
Room Checksums
By Trane
T2-huyet thanh hoc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.09 0.09 2.77 0.09 4.04 Partition/Door -0.13 -0.13 0.00 Diffuser 337 101
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 337 101
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 337 101
Infiltration 0.14 0.14 4.31 0.04 1.79 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.23 0.00 0.23 7.08 0.13 5.83 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 32 0
AHU Vent 32 0
Internal Loads Internal Loads Infil 3 0
Lights 1.17 0.29 1.46 44.92 1.17 52.47 Lights 0.00 0.00 0.00 MinStop/Rh 101 101
People 0.41 0 0 12.62 0.22 9.87 People 0.00 0 0.00 Return 340 101
Misc 0.67 0.00 0.67 20.62 0.67 30.04 Misc 0.00 0.00 0.00 Exhaust 35 0
Sub Total ==> 2.25 0.29 2.54 78.15 2.06 92.38 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 1.79 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 13.54 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -2.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.69 RA Preheat Diff. -0.32 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.33 0.00 % OA 9.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 30.97 9.29
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 103.54
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.34
W/m² 298.93 -41.56
Grand Total ==> 2.52 0.17 3.25 100.00 2.23 100.00 Grand Total ==> -0.13 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.26 2.67 337 26.1 19.5 11.6 18.4 16.9 11.6 Floor 11 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.26 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 94 of 323
Room Checksums
By Trane
T2-kham da lieu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 14.36 0.28 18.79 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 3.19 0.05 3.36 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.21 0.07 0.28 14.89 0.19 12.75 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.09 0.09 4.79 0.09 6.04 Partition/Door -0.12 -0.12 0.00 Diffuser 154 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 154 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 154 46
Infiltration 0.11 0.11 5.85 0.03 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.07 0.81 43.09 0.64 42.95 Sub Total ==> -0.15 -0.16 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 7.98 0.12 8.05 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.24 0 0 12.77 0.13 8.72 People 0.00 0 0.00 Return 156 46
Misc 0.52 0.00 0.52 27.66 0.53 35.57 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.88 0.03 0.91 48.40 0.78 52.35 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 4.70 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 8.51 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -3.19 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.19 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.29 0.00 % OA 8.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 13.03 3.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.25
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.31
W/m² 158.28 -37.27
Grand Total ==> 1.69 -0.03 1.88 100.00 1.49 100.00 Grand Total ==> -0.15 -0.73 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.87 1.59 153 27.3 19.9 11.6 15.9 15.9 11.4 Floor 12 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 13 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.87 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 95 of 323
Room Checksums
By Trane
T2-kham truyen nhiem

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.28 0.00 0.28 14.07 0.28 17.39 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.51 0.05 3.11 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.19 0.06 0.25 12.56 0.19 11.80 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.21 0.21 10.55 0.21 13.04 Partition/Door -0.28 -0.28 0.00 Diffuser 166 50
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 166 50
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 166 50
Infiltration 0.11 0.11 5.53 0.03 1.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.84 0.06 0.90 45.23 0.76 47.20 Sub Total ==> -0.31 -0.32 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 7.54 0.12 7.45 Lights 0.00 0.00 0.00 MinStop/Rh 50 50
People 0.24 0 0 12.06 0.13 8.07 People 0.00 0 0.00 Return 169 50
Misc 0.53 0.00 0.53 26.63 0.53 32.92 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.89 0.03 0.92 46.23 0.78 48.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 4.35 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 8.54 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -3.02 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.02 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 7.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 14.08 4.23
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.36
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.92
W/m² 168.84 -52.84
Grand Total ==> 1.80 -0.04 1.99 100.00 1.61 100.00 Grand Total ==> -0.31 -0.93 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.99 1.71 166 27.2 19.8 11.6 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 32 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.99 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 96 of 323
Room Checksums
By Trane
T2-kho

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 4.58 0.06 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 114 34
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 114 34
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 114 34
Infiltration 0.13 0.13 9.92 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.19 0.00 0.19 14.50 0.09 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.10 0.03 0.13 9.92 0.10 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 34 34
People 0.17 0 0 12.98 0.09 0.00 People 0.00 0 0.00 Return 117 34
Misc 0.67 0.00 0.67 51.15 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.94 0.03 0.97 74.05 0.86 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.12 9.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 3.05 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.14 0.00 % OA 8.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.54 3.16
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 86.30
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.19
W/m² 122.05 -24.73
Grand Total ==> 1.15 0.00 1.31 100.00 0.97 100.00 Grand Total ==> -0.13 -0.41 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.32 1.05 114 26.1 20.0 12.3 17.8 17.0 11.9 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.32 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 97 of 323
Room Checksums
By Trane
T2-kho bong bang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 12.27 0.27 16.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.27 0.05 3.07 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.09 0.31 14.09 0.22 13.50 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.73 0.06 3.68 Partition/Door -0.13 -0.13 0.00 Diffuser 190 57
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 190 57
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 190 57
Infiltration 0.18 0.18 8.18 0.04 2.45 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.78 0.09 0.87 39.55 0.64 39.26 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.15 0.04 0.19 8.64 0.15 9.20 Lights 0.00 0.00 0.00 MinStop/Rh 57 57
People 0.25 0 0 11.36 0.14 8.59 People 0.00 0 0.00 Return 195 57
Misc 0.67 0.00 0.67 30.45 0.67 41.10 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.07 0.04 1.11 50.45 0.96 58.90 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 1.84 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 7.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.91 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.18 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.04 3.61
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.97
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.14
W/m² 139.91 -24.53
Grand Total ==> 1.88 0.08 2.20 100.00 1.63 100.00 Grand Total ==> -0.16 -0.62 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.21 1.83 190 26.1 20.0 12.2 17.8 16.9 11.8 Floor 16 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.21 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 98 of 323
Room Checksums
By Trane
T2-kho cap phat BHYT

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 8.08 0.27 12.11 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.24 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.38 0.13 0.51 15.27 0.38 17.04 Wall Cond -0.04 -0.05 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.48 Partition/Door -0.19 -0.19 0.00 Diffuser 259 78
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 259 78
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 259 78
Infiltration 0.39 0.39 11.68 0.09 4.04 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.19 0.13 1.32 39.52 0.89 39.91 Sub Total ==> -0.24 -0.25 0.00 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 9 0
Lights 0.32 0.08 0.40 11.98 0.32 14.35 Lights 0.00 0.00 0.00 MinStop/Rh 78 78
People 0.53 0 1 15.87 0.29 13.00 People 0.00 0 0.00 Return 268 78
Misc 0.67 0.00 0.67 20.06 0.67 30.04 Misc 0.00 0.00 0.00 Exhaust 38 0
Sub Total ==> 1.52 0.08 1.60 47.90 1.28 57.40 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.69 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.37 11.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.50 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 11.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 7.84 2.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.89
W/m² 101.04 -16.82
Grand Total ==> 2.77 0.10 3.34 100.00 2.23 100.00 Grand Total ==> -0.24 -0.86 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.52 259 26.2 20.1 12.3 17.8 16.7 11.6 Floor 33 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 22 3 12 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 99 of 323
Room Checksums
By Trane
T2-kho cap phat DVYT

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.54 0.00 0.54 11.44 0.54 17.25 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.10 0.00 0.10 2.12 0.10 3.19 Glass/Door Cond -0.02 -0.02 1.36
Cooling Heating
Wall Cond 0.44 0.17 0.61 12.92 0.44 14.06 Wall Cond -0.04 -0.06 4.08
Partition/Door 0.27 0.27 5.72 0.27 8.63 Partition/Door -0.53 -0.53 36.05 Diffuser 364 109
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 364 109
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 364 109
Infiltration 0.57 0.57 12.08 0.13 4.15 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.92 0.17 2.09 44.28 1.48 47.28 Sub Total ==> -0.59 -0.61 41.50 Nom Vent 42 0
AHU Vent 42 0
Internal Loads Internal Loads Infil 13 0
Lights 0.47 0.12 0.59 12.50 0.47 15.02 Lights 0.00 0.00 0.00 MinStop/Rh 109 109
People 0.77 0 1 16.31 0.42 13.42 People 0.00 0 0.00 Return 377 109
Misc 0.67 0.00 0.67 14.19 0.67 21.41 Misc 0.00 0.00 0.00 Exhaust 55 0
Sub Total ==> 1.91 0.12 2.03 43.01 1.56 49.84 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 2.88 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.54 11.44 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -1.48 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.13 2.75 RA Preheat Diff. -0.43 29.25 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.44 29.93 % OA 11.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.68 Lps/m² 7.55 2.27
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.94
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.19
W/m² 98.10 -21.50
Grand Total ==> 3.92 0.13 4.72 100.00 3.13 100.00 Grand Total ==> -0.59 -1.47 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.73 3.55 364 26.2 20.1 12.4 17.8 16.7 11.6 Floor 48 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 60 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.73 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 29 5 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 100 of 323
Room Checksums
By Trane
T2-kho cap phat quan su

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 8.08 0.27 12.11 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.24 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.38 0.13 0.51 15.27 0.38 17.04 Wall Cond -0.04 -0.05 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.48 Partition/Door -0.19 -0.19 0.00 Diffuser 259 78
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 259 78
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 259 78
Infiltration 0.39 0.39 11.68 0.09 4.04 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.19 0.13 1.32 39.52 0.89 39.91 Sub Total ==> -0.24 -0.25 0.00 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 9 0
Lights 0.32 0.08 0.40 11.98 0.32 14.35 Lights 0.00 0.00 0.00 MinStop/Rh 78 78
People 0.53 0 1 15.87 0.29 13.00 People 0.00 0 0.00 Return 268 78
Misc 0.67 0.00 0.67 20.06 0.67 30.04 Misc 0.00 0.00 0.00 Exhaust 38 0
Sub Total ==> 1.52 0.08 1.60 47.90 1.28 57.40 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.69 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.37 11.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.50 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 11.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 7.84 2.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.89
W/m² 101.04 -16.82
Grand Total ==> 2.77 0.10 3.34 100.00 2.23 100.00 Grand Total ==> -0.24 -0.86 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.52 259 26.2 20.1 12.3 17.8 16.7 11.6 Floor 33 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 22 3 12 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 101 of 323
Room Checksums
By Trane
T2-kho chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 10.76 0.27 15.25 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.99 0.05 2.82 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.09 0.31 12.35 0.22 12.43 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.39 0.06 3.39 Partition/Door -0.13 -0.13 0.00 Diffuser 206 62
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 206 62
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 206 62
Infiltration 0.25 0.25 9.96 0.06 3.39 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.85 0.09 0.94 37.45 0.66 37.29 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 10.36 0.21 11.86 Lights 0.00 0.00 0.00 MinStop/Rh 62 62
People 0.35 0 0 13.94 0.19 10.73 People 0.00 0 0.00 Return 212 62
Misc 0.67 0.00 0.67 26.69 0.67 37.85 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 51.00 1.07 60.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.26 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.24 9.56 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.19 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 9.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.49 2.85
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.89
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.63
W/m² 115.81 -18.75
Grand Total ==> 2.12 0.07 2.51 100.00 1.77 100.00 Grand Total ==> -0.16 -0.66 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.51 1.98 206 26.2 20.1 12.3 17.8 16.8 11.7 Floor 22 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.51 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 102 of 323
Room Checksums
By Trane
T2-kho du tru dung cu y te

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.34 0.13 9.70 Partition/Door -0.26 -0.26 0.00 Diffuser 155 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 47
Infiltration 0.29 0.29 14.15 0.07 5.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.49 0.20 14.93 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.15 0.23 17.16 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.37 0 0 18.05 0.20 14.93 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 32.68 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 64.88 1.10 82.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.93 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 13.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.63 1.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.98
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.46
W/m² 87.21 -19.11
Grand Total ==> 1.73 -0.01 2.05 100.00 1.34 100.00 Grand Total ==> -0.26 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.04 1.45 155 26.2 20.2 12.4 17.8 16.7 11.6 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 103 of 323
Room Checksums
By Trane
T2-kho le

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 12.27 0.27 16.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.27 0.05 3.07 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.09 0.31 14.09 0.22 13.50 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.73 0.06 3.68 Partition/Door -0.13 -0.13 0.00 Diffuser 190 57
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 190 57
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 190 57
Infiltration 0.18 0.18 8.18 0.04 2.45 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.78 0.09 0.87 39.55 0.64 39.26 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.15 0.04 0.19 8.64 0.15 9.20 Lights 0.00 0.00 0.00 MinStop/Rh 57 57
People 0.25 0 0 11.36 0.14 8.59 People 0.00 0 0.00 Return 195 57
Misc 0.67 0.00 0.67 30.45 0.67 41.10 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.07 0.04 1.11 50.45 0.96 58.90 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 1.84 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 7.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.91 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.18 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.04 3.61
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.97
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.14
W/m² 139.91 -24.53
Grand Total ==> 1.88 0.08 2.20 100.00 1.63 100.00 Grand Total ==> -0.16 -0.62 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.21 1.83 190 26.1 20.0 12.2 17.8 16.9 11.8 Floor 16 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.21 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 104 of 323
Room Checksums
By Trane
T2-kho thanh pham tam

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.12 0.12 9.38 0.12 11.88 Partition/Door -0.23 -0.23 0.00 Diffuser 116 35
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 116 35
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 116 35
Infiltration 0.11 0.11 8.59 0.03 2.97 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.23 0.00 0.23 17.97 0.15 14.85 Sub Total ==> -0.23 -0.23 0.00 Nom Vent 8 0
AHU Vent 8 0
Internal Loads Internal Loads Infil 2 0
Lights 0.09 0.02 0.11 8.59 0.09 8.91 Lights 0.00 0.00 0.00 MinStop/Rh 35 35
People 0.14 0 0 10.94 0.08 7.92 People 0.00 0 0.00 Return 118 35
Misc 0.67 0.00 0.67 52.34 0.67 66.34 Misc 0.00 0.00 0.00 Exhaust 10 0
Sub Total ==> 0.90 0.02 0.92 71.88 0.84 83.17 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 1.98 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.10 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.78 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 3.13 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.14 0.00 % OA 6.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.16 3.95
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 90.33
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.87
W/m² 145.56 -42.31
Grand Total ==> 1.15 -0.01 1.28 100.00 1.01 100.00 Grand Total ==> -0.23 -0.51 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.28 1.06 116 26.1 20.0 12.2 17.8 17.1 12.0 Floor 9 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 26 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.28 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 105 of 323
Room Checksums
By Trane
T2-Kho va xu ly dung cu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.42 0.13 0.55 26.83 0.42 27.27 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.19 0.19 9.27 0.19 12.34 Partition/Door -0.39 -0.39 0.00 Diffuser 196 59
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 196 59
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 196 59
Infiltration 0.13 0.13 6.34 0.03 1.95 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.74 0.13 0.87 42.44 0.64 41.56 Sub Total ==> -0.42 -0.43 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 6.83 0.11 7.14 Lights 0.00 0.00 0.00 MinStop/Rh 59 59
People 0.18 0 0 8.78 0.10 6.49 People 0.00 0 0.00 Return 199 59
Misc 0.67 0.00 0.67 32.68 0.67 43.51 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.96 0.03 0.99 48.29 0.88 57.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 1.30 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.13 6.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.49 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.41 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 4.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 18.03 5.41
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 96.30
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.34
W/m² 187.07 -55.66
Grand Total ==> 1.72 0.13 2.05 100.00 1.54 100.00 Grand Total ==> -0.42 -0.80 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.04 1.76 196 26.0 19.9 12.1 18.4 17.2 11.8 Floor 11 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 106 of 323
Room Checksums
By Trane
T2-Labo xet nghiem hoa sinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 1.30 0.13 1.98 Partition/Door -0.26 -0.26 13.76 Diffuser 839 252
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 839 252
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 839 252
Infiltration 0.44 0.44 4.39 0.11 1.67 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.57 0.00 0.57 5.68 0.24 3.65 Sub Total ==> -0.26 -0.26 13.76 Nom Vent 74 0
AHU Vent 74 0
Internal Loads Internal Loads Infil 10 0
Lights 4.71 1.18 5.89 58.72 4.71 71.69 Lights 0.00 0.00 0.00 MinStop/Rh 252 252
People 1.66 0 2 16.55 0.88 13.39 People 0.00 0 0.00 Return 849 252
Misc 0.67 0.00 0.67 6.68 0.67 10.20 Misc 0.00 0.00 0.00 Exhaust 84 0
Sub Total ==> 7.04 1.18 8.22 81.95 6.26 95.28 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 1.07 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.02 10.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -0.90 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.31 3.09 RA Preheat Diff. -0.81 42.86 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.81 42.86 % OA 8.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.53 Lps/m² 19.11 5.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.38
W/m² 228.03 -24.43
Grand Total ==> 7.68 1.02 10.03 100.00 6.57 100.00 Grand Total ==> -0.26 -1.89 100.00 No. People 13

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 10.01 8.14 838 26.1 20.0 12.3 18.4 16.9 11.5 Floor 44 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.01 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 107 of 323
Room Checksums
By Trane
T2-Labo xet nghiem huyet hoc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.37 0.37 11.01 0.37 14.80 Partition/Door -0.50 -0.50 40.32 Diffuser 381 114
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 381 114
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 381 114
Infiltration 0.11 0.11 3.27 0.03 1.20 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.48 0.00 0.48 14.29 0.40 16.00 Sub Total ==> -0.50 -0.50 40.32 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 2 0
Lights 1.17 0.29 1.46 43.45 1.17 46.80 Lights 0.00 0.00 0.00 MinStop/Rh 114 114
People 0.41 0 0 12.20 0.22 8.80 People 0.00 0 0.00 Return 383 114
Misc 0.67 0.00 0.67 19.94 0.67 26.80 Misc 0.00 0.00 0.00 Exhaust 21 0
Sub Total ==> 2.25 0.29 2.54 75.60 2.06 82.40 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 1.60 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 7.44 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.49 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.14 4.17 RA Preheat Diff. -0.37 29.84 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.37 29.84 % OA 4.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 35.24 10.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 112.51
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.19
W/m² 313.02 -80.07
Grand Total ==> 2.77 0.20 3.36 100.00 2.50 100.00 Grand Total ==> -0.50 -1.24 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.38 2.94 380 26.0 19.4 11.5 18.4 16.8 11.5 Floor 11 Main Htg -0.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 56 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.38 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 108 of 323
Room Checksums
By Trane
T2-Labo xet nghiem vi sinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 1.30 0.13 1.98 Partition/Door -0.26 -0.26 13.76 Diffuser 839 252
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 839 252
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 839 252
Infiltration 0.44 0.44 4.39 0.11 1.67 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.57 0.00 0.57 5.68 0.24 3.65 Sub Total ==> -0.26 -0.26 13.76 Nom Vent 74 0
AHU Vent 74 0
Internal Loads Internal Loads Infil 10 0
Lights 4.71 1.18 5.89 58.72 4.71 71.69 Lights 0.00 0.00 0.00 MinStop/Rh 252 252
People 1.66 0 2 16.55 0.88 13.39 People 0.00 0 0.00 Return 849 252
Misc 0.67 0.00 0.67 6.68 0.67 10.20 Misc 0.00 0.00 0.00 Exhaust 84 0
Sub Total ==> 7.04 1.18 8.22 81.95 6.26 95.28 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 1.07 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.02 10.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -0.90 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.31 3.09 RA Preheat Diff. -0.81 42.86 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.81 42.86 % OA 8.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.53 Lps/m² 19.11 5.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.38
W/m² 228.03 -24.43
Grand Total ==> 7.68 1.02 10.03 100.00 6.57 100.00 Grand Total ==> -0.26 -1.89 100.00 No. People 13

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 10.01 8.14 838 26.1 20.0 12.3 18.4 16.9 11.5 Floor 44 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.01 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 109 of 323
Room Checksums
By Trane
T2-Luu mau benh pham

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.44 0.13 0.57 30.81 0.44 32.59 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.09 0.09 4.86 0.09 6.67 Partition/Door -0.13 -0.13 0.00 Diffuser 203 61
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 203 61
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 203 61
Infiltration 0.11 0.11 5.95 0.03 2.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.64 0.13 0.77 41.62 0.56 41.48 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.11 0.03 0.14 7.57 0.11 8.15 Lights 0.00 0.00 0.00 MinStop/Rh 61 61
People 0.22 0 0 11.89 0.12 8.89 People 0.00 0 0.00 Return 206 61
Misc 0.52 0.00 0.52 28.11 0.52 38.52 Misc 0.00 0.00 0.00 Exhaust 14 0
Sub Total ==> 0.85 0.03 0.88 47.57 0.75 55.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.96 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 8.65 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.62 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.78 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 5.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 18.68 5.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.92
W/m² 168.77 -32.46
Grand Total ==> 1.53 0.09 1.85 100.00 1.35 100.00 Grand Total ==> -0.16 -0.56 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.84 1.55 203 26.0 19.4 11.5 18.4 16.9 11.5 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.84 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 110 of 323
Room Checksums
By Trane
T2-Luu mau tru mo

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.44 0.13 0.57 30.81 0.44 32.59 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.09 0.09 4.86 0.09 6.67 Partition/Door -0.13 -0.13 0.00 Diffuser 203 61
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 203 61
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 203 61
Infiltration 0.11 0.11 5.95 0.03 2.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.64 0.13 0.77 41.62 0.56 41.48 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.11 0.03 0.14 7.57 0.11 8.15 Lights 0.00 0.00 0.00 MinStop/Rh 61 61
People 0.22 0 0 11.89 0.12 8.89 People 0.00 0 0.00 Return 206 61
Misc 0.52 0.00 0.52 28.11 0.52 38.52 Misc 0.00 0.00 0.00 Exhaust 14 0
Sub Total ==> 0.85 0.03 0.88 47.57 0.75 55.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.96 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 8.65 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.62 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.78 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 5.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 18.68 5.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.92
W/m² 168.77 -32.46
Grand Total ==> 1.53 0.09 1.85 100.00 1.35 100.00 Grand Total ==> -0.16 -0.56 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.84 1.55 203 26.0 19.4 11.5 18.4 16.9 11.5 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.84 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 111 of 323
Room Checksums
By Trane
T2-nan vien phong chinh tri

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.26 0.26 7.51 0.26 12.50 Partition/Door -0.52 -0.52 44.44 Diffuser 217 65
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 217 65
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 217 65
Infiltration 0.60 0.60 17.34 0.15 7.21 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.86 0.00 0.86 24.86 0.41 19.71 Sub Total ==> -0.52 -0.52 44.44 Nom Vent 42 0
AHU Vent 42 0
Internal Loads Internal Loads Infil 13 0
Lights 0.47 0.12 0.59 17.05 0.47 22.60 Lights 0.00 0.00 0.00 MinStop/Rh 65 65
People 0.78 0 1 22.54 0.42 20.19 People 0.00 0 0.00 Return 231 65
Misc 0.67 0.00 0.67 19.36 0.67 32.21 Misc 0.00 0.00 0.00 Exhaust 56 0
Sub Total ==> 1.92 0.12 2.04 58.96 1.56 75.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 5.29 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.57 16.47 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -2.60 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.31 RA Preheat Diff. -0.32 27.35 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 27.35 % OA 19.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.85 Lps/m² 4.45 1.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 62.75
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 14.09
W/m² 70.91 -17.39
Grand Total ==> 2.89 -0.08 3.46 100.00 2.08 100.00 Grand Total ==> -0.53 -1.17 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.46 2.24 217 26.6 20.4 12.6 17.0 16.3 11.3 Floor 49 Main Htg -0.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 112 of 323
Room Checksums
By Trane
T2-nhan vien ban hanh chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.15 0.33 1.48 30.83 1.15 36.39 Wall Cond -0.12 -0.15 9.26
Partition/Door 0.26 0.26 5.42 0.26 8.23 Partition/Door -0.52 -0.52 32.10 Diffuser 332 100
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 332 100
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 332 100
Infiltration 0.54 0.54 11.25 0.12 3.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.95 0.33 2.28 47.50 1.53 48.42 Sub Total ==> -0.64 -0.67 41.36 Nom Vent 40 0
AHU Vent 40 0
Internal Loads Internal Loads Infil 13 0
Lights 0.45 0.11 0.56 11.67 0.45 14.24 Lights 0.00 0.00 0.00 MinStop/Rh 100 100
People 0.74 0 1 15.42 0.40 12.66 People 0.00 0 0.00 Return 345 100
Misc 0.67 0.00 0.67 13.96 0.67 21.20 Misc 0.00 0.00 0.00 Exhaust 52 0
Sub Total ==> 1.86 0.11 1.97 41.04 1.52 48.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 3.48 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.51 10.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -1.67 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 2.50 RA Preheat Diff. -0.48 29.63 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.49 30.25 % OA 12.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 -1.23 Lps/m² 7.23 2.17
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 69.01
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.54
W/m² 104.73 -24.66
Grand Total ==> 3.92 0.25 4.80 100.00 3.16 100.00 Grand Total ==> -0.65 -1.62 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.81 3.70 332 26.5 20.2 12.4 17.0 16.4 11.5 Floor 46 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.81 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 59 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 113 of 323
Room Checksums
By Trane
T2-phong bac si

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 3.02 0.06 4.72 Partition/Door -0.13 -0.13 0.00 Diffuser 162 49
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 162 49
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 162 49
Infiltration 0.29 0.29 14.57 0.07 5.51 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.35 0.00 0.35 17.59 0.13 10.24 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.57 0.23 18.11 Lights 0.00 0.00 0.00 MinStop/Rh 49 49
People 0.37 0 0 18.59 0.20 15.75 People 0.00 0 0.00 Return 168 49
Misc 0.67 0.00 0.67 33.67 0.67 52.76 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 66.83 1.10 86.61 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.15 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.28 14.07 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.51 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.02 RA Preheat Diff. -0.16 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.16 0.00 % OA 12.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.90 2.07
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.76
W/m² 84.99 -12.07
Grand Total ==> 1.66 -0.01 1.99 100.00 1.27 100.00 Grand Total ==> -0.13 -0.45 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.99 1.39 161 26.1 20.1 12.4 18.4 16.9 11.5 Floor 23 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.99 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 114 of 323
Room Checksums
By Trane
T2-phong bao che

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.05 0.05 4.13 0.05 0.00 Partition/Door -0.10 -0.10 0.00 Diffuser 106 32
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 106 32
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 106 32
Infiltration 0.11 0.11 9.09 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.16 0.00 0.16 13.22 0.08 0.00 Sub Total ==> -0.10 -0.10 0.00 Nom Vent 8 0
AHU Vent 8 0
Internal Loads Internal Loads Infil 2 0
Lights 0.09 0.02 0.11 9.09 0.09 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 32 32
People 0.14 0 0 11.57 0.08 0.00 People 0.00 0 0.00 Return 109 32
Misc 0.67 0.00 0.67 55.37 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 10 0
Sub Total ==> 0.90 0.02 0.92 76.03 0.84 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.10 8.26 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.83 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 3.31 RA Preheat Diff. -0.13 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.13 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 12.10 3.63
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 88.89
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.02 -25.43
Grand Total ==> 1.08 -0.01 1.21 100.00 0.94 100.00 Grand Total ==> -0.10 -0.36 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.20 0.98 106 26.1 20.0 12.2 17.8 17.0 11.9 Floor 9 Main Htg -0.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 11 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.20 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 115 of 323
Room Checksums
By Trane
T2-phong cat loc XL mo

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.09 0.09 6.47 0.09 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 148 44
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 148 44
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 148 44
Infiltration 0.13 0.13 9.35 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.22 0.00 0.22 15.83 0.12 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 15 0
AHU Vent 15 0
Internal Loads Internal Loads Infil 3 0
Lights 0.10 0.02 0.12 8.63 0.10 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 44 44
People 0.26 0 0 18.71 0.13 0.00 People 0.00 0 0.00 Return 151 44
Misc 0.59 0.00 0.59 42.45 0.59 0.00 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 0.95 0.02 0.97 69.78 0.82 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.19 13.67 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 3.60 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.14 0.00 % OA 10.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.59 4.08
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 105.73
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.78
W/m² 128.49 -24.74
Grand Total ==> 1.21 -0.06 1.39 100.00 0.98 100.00 Grand Total ==> -0.13 -0.41 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.40 1.03 148 26.0 19.5 11.6 18.4 17.0 11.6 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.40 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 116 of 323
Room Checksums
By Trane
T2-phong cat nuoc 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.34 0.13 9.70 Partition/Door -0.26 -0.26 0.00 Diffuser 155 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 47
Infiltration 0.29 0.29 14.15 0.07 5.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.49 0.20 14.93 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.15 0.23 17.16 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.37 0 0 18.05 0.20 14.93 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 32.68 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 64.88 1.10 82.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.93 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 13.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.63 1.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.98
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.46
W/m² 87.21 -19.11
Grand Total ==> 1.73 -0.01 2.05 100.00 1.34 100.00 Grand Total ==> -0.26 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.04 1.45 155 26.2 20.2 12.4 17.8 16.7 11.6 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 117 of 323
Room Checksums
By Trane
T2-phong cat nuoc 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.34 0.13 9.70 Partition/Door -0.26 -0.26 0.00 Diffuser 155 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 47
Infiltration 0.29 0.29 14.15 0.07 5.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.49 0.20 14.93 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.15 0.23 17.16 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.37 0 0 18.05 0.20 14.93 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 32.68 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 64.88 1.10 82.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.93 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 13.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.63 1.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.98
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.46
W/m² 87.21 -19.11
Grand Total ==> 1.73 -0.01 2.05 100.00 1.34 100.00 Grand Total ==> -0.26 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.04 1.45 155 26.2 20.2 12.4 17.8 16.7 11.6 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 118 of 323
Room Checksums
By Trane
T2-phong cham cuu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.18 0.18 12.16 0.18 16.82 Partition/Door -0.24 -0.24 0.00 Diffuser 111 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 111 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 111 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 18.24 0.21 19.63 Sub Total ==> -0.24 -0.24 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 6.54 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 30.41 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.38 2.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.93
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.99
W/m² 125.12 -38.46
Grand Total ==> 1.11 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.24 -0.66 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.48 0.86 92 26.9 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 28 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.48 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 119 of 323
Room Checksums
By Trane
T2-phong cham cuu 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 13.24 0.27 16.46 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 2.94 0.06 3.66 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.26 0.09 0.35 17.16 0.26 15.85 Wall Cond -0.03 -0.03 0.00
Partition/Door 0.18 0.18 8.82 0.18 10.98 Partition/Door -0.24 -0.24 0.00 Diffuser 168 50
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 168 50
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 168 50
Infiltration 0.11 0.11 5.39 0.03 1.83 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.88 0.09 0.97 47.55 0.80 48.78 Sub Total ==> -0.28 -0.28 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 7.35 0.12 7.32 Lights 0.00 0.00 0.00 MinStop/Rh 50 50
People 0.24 0 0 11.76 0.13 7.93 People 0.00 0 0.00 Return 171 50
Misc 0.52 0.00 0.52 25.49 0.52 31.71 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.88 0.03 0.91 44.61 0.77 46.95 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 4.27 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 7.84 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.94 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.94 RA Preheat Diff. -0.32 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 0.00 % OA 7.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 14.26 4.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.81
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.81
W/m² 172.07 -50.06
Grand Total ==> 1.83 -0.01 2.04 100.00 1.64 100.00 Grand Total ==> -0.28 -0.91 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.03 1.75 168 27.2 19.8 11.5 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 27 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.03 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 16 3 17 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 120 of 323
Room Checksums
By Trane
T2-phong che tao luu tru

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.21 0.21 5.25 0.21 7.72 Partition/Door -0.28 -0.28 25.93 Diffuser 413 124
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 413 124
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 413 124
Infiltration 0.17 0.17 4.25 0.05 1.84 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.38 0.00 0.38 9.50 0.26 9.56 Sub Total ==> -0.28 -0.28 25.93 Nom Vent 40 0
AHU Vent 40 0
Internal Loads Internal Loads Infil 4 0
Lights 1.46 0.37 1.83 45.75 1.46 53.68 Lights 0.00 0.00 0.00 MinStop/Rh 124 124
People 0.52 0 1 13.00 0.28 10.29 People 0.00 0 0.00 Return 417 124
Misc 0.67 0.00 0.67 16.75 0.67 24.63 Misc 0.00 0.00 0.00 Exhaust 43 0
Sub Total ==> 2.65 0.37 3.02 75.50 2.41 88.60 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 1.84 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.55 13.75 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.10 -0.10 -2.50 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.15 3.75 RA Preheat Diff. -0.40 37.04 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.40 37.04 % OA 9.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 30.60 9.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 102.89
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.36
W/m² 297.20 -50.55
Grand Total ==> 3.08 0.22 4.00 100.00 2.72 100.00 Grand Total ==> -0.28 -1.08 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.01 3.28 413 26.1 19.5 11.6 18.4 16.9 11.6 Floor 14 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 32 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.01 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 121 of 323
Room Checksums
By Trane
T2-Phong choc hut te bao

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.44 0.13 0.57 30.81 0.44 32.59 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.09 0.09 4.86 0.09 6.67 Partition/Door -0.13 -0.13 0.00 Diffuser 203 61
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 203 61
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 203 61
Infiltration 0.11 0.11 5.95 0.03 2.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.64 0.13 0.77 41.62 0.56 41.48 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.11 0.03 0.14 7.57 0.11 8.15 Lights 0.00 0.00 0.00 MinStop/Rh 61 61
People 0.22 0 0 11.89 0.12 8.89 People 0.00 0 0.00 Return 206 61
Misc 0.52 0.00 0.52 28.11 0.52 38.52 Misc 0.00 0.00 0.00 Exhaust 14 0
Sub Total ==> 0.85 0.03 0.88 47.57 0.75 55.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.96 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 8.65 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.62 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.78 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 5.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 18.68 5.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.92
W/m² 168.77 -32.46
Grand Total ==> 1.53 0.09 1.85 100.00 1.35 100.00 Grand Total ==> -0.16 -0.56 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.84 1.55 203 26.0 19.4 11.5 18.4 16.9 11.5 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.84 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 122 of 323
Room Checksums
By Trane
T2-phong dat may elisa

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 24 / 18 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.8 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.8 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 13.87 0.19 18.45 Partition/Door -0.25 -0.25 0.00 Diffuser 156 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 156 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 156 47
Infiltration 0.07 0.07 5.11 0.03 2.91 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.26 0.00 0.26 18.98 0.22 21.36 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.08 0.02 0.10 7.30 0.11 10.68 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.22 0 0 16.06 0.12 11.65 People 0.00 0 0.00 Return 158 47
Misc 0.45 0.00 0.45 32.85 0.54 52.43 Misc 0.00 0.00 0.00 Exhaust 14 0
Sub Total ==> 0.75 0.02 0.77 56.20 0.77 74.76 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.88 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.33 24.09 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.92 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 3.65 RA Preheat Diff. -0.15 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.15 0.00 % OA 9.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 14.28 4.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 114.35
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.01
W/m² 124.80 -36.97
Grand Total ==> 1.05 -0.06 1.37 100.00 1.03 100.00 Grand Total ==> -0.25 -0.55 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.36 0.87 129 25.8 19.8 12.1 18.4 17.0 11.7 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.36 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 123 of 323
Room Checksums
By Trane
T2-phong dinh danh vi khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 4.11 0.13 5.78 Partition/Door -0.25 -0.25 0.00 Diffuser 287 86
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 287 86
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 287 86
Infiltration 0.11 0.11 3.48 0.03 1.33 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.24 0.00 0.24 7.59 0.16 7.11 Sub Total ==> -0.25 -0.25 0.00 Nom Vent 18 0
AHU Vent 18 0
Internal Loads Internal Loads Infil 2 0
Lights 1.18 0.30 1.48 46.84 1.18 52.44 Lights 0.00 0.00 0.00 MinStop/Rh 86 86
People 0.42 0 0 13.29 0.22 9.78 People 0.00 0 0.00 Return 290 86
Misc 0.67 0.00 0.67 21.20 0.67 29.78 Misc 0.00 0.00 0.00 Exhaust 21 0
Sub Total ==> 2.27 0.30 2.57 81.33 2.07 92.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.89 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.26 8.23 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.63 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.11 3.48 RA Preheat Diff. -0.28 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.28 0.00 % OA 6.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 26.39 7.92
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.29
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.46
W/m² 288.94 -48.70
Grand Total ==> 2.53 0.26 3.16 100.00 2.25 100.00 Grand Total ==> -0.25 -0.81 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.15 2.67 287 26.0 19.9 12.2 18.4 17.1 11.7 Floor 11 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 124 of 323
Room Checksums
By Trane
T2-phong do thi luc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.49 0.00 0.49 15.61 0.53 22.46 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.91 0.05 2.12 Glass/Door Cond -0.01 -0.01 0.73
Cooling Heating
Wall Cond 0.22 0.07 0.29 9.24 0.21 8.90 Wall Cond -0.03 -0.04 2.92
Partition/Door 0.31 0.31 9.87 0.31 13.14 Partition/Door -0.41 -0.41 29.93 Diffuser 243 73
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 243 73
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 243 73
Infiltration 0.26 0.26 8.28 0.06 2.54 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.34 0.07 1.41 44.90 1.16 49.15 Sub Total ==> -0.45 -0.46 33.58 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 6 0
Lights 0.26 0.06 0.32 10.19 0.26 11.02 Lights 0.00 0.00 0.00 MinStop/Rh 73 73
People 0.52 0 1 16.56 0.28 11.86 People 0.00 0 0.00 Return 249 73
Misc 0.52 0.00 0.52 16.56 0.52 22.03 Misc 0.00 0.00 0.00 Exhaust 35 0
Sub Total ==> 1.30 0.06 1.36 43.31 1.06 44.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 5.93 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.41 13.06 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -4.14 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 2.87 RA Preheat Diff. -0.46 33.58 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.46 33.58 % OA 11.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.73 Lps/m² 9.35 2.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.30
W/m² 120.40 -35.03
Grand Total ==> 2.78 -0.14 3.14 100.00 2.36 100.00 Grand Total ==> -0.45 -1.37 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.13 2.46 243 27.3 19.9 11.7 15.9 15.9 11.4 Floor 26 Main Htg -0.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 47 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.13 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 17 3 16 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 125 of 323
Room Checksums
By Trane
T2-phong do thinh luc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.28 0.00 0.28 14.29 0.28 17.72 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.55 0.05 3.16 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.19 0.06 0.25 12.76 0.19 12.03 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.18 0.18 9.18 0.18 11.39 Partition/Door -0.24 -0.24 0.00 Diffuser 163 49
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 163 49
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 163 49
Infiltration 0.11 0.11 5.61 0.03 1.90 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.81 0.06 0.87 44.39 0.73 46.20 Sub Total ==> -0.27 -0.28 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 7.65 0.12 7.59 Lights 0.00 0.00 0.00 MinStop/Rh 49 49
People 0.24 0 0 12.24 0.13 8.23 People 0.00 0 0.00 Return 166 49
Misc 0.53 0.00 0.53 27.04 0.53 33.54 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.89 0.03 0.92 46.94 0.78 49.37 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 4.43 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 8.67 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -3.06 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.06 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 13.81 4.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.02
W/m² 166.08 -48.77
Grand Total ==> 1.77 -0.04 1.96 100.00 1.58 100.00 Grand Total ==> -0.27 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.96 1.68 163 27.2 19.8 11.6 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 27 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 126 of 323
Room Checksums
By Trane
T2-phong giam doc 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.80 0.23 1.03 33.44 0.85 38.81 Wall Cond -0.10 -0.13 0.00
Partition/Door 0.10 0.10 3.25 0.10 4.57 Partition/Door -0.19 -0.19 0.00 Diffuser 229 69
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 229 69
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 229 69
Infiltration 0.27 0.27 8.77 0.04 1.83 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.17 0.23 1.40 45.45 0.99 45.21 Sub Total ==> -0.29 -0.32 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 10.06 0.25 11.42 Lights 0.00 0.00 0.00 MinStop/Rh 69 69
People 0.41 0 0 13.31 0.22 10.05 People 0.00 0 0.00 Return 236 69
Misc 0.67 0.00 0.67 21.75 0.67 30.59 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.33 0.06 1.39 45.13 1.14 52.05 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.74 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.26 8.44 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.62 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.60 RA Preheat Diff. -0.33 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.34 0.00 % OA 9.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 0.00 Lps/m² 9.01 2.70
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.24
W/m² 121.29 -24.99
Grand Total ==> 2.56 0.18 3.08 100.00 2.19 100.00 Grand Total ==> -0.29 -0.97 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.08 2.49 226 26.4 20.1 12.3 17.0 16.5 11.6 Floor 25 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.08 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 48 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 127 of 323
Room Checksums
By Trane
T2-phong giam doc 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.67 0.19 0.86 30.50 0.67 33.33 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.10 0.10 3.55 0.10 4.98 Partition/Door -0.19 -0.19 0.00 Diffuser 210 63
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 210 63
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 210 63
Infiltration 0.22 0.22 7.80 0.04 1.99 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.99 0.19 1.18 41.84 0.81 40.30 Sub Total ==> -0.25 -0.27 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 10.99 0.25 12.44 Lights 0.00 0.00 0.00 MinStop/Rh 63 63
People 0.41 0 0 14.54 0.22 10.95 People 0.00 0 0.00 Return 217 63
Misc 0.67 0.00 0.67 23.76 0.67 33.33 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.33 0.06 1.39 49.29 1.14 56.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.22 7.80 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.77 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.84 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 10.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.27 2.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.36
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.99
W/m² 111.13 -22.41
Grand Total ==> 2.38 0.14 2.82 100.00 2.01 100.00 Grand Total ==> -0.25 -0.88 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.82 2.29 210 26.4 20.1 12.3 17.0 16.5 11.7 Floor 25 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.82 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 128 of 323
Room Checksums
By Trane
T2-phong giam doc 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.67 0.19 0.86 30.50 0.67 33.33 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.10 0.10 3.55 0.10 4.98 Partition/Door -0.19 -0.19 0.00 Diffuser 210 63
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 210 63
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 210 63
Infiltration 0.22 0.22 7.80 0.04 1.99 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.99 0.19 1.18 41.84 0.81 40.30 Sub Total ==> -0.25 -0.27 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 10.99 0.25 12.44 Lights 0.00 0.00 0.00 MinStop/Rh 63 63
People 0.41 0 0 14.54 0.22 10.95 People 0.00 0 0.00 Return 217 63
Misc 0.67 0.00 0.67 23.76 0.67 33.33 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.33 0.06 1.39 49.29 1.14 56.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.22 7.80 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.77 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.84 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 10.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.27 2.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.36
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.99
W/m² 111.13 -22.41
Grand Total ==> 2.38 0.14 2.82 100.00 2.01 100.00 Grand Total ==> -0.25 -0.88 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.82 2.29 210 26.4 20.1 12.3 17.0 16.5 11.7 Floor 25 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.82 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 129 of 323
Room Checksums
By Trane
T2-phong giam doc 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.67 0.19 0.86 30.50 0.67 33.33 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.10 0.10 3.55 0.10 4.98 Partition/Door -0.19 -0.19 0.00 Diffuser 210 63
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 210 63
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 210 63
Infiltration 0.22 0.22 7.80 0.04 1.99 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.99 0.19 1.18 41.84 0.81 40.30 Sub Total ==> -0.25 -0.27 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 10.99 0.25 12.44 Lights 0.00 0.00 0.00 MinStop/Rh 63 63
People 0.41 0 0 14.54 0.22 10.95 People 0.00 0 0.00 Return 217 63
Misc 0.67 0.00 0.67 23.76 0.67 33.33 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.33 0.06 1.39 49.29 1.14 56.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.22 7.80 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.77 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.84 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 10.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.27 2.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.36
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.99
W/m² 111.13 -22.41
Grand Total ==> 2.38 0.14 2.82 100.00 2.01 100.00 Grand Total ==> -0.25 -0.88 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.82 2.29 210 26.4 20.1 12.3 17.0 16.5 11.7 Floor 25 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.82 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 130 of 323
Room Checksums
By Trane
T2-phong giam doc 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.67 0.19 0.86 30.50 0.67 33.33 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.10 0.10 3.55 0.10 4.98 Partition/Door -0.19 -0.19 0.00 Diffuser 210 63
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 210 63
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 210 63
Infiltration 0.22 0.22 7.80 0.04 1.99 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.99 0.19 1.18 41.84 0.81 40.30 Sub Total ==> -0.25 -0.27 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 10.99 0.25 12.44 Lights 0.00 0.00 0.00 MinStop/Rh 63 63
People 0.41 0 0 14.54 0.22 10.95 People 0.00 0 0.00 Return 217 63
Misc 0.67 0.00 0.67 23.76 0.67 33.33 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.33 0.06 1.39 49.29 1.14 56.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.22 7.80 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.77 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.84 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 10.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.27 2.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.36
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.99
W/m² 111.13 -22.41
Grand Total ==> 2.38 0.14 2.82 100.00 2.01 100.00 Grand Total ==> -0.25 -0.88 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.82 2.29 210 26.4 20.1 12.3 17.0 16.5 11.7 Floor 25 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 22 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.82 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 131 of 323
Room Checksums
By Trane
T2-phong giao ban

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.39 0.39 10.83 0.39 17.57 Partition/Door -0.78 -0.78 53.06 Diffuser 232 70
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 232 70
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 232 70
Infiltration 0.59 0.59 16.39 0.15 6.76 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.98 0.00 0.98 27.22 0.54 24.32 Sub Total ==> -0.78 -0.78 53.06 Nom Vent 42 0
AHU Vent 42 0
Internal Loads Internal Loads Infil 13 0
Lights 0.48 0.12 0.60 16.67 0.48 21.62 Lights 0.00 0.00 0.00 MinStop/Rh 70 70
People 0.78 0 1 21.67 0.42 18.92 People 0.00 0 0.00 Return 246 70
Misc 0.67 0.00 0.67 18.61 0.67 30.18 Misc 0.00 0.00 0.00 Exhaust 56 0
Sub Total ==> 1.93 0.12 2.05 56.94 1.57 70.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 4.95 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.57 15.83 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -2.50 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 2.50 RA Preheat Diff. -0.34 23.13 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.34 23.13 % OA 18.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.68 Lps/m² 4.76 1.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 64.51
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 13.56
W/m² 73.68 -23.08
Grand Total ==> 3.02 -0.08 3.60 100.00 2.22 100.00 Grand Total ==> -0.79 -1.47 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.60 2.38 231 26.6 20.4 12.6 17.0 16.3 11.4 Floor 49 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 88 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.60 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 132 of 323
Room Checksums
By Trane
T2-phong giao ban DT

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 9 / 13 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 32 OADB: 19 SADB 18.1 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 3.47 0.00 3.47 47.02 4.07 73.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.32 0.00 0.32 4.34 0.23 4.13 Glass/Door Cond -0.07 -0.07 3.95
Cooling Heating
Wall Cond 0.12 0.20 0.32 4.34 0.10 1.80 Wall Cond -0.01 -0.03 1.69
Partition/Door 0.06 0.06 0.81 0.06 1.08 Partition/Door -0.13 -0.13 7.34 Diffuser 647 194
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 647 194
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 647 194
Infiltration 0.27 0.27 3.66 0.03 0.54 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.24 0.20 4.44 60.16 4.49 80.61 Sub Total ==> -0.21 -0.23 12.99 Nom Vent 32 0
AHU Vent 32 0
Internal Loads Internal Loads Infil 3 0
Lights 0.23 0.06 0.29 3.93 0.17 3.05 Lights 0.00 0.00 0.00 MinStop/Rh 194 194
People 1.00 0 1 13.55 0.40 7.18 People 0.00 0 0.00 Return 651 194
Misc 0.67 0.00 0.67 9.08 0.47 8.44 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 1.90 0.06 1.96 26.56 1.04 18.67 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 0.72 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.82 11.11 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -1.08 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.24 3.25 RA Preheat Diff. -0.77 43.50 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.78 44.07 % OA 10.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.56 Lps/m² 27.66 8.30
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 87.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.17
W/m² 315.64 -42.40
Grand Total ==> 6.18 0.14 7.38 100.00 5.57 100.00 Grand Total ==> -0.21 -1.77 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.39 6.15 643 26.1 20.1 12.3 17.8 17.0 12.0 Floor 23 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.39 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 18 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 133 of 323
Room Checksums
By Trane
T2-phong ho so

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.31 0.13 9.70 Partition/Door -0.26 -0.26 0.00 Diffuser 170 51
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 170 51
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 170 51
Infiltration 0.29 0.29 14.08 0.07 5.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.39 0.20 14.93 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.08 0.23 17.16 Lights 0.00 0.00 0.00 MinStop/Rh 51 51
People 0.37 0 0 17.96 0.20 14.93 People 0.00 0 0.00 Return 177 51
Misc 0.67 0.00 0.67 32.52 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 64.56 1.10 82.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.28 13.59 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.91 RA Preheat Diff. -0.16 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.16 0.00 % OA 11.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.26 2.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.52
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.36
W/m² 87.97 -18.12
Grand Total ==> 1.73 -0.01 2.06 100.00 1.34 100.00 Grand Total ==> -0.26 -0.58 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.06 1.46 170 26.1 20.1 12.4 18.4 16.9 11.6 Floor 23 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.06 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 134 of 323
Room Checksums
By Trane
T2-phong hop chinh tri

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 1.45 0.00 1.45 18.49 1.45 31.80 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.27 0.00 0.27 3.44 0.27 5.92 Glass/Door Cond -0.06 -0.06 3.39
Cooling Heating
Wall Cond 0.20 0.16 0.36 4.59 0.20 4.39 Wall Cond -0.02 -0.04 2.26
Partition/Door 0.13 0.13 1.66 0.13 2.85 Partition/Door -0.26 -0.26 14.69 Diffuser 478 143
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 478 143
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 478 143
Infiltration 0.58 0.58 7.40 0.14 3.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.63 0.16 2.79 35.59 2.19 48.03 Sub Total ==> -0.34 -0.36 20.34 Nom Vent 136 0
AHU Vent 136 0
Internal Loads Internal Loads Infil 13 0
Lights 0.47 0.12 0.59 7.53 0.47 10.31 Lights 0.00 0.00 0.00 MinStop/Rh 143 143
People 2.08 0 2 26.53 1.12 24.56 People 0.00 0 0.00 Return 491 143
Misc 0.67 0.00 0.67 8.55 0.67 14.69 Misc 0.00 0.00 0.00 Exhaust 149 0
Sub Total ==> 3.22 0.12 3.34 42.60 2.26 49.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 2.41 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.77 22.58 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.24 -0.24 -3.06 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.18 2.30 RA Preheat Diff. -0.70 39.55 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.71 40.11 % OA 28.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.78 2.94
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 60.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.23
W/m² 160.51 -21.60
Grand Total ==> 5.96 -0.07 7.84 100.00 4.56 100.00 Grand Total ==> -0.35 -1.77 100.00 No. People 16

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.84 5.19 478 26.8 20.7 12.9 17.0 16.4 11.5 Floor 49 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.84 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 14 48 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 135 of 323
Room Checksums
By Trane
T2-phong ke toan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.34 0.13 9.70 Partition/Door -0.26 -0.26 0.00 Diffuser 155 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 47
Infiltration 0.29 0.29 14.15 0.07 5.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.49 0.20 14.93 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.15 0.23 17.16 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.37 0 0 18.05 0.20 14.93 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 32.68 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 64.88 1.10 82.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.93 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 13.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.63 1.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.98
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.46
W/m² 87.21 -19.11
Grand Total ==> 1.73 -0.01 2.05 100.00 1.34 100.00 Grand Total ==> -0.26 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.04 1.45 155 26.2 20.2 12.4 17.8 16.7 11.6 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 136 of 323
Room Checksums
By Trane
T2-phong kham dong y

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.31 0.31 19.14 0.31 25.83 Partition/Door -0.41 -0.41 0.00 Diffuser 124 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 124 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 124 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 24.69 0.34 28.33 Sub Total ==> -0.41 -0.41 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.83 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 27.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 13.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.49 3.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.95
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.20 -54.78
Grand Total ==> 1.24 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.41 -0.87 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 0.99 105 26.9 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 47 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 137 of 323
Room Checksums
By Trane
T2-phong kham mat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.31 0.31 19.14 0.31 25.83 Partition/Door -0.41 -0.41 0.00 Diffuser 124 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 124 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 124 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 24.69 0.34 28.33 Sub Total ==> -0.41 -0.41 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.83 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 27.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 13.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.49 3.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.95
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.20 -54.78
Grand Total ==> 1.24 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.41 -0.87 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 0.99 105 26.9 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 47 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 138 of 323
Room Checksums
By Trane
T2-phong kham rang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 16 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.28 0.00 0.28 14.29 0.28 17.72 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.55 0.05 3.16 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.19 0.06 0.25 12.76 0.19 12.03 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.18 0.18 9.18 0.18 11.39 Partition/Door -0.24 -0.24 0.00 Diffuser 163 49
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 163 49
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 163 49
Infiltration 0.11 0.11 5.61 0.03 1.90 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.81 0.06 0.87 44.39 0.73 46.20 Sub Total ==> -0.27 -0.28 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.12 0.03 0.15 7.65 0.12 7.59 Lights 0.00 0.00 0.00 MinStop/Rh 49 49
People 0.24 0 0 12.24 0.13 8.23 People 0.00 0 0.00 Return 166 49
Misc 0.53 0.00 0.53 27.04 0.53 33.54 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.89 0.03 0.92 46.94 0.78 49.37 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 4.43 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 8.67 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -3.06 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.06 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 13.81 4.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.02
W/m² 166.08 -48.77
Grand Total ==> 1.77 -0.04 1.96 100.00 1.58 100.00 Grand Total ==> -0.27 -0.89 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.96 1.68 163 27.2 19.8 11.6 15.9 15.9 11.4 Floor 12 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 27 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.96 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 13 3 20 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 139 of 323
Room Checksums
By Trane
T2-phong kham rang 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.31 0.31 19.14 0.31 25.83 Partition/Door -0.41 -0.41 0.00 Diffuser 124 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 124 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 124 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 24.69 0.34 28.33 Sub Total ==> -0.41 -0.41 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.83 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 27.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 13.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.49 3.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.95
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.20 -54.78
Grand Total ==> 1.24 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.41 -0.87 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 0.99 105 26.9 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 47 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 140 of 323
Room Checksums
By Trane
T2-phong kham tai mui hong

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.31 0.31 19.14 0.31 25.83 Partition/Door -0.41 -0.41 0.00 Diffuser 124 37
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 124 37
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 124 37
Infiltration 0.09 0.09 5.56 0.03 2.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 24.69 0.34 28.33 Sub Total ==> -0.41 -0.41 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.79 0.12 10.00 Lights 0.00 0.00 0.00 MinStop/Rh 37 37
People 0.24 0 0 14.81 0.13 10.83 People 0.00 0 0.00 Return 126 37
Misc 0.45 0.00 0.45 27.78 0.54 45.00 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 49.38 0.79 65.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.83 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 27.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.32 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.47 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 13.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.49 3.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 76.95
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.20 -54.78
Grand Total ==> 1.24 -0.11 1.62 100.00 1.20 100.00 Grand Total ==> -0.41 -0.87 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.61 0.99 105 26.9 20.6 12.7 15.9 15.9 11.4 Floor 12 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 47 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.61 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 141 of 323
Room Checksums
By Trane
T2-phong kham than kinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 33 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.20 0.05 0.25 14.88 0.24 17.52 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.29 0.29 17.26 0.29 21.17 Partition/Door -0.39 -0.39 0.00 Diffuser 141 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 141 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 141 42
Infiltration 0.08 0.08 4.76 0.03 2.19 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.57 0.05 0.62 36.90 0.56 40.88 Sub Total ==> -0.42 -0.43 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.07 0.02 0.09 5.36 0.11 8.03 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.21 0 0 12.50 0.12 8.76 People 0.00 0 0.00 Return 144 42
Misc 0.41 0.00 0.41 24.40 0.52 37.96 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 0.69 0.02 0.71 42.26 0.75 54.74 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 4.38 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.38 22.62 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.17 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.38 RA Preheat Diff. -0.27 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 10.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.98 3.89
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 84.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.48
W/m² 154.23 -63.32
Grand Total ==> 1.32 -0.06 1.68 100.00 1.37 100.00 Grand Total ==> -0.42 -0.96 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.68 1.15 116 26.9 20.4 12.4 15.9 15.9 11.4 Floor 11 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 45 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.68 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 142 of 323
Room Checksums
By Trane
T2-phong kham tuyen nguoi cho mau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.33 0.33 9.22 0.33 16.26 Partition/Door -0.44 -0.44 42.31 Diffuser 308 92
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 308 92
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 308 92
Infiltration 0.50 0.50 13.97 0.11 5.42 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.83 0.00 0.83 23.18 0.44 21.67 Sub Total ==> -0.44 -0.44 42.31 Nom Vent 57 0
AHU Vent 57 0
Internal Loads Internal Loads Infil 11 0
Lights 0.37 0.09 0.46 12.85 0.37 18.23 Lights 0.00 0.00 0.00 MinStop/Rh 92 92
People 0.97 0 1 27.09 0.49 24.14 People 0.00 0 0.00 Return 319 92
Misc 0.59 0.00 0.59 16.48 0.59 29.06 Misc 0.00 0.00 0.00 Exhaust 69 0
Sub Total ==> 1.93 0.09 2.02 56.42 1.45 71.43 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 6.90 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.78 21.79 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.16 -0.16 -4.47 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.11 3.07 RA Preheat Diff. -0.30 28.85 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 28.85 % OA 18.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.47 2.24
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.46
W/m² 87.20 -17.99
Grand Total ==> 2.90 -0.21 3.58 100.00 2.03 100.00 Grand Total ==> -0.44 -1.04 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.59 2.16 307 26.1 19.8 11.9 18.4 16.7 11.2 Floor 41 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 50 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.59 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 143 of 323
Room Checksums
By Trane
T2-phong kham X quang vu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.41 0.41 23.56 0.41 31.30 Partition/Door -0.54 -0.54 51.43 Diffuser 136 41
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 136 41
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 136 41
Infiltration 0.09 0.09 5.17 0.03 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.50 0.00 0.50 28.74 0.44 33.59 Sub Total ==> -0.54 -0.54 51.43 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 6.32 0.12 9.16 Lights 0.00 0.00 0.00 MinStop/Rh 41 41
People 0.25 0 0 14.37 0.14 10.69 People 0.00 0 0.00 Return 138 41
Misc 0.45 0.00 0.45 25.86 0.54 41.22 Misc 0.00 0.00 0.00 Exhaust 17 0
Sub Total ==> 0.79 0.02 0.81 46.55 0.80 61.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 5.34 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.47 27.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -4.60 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.30 RA Preheat Diff. -0.25 23.81 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 24.76 % OA 12.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.94 3.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.08
W/m² 141.12 -64.41
Grand Total ==> 1.36 -0.13 1.74 100.00 1.31 100.00 Grand Total ==> -0.54 -1.05 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.75 1.11 117 26.9 20.5 12.6 15.9 15.9 11.4 Floor 12 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 62 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.75 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 144 of 323
Room Checksums
By Trane
T2-phong kho mau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.09 0.09 4.11 0.09 6.87 Partition/Door -0.13 -0.13 0.00 Diffuser 199 60
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 199 60
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 199 60
Infiltration 0.28 0.28 12.79 0.06 4.58 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.37 0.00 0.37 16.89 0.15 11.45 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 33 0
AHU Vent 33 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 11.87 0.21 16.03 Lights 0.00 0.00 0.00 MinStop/Rh 60 60
People 0.55 0 1 25.11 0.28 21.37 People 0.00 0 0.00 Return 206 60
Misc 0.59 0.00 0.59 26.94 0.59 45.04 Misc 0.00 0.00 0.00 Exhaust 39 0
Sub Total ==> 1.35 0.05 1.40 63.93 1.08 82.44 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 6.11 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 20.09 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -4.11 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.20 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 16.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.50 2.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.99
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.59
W/m² 94.34 -13.62
Grand Total ==> 1.80 -0.12 2.19 100.00 1.31 100.00 Grand Total ==> -0.13 -0.51 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.21 1.40 199 26.1 19.7 11.8 18.4 16.7 11.3 Floor 23 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.21 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 145 of 323
Room Checksums
By Trane
T2-phong lanh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.27 0.00 0.27 12.27 0.27 16.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 2.27 0.05 3.07 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.22 0.09 0.31 14.09 0.22 13.50 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.73 0.06 3.68 Partition/Door -0.13 -0.13 0.00 Diffuser 190 57
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 190 57
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 190 57
Infiltration 0.18 0.18 8.18 0.04 2.45 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.78 0.09 0.87 39.55 0.64 39.26 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.15 0.04 0.19 8.64 0.15 9.20 Lights 0.00 0.00 0.00 MinStop/Rh 57 57
People 0.25 0 0 11.36 0.14 8.59 People 0.00 0 0.00 Return 195 57
Misc 0.67 0.00 0.67 30.45 0.67 41.10 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.07 0.04 1.11 50.45 0.96 58.90 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 1.84 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 7.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.91 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.18 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 7.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.04 3.61
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.97
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.14
W/m² 139.91 -24.53
Grand Total ==> 1.88 0.08 2.20 100.00 1.63 100.00 Grand Total ==> -0.16 -0.62 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.21 1.83 190 26.1 20.0 12.2 17.8 16.9 11.8 Floor 16 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.21 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 146 of 323
Room Checksums
By Trane
T2-phong luyen hoan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 3.02 0.06 4.69 Partition/Door -0.13 -0.13 0.00 Diffuser 149 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 149 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 149 45
Infiltration 0.29 0.29 14.57 0.07 5.47 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.35 0.00 0.35 17.59 0.13 10.16 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 21 0
AHU Vent 21 0
Internal Loads Internal Loads Infil 7 0
Lights 0.24 0.06 0.30 15.08 0.24 18.75 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.38 0 0 19.10 0.21 16.41 People 0.00 0 0.00 Return 155 45
Misc 0.66 0.00 0.66 33.17 0.66 51.56 Misc 0.00 0.00 0.00 Exhaust 28 0
Sub Total ==> 1.28 0.06 1.34 67.34 1.11 86.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.13 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.28 14.07 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.51 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.51 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.18 0.00 % OA 14.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.16 1.85
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.65
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.11
W/m² 82.52 -12.69
Grand Total ==> 1.67 -0.01 1.99 100.00 1.28 100.00 Grand Total ==> -0.13 -0.49 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.99 1.39 148 26.3 20.2 12.5 17.8 16.7 11.5 Floor 24 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.99 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 147 of 323
Room Checksums
By Trane
T2-phong ngam rua

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.76 0.03 2.48 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.21 0.09 0.30 17.65 0.21 17.36 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 141 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 141 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 141 42
Infiltration 0.15 0.15 8.82 0.04 3.31 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.39 0.09 0.48 28.24 0.28 23.14 Sub Total ==> -0.03 -0.04 0.00 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 4 0
Lights 0.13 0.03 0.16 9.41 0.13 10.74 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.21 0 0 12.35 0.11 9.09 People 0.00 0 0.00 Return 145 42
Misc 0.67 0.00 0.67 39.41 0.67 55.37 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 1.01 0.03 1.04 61.18 0.91 75.21 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 1.65 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.15 8.82 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.18 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.94 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 8.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 10.69 3.21
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.74
W/m² 129.14 -14.93
Grand Total ==> 1.42 0.08 1.70 100.00 1.21 100.00 Grand Total ==> -0.03 -0.37 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.71 1.38 141 26.2 20.0 12.3 17.8 16.8 11.7 Floor 13 Main Htg -0.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.71 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 3 0 0 Total -0.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 148 of 323
Room Checksums
By Trane
T2-phong nghi nguoi cho mau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.20 0.20 9.30 0.20 14.18 Partition/Door -0.39 -0.39 0.00 Diffuser 180 54
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 180 54
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 180 54
Infiltration 0.29 0.29 13.49 0.07 4.96 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.49 0.00 0.49 22.79 0.27 19.15 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 13.49 0.23 16.31 Lights 0.00 0.00 0.00 MinStop/Rh 54 54
People 0.38 0 0 17.67 0.20 14.18 People 0.00 0 0.00 Return 187 54
Misc 0.67 0.00 0.67 31.16 0.67 47.52 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 62.33 1.10 78.01 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.84 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.28 13.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.40 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.26 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 11.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.68 2.30
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.94
W/m² 91.38 -24.22
Grand Total ==> 1.81 -0.01 2.15 100.00 1.41 100.00 Grand Total ==> -0.39 -0.73 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.14 1.54 180 26.1 20.1 12.4 18.4 17.0 11.6 Floor 23 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 45 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 149 of 323
Room Checksums
By Trane
T2-phong nhan vien

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.20 0.20 9.30 0.20 14.18 Partition/Door -0.39 -0.39 0.00 Diffuser 180 54
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 180 54
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 180 54
Infiltration 0.29 0.29 13.49 0.07 4.96 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.49 0.00 0.49 22.79 0.27 19.15 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 13.49 0.23 16.31 Lights 0.00 0.00 0.00 MinStop/Rh 54 54
People 0.38 0 0 17.67 0.20 14.18 People 0.00 0 0.00 Return 187 54
Misc 0.67 0.00 0.67 31.16 0.67 47.52 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 62.33 1.10 78.01 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.84 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.28 13.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.40 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.26 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 11.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.68 2.30
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.94
W/m² 91.38 -24.22
Grand Total ==> 1.81 -0.01 2.15 100.00 1.41 100.00 Grand Total ==> -0.39 -0.73 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.14 1.54 180 26.1 20.1 12.4 18.4 17.0 11.6 Floor 23 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 45 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 150 of 323
Room Checksums
By Trane
T2-phong noi soi TMH

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.18 0.18 12.16 0.18 16.82 Partition/Door -0.24 -0.24 0.00 Diffuser 111 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 111 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 111 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 18.24 0.21 19.63 Sub Total ==> -0.24 -0.24 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 6.54 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 30.41 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.38 2.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.93
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.99
W/m² 125.12 -38.46
Grand Total ==> 1.11 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.24 -0.66 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.48 0.86 92 26.9 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 28 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.48 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 151 of 323
Room Checksums
By Trane
T2-phong nuoi cay

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.56 0.06 2.39 Partition/Door -0.13 -0.13 0.00 Diffuser 321 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 321 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 321 96
Infiltration 0.17 0.17 4.42 0.04 1.59 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.23 0.00 0.23 5.97 0.10 3.98 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 40 0
AHU Vent 40 0
Internal Loads Internal Loads Infil 4 0
Lights 1.45 0.36 1.81 47.01 1.45 57.77 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.51 0 1 13.25 0.27 10.76 People 0.00 0 0.00 Return 325 96
Misc 0.67 0.00 0.67 17.40 0.67 26.69 Misc 0.00 0.00 0.00 Exhaust 43 0
Sub Total ==> 2.63 0.36 2.99 77.66 2.39 95.22 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.80 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.56 14.55 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.30 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.12 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 12.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 23.76 7.13
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.33
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.51
W/m² 284.97 -32.35
Grand Total ==> 2.88 0.29 3.85 100.00 2.51 100.00 Grand Total ==> -0.13 -0.75 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.85 3.06 320 26.1 20.1 12.4 18.4 17.0 11.6 Floor 14 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.85 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 152 of 323
Room Checksums
By Trane
T2-phong rua hap

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 3.02 0.06 4.69 Partition/Door -0.13 -0.13 0.00 Diffuser 149 45
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 149 45
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 149 45
Infiltration 0.29 0.29 14.57 0.07 5.47 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.35 0.00 0.35 17.59 0.13 10.16 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 21 0
AHU Vent 21 0
Internal Loads Internal Loads Infil 7 0
Lights 0.24 0.06 0.30 15.08 0.24 18.75 Lights 0.00 0.00 0.00 MinStop/Rh 45 45
People 0.38 0 0 19.10 0.21 16.41 People 0.00 0 0.00 Return 155 45
Misc 0.66 0.00 0.66 33.17 0.66 51.56 Misc 0.00 0.00 0.00 Exhaust 28 0
Sub Total ==> 1.28 0.06 1.34 67.34 1.11 86.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.13 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.28 14.07 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.51 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.51 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.18 0.00 % OA 14.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.16 1.85
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.65
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.11
W/m² 82.52 -12.69
Grand Total ==> 1.67 -0.01 1.99 100.00 1.28 100.00 Grand Total ==> -0.13 -0.49 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.99 1.39 148 26.3 20.2 12.5 17.8 16.7 11.5 Floor 24 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.99 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 153 of 323
Room Checksums
By Trane
T2-Phong rua tiet trung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 4.58 0.06 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 114 34
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 114 34
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 114 34
Infiltration 0.13 0.13 9.92 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.19 0.00 0.19 14.50 0.09 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.10 0.03 0.13 9.92 0.10 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 34 34
People 0.17 0 0 12.98 0.09 0.00 People 0.00 0 0.00 Return 117 34
Misc 0.67 0.00 0.67 51.15 0.67 0.00 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.94 0.03 0.97 74.05 0.86 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.12 9.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 3.05 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.14 0.00 % OA 8.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.54 3.16
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 86.30
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.19
W/m² 122.05 -24.73
Grand Total ==> 1.15 0.00 1.31 100.00 0.97 100.00 Grand Total ==> -0.13 -0.41 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.32 1.05 114 26.1 20.0 12.3 17.8 17.0 11.9 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.32 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 154 of 323
Room Checksums
By Trane
T2-phong sang loc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.09 0.09 4.11 0.09 6.87 Partition/Door -0.13 -0.13 0.00 Diffuser 199 60
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 199 60
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 199 60
Infiltration 0.28 0.28 12.79 0.06 4.58 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.37 0.00 0.37 16.89 0.15 11.45 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 33 0
AHU Vent 33 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 11.87 0.21 16.03 Lights 0.00 0.00 0.00 MinStop/Rh 60 60
People 0.55 0 1 25.11 0.28 21.37 People 0.00 0 0.00 Return 206 60
Misc 0.59 0.00 0.59 26.94 0.59 45.04 Misc 0.00 0.00 0.00 Exhaust 39 0
Sub Total ==> 1.35 0.05 1.40 63.93 1.08 82.44 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 6.11 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.44 20.09 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -4.11 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 3.20 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 16.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.50 2.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.99
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.59
W/m² 94.34 -13.62
Grand Total ==> 1.80 -0.12 2.19 100.00 1.31 100.00 Grand Total ==> -0.13 -0.51 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.21 1.40 199 26.1 19.7 11.8 18.4 16.7 11.3 Floor 23 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.21 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 155 of 323
Room Checksums
By Trane
T2-phong sinh hoc phan tu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.56 0.06 2.39 Partition/Door -0.13 -0.13 0.00 Diffuser 321 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 321 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 321 96
Infiltration 0.17 0.17 4.42 0.04 1.59 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.23 0.00 0.23 5.97 0.10 3.98 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 40 0
AHU Vent 40 0
Internal Loads Internal Loads Infil 4 0
Lights 1.45 0.36 1.81 47.01 1.45 57.77 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.51 0 1 13.25 0.27 10.76 People 0.00 0 0.00 Return 325 96
Misc 0.67 0.00 0.67 17.40 0.67 26.69 Misc 0.00 0.00 0.00 Exhaust 43 0
Sub Total ==> 2.63 0.36 2.99 77.66 2.39 95.22 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.80 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.56 14.55 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.30 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.12 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 12.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 23.76 7.13
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.33
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.51
W/m² 284.97 -32.35
Grand Total ==> 2.88 0.29 3.85 100.00 2.51 100.00 Grand Total ==> -0.13 -0.75 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.85 3.06 320 26.1 20.1 12.4 18.4 17.0 11.6 Floor 14 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.85 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 156 of 323
Room Checksums
By Trane
T2-phong T khoa

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.34 0.13 9.70 Partition/Door -0.26 -0.26 0.00 Diffuser 155 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 47
Infiltration 0.29 0.29 14.15 0.07 5.22 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.49 0.20 14.93 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 14.15 0.23 17.16 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.37 0 0 18.05 0.20 14.93 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 32.68 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.27 0.06 1.33 64.88 1.10 82.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 2.99 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.93 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 13.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.63 1.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.98
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.46
W/m² 87.21 -19.11
Grand Total ==> 1.73 -0.01 2.05 100.00 1.34 100.00 Grand Total ==> -0.26 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.04 1.45 155 26.2 20.2 12.4 17.8 16.7 11.6 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 157 of 323
Room Checksums
By Trane
T2-phong tach chiet

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 4.37 0.00 4.37 65.03 4.37 74.96 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.14 0.00 0.14 2.08 0.14 2.40 Glass/Door Cond -0.07 -0.07 4.22
Cooling Heating
Wall Cond 0.09 0.14 0.23 3.42 0.09 1.54 Wall Cond -0.01 -0.03 1.81
Partition/Door 0.06 0.06 0.89 0.06 1.03 Partition/Door -0.13 -0.13 7.83 Diffuser 745 224
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 745 224
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 745 224
Infiltration 0.17 0.17 2.53 0.03 0.51 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.83 0.14 4.97 73.96 4.69 80.45 Sub Total ==> -0.21 -0.23 13.86 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.23 0.06 0.29 4.32 0.23 3.95 Lights 0.00 0.00 0.00 MinStop/Rh 224 224
People 0.38 0 0 5.65 0.20 3.43 People 0.00 0 0.00 Return 752 224
Misc 0.67 0.00 0.67 9.97 0.67 11.49 Misc 0.00 0.00 0.00 Exhaust 27 0
Sub Total ==> 1.28 0.06 1.34 19.94 1.10 18.87 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 0.69 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 2.53 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -0.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 4.02 RA Preheat Diff. -0.72 43.37 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.72 43.37 % OA 2.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.60 Lps/m² 31.78 9.53
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.48
W/m² 286.90 -39.73
Grand Total ==> 6.15 0.13 6.72 100.00 5.83 100.00 Grand Total ==> -0.21 -1.66 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 6.73 6.28 745 25.9 19.8 12.1 18.4 17.3 12.1 Floor 23 Main Htg -0.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 6.73 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 18 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 158 of 323
Room Checksums
By Trane
T2-phong thu gom mau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 9 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 24 / 18 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.8 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.8 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.39 0.39 16.32 0.39 25.00 Partition/Door -0.52 -0.52 0.00 Diffuser 238 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 238 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 238 71
Infiltration 0.15 0.15 6.28 0.06 3.85 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.54 0.00 0.54 22.59 0.45 28.85 Sub Total ==> -0.52 -0.52 0.00 Nom Vent 26 0
AHU Vent 26 0
Internal Loads Internal Loads Infil 5 0
Lights 0.17 0.04 0.21 8.79 0.23 14.74 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.47 0 0 19.67 0.26 16.67 People 0.00 0 0.00 Return 243 71
Misc 0.45 0.00 0.45 18.83 0.54 34.62 Misc 0.00 0.00 0.00 Exhaust 31 0
Sub Total ==> 1.09 0.04 1.13 47.28 1.03 66.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 5.13 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.74 30.96 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -3.77 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.93 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 13.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 10.14 3.04
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 99.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.79
W/m² 102.04 -31.97
Grand Total ==> 1.71 -0.13 2.39 100.00 1.56 100.00 Grand Total ==> -0.52 -0.98 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.39 1.31 197 25.8 20.1 12.5 18.4 16.9 11.5 Floor 23 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.39 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 159 of 323
Room Checksums
By Trane
T2-phong tiep khach

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.39 0.39 10.83 0.39 17.57 Partition/Door -0.78 -0.78 53.06 Diffuser 232 70
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 232 70
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 232 70
Infiltration 0.59 0.59 16.39 0.15 6.76 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.98 0.00 0.98 27.22 0.54 24.32 Sub Total ==> -0.78 -0.78 53.06 Nom Vent 42 0
AHU Vent 42 0
Internal Loads Internal Loads Infil 13 0
Lights 0.48 0.12 0.60 16.67 0.48 21.62 Lights 0.00 0.00 0.00 MinStop/Rh 70 70
People 0.78 0 1 21.67 0.42 18.92 People 0.00 0 0.00 Return 246 70
Misc 0.67 0.00 0.67 18.61 0.67 30.18 Misc 0.00 0.00 0.00 Exhaust 56 0
Sub Total ==> 1.93 0.12 2.05 56.94 1.57 70.72 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 4.95 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.57 15.83 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -2.50 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 2.50 RA Preheat Diff. -0.34 23.13 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.34 23.13 % OA 18.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.68 Lps/m² 4.76 1.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 64.51
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 13.56
W/m² 73.68 -23.08
Grand Total ==> 3.02 -0.08 3.60 100.00 2.22 100.00 Grand Total ==> -0.79 -1.47 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.60 2.38 231 26.6 20.4 12.6 17.0 16.3 11.4 Floor 49 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 88 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.60 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 160 of 323
Room Checksums
By Trane
T2-phong xet nghiem PCR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.09 0.09 6.47 0.09 0.00 Partition/Door -0.13 -0.13 0.00 Diffuser 148 44
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 148 44
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 148 44
Infiltration 0.13 0.13 9.35 0.03 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.22 0.00 0.22 15.83 0.12 0.00 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 15 0
AHU Vent 15 0
Internal Loads Internal Loads Infil 3 0
Lights 0.10 0.02 0.12 8.63 0.10 0.00 Lights 0.00 0.00 0.00 MinStop/Rh 44 44
People 0.26 0 0 18.71 0.13 0.00 People 0.00 0 0.00 Return 151 44
Misc 0.59 0.00 0.59 42.45 0.59 0.00 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 0.95 0.02 0.97 69.78 0.82 0.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 0.00 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.19 13.67 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 3.60 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.14 0.00 % OA 10.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.59 4.08
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 105.73
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.78
W/m² 128.49 -24.74
Grand Total ==> 1.21 -0.06 1.39 100.00 0.98 100.00 Grand Total ==> -0.13 -0.41 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.40 1.03 148 26.0 19.5 11.6 18.4 17.0 11.6 Floor 11 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.40 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 161 of 323
Room Checksums
By Trane
T2-phong xet nghiem sinh hoa

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.7 21.0
Ra Plenum 25.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.14 0.14 3.77 0.14 5.38 Partition/Door -0.28 -0.28 0.00 Diffuser 334 100
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 334 100
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 334 100
Infiltration 0.14 0.14 3.77 0.03 1.15 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.28 0.00 0.28 7.55 0.17 6.54 Sub Total ==> -0.28 -0.28 0.00 Nom Vent 23 0
AHU Vent 23 0
Internal Loads Internal Loads Infil 3 0
Lights 1.46 0.37 1.83 49.33 1.46 56.15 Lights 0.00 0.00 0.00 MinStop/Rh 100 100
People 0.52 0 1 14.02 0.28 10.77 People 0.00 0 0.00 Return 337 100
Misc 0.67 0.00 0.67 18.06 0.67 25.77 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 2.65 0.37 3.02 81.40 2.41 92.69 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 0.77 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.32 8.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -0.81 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.23 RA Preheat Diff. -0.32 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 0.00 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 24.72 7.42
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.26 -44.87
Grand Total ==> 2.95 0.32 3.71 100.00 2.60 100.00 Grand Total ==> -0.28 -0.92 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.72 3.13 334 26.0 20.0 12.2 18.4 17.0 11.7 Floor 14 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 32 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.72 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 162 of 323
Room Checksums
By Trane
T2-phong XQ rang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 34 OADB: 19 SADB 16.2 21.0
Ra Plenum 27.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.18 0.18 12.16 0.18 16.82 Partition/Door -0.24 -0.24 0.00 Diffuser 111 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 111 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 111 33
Infiltration 0.09 0.09 6.08 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 18.24 0.21 19.63 Sub Total ==> -0.24 -0.24 0.00 Nom Vent 13 0
AHU Vent 13 0
Internal Loads Internal Loads Infil 3 0
Lights 0.09 0.02 0.11 7.43 0.12 11.21 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.24 0 0 16.22 0.13 12.15 People 0.00 0 0.00 Return 113 33
Misc 0.45 0.00 0.45 30.41 0.54 50.47 Misc 0.00 0.00 0.00 Exhaust 16 0
Sub Total ==> 0.78 0.02 0.80 54.05 0.79 73.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 6.54 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.45 30.41 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -4.73 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.03 2.03 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.38 2.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.93
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.99
W/m² 125.12 -38.46
Grand Total ==> 1.11 -0.11 1.48 100.00 1.07 100.00 Grand Total ==> -0.24 -0.66 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.48 0.86 92 26.9 20.7 12.9 15.9 15.9 11.4 Floor 12 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 28 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.48 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 163 of 323
Room Checksums
By Trane
T2-soi nhan dan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.07 0.07 4.79 0.07 6.67 Partition/Door -0.14 -0.14 0.00 Diffuser 121 36
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 121 36
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 121 36
Infiltration 0.17 0.17 11.64 0.04 3.81 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.24 0.00 0.24 16.44 0.11 10.48 Sub Total ==> -0.14 -0.14 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 4 0
Lights 0.13 0.03 0.16 10.96 0.13 12.38 Lights 0.00 0.00 0.00 MinStop/Rh 36 36
People 0.21 0 0 14.38 0.12 11.43 People 0.00 0 0.00 Return 125 36
Misc 0.67 0.00 0.67 45.89 0.67 63.81 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 1.01 0.03 1.04 71.23 0.92 87.62 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.02 -0.02 0.00 0.00 0.02 1.90 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.16 10.96 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -1.37 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.74 RA Preheat Diff. -0.14 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.15 0.00 % OA 9.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 9.02 2.71
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.15
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.21
W/m² 108.47 -21.19
Grand Total ==> 1.27 -0.01 1.46 100.00 1.05 100.00 Grand Total ==> -0.14 -0.43 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.46 1.12 121 26.2 20.1 12.3 17.8 16.9 11.8 Floor 13 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 16 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 164 of 323
Room Checksums
By Trane
T2-tiep nhan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.1 21.0
Ra Plenum 26.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.23 0.23 11.98 0.23 17.16 Partition/Door -0.47 -0.47 0.00 Diffuser 157 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 157 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 157 47
Infiltration 0.23 0.23 11.98 0.06 4.48 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.46 0.00 0.46 23.96 0.29 21.64 Sub Total ==> -0.47 -0.47 0.00 Nom Vent 16 0
AHU Vent 16 0
Internal Loads Internal Loads Infil 5 0
Lights 0.19 0.05 0.24 12.50 0.19 14.18 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.30 0 0 15.63 0.16 11.94 People 0.00 0 0.00 Return 162 47
Misc 0.67 0.00 0.67 34.90 0.67 50.00 Misc 0.00 0.00 0.00 Exhaust 21 0
Sub Total ==> 1.16 0.05 1.21 63.02 1.02 76.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 2.24 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.22 11.46 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.56 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.13 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 10.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.34 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.24
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.75
W/m² 102.54 -35.04
Grand Total ==> 1.65 -0.01 1.92 100.00 1.34 100.00 Grand Total ==> -0.47 -0.85 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.93 1.45 157 26.2 20.1 12.3 17.8 16.9 11.7 Floor 19 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 53 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.93 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 165 of 323
Room Checksums
By Trane
T2-tr ban tai chinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.58 0.17 0.75 27.37 0.58 30.37 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.13 0.13 4.74 0.13 6.81 Partition/Door -0.26 -0.26 0.00 Diffuser 201 60
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 201 60
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 201 60
Infiltration 0.26 0.26 9.49 0.06 3.14 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.97 0.17 1.14 41.61 0.77 40.31 Sub Total ==> -0.32 -0.34 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 10.22 0.22 11.52 Lights 0.00 0.00 0.00 MinStop/Rh 60 60
People 0.37 0 0 13.50 0.20 10.47 People 0.00 0 0.00 Return 207 60
Misc 0.67 0.00 0.67 24.45 0.67 35.08 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.26 0.06 1.32 48.18 1.09 57.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 2.62 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.12 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.55 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 9.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.86 2.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.26
W/m² 121.03 -27.34
Grand Total ==> 2.28 0.14 2.74 100.00 1.91 100.00 Grand Total ==> -0.32 -0.92 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.75 2.20 201 26.5 20.2 12.3 17.0 16.6 11.7 Floor 23 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.75 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 166 of 323
Room Checksums
By Trane
T2-tr p chinh tri

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.3 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.3 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.58 0.17 0.75 27.37 0.58 30.37 Wall Cond -0.06 -0.08 0.00
Partition/Door 0.13 0.13 4.74 0.13 6.81 Partition/Door -0.26 -0.26 0.00 Diffuser 201 60
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 201 60
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 201 60
Infiltration 0.26 0.26 9.49 0.06 3.14 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.97 0.17 1.14 41.61 0.77 40.31 Sub Total ==> -0.32 -0.34 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 10.22 0.22 11.52 Lights 0.00 0.00 0.00 MinStop/Rh 60 60
People 0.37 0 0 13.50 0.20 10.47 People 0.00 0 0.00 Return 207 60
Misc 0.67 0.00 0.67 24.45 0.67 35.08 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.26 0.06 1.32 48.18 1.09 57.07 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 2.62 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.12 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.46 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.55 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 9.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 8.86 2.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.26
W/m² 121.03 -27.34
Grand Total ==> 2.28 0.14 2.74 100.00 1.91 100.00 Grand Total ==> -0.32 -0.92 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.75 2.20 201 26.5 20.2 12.3 17.0 16.6 11.7 Floor 23 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.75 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 167 of 323
Room Checksums
By Trane
T2-UBKT

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 17.3 21.0
Ra Plenum 26.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.84 0.00 2.84 63.11 2.84 71.18 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.09 0.00 0.09 2.00 0.09 2.26 Glass/Door Cond -0.05 -0.05 3.50
Cooling Heating
Wall Cond 0.00 0.07 0.07 1.56 0.00 0.00 Wall Cond 0.00 -0.01 0.70
Partition/Door 0.06 0.06 1.33 0.06 1.50 Partition/Door -0.13 -0.13 9.09 Diffuser 419 126
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 419 126
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 419 126
Infiltration 0.11 0.11 2.44 0.02 0.50 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.10 0.07 3.17 70.44 3.01 75.44 Sub Total ==> -0.18 -0.19 13.29 Nom Vent 14 0
AHU Vent 14 0
Internal Loads Internal Loads Infil 4 0
Lights 0.15 0.04 0.19 4.22 0.15 3.76 Lights 0.00 0.00 0.00 MinStop/Rh 126 126
People 0.25 0 0 5.56 0.13 3.26 People 0.00 0 0.00 Return 423 126
Misc 0.67 0.00 0.67 14.89 0.67 16.79 Misc 0.00 0.00 0.00 Exhaust 18 0
Sub Total ==> 1.07 0.04 1.11 24.67 0.95 23.81 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.75 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.10 2.22 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -0.67 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.15 3.33 RA Preheat Diff. -0.61 42.66 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.62 43.36 % OA 3.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.70 Lps/m² 26.86 8.06
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.46
W/m² 288.81 -51.32
Grand Total ==> 4.20 0.05 4.50 100.00 3.99 100.00 Grand Total ==> -0.18 -1.43 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.51 4.23 419 26.2 19.9 12.1 17.0 16.9 12.1 Floor 16 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.51 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 12 79 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 168 of 323
Room Checksums
By Trane
T3- hanh lang vo khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 20.4 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,568 1,568
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,568 1,568
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,568 1,568
Infiltration 1.39 1.39 30.89 0.44 13.92 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.39 0.00 1.39 30.89 0.44 13.92 Sub Total ==> 0.00 0.00 0.00 Nom Vent 64 0
AHU Vent 64 0
Internal Loads Internal Loads Infil 31 0
Lights 1.14 0.28 1.42 31.56 1.14 36.08 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 2.89 0 3 64.22 1.55 49.05 People 0.00 0 0.00 Return 1,599 1,568
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 95 0
Sub Total ==> 4.03 0.28 4.31 95.78 2.69 85.13 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.95 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.18 -26.22 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.44 OA Preheat Diff. -0.72 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.05 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 13.75 13.75
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 105.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.66
W/m² 130.48 -4.94
Grand Total ==> 5.45 0.23 4.50 100.00 3.16 100.00 Grand Total ==> 0.00 -0.77 100.00 No. People 23

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.50 2.83 1,568 21.8 19.2 13.0 20.4 18.5 12.7 Floor 114 Main Htg -0.6 1,568 20.7 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 10.38 3.68 160 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 14.88 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 169 of 323
Room Checksums
By Trane
T3- Phong sieu am gang suc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 16 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.0 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.31 0.31 6.74 0.00 0.00 Roof Cond 0.00 -0.05 3.88
Glass Solar 2.10 0.00 2.10 45.65 2.10 59.66 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.09 0.00 0.09 1.96 0.09 2.56 Glass/Door Cond -0.04 -0.04 3.10
Cooling Heating
Wall Cond 0.06 0.08 0.14 3.04 0.06 1.70 Wall Cond -0.01 -0.01 0.78
Partition/Door 0.10 0.10 2.17 0.10 2.84 Partition/Door -0.13 -0.13 10.08 Diffuser 496 149
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 496 149
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 496 149
Infiltration 0.16 0.16 3.48 0.03 0.85 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.51 0.39 2.90 63.04 2.38 67.61 Sub Total ==> -0.18 -0.23 17.83 Nom Vent 28 0
AHU Vent 28 0
Internal Loads Internal Loads Infil 5 0
Lights 0.25 0.06 0.31 6.74 0.25 7.10 Lights 0.00 0.00 0.00 MinStop/Rh 149 149
People 0.50 0 1 10.87 0.27 7.67 People 0.00 0 0.00 Return 501 149
Misc 0.53 0.00 0.53 11.52 0.53 15.06 Misc 0.00 0.00 0.00 Exhaust 33 0
Sub Total ==> 1.28 0.06 1.34 29.13 1.05 29.83 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 2.56 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.26 5.65 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -1.74 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.18 3.91 RA Preheat Diff. -0.52 40.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.56 43.41 % OA 5.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 -1.55 Lps/m² 19.98 5.99
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 107.92
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.40
W/m² 185.03 -29.65
Grand Total ==> 3.88 0.28 4.60 100.00 3.52 100.00 Grand Total ==> -0.19 -1.29 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.59 4.07 496 26.1 19.4 11.4 18.0 16.7 11.4 Floor 25 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.59 Roof 25 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 9 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 170 of 323
Room Checksums
By Trane
T3-bo parafin

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 18.11 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 7.17 0.19 13.97 Partition/Door -0.26 -0.26 0.00 Diffuser 166 50
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 166 50
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 166 50
Infiltration 0.17 0.17 6.42 0.06 4.41 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.36 0.48 0.84 31.70 0.25 18.38 Sub Total ==> -0.26 -0.31 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.15 0.04 0.19 7.17 0.22 16.18 Lights 0.00 0.00 0.00 MinStop/Rh 50 50
People 0.42 0 0 15.85 0.25 18.38 People 0.00 0 0.00 Return 171 50
Misc 0.41 0.00 0.41 15.47 0.54 39.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 0.98 0.04 1.02 38.49 1.01 74.26 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 7.35 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.86 32.45 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -4.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 1.89 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 18.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.03 0.00 Lps/m² 7.50 2.25
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 62.52
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.34
W/m² 119.88 -22.69
Grand Total ==> 1.44 0.30 2.65 100.00 1.36 100.00 Grand Total ==> -0.27 -0.75 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.65 1.47 127 26.5 20.9 13.3 17.1 15.4 10.3 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.65 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 171 of 323
Room Checksums
By Trane
T3-hanh lang 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.6 23.3
Ra Plenum 28.0 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 28.0 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 28.1 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 5.96 5.96 24.24 0.00 0.00 Roof Cond 0.00 -0.58 16.38
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 4.24 1.23 5.47 22.24 4.24 36.84 Wall Cond -0.50 -0.63 17.80
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door -2.62 -2.62 74.01 Diffuser 1,107 1,107
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,107 1,107
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,107 1,107
Infiltration 2.57 2.57 10.45 0.52 4.52 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.81 7.19 14.00 56.93 4.76 41.36 Sub Total ==> -3.12 -3.83 108.19 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 72 0
Lights 2.59 0.65 3.24 13.18 2.59 22.50 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 6.74 0 7 27.41 3.67 31.89 People 0.00 0 0.00 Return 1,179 1,107
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 101 0
Sub Total ==> 9.33 0.65 9.98 40.59 6.26 54.39 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.49 -0.49 0.00 0.00 0.49 4.26 Ceiling Load -0.10 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.33 1.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -0.53 OA Preheat Diff. 0.03 -0.85
Sup. Fan Heat 0.41 1.67 RA Preheat Diff. -0.08 2.26 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.34 -9.60 Lps/m² 4.22 4.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 45.01
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.65
W/m² 93.81 -13.49
Grand Total ==> 16.63 7.22 24.59 100.00 11.51 100.00 Grand Total ==> -3.22 -3.54 100.00 No. People 52

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 24.59 19.23 1,107 28.4 21.7 13.6 18.6 16.0 10.3 Floor 262 Main Htg -3.5 1,107 20.8 23.3
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 297 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 24.59 Roof 262 0 0 Humidif 0.0 0 0.0 0.0
Wall 248 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -3.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 172 of 323
Room Checksums
By Trane
T3-hanh lang 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.5 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.55 0.00 0.55 3.85 0.55 7.93 Glass/Door Cond -0.14 -0.14 7.33
Cooling Heating
Wall Cond 0.06 0.63 0.69 4.83 0.06 0.86 Wall Cond -0.01 -0.07 3.66
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 585 175
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 585 175
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 585 175
Infiltration 2.75 2.75 19.26 0.54 7.78 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.36 0.63 3.99 27.94 1.15 16.57 Sub Total ==> -0.15 -0.21 10.99 Nom Vent 29 0
AHU Vent 29 0
Internal Loads Internal Loads Infil 70 0
Lights 2.55 0.64 3.19 22.34 2.55 36.74 Lights 0.00 0.00 0.00 MinStop/Rh 175 175
People 6.46 0 6 45.24 3.47 50.00 People 0.00 0 0.00 Return 655 175
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 99 0
Sub Total ==> 9.01 0.64 9.65 67.58 6.02 86.74 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.23 0.23 0.00 0.00 -0.23 -3.31 Ceiling Load -0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 2.52 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.06 0.06 0.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.22 1.54 RA Preheat Diff. -0.80 41.88 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.84 43.98 % OA 4.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.06 3.14 Lps/m² 2.29 0.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 40.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 17.87
W/m² 55.92 -4.20
Grand Total ==> 12.14 1.56 14.28 100.00 6.94 100.00 Grand Total ==> -0.23 -1.91 100.00 No. People 51

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 14.27 8.75 585 26.6 21.2 13.7 17.1 14.8 9.6 Floor 255 Main Htg -1.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 14.27 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 108 79 74 Opt Vent 0.0 0 0.0 0.0
Ext Door 79 0 0 Total -1.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 173 of 323
Room Checksums
By Trane
T3-hanh lang 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.1 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.6 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.51 0.00 0.51 4.99 0.51 12.17 Glass/Door Cond -0.14 -0.14 1.18
Cooling Heating
Wall Cond 0.05 0.54 0.59 5.77 0.05 1.19 Wall Cond -0.01 -0.06 0.50
Partition/Door -0.93 -0.93 -9.10 -0.93 -22.20 Partition/Door -10.34 -10.34 86.96 Diffuser 280 84
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 280 84
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 280 84
Infiltration 1.94 1.94 18.98 0.37 8.83 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.57 0.54 2.11 20.65 0.00 0.00 Sub Total ==> -10.49 -10.54 88.65 Nom Vent 97 0
AHU Vent 97 0
Internal Loads Internal Loads Infil 48 0
Lights 1.72 0.43 2.15 21.04 1.72 41.05 Lights 0.00 0.00 0.00 MinStop/Rh 84 84
People 4.48 0 4 43.84 2.44 58.23 People 0.00 0 0.00 Return 328 84
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 145 0
Sub Total ==> 6.20 0.43 6.63 64.87 4.16 99.28 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 0.72 Ceiling Load -0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.40 13.70 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 0.98 RA Preheat Diff. -0.63 5.30 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.66 5.55 % OA 34.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.06 0.50 Lps/m² 1.61 0.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 27.38
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 17.01
W/m² 58.76 -64.54
Grand Total ==> 7.80 0.92 10.22 100.00 4.19 100.00 Grand Total ==> -10.57 -11.89 100.00 No. People 35

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 10.23 5.42 280 27.6 22.1 14.5 14.7 12.2 7.9 Floor 174 Main Htg -11.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 1,176 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.23 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 108 79 74 Opt Vent 0.0 0 0.0 0.0
Ext Door 79 0 0 Total -11.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 174 of 323
Room Checksums
By Trane
T3-hanh lang 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.55 0.00 0.55 4.95 0.55 10.87 Glass/Door Cond -0.14 -0.14 11.11
Cooling Heating
Wall Cond 0.06 0.61 0.67 6.04 0.06 1.19 Wall Cond -0.01 -0.07 5.56
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 468 140
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 468 140
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 468 140
Infiltration 1.87 1.87 16.85 0.37 7.31 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.48 0.61 3.09 27.84 0.98 19.37 Sub Total ==> -0.15 -0.21 16.67 Nom Vent 97 0
AHU Vent 97 0
Internal Loads Internal Loads Infil 48 0
Lights 1.74 0.43 2.17 19.55 1.74 34.39 Lights 0.00 0.00 0.00 MinStop/Rh 140 140
People 4.41 0 4 39.73 2.37 46.84 People 0.00 0 0.00 Return 516 140
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 145 0
Sub Total ==> 6.15 0.43 6.58 59.28 4.11 81.23 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -0.03 0.03 0.00 0.00 -0.03 -0.59 Ceiling Load -0.06 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.25 11.26 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.01 0.01 0.09 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.17 1.53 RA Preheat Diff. -0.49 38.89 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.52 41.27 % OA 20.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.04 3.17 Lps/m² 2.69 0.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 42.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 15.66
W/m² 63.84 -4.21
Grand Total ==> 8.60 1.08 11.10 100.00 5.06 100.00 Grand Total ==> -0.21 -1.26 100.00 No. People 35

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.11 6.50 468 27.3 21.7 14.1 18.0 15.6 10.2 Floor 174 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.11 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 108 79 74 Opt Vent 0.0 0 0.0 0.0
Ext Door 79 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 175 of 323
Room Checksums
By Trane
T3-hanh lang sach

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 7 / 24 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 29 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.1 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 2.78 2.78 14.09 0.00 0.00 Roof Cond 0.00 -0.28 2.17
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.37 1.37 6.94 1.37 6.45 Partition/Door -1.37 -1.37 10.62 Diffuser 2,433 730
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,433 730
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,433 730
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.37 2.78 4.15 21.03 1.37 6.45 Sub Total ==> -1.37 -1.65 12.79 Nom Vent 369 0
AHU Vent 369 0
Internal Loads Internal Loads Infil 0 0
Lights 1.46 0.37 1.83 9.28 1.46 6.88 Lights 0.00 0.00 0.00 MinStop/Rh 730 730
People 3.50 0 4 17.74 1.94 9.14 People 0.00 0 0.00 Return 2,433 730
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 369 0
Sub Total ==> 4.96 0.37 5.33 27.01 3.40 16.02 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.21 -1.21 0.00 0.00 1.64 7.72 Ceiling Load -0.06 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 11.93 60.47 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.38 0.38 1.93 14.82 69.81 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -2.33 -2.33 -11.81 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 1.37 RA Preheat Diff. -5.49 42.56 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -5.73 44.42 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.03 0.23 Lps/m² 18.33 5.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 123.28
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.73
W/m² 148.61 -53.97
Grand Total ==> 7.92 -0.39 19.73 100.00 21.23 100.00 Grand Total ==> -1.43 -12.90 100.00 No. People 27

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 19.73 8.23 730 26.7 22.1 14.9 14.7 14.7 10.5 Floor 133 Main Htg -7.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 155 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 19.73 Roof 133 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -7.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 176 of 323
Room Checksums
By Trane
T3-hoi truong 300 cho

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 32 OADB: 19 SADB 18.0 21.6
Ra Plenum 27.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 7.28 7.28 9.34 0.00 0.00 Roof Cond 0.00 -0.80 10.80
Glass Solar 0.12 0.00 0.12 0.15 5.28 14.87 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.07 0.00 0.07 0.09 0.43 1.21 Glass/Door Cond -0.11 -0.11 1.48
Cooling Heating
Wall Cond 0.10 0.12 0.22 0.28 0.11 0.31 Wall Cond -0.02 -0.04 0.54
Partition/Door 1.31 1.31 1.68 1.31 3.69 Partition/Door -2.62 -2.62 35.36 Diffuser 4,086 4,086
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 4,086 4,086
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 4,086 4,086
Infiltration 2.06 2.06 2.64 0.87 2.45 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.66 7.40 11.06 14.20 8.00 22.54 Sub Total ==> -2.75 -3.57 48.18 Nom Vent 2,082 0
AHU Vent 2,082 0
Internal Loads Internal Loads Infil 100 0
Lights 2.29 0.57 2.86 3.67 3.59 10.11 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 26.10 0 26 33.50 21.01 59.18 People 0.00 0 0.00 Return 4,185 4,086
Misc 0.48 0.00 0.48 0.62 0.96 2.70 Misc 0.00 0.00 0.00 Exhaust 2,182 0
Sub Total ==> 28.87 0.57 29.44 37.79 25.56 72.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.70 -1.70 0.00 0.00 1.94 5.46 Ceiling Load -0.13 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 42.98 55.17 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -7.07 -7.07 -9.07 OA Preheat Diff. 3.73 -50.34
Sup. Fan Heat 1.50 1.93 RA Preheat Diff. -7.23 97.57 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 51.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.34 4.59 Lps/m² 11.25 11.25
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.66
W/m² 214.52 -20.37
Grand Total ==> 34.23 -0.80 77.91 100.00 35.50 100.00 Grand Total ==> -2.88 -7.41 100.00 No. People 300

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 77.90 18.94 4,086 27.3 22.9 16.0 18.0 18.0 13.1 Floor 363 Main Htg -7.4 4,086 20.1 21.6
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 297 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 77.90 Roof 363 0 0 Humidif 0.0 0 0.0 0.0
Wall 44 27 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -7.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 177 of 323
Room Checksums
By Trane
T3-kho do tiet trung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.0 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.63 1.63 22.61 0.00 0.00 Roof Cond 0.00 -0.14 8.24
Glass Solar 0.55 0.00 0.55 7.63 0.55 15.49 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.10 0.00 0.10 1.39 0.10 2.82 Glass/Door Cond -0.02 -0.02 1.18
Cooling Heating
Wall Cond 0.44 0.16 0.60 8.32 0.44 12.39 Wall Cond -0.04 -0.06 3.53
Partition/Door 0.13 0.13 1.80 0.13 3.66 Partition/Door -0.26 -0.26 15.29 Diffuser 285 86
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 285 86
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 285 86
Infiltration 0.82 0.82 11.37 0.18 5.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.04 1.79 3.83 53.12 1.40 39.44 Sub Total ==> -0.32 -0.48 28.24 Nom Vent 58 0
AHU Vent 58 0
Internal Loads Internal Loads Infil 18 0
Lights 0.66 0.16 0.82 11.37 0.66 18.59 Lights 0.00 0.00 0.00 MinStop/Rh 86 86
People 1.07 0 1 14.84 0.58 16.34 People 0.00 0 0.00 Return 304 86
Misc 0.67 0.00 0.67 9.29 0.67 18.87 Misc 0.00 0.00 0.00 Exhaust 76 0
Sub Total ==> 2.40 0.16 2.56 35.51 1.91 53.80 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.24 -0.24 0.00 0.00 0.24 6.76 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.91 12.62 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.19 -0.19 -2.64 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 1.39 RA Preheat Diff. -0.64 37.65 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.67 39.41 % OA 20.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.09 -5.29 Lps/m² 4.28 1.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 39.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.25
W/m² 108.05 -15.46
Grand Total ==> 4.68 1.52 7.21 100.00 3.55 100.00 Grand Total ==> -0.35 -1.70 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.20 5.43 285 27.3 20.7 12.6 14.7 13.8 9.6 Floor 67 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.20 Roof 67 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 178 of 323
Room Checksums
By Trane
T3-kho do vai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 7 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 34 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.63 0.13 9.85 Partition/Door -0.26 -0.26 0.00 Diffuser 140 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 140 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 140 42
Infiltration 0.27 0.27 13.78 0.06 4.55 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 20.41 0.19 14.39 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.27 0.21 15.91 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.35 0 0 17.86 0.19 14.39 People 0.00 0 0.00 Return 146 42
Misc 0.67 0.00 0.67 34.18 0.67 50.76 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 65.31 1.07 81.06 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.06 4.55 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -2.04 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.55 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 13.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 6.44 1.93
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.12
W/m² 89.91 -21.55
Grand Total ==> 1.68 -0.04 1.96 100.00 1.32 100.00 Grand Total ==> -0.27 -0.67 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.95 1.39 139 26.6 20.3 12.4 17.1 16.6 11.7 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 179 of 323
Room Checksums
By Trane
T3-kho dung cu vo khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.44 0.13 9.49 Partition/Door -0.26 -0.26 0.00 Diffuser 109 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 109 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 109 33
Infiltration 0.29 0.29 14.36 0.06 4.38 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.79 0.19 13.87 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 13.86 0.22 16.06 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.36 0 0 17.82 0.20 14.60 People 0.00 0 0.00 Return 115 33
Misc 0.67 0.00 0.67 33.17 0.67 48.91 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 64.85 1.09 79.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.09 6.57 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 15.35 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.98 RA Preheat Diff. -0.25 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 0.00 % OA 18.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 4.81 1.44
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 54.07
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.24
W/m² 88.92 -23.26
Grand Total ==> 1.74 -0.07 2.02 100.00 1.37 100.00 Grand Total ==> -0.27 -0.79 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.02 1.40 108 27.0 20.5 12.6 14.7 14.7 10.5 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.02 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 180 of 323
Room Checksums
By Trane
T3-kho vat tu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.93 0.93 14.81 0.00 0.00 Roof Cond 0.00 -0.10 7.94
Glass Solar 1.97 0.00 1.97 31.37 1.97 50.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.17 0.00 0.17 2.71 0.17 4.31 Glass/Door Cond -0.04 -0.04 3.17
Cooling Heating
Wall Cond 0.10 0.11 0.21 3.34 0.10 2.54 Wall Cond -0.01 -0.02 1.59
Partition/Door 0.06 0.06 0.96 0.06 1.52 Partition/Door -0.13 -0.13 10.32 Diffuser 474 142
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 474 142
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 474 142
Infiltration 0.53 0.53 8.44 0.13 3.30 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.83 1.04 3.87 61.62 2.43 61.68 Sub Total ==> -0.18 -0.29 23.02 Nom Vent 39 0
AHU Vent 39 0
Internal Loads Internal Loads Infil 12 0
Lights 0.41 0.10 0.51 8.12 0.41 10.41 Lights 0.00 0.00 0.00 MinStop/Rh 142 142
People 0.68 0 1 10.83 0.35 8.88 People 0.00 0 0.00 Return 487 142
Misc 0.62 0.00 0.62 9.87 0.62 15.74 Misc 0.00 0.00 0.00 Exhaust 51 0
Sub Total ==> 1.71 0.10 1.81 28.82 1.38 35.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 3.30 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.53 8.44 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.10 -0.10 -1.59 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.17 2.71 RA Preheat Diff. -0.50 39.68 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.53 42.06 % OA 8.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.06 -4.76 Lps/m² 10.68 3.21
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.34
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.05
W/m² 141.71 -16.35
Grand Total ==> 4.67 0.91 6.28 100.00 3.94 100.00 Grand Total ==> -0.20 -1.26 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 6.29 5.21 474 26.8 20.2 12.2 18.0 16.7 11.5 Floor 44 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 6.29 Roof 44 0 0 Humidif 0.0 0 0.0 0.0
Wall 18 10 56 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 181 of 323
Room Checksums
By Trane
T3-oxy cao ap oxy giam ap

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 16 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.0 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.13 1.13 8.42 0.00 0.00 Roof Cond 0.00 -0.20 5.56
Glass Solar 6.12 0.00 6.12 45.60 6.12 63.03 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.27 0.00 0.27 2.01 0.27 2.78 Glass/Door Cond -0.11 -0.11 3.06
Cooling Heating
Wall Cond 0.16 0.24 0.40 2.98 0.16 1.65 Wall Cond -0.02 -0.04 1.11
Partition/Door 0.28 0.28 2.09 0.28 2.88 Partition/Door -0.38 -0.38 10.56 Diffuser 1,369 411
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,369 411
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,369 411
Infiltration 0.57 0.57 4.25 0.12 1.24 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.40 1.37 8.77 65.35 6.95 71.58 Sub Total ==> -0.51 -0.73 20.28 Nom Vent 101 0
AHU Vent 101 0
Internal Loads Internal Loads Infil 20 0
Lights 0.90 0.22 1.12 8.35 0.90 9.27 Lights 0.00 0.00 0.00 MinStop/Rh 411 411
People 1.85 0 2 13.79 1.00 10.30 People 0.00 0 0.00 Return 1,389 411
Misc 0.53 0.00 0.53 3.95 0.53 5.46 Misc 0.00 0.00 0.00 Exhaust 121 0
Sub Total ==> 3.28 0.22 3.50 26.08 2.43 25.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.33 -0.33 0.00 0.00 0.33 3.40 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.95 7.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.30 -0.30 -2.24 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.50 3.73 RA Preheat Diff. -1.43 39.72 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.53 42.50 % OA 7.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.09 -2.50 Lps/m² 15.04 4.51
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 101.90
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.78
W/m² 147.49 -22.69
Grand Total ==> 11.01 0.96 13.42 100.00 9.71 100.00 Grand Total ==> -0.54 -3.60 100.00 No. People 18

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 13.43 11.51 1,369 26.1 19.4 11.5 18.0 16.7 11.5 Floor 91 Main Htg -2.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 43 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 13.43 Roof 91 0 0 Humidif 0.0 0 0.0 0.0
Wall 43 27 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 182 of 323
Room Checksums
By Trane
T3-phong bac si 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.58 0.00 0.58 21.32 0.58 28.71 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.04 0.00 0.04 1.47 0.04 1.98 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.16 0.06 0.22 8.09 0.16 7.92 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.21 0.06 2.97 Partition/Door -0.13 -0.13 0.00 Diffuser 216 65
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 216 65
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 216 65
Infiltration 0.25 0.25 9.19 0.05 2.48 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.09 0.06 1.15 42.28 0.89 44.06 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 9.56 0.21 10.40 Lights 0.00 0.00 0.00 MinStop/Rh 65 65
People 0.35 0 0 12.87 0.19 9.41 People 0.00 0 0.00 Return 222 65
Misc 0.67 0.00 0.67 24.63 0.67 33.17 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 47.06 1.07 52.97 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.97 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.19 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.47 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.94 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 9.94 2.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.15
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.97
W/m² 125.46 -22.13
Grand Total ==> 2.38 0.01 2.72 100.00 2.02 100.00 Grand Total ==> -0.17 -0.79 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.18 216 26.6 20.2 12.3 17.1 16.8 12.0 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 183 of 323
Room Checksums
By Trane
T3-phong bac si 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.58 0.00 0.58 21.32 0.58 28.71 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.04 0.00 0.04 1.47 0.04 1.98 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.16 0.06 0.22 8.09 0.16 7.92 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.21 0.06 2.97 Partition/Door -0.13 -0.13 0.00 Diffuser 216 65
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 216 65
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 216 65
Infiltration 0.25 0.25 9.19 0.05 2.48 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.09 0.06 1.15 42.28 0.89 44.06 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 9.56 0.21 10.40 Lights 0.00 0.00 0.00 MinStop/Rh 65 65
People 0.35 0 0 12.87 0.19 9.41 People 0.00 0 0.00 Return 222 65
Misc 0.67 0.00 0.67 24.63 0.67 33.17 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 47.06 1.07 52.97 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.97 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.19 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.47 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.94 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 9.94 2.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.15
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.97
W/m² 125.46 -22.13
Grand Total ==> 2.38 0.01 2.72 100.00 2.02 100.00 Grand Total ==> -0.17 -0.79 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.18 216 26.6 20.2 12.3 17.1 16.8 12.0 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 184 of 323
Room Checksums
By Trane
T3-phong bac si 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.58 0.00 0.58 21.32 0.58 28.71 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.04 0.00 0.04 1.47 0.04 1.98 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.16 0.06 0.22 8.09 0.16 7.92 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.06 0.06 2.21 0.06 2.97 Partition/Door -0.13 -0.13 0.00 Diffuser 216 65
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 216 65
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 216 65
Infiltration 0.25 0.25 9.19 0.05 2.48 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.09 0.06 1.15 42.28 0.89 44.06 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 9.56 0.21 10.40 Lights 0.00 0.00 0.00 MinStop/Rh 65 65
People 0.35 0 0 12.87 0.19 9.41 People 0.00 0 0.00 Return 222 65
Misc 0.67 0.00 0.67 24.63 0.67 33.17 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 47.06 1.07 52.97 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 2.97 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.25 9.19 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.47 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.94 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 9.94 2.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.15
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.97
W/m² 125.46 -22.13
Grand Total ==> 2.38 0.01 2.72 100.00 2.02 100.00 Grand Total ==> -0.17 -0.79 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.18 216 26.6 20.2 12.3 17.1 16.8 12.0 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 185 of 323
Room Checksums
By Trane
T3-phong bac si 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.26 0.26 12.38 0.26 17.93 Partition/Door -0.52 -0.52 0.00 Diffuser 155 47
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 155 47
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 155 47
Infiltration 0.27 0.27 12.86 0.06 4.14 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.53 0.00 0.53 25.24 0.32 22.07 Sub Total ==> -0.52 -0.52 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 12.38 0.21 14.48 Lights 0.00 0.00 0.00 MinStop/Rh 47 47
People 0.35 0 0 16.67 0.19 13.10 People 0.00 0 0.00 Return 161 47
Misc 0.67 0.00 0.67 31.90 0.67 46.21 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 60.95 1.07 73.79 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.06 4.14 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 12.86 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -1.90 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.86 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.22 0.00 % OA 12.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 7.15 2.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.55
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.29
W/m² 97.16 -34.53
Grand Total ==> 1.81 -0.04 2.10 100.00 1.45 100.00 Grand Total ==> -0.53 -0.97 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.11 1.54 155 26.6 20.3 12.4 17.1 16.7 11.8 Floor 22 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 59 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.11 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 186 of 323
Room Checksums
By Trane
T3-phong bac si nam

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.63 0.13 9.77 Partition/Door -0.26 -0.26 0.00 Diffuser 159 48
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 159 48
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 159 48
Infiltration 0.27 0.27 13.78 0.06 4.51 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 20.41 0.19 14.29 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.27 0.21 15.79 Lights 0.00 0.00 0.00 MinStop/Rh 48 48
People 0.35 0 0 17.86 0.19 14.29 People 0.00 0 0.00 Return 165 48
Misc 0.67 0.00 0.67 34.18 0.67 50.38 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 65.31 1.07 80.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.26 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -2.55 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.06 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.18 0.00 % OA 11.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 7.35 2.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.63
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.11
W/m² 89.96 -20.54
Grand Total ==> 1.69 -0.06 1.96 100.00 1.33 100.00 Grand Total ==> -0.27 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.95 1.39 158 26.8 20.3 12.4 18.0 17.1 11.9 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 187 of 323
Room Checksums
By Trane
T3-phong bac si nam 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.14 1.14 27.27 0.00 0.00 Roof Cond 0.00 -0.10 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.44 0.06 3.26 Partition/Door -0.13 -0.13 0.00 Diffuser 221 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 221 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 221 66
Infiltration 0.54 0.54 12.92 0.13 7.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 1.14 1.74 41.63 0.19 10.33 Sub Total ==> -0.13 -0.23 0.00 Nom Vent 39 0
AHU Vent 39 0
Internal Loads Internal Loads Infil 12 0
Lights 0.44 0.11 0.55 13.16 0.44 23.91 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.71 0 1 16.99 0.39 21.20 People 0.00 0 0.00 Return 234 66
Misc 0.67 0.00 0.67 16.03 0.67 36.41 Misc 0.00 0.00 0.00 Exhaust 51 0
Sub Total ==> 1.82 0.11 1.93 46.17 1.50 81.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.15 -0.15 0.00 0.00 0.15 8.15 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.55 13.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -2.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 1.91 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 17.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 0.00 Lps/m² 4.99 1.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -8.86
Grand Total ==> 2.57 0.98 4.18 100.00 1.84 100.00 Grand Total ==> -0.15 -0.64 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.19 3.07 221 27.2 20.6 12.6 18.0 15.6 10.1 Floor 44 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.19 Roof 44 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 188 of 323
Room Checksums
By Trane
T3-phong bac si nu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.63 0.13 9.77 Partition/Door -0.26 -0.26 0.00 Diffuser 159 48
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 159 48
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 159 48
Infiltration 0.27 0.27 13.78 0.06 4.51 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.40 0.00 0.40 20.41 0.19 14.29 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.27 0.21 15.79 Lights 0.00 0.00 0.00 MinStop/Rh 48 48
People 0.35 0 0 17.86 0.19 14.29 People 0.00 0 0.00 Return 165 48
Misc 0.67 0.00 0.67 34.18 0.67 50.38 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 65.31 1.07 80.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.26 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -2.55 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.06 RA Preheat Diff. -0.17 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.18 0.00 % OA 11.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 7.35 2.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.63
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.11
W/m² 89.96 -20.54
Grand Total ==> 1.69 -0.06 1.96 100.00 1.33 100.00 Grand Total ==> -0.27 -0.63 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.95 1.39 158 26.8 20.3 12.4 18.0 17.1 11.9 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 189 of 323
Room Checksums
By Trane
T3-phong bac si nu 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.14 1.14 27.27 0.00 0.00 Roof Cond 0.00 -0.10 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.44 0.06 3.26 Partition/Door -0.13 -0.13 0.00 Diffuser 221 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 221 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 221 66
Infiltration 0.54 0.54 12.92 0.13 7.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 1.14 1.74 41.63 0.19 10.33 Sub Total ==> -0.13 -0.23 0.00 Nom Vent 39 0
AHU Vent 39 0
Internal Loads Internal Loads Infil 12 0
Lights 0.44 0.11 0.55 13.16 0.44 23.91 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.71 0 1 16.99 0.39 21.20 People 0.00 0 0.00 Return 234 66
Misc 0.67 0.00 0.67 16.03 0.67 36.41 Misc 0.00 0.00 0.00 Exhaust 51 0
Sub Total ==> 1.82 0.11 1.93 46.17 1.50 81.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.15 -0.15 0.00 0.00 0.15 8.15 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.55 13.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -2.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 1.91 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 17.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 0.00 Lps/m² 4.99 1.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -8.86
Grand Total ==> 2.57 0.98 4.18 100.00 1.84 100.00 Grand Total ==> -0.15 -0.64 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.19 3.07 221 27.2 20.6 12.6 18.0 15.6 10.1 Floor 44 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.19 Roof 44 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 190 of 323
Room Checksums
By Trane
T3-phong benh nhan1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 16 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 18.3 22.0
Ra Plenum 26.0 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.13 1.13 9.11 0.00 0.00 Roof Cond 0.00 -0.20 4.93
Glass Solar 6.12 0.00 6.12 49.32 6.12 68.92 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.21 0.00 0.21 1.69 0.21 2.36 Glass/Door Cond -0.18 -0.18 4.43
Cooling Heating
Wall Cond 0.15 0.24 0.39 3.14 0.15 1.69 Wall Cond -0.03 -0.05 1.23
Partition/Door 0.19 0.19 1.53 0.19 2.14 Partition/Door -0.47 -0.47 11.58 Diffuser 1,065 320
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,065 320
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,065 320
Infiltration 0.66 0.66 5.32 0.11 1.24 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 7.33 1.37 8.70 70.10 6.78 76.35 Sub Total ==> -0.68 -0.90 22.17 Nom Vent 101 0
AHU Vent 101 0
Internal Loads Internal Loads Infil 25 0
Lights 0.57 0.14 0.71 5.72 0.57 6.42 Lights 0.00 0.00 0.00 MinStop/Rh 320 320
People 1.20 0 1 9.67 0.67 7.55 People 0.00 0 0.00 Return 1,090 320
Misc 0.70 0.00 0.70 5.64 0.70 7.88 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 2.47 0.14 2.61 21.03 1.94 21.85 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.16 -0.16 0.00 0.00 0.16 1.80 Ceiling Load -0.20 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.87 7.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.16 -0.16 -1.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.39 3.14 RA Preheat Diff. -1.12 27.59 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.59 39.16 % OA 9.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.45 11.08 Lps/m² 11.71 3.51
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.89
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.34
W/m² 136.20 -27.01
Grand Total ==> 9.96 1.19 12.41 100.00 8.88 100.00 Grand Total ==> -0.88 -4.06 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.40 10.67 1,065 26.1 20.0 12.2 18.0 16.9 11.7 Floor 91 Main Htg -2.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 43 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.40 Roof 91 0 0 Humidif 0.0 0 0.0 0.0
Wall 43 27 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 191 of 323
Room Checksums
By Trane
T3-Phong cung cap vat tu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.13 0.19 13.29 Partition/Door -0.39 -0.39 0.00 Diffuser 115 35
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 115 35
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 115 35
Infiltration 0.29 0.29 13.94 0.06 4.20 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.48 0.00 0.48 23.08 0.25 17.48 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 13.46 0.22 15.38 Lights 0.00 0.00 0.00 MinStop/Rh 35 35
People 0.36 0 0 17.31 0.20 13.99 People 0.00 0 0.00 Return 121 35
Misc 0.67 0.00 0.67 32.21 0.67 46.85 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 62.98 1.09 76.22 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.09 6.29 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 14.90 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.92 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 17.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 5.07 1.52
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 54.92
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.83
W/m² 92.30 -29.59
Grand Total ==> 1.80 -0.07 2.08 100.00 1.43 100.00 Grand Total ==> -0.40 -0.94 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.10 1.48 114 27.0 20.5 12.6 14.7 14.7 10.5 Floor 23 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.10 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 192 of 323
Room Checksums
By Trane
T3-Phong dieu khien

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.44 0.13 9.49 Partition/Door -0.26 -0.26 0.00 Diffuser 109 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 109 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 109 33
Infiltration 0.29 0.29 14.36 0.06 4.38 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.79 0.19 13.87 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 13.86 0.22 16.06 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.36 0 0 17.82 0.20 14.60 People 0.00 0 0.00 Return 115 33
Misc 0.67 0.00 0.67 33.17 0.67 48.91 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 64.85 1.09 79.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.09 6.57 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 15.35 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.98 RA Preheat Diff. -0.25 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 0.00 % OA 18.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 4.81 1.44
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 54.07
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.24
W/m² 88.92 -23.26
Grand Total ==> 1.74 -0.07 2.02 100.00 1.37 100.00 Grand Total ==> -0.27 -0.79 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.02 1.40 108 27.0 20.5 12.6 14.7 14.7 10.5 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.02 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 193 of 323
Room Checksums
By Trane
T3-phong dieu tri bang dien

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.58 0.00 0.58 21.48 0.58 29.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.85 0.05 2.54 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.17 0.06 0.23 8.52 0.17 8.63 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 3.70 0.10 5.08 Partition/Door -0.13 -0.13 0.00 Diffuser 243 73
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 243 73
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 243 73
Infiltration 0.21 0.21 7.78 0.05 2.54 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.06 1.17 43.33 0.95 48.22 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 24 0
AHU Vent 24 0
Internal Loads Internal Loads Infil 5 0
Lights 0.21 0.05 0.26 9.63 0.21 10.66 Lights 0.00 0.00 0.00 MinStop/Rh 73 73
People 0.43 0 0 15.93 0.22 11.17 People 0.00 0 0.00 Return 247 73
Misc 0.50 0.00 0.50 18.52 0.50 25.38 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.14 0.05 1.19 44.07 0.93 47.21 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.57 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.34 12.59 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -3.33 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 3.33 RA Preheat Diff. -0.33 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 11.18 3.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.03
W/m² 124.50 -23.92
Grand Total ==> 2.34 -0.07 2.70 100.00 1.97 100.00 Grand Total ==> -0.17 -0.87 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.70 2.11 243 26.6 19.7 11.6 17.1 16.5 11.6 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.70 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 194 of 323
Room Checksums
By Trane
T3-phong dieu tri lanh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 32 OADB: 19 SADB 18.3 21.0
Ra Plenum 27.1 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.10 0.10 4.88 0.10 7.58 Partition/Door -0.13 -0.13 0.00 Diffuser 184 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 184 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 184 55
Infiltration 0.17 0.17 8.29 0.06 4.55 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 13.17 0.16 12.12 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 30 0
AHU Vent 30 0
Internal Loads Internal Loads Infil 6 0
Lights 0.15 0.04 0.19 9.27 0.20 15.15 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.42 0 0 20.49 0.26 19.70 People 0.00 0 0.00 Return 190 55
Misc 0.42 0.00 0.42 20.49 0.59 44.70 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 0.99 0.04 1.03 50.24 1.05 79.55 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.11 8.33 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.84 40.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.14 -0.14 -6.83 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.44 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 16.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 8.46 2.54
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.69
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -15.81
Grand Total ==> 1.38 -0.22 2.05 100.00 1.32 100.00 Grand Total ==> -0.14 -0.55 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.05 0.89 138 27.0 20.9 13.1 18.0 17.1 12.0 Floor 22 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.05 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 195 of 323
Room Checksums
By Trane
T3-phong do kham tien dinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 32 OADB: 19 SADB 18.3 21.0
Ra Plenum 27.1 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.10 0.10 4.88 0.10 7.58 Partition/Door -0.13 -0.13 0.00 Diffuser 184 55
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 184 55
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 184 55
Infiltration 0.17 0.17 8.29 0.06 4.55 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 13.17 0.16 12.12 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 30 0
AHU Vent 30 0
Internal Loads Internal Loads Infil 6 0
Lights 0.15 0.04 0.19 9.27 0.20 15.15 Lights 0.00 0.00 0.00 MinStop/Rh 55 55
People 0.42 0 0 20.49 0.26 19.70 People 0.00 0 0.00 Return 190 55
Misc 0.42 0.00 0.42 20.49 0.59 44.70 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 0.99 0.04 1.03 50.24 1.05 79.55 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.11 8.33 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.84 40.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.14 -0.14 -6.83 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.44 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 16.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 8.46 2.54
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.69
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -15.81
Grand Total ==> 1.38 -0.22 2.05 100.00 1.32 100.00 Grand Total ==> -0.14 -0.55 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.05 0.89 138 27.0 20.9 13.1 18.0 17.1 12.0 Floor 22 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.05 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 196 of 323
Room Checksums
By Trane
T3-Phong do thai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.1 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.81 0.23 1.04 33.88 0.81 37.16 Wall Cond -0.06 -0.07 6.09
Partition/Door 0.13 0.13 4.23 0.13 5.96 Partition/Door -0.26 -0.26 22.61 Diffuser 176 53
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 176 53
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 176 53
Infiltration 0.28 0.28 9.12 0.06 2.75 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.22 0.23 1.45 47.23 1.00 45.87 Sub Total ==> -0.32 -0.33 28.70 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 9.12 0.22 10.09 Lights 0.00 0.00 0.00 MinStop/Rh 53 53
People 0.37 0 0 12.05 0.20 9.17 People 0.00 0 0.00 Return 182 53
Misc 0.67 0.00 0.67 21.82 0.67 30.73 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.26 0.06 1.32 43.00 1.09 50.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.13 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 10.10 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.28 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 1.95 RA Preheat Diff. -0.40 34.78 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.41 35.65 % OA 11.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.87 Lps/m² 7.74 2.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 57.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.37
W/m² 135.55 -32.77
Grand Total ==> 2.57 0.13 3.07 100.00 2.18 100.00 Grand Total ==> -0.33 -1.15 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.08 2.48 176 27.3 20.4 12.3 14.7 14.7 10.5 Floor 23 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.08 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 197 of 323
Room Checksums
By Trane
T3-phong do thinh luc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 18.3 21.0
Ra Plenum 27.1 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.29 0.29 12.95 0.29 20.14 Partition/Door -0.39 -0.39 0.00 Diffuser 203 61
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 203 61
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 203 61
Infiltration 0.17 0.17 7.59 0.06 4.17 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.46 0.00 0.46 20.54 0.35 24.31 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 24 0
AHU Vent 24 0
Internal Loads Internal Loads Infil 5 0
Lights 0.15 0.04 0.19 8.48 0.21 14.58 Lights 0.00 0.00 0.00 MinStop/Rh 61 61
People 0.42 0 0 18.75 0.24 16.67 People 0.00 0 0.00 Return 208 61
Misc 0.41 0.00 0.41 18.30 0.54 37.50 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 0.98 0.04 1.02 45.54 0.99 68.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.10 6.94 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.84 37.50 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.14 -0.14 -6.25 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.68 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.23 0.00 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 9.37 2.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 90.90
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.70
W/m² 103.03 -28.79
Grand Total ==> 1.56 -0.22 2.24 100.00 1.44 100.00 Grand Total ==> -0.40 -0.85 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.24 1.08 163 27.0 20.7 12.9 18.0 17.2 12.0 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.24 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 198 of 323
Room Checksums
By Trane
T3-Phong dong goi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.0 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.63 1.63 22.61 0.00 0.00 Roof Cond 0.00 -0.14 8.24
Glass Solar 0.55 0.00 0.55 7.63 0.55 15.49 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.10 0.00 0.10 1.39 0.10 2.82 Glass/Door Cond -0.02 -0.02 1.18
Cooling Heating
Wall Cond 0.44 0.16 0.60 8.32 0.44 12.39 Wall Cond -0.04 -0.06 3.53
Partition/Door 0.13 0.13 1.80 0.13 3.66 Partition/Door -0.26 -0.26 15.29 Diffuser 285 86
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 285 86
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 285 86
Infiltration 0.82 0.82 11.37 0.18 5.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.04 1.79 3.83 53.12 1.40 39.44 Sub Total ==> -0.32 -0.48 28.24 Nom Vent 58 0
AHU Vent 58 0
Internal Loads Internal Loads Infil 18 0
Lights 0.66 0.16 0.82 11.37 0.66 18.59 Lights 0.00 0.00 0.00 MinStop/Rh 86 86
People 1.07 0 1 14.84 0.58 16.34 People 0.00 0 0.00 Return 304 86
Misc 0.67 0.00 0.67 9.29 0.67 18.87 Misc 0.00 0.00 0.00 Exhaust 76 0
Sub Total ==> 2.40 0.16 2.56 35.51 1.91 53.80 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.24 -0.24 0.00 0.00 0.24 6.76 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.91 12.62 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.19 -0.19 -2.64 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 1.39 RA Preheat Diff. -0.64 37.65 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.67 39.41 % OA 20.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.09 -5.29 Lps/m² 4.28 1.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 39.59
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.25
W/m² 108.05 -15.46
Grand Total ==> 4.68 1.52 7.21 100.00 3.55 100.00 Grand Total ==> -0.35 -1.70 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.20 5.43 285 27.3 20.7 12.6 14.7 13.8 9.6 Floor 67 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.20 Roof 67 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 199 of 323
Room Checksums
By Trane
T3-phong giao ban 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 16 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 25 / 19 OADB: 29 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.0 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.31 0.31 6.86 0.00 0.00 Roof Cond 0.00 -0.05 4.46
Glass Solar 2.10 0.00 2.10 46.46 2.10 60.17 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.07 0.00 0.07 1.55 0.07 2.01 Glass/Door Cond -0.04 -0.04 3.57
Cooling Heating
Wall Cond 0.05 0.08 0.13 2.88 0.05 1.43 Wall Cond -0.01 -0.01 0.89
Partition/Door 0.06 0.06 1.33 0.06 1.72 Partition/Door -0.13 -0.13 11.61 Diffuser 420 126
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 420 126
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 420 126
Infiltration 0.18 0.18 3.98 0.03 0.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.46 0.39 2.85 63.05 2.31 66.19 Sub Total ==> -0.18 -0.23 20.54 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 6.86 0.25 7.16 Lights 0.00 0.00 0.00 MinStop/Rh 126 126
People 0.40 0 0 8.85 0.22 6.30 People 0.00 0 0.00 Return 427 126
Misc 0.67 0.00 0.67 14.82 0.67 19.20 Misc 0.00 0.00 0.00 Exhaust 28 0
Sub Total ==> 1.32 0.06 1.38 30.53 1.14 32.66 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 1.15 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.18 3.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.04 -0.04 -0.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.15 3.32 RA Preheat Diff. -0.44 39.29 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.47 41.96 % OA 5.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 -1.79 Lps/m² 16.94 5.08
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.46
W/m² 182.99 -26.24
Grand Total ==> 3.82 0.37 4.52 100.00 3.49 100.00 Grand Total ==> -0.19 -1.12 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.54 4.07 420 26.0 19.9 12.1 18.0 17.0 11.8 Floor 25 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.54 Roof 25 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 9 62 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 200 of 323
Room Checksums
By Trane
T3-phong hoi chan giao ban

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.14 1.14 27.27 0.00 0.00 Roof Cond 0.00 -0.10 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.44 0.06 3.26 Partition/Door -0.13 -0.13 0.00 Diffuser 221 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 221 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 221 66
Infiltration 0.54 0.54 12.92 0.13 7.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 1.14 1.74 41.63 0.19 10.33 Sub Total ==> -0.13 -0.23 0.00 Nom Vent 39 0
AHU Vent 39 0
Internal Loads Internal Loads Infil 12 0
Lights 0.44 0.11 0.55 13.16 0.44 23.91 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.71 0 1 16.99 0.39 21.20 People 0.00 0 0.00 Return 234 66
Misc 0.67 0.00 0.67 16.03 0.67 36.41 Misc 0.00 0.00 0.00 Exhaust 51 0
Sub Total ==> 1.82 0.11 1.93 46.17 1.50 81.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.15 -0.15 0.00 0.00 0.15 8.15 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.55 13.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -2.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 1.91 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 17.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 0.00 Lps/m² 4.99 1.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -8.86
Grand Total ==> 2.57 0.98 4.18 100.00 1.84 100.00 Grand Total ==> -0.15 -0.64 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.19 3.07 221 27.2 20.6 12.6 18.0 15.6 10.1 Floor 44 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.19 Roof 44 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 201 of 323
Room Checksums
By Trane
T3-phong hoi tinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.7 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.9 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 314 94
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 314 94
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 314 94
Infiltration 0.82 0.82 22.34 0.17 7.66 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.82 0.00 0.82 22.34 0.17 7.66 Sub Total ==> 0.00 0.00 0.00 Nom Vent 47 0
AHU Vent 47 0
Internal Loads Internal Loads Infil 19 0
Lights 0.65 0.16 0.81 22.07 0.65 29.28 Lights 0.00 0.00 0.00 MinStop/Rh 94 94
People 0.84 0 1 22.89 0.44 19.82 People 0.00 0 0.00 Return 333 94
Misc 0.63 0.00 0.63 17.17 0.63 28.38 Misc 0.00 0.00 0.00 Exhaust 66 0
Sub Total ==> 2.12 0.16 2.28 62.13 1.72 77.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.33 -0.33 0.00 0.00 0.33 14.86 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.68 18.53 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.22 -0.22 -5.99 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.11 3.00 RA Preheat Diff. -0.33 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 14.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.05 0.00 Lps/m² 4.65 1.39
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.64
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 18.43
W/m² 54.22 -5.56
Grand Total ==> 3.27 -0.39 3.67 100.00 2.22 100.00 Grand Total ==> -0.02 -0.73 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.67 2.17 312 26.9 19.9 11.8 18.0 16.8 11.6 Floor 68 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.67 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 202 of 323
Room Checksums
By Trane
T3-phong ke toan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 3.17 0.06 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 152 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 152 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 152 46
Infiltration 0.27 0.27 14.29 0.06 4.76 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.33 0.00 0.33 17.46 0.12 9.52 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 13.76 0.21 16.67 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.35 0 0 18.52 0.19 15.08 People 0.00 0 0.00 Return 158 46
Misc 0.67 0.00 0.67 35.45 0.67 53.17 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 67.72 1.07 84.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.56 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 14.29 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -2.65 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 3.17 RA Preheat Diff. -0.16 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 12.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 6.99 2.10
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.51
W/m² 86.84 -14.16
Grand Total ==> 1.62 -0.06 1.89 100.00 1.26 100.00 Grand Total ==> -0.14 -0.48 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.89 1.33 150 26.8 20.3 12.4 18.0 17.1 11.9 Floor 22 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.89 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 203 of 323
Room Checksums
By Trane
T3-phong keo gian cot song

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 8.72 0.19 13.67 Partition/Door -0.26 -0.26 0.00 Diffuser 170 51
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 170 51
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 170 51
Infiltration 0.26 0.26 11.93 0.06 4.32 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.45 0.00 0.45 20.64 0.25 17.99 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 30 0
AHU Vent 30 0
Internal Loads Internal Loads Infil 6 0
Lights 0.20 0.05 0.25 11.47 0.20 14.39 Lights 0.00 0.00 0.00 MinStop/Rh 51 51
People 0.51 0 1 23.39 0.26 18.71 People 0.00 0 0.00 Return 176 51
Misc 0.59 0.00 0.59 27.06 0.59 42.45 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 1.30 0.05 1.35 61.93 1.05 75.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 6.47 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.43 19.72 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -5.05 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.75 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 17.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 7.83 2.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.92
W/m² 100.76 -23.56
Grand Total ==> 1.84 -0.15 2.18 100.00 1.39 100.00 Grand Total ==> -0.27 -0.75 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.19 1.43 170 26.6 19.9 11.9 17.1 16.5 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 204 of 323
Room Checksums
By Trane
T3-phong kham benh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.58 0.00 0.58 21.48 0.58 29.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.85 0.05 2.54 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.17 0.06 0.23 8.52 0.17 8.63 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 3.70 0.10 5.08 Partition/Door -0.13 -0.13 0.00 Diffuser 243 73
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 243 73
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 243 73
Infiltration 0.21 0.21 7.78 0.05 2.54 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.06 1.17 43.33 0.95 48.22 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 24 0
AHU Vent 24 0
Internal Loads Internal Loads Infil 5 0
Lights 0.21 0.05 0.26 9.63 0.21 10.66 Lights 0.00 0.00 0.00 MinStop/Rh 73 73
People 0.43 0 0 15.93 0.22 11.17 People 0.00 0 0.00 Return 247 73
Misc 0.50 0.00 0.50 18.52 0.50 25.38 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.14 0.05 1.19 44.07 0.93 47.21 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.57 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.34 12.59 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -3.33 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 3.33 RA Preheat Diff. -0.33 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 11.18 3.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.03
W/m² 124.50 -23.92
Grand Total ==> 2.34 -0.07 2.70 100.00 1.97 100.00 Grand Total ==> -0.17 -0.87 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.70 2.11 243 26.6 19.7 11.6 17.1 16.5 11.6 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.70 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 205 of 323
Room Checksums
By Trane
T3-Phong kho thiet bi

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 6.44 0.13 9.49 Partition/Door -0.26 -0.26 0.00 Diffuser 109 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 109 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 109 33
Infiltration 0.29 0.29 14.36 0.06 4.38 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.42 0.00 0.42 20.79 0.19 13.87 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 13.86 0.22 16.06 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.36 0 0 17.82 0.20 14.60 People 0.00 0 0.00 Return 115 33
Misc 0.67 0.00 0.67 33.17 0.67 48.91 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 64.85 1.09 79.56 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.09 6.57 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 15.35 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.98 RA Preheat Diff. -0.25 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 0.00 % OA 18.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 4.81 1.44
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 54.07
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.24
W/m² 88.92 -23.26
Grand Total ==> 1.74 -0.07 2.02 100.00 1.37 100.00 Grand Total ==> -0.27 -0.79 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.02 1.40 108 27.0 20.5 12.6 14.7 14.7 10.5 Floor 23 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.02 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 206 of 323
Room Checksums
By Trane
T3-Phong khu khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.13 0.19 13.29 Partition/Door -0.39 -0.39 0.00 Diffuser 115 35
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 115 35
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 115 35
Infiltration 0.29 0.29 13.94 0.06 4.20 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.48 0.00 0.48 23.08 0.25 17.48 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 20 0
AHU Vent 20 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.06 0.28 13.46 0.22 15.38 Lights 0.00 0.00 0.00 MinStop/Rh 35 35
People 0.36 0 0 17.31 0.20 13.99 People 0.00 0 0.00 Return 121 35
Misc 0.67 0.00 0.67 32.21 0.67 46.85 Misc 0.00 0.00 0.00 Exhaust 26 0
Sub Total ==> 1.25 0.06 1.31 62.98 1.09 76.22 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.09 6.29 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 14.90 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.92 RA Preheat Diff. -0.26 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.27 0.00 % OA 17.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 5.07 1.52
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 54.92
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.83
W/m² 92.30 -29.59
Grand Total ==> 1.80 -0.07 2.08 100.00 1.43 100.00 Grand Total ==> -0.40 -0.94 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.10 1.48 114 27.0 20.5 12.6 14.7 14.7 10.5 Floor 23 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.10 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 207 of 323
Room Checksums
By Trane
T3-phong mo 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 9 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 27 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 675 675
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 102 0
AHU Vent 102 0
Internal Loads Internal Loads Infil 0 0
Lights 0.41 0.10 0.51 14.57 0.41 10.35 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.97 0 1 27.71 0.54 13.64 People 0.00 0 0.00 Return 675 675
Misc 3.00 0.00 3.00 85.71 3.00 75.76 Misc 0.00 0.00 0.00 Exhaust 102 0
Sub Total ==> 4.38 0.10 4.48 128.00 3.95 99.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.97 -27.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.29 OA Preheat Diff. -0.43 0.00
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.47 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.33 18.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.49
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.57 -24.48
Grand Total ==> 4.39 0.08 3.50 100.00 3.96 100.00 Grand Total ==> 0.00 -0.90 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.50 3.14 675 21.0 16.6 10.1 17.3 15.1 9.9 Floor 37 Main Htg -0.9 675 19.9 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 6.65 2.36 102 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 208 of 323
Room Checksums
By Trane
T3-phong mo 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 22 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 28 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 675 675
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 102 0
AHU Vent 102 0
Internal Loads Internal Loads Infil 0 0
Lights 0.41 0.10 0.51 14.57 0.41 10.35 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.97 0 1 27.71 0.54 13.64 People 0.00 0 0.00 Return 675 675
Misc 3.00 0.00 3.00 85.71 3.00 75.76 Misc 0.00 0.00 0.00 Exhaust 102 0
Sub Total ==> 4.38 0.10 4.48 128.00 3.95 99.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.97 -27.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.29 OA Preheat Diff. -0.75 61.48
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.47 38.52 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.33 18.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.58 -24.51
Grand Total ==> 4.39 0.08 3.50 100.00 3.96 100.00 Grand Total ==> 0.00 -1.22 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.49 3.14 675 21.0 16.6 10.1 17.3 15.1 9.9 Floor 37 Main Htg -0.9 675 19.9 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 6.65 2.36 102 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 209 of 323
Room Checksums
By Trane
T3-phong mo 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 22 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 28 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 675 675
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 102 0
AHU Vent 102 0
Internal Loads Internal Loads Infil 0 0
Lights 0.41 0.10 0.51 14.57 0.41 10.35 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.97 0 1 27.71 0.54 13.64 People 0.00 0 0.00 Return 675 675
Misc 3.00 0.00 3.00 85.71 3.00 75.76 Misc 0.00 0.00 0.00 Exhaust 102 0
Sub Total ==> 4.38 0.10 4.48 128.00 3.95 99.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.97 -27.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.29 OA Preheat Diff. -0.75 61.48
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.47 38.52 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.33 18.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.58 -24.51
Grand Total ==> 4.39 0.08 3.50 100.00 3.96 100.00 Grand Total ==> 0.00 -1.22 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.49 3.14 675 21.0 16.6 10.1 17.3 15.1 9.9 Floor 37 Main Htg -0.9 675 19.9 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 6.65 2.36 102 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 210 of 323
Room Checksums
By Trane
T3-phong mo 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 22 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 28 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 675 675
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 102 0
AHU Vent 102 0
Internal Loads Internal Loads Infil 0 0
Lights 0.41 0.10 0.51 14.57 0.41 10.35 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.97 0 1 27.71 0.54 13.64 People 0.00 0 0.00 Return 675 675
Misc 3.00 0.00 3.00 85.71 3.00 75.76 Misc 0.00 0.00 0.00 Exhaust 102 0
Sub Total ==> 4.38 0.10 4.48 128.00 3.95 99.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.97 -27.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.29 OA Preheat Diff. -0.75 61.48
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.47 38.52 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.33 18.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.58 -24.51
Grand Total ==> 4.39 0.08 3.50 100.00 3.96 100.00 Grand Total ==> 0.00 -1.22 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.49 3.14 675 21.0 16.6 10.1 17.3 15.1 9.9 Floor 37 Main Htg -0.9 675 19.9 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 6.65 2.36 102 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 211 of 323
Room Checksums
By Trane
T3-phong mo 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 22 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 28 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 675 675
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 102 0
AHU Vent 102 0
Internal Loads Internal Loads Infil 0 0
Lights 0.41 0.10 0.51 14.57 0.41 10.35 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.97 0 1 27.71 0.54 13.64 People 0.00 0 0.00 Return 675 675
Misc 3.00 0.00 3.00 85.71 3.00 75.76 Misc 0.00 0.00 0.00 Exhaust 102 0
Sub Total ==> 4.38 0.10 4.48 128.00 3.95 99.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.97 -27.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.29 OA Preheat Diff. -0.75 61.48
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.47 38.52 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.33 18.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.58 -24.51
Grand Total ==> 4.39 0.08 3.50 100.00 3.96 100.00 Grand Total ==> 0.00 -1.22 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.49 3.14 675 21.0 16.6 10.1 17.3 15.1 9.9 Floor 37 Main Htg -0.9 675 19.9 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 6.65 2.36 102 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 212 of 323
Room Checksums
By Trane
T3-phong mo 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 22 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 28 / 23 OADB: 34 OADB: 19 SADB 17.3 21.0
Ra Plenum 22.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.1 21.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 675 675
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.00 0.00 0.00 0.00 0.00 0.00 Sub Total ==> 0.00 0.00 0.00 Nom Vent 102 0
AHU Vent 102 0
Internal Loads Internal Loads Infil 0 0
Lights 0.41 0.10 0.51 14.57 0.41 10.35 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 0.97 0 1 27.71 0.54 13.64 People 0.00 0 0.00 Return 675 675
Misc 3.00 0.00 3.00 85.71 3.00 75.76 Misc 0.00 0.00 0.00 Exhaust 102 0
Sub Total ==> 4.38 0.10 4.48 128.00 3.95 99.75 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.01 -0.01 0.00 0.00 0.01 0.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.97 -27.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.01 -0.01 -0.29 OA Preheat Diff. -0.75 61.48
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -0.47 38.52 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 18.33 18.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.63
W/m² 275.58 -24.51
Grand Total ==> 4.39 0.08 3.50 100.00 3.96 100.00 Grand Total ==> 0.00 -1.22 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.49 3.14 675 21.0 16.6 10.1 17.3 15.1 9.9 Floor 37 Main Htg -0.9 675 19.9 21.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 6.65 2.36 102 33.5 28.8 23.4 15.0 14.2 9.9 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 213 of 323
Room Checksums
By Trane
T3-phong nghi giua ca mo

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 2 / 10 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 24 / 18 OADB: 32 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.4 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.4 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 110 33
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 110 33
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 110 33
Infiltration 0.14 0.14 6.76 0.06 4.84 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.14 0.00 0.14 6.76 0.06 4.84 Sub Total ==> 0.00 0.00 0.00 Nom Vent 32 0
AHU Vent 32 0
Internal Loads Internal Loads Infil 6 0
Lights 0.19 0.05 0.24 11.59 0.20 16.13 Lights 0.00 0.00 0.00 MinStop/Rh 33 33
People 0.51 0 1 24.64 0.27 21.77 People 0.00 0 0.00 Return 117 33
Misc 0.53 0.00 0.53 25.60 0.59 47.58 Misc 0.00 0.00 0.00 Exhaust 38 0
Sub Total ==> 1.23 0.05 1.28 61.84 1.06 85.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.12 9.68 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.72 34.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -5.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.93 RA Preheat Diff. -0.25 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.26 0.00 % OA 28.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 4.86 1.46
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 53.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.00
W/m² 90.82 -11.94
Grand Total ==> 1.47 -0.16 2.07 100.00 1.24 100.00 Grand Total ==> -0.01 -0.53 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.06 1.04 96 26.4 20.9 13.4 14.7 14.7 10.5 Floor 23 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.06 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 214 of 323
Room Checksums
By Trane
T3-phong nhan vien

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 23.05 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 2.47 0.06 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 154 46
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 154 46
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 154 46
Infiltration 0.26 0.26 10.70 0.06 4.76 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.32 0.56 0.88 36.21 0.12 9.52 Sub Total ==> -0.13 -0.18 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 10.70 0.21 16.67 Lights 0.00 0.00 0.00 MinStop/Rh 46 46
People 0.35 0 0 14.40 0.19 15.08 People 0.00 0 0.00 Return 160 46
Misc 0.67 0.00 0.67 27.57 0.67 53.17 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 52.67 1.07 84.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 5.56 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 11.11 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.47 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.47 RA Preheat Diff. -0.16 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.17 0.00 % OA 12.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.03 0.00 Lps/m² 7.07 2.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 62.85
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.89
W/m² 112.49 -14.26
Grand Total ==> 1.62 0.48 2.43 100.00 1.26 100.00 Grand Total ==> -0.14 -0.48 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.44 1.89 153 27.1 20.4 12.4 18.0 16.2 10.9 Floor 22 Main Htg -0.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.44 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 215 of 323
Room Checksums
By Trane
T3-Phong nhan vien khu trung

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.0 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.0 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.03 1.03 19.04 0.00 0.00 Roof Cond 0.00 -0.09 6.21
Glass Solar 0.55 0.00 0.55 10.17 0.55 18.64 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.11 0.00 0.11 2.03 0.11 3.73 Glass/Door Cond -0.02 -0.02 1.38
Cooling Heating
Wall Cond 0.47 0.16 0.63 11.65 0.47 15.93 Wall Cond -0.04 -0.06 4.14
Partition/Door 0.10 0.10 1.85 0.10 3.39 Partition/Door -0.13 -0.13 8.97 Diffuser 262 79
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 262 79
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 262 79
Infiltration 0.44 0.44 8.13 0.10 3.39 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.67 1.19 2.86 52.87 1.33 45.08 Sub Total ==> -0.19 -0.30 20.69 Nom Vent 47 0
AHU Vent 47 0
Internal Loads Internal Loads Infil 9 0
Lights 0.42 0.10 0.52 9.61 0.42 14.24 Lights 0.00 0.00 0.00 MinStop/Rh 79 79
People 0.85 0 1 15.71 0.45 15.25 People 0.00 0 0.00 Return 272 79
Misc 0.52 0.00 0.52 9.61 0.52 17.63 Misc 0.00 0.00 0.00 Exhaust 56 0
Sub Total ==> 1.79 0.10 1.89 34.94 1.39 47.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.23 -0.23 0.00 0.00 0.23 7.80 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.77 14.23 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.21 -0.21 -3.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 1.85 RA Preheat Diff. -0.59 40.69 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.62 42.76 % OA 17.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.06 -4.14 Lps/m² 6.22 1.87
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 48.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.83
W/m² 127.68 -19.79
Grand Total ==> 3.69 0.85 5.41 100.00 2.95 100.00 Grand Total ==> -0.21 -1.45 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.39 4.15 262 27.3 20.1 11.9 14.7 14.5 10.3 Floor 42 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.39 Roof 42 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 216 of 323
Room Checksums
By Trane
T3-phong sinh hoat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 2.01 0.06 3.82 Partition/Door -0.13 -0.13 0.00 Diffuser 189 57
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 189 57
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 189 57
Infiltration 0.27 0.27 9.03 0.06 3.82 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.33 0.00 0.33 11.04 0.12 7.64 Sub Total ==> -0.13 -0.13 0.00 Nom Vent 60 0
AHU Vent 60 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 8.70 0.21 13.38 Lights 0.00 0.00 0.00 MinStop/Rh 57 57
People 0.92 0 1 30.77 0.50 31.85 People 0.00 0 0.00 Return 195 57
Misc 0.67 0.00 0.67 22.41 0.67 42.68 Misc 0.00 0.00 0.00 Exhaust 66 0
Sub Total ==> 1.80 0.05 1.85 61.87 1.38 87.90 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 4.46 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.87 29.10 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -4.35 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.34 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.21 0.00 % OA 31.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 8.71 2.61
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 63.22
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.26
W/m² 137.75 -16.09
Grand Total ==> 2.19 -0.14 2.99 100.00 1.57 100.00 Grand Total ==> -0.14 -0.56 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.99 1.74 188 27.2 20.9 13.1 18.0 16.8 11.6 Floor 22 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.99 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 217 of 323
Room Checksums
By Trane
T3-phong song ngan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 8.72 0.19 13.67 Partition/Door -0.26 -0.26 0.00 Diffuser 170 51
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 170 51
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 170 51
Infiltration 0.26 0.26 11.93 0.06 4.32 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.45 0.00 0.45 20.64 0.25 17.99 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 30 0
AHU Vent 30 0
Internal Loads Internal Loads Infil 6 0
Lights 0.20 0.05 0.25 11.47 0.20 14.39 Lights 0.00 0.00 0.00 MinStop/Rh 51 51
People 0.51 0 1 23.39 0.26 18.71 People 0.00 0 0.00 Return 176 51
Misc 0.59 0.00 0.59 27.06 0.59 42.45 Misc 0.00 0.00 0.00 Exhaust 36 0
Sub Total ==> 1.30 0.05 1.35 61.93 1.05 75.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 6.47 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.43 19.72 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -5.05 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.75 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 17.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 7.83 2.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.92
W/m² 100.76 -23.56
Grand Total ==> 1.84 -0.15 2.18 100.00 1.39 100.00 Grand Total ==> -0.27 -0.75 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.19 1.43 170 26.6 19.9 11.9 17.1 16.5 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 218 of 323
Room Checksums
By Trane
T3-Phong tap luyen

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.5 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.07 1.07 19.71 0.00 0.00 Roof Cond 0.00 -0.09 7.32
Glass Solar 0.55 0.00 0.55 10.13 0.55 18.90 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.11 0.00 0.11 2.03 0.11 3.78 Glass/Door Cond -0.02 -0.02 1.63
Cooling Heating
Wall Cond 0.47 0.17 0.64 11.79 0.47 16.15 Wall Cond -0.04 -0.06 4.88
Partition/Door 0.10 0.10 1.84 0.10 3.44 Partition/Door -0.13 -0.13 10.57 Diffuser 356 107
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 356 107
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 356 107
Infiltration 0.42 0.42 7.73 0.10 3.44 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.65 1.24 2.89 53.22 1.33 45.70 Sub Total ==> -0.19 -0.30 24.39 Nom Vent 47 0
AHU Vent 47 0
Internal Loads Internal Loads Infil 9 0
Lights 0.42 0.10 0.52 9.58 0.42 14.43 Lights 0.00 0.00 0.00 MinStop/Rh 107 107
People 0.85 0 1 15.65 0.45 15.46 People 0.00 0 0.00 Return 365 107
Misc 0.52 0.00 0.52 9.58 0.52 17.87 Misc 0.00 0.00 0.00 Exhaust 56 0
Sub Total ==> 1.79 0.10 1.89 34.81 1.39 47.77 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.19 -0.19 0.00 0.00 0.19 6.53 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.69 12.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.17 -0.17 -3.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.13 2.39 RA Preheat Diff. -0.49 39.84 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.51 41.46 % OA 13.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 -5.69 Lps/m² 8.43 2.53
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 65.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.80
W/m² 128.18 -17.11
Grand Total ==> 3.63 0.98 5.43 100.00 2.91 100.00 Grand Total ==> -0.20 -1.23 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.41 4.25 356 26.7 19.8 11.7 17.1 15.7 10.7 Floor 42 Main Htg -0.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.41 Roof 42 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 219 of 323
Room Checksums
By Trane
T3-phong thay do

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.24 0.24 13.95 0.00 0.00 Roof Cond 0.00 -0.02 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.29 0.29 16.86 0.29 25.44 Partition/Door -0.39 -0.39 0.00 Diffuser 140 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 140 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 140 42
Infiltration 0.08 0.08 4.65 0.03 2.63 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.37 0.24 0.61 35.47 0.32 28.07 Sub Total ==> -0.39 -0.41 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 2 0
Lights 0.07 0.02 0.09 5.23 0.11 9.65 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.21 0 0 12.21 0.12 10.53 People 0.00 0 0.00 Return 142 42
Misc 0.41 0.00 0.41 23.84 0.54 47.37 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 0.69 0.02 0.71 41.28 0.77 67.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.05 4.39 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.42 24.42 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -3.49 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.33 RA Preheat Diff. -0.19 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.20 0.00 % OA 10.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 0.00 Lps/m² 12.71 3.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.38
W/m² 156.75 -54.00
Grand Total ==> 1.11 0.15 1.72 100.00 1.14 100.00 Grand Total ==> -0.39 -0.79 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.72 1.15 112 26.5 20.3 12.4 17.1 16.2 11.2 Floor 11 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.72 Roof 11 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 220 of 323
Room Checksums
By Trane
T3-phong tien me

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 8 Mo/Hr: 8 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 32 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.3 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 392 118
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 392 118
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 392 118
Infiltration 0.34 0.34 9.58 0.11 2.49 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.34 0.00 0.34 9.58 0.11 2.49 Sub Total ==> 0.00 0.00 0.00 Nom Vent 59 0
AHU Vent 59 0
Internal Loads Internal Loads Infil 12 0
Lights 0.30 0.07 0.37 10.42 0.39 8.84 Lights 0.00 0.00 0.00 MinStop/Rh 118 118
People 0.84 0 1 23.66 0.51 11.56 People 0.00 0 0.00 Return 404 118
Misc 0.42 0.00 0.42 11.83 0.59 13.38 Misc 0.00 0.00 0.00 Exhaust 71 0
Sub Total ==> 1.56 0.07 1.63 45.92 1.49 33.79 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.20 -0.20 0.00 0.00 0.22 4.99 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.73 48.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.04 0.04 1.13 2.59 58.73 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.23 -0.23 -6.48 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 1.13 RA Preheat Diff. -0.89 47.59 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.92 49.20 % OA 15.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.06 3.21 Lps/m² 9.17 2.75
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.07
W/m² 82.83 -22.09
Grand Total ==> 2.14 -0.36 3.55 100.00 4.41 100.00 Grand Total ==> -0.02 -1.87 100.00 No. People 9

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.55 1.15 118 26.3 22.4 15.6 14.7 14.7 10.5 Floor 43 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.55 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 221 of 323
Room Checksums
By Trane
T3-phong tiep nhan benh nhan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 26.7 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 139 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 139 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 139 42
Infiltration 0.55 0.55 18.58 0.12 6.90 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.55 0.00 0.55 18.58 0.12 6.90 Sub Total ==> 0.00 0.00 0.00 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 12 0
Lights 0.42 0.10 0.52 17.57 0.42 24.14 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.68 0 1 22.97 0.37 21.26 People 0.00 0 0.00 Return 151 42
Misc 0.67 0.00 0.67 22.64 0.67 38.51 Misc 0.00 0.00 0.00 Exhaust 49 0
Sub Total ==> 1.77 0.10 1.87 63.18 1.46 83.91 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.16 9.20 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.59 19.93 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.10 -0.10 -3.38 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 1.69 RA Preheat Diff. -0.31 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.33 0.00 % OA 26.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.03 0.00 Lps/m² 3.25 0.97
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 47.12
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 14.51
W/m² 68.88 -8.14
Grand Total ==> 2.45 -0.13 2.96 100.00 1.74 100.00 Grand Total ==> -0.02 -0.67 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.95 1.78 137 27.2 20.8 12.9 14.7 14.7 10.5 Floor 43 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.95 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 222 of 323
Room Checksums
By Trane
T3-Phong tiet khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 15.0 21.0
Ra Plenum 27.1 20.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.7
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.5 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.69 1.69 25.96 0.00 0.00 Roof Cond 0.00 -0.14 10.69
Glass Solar 0.24 0.00 0.24 3.69 0.27 9.25 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 0.77 0.05 1.71 Glass/Door Cond -0.01 -0.01 0.76
Cooling Heating
Wall Cond 0.20 0.07 0.27 4.15 0.21 7.19 Wall Cond -0.02 -0.03 2.29
Partition/Door 0.06 0.06 0.92 0.06 2.05 Partition/Door -0.13 -0.13 9.92 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.83 0.83 12.75 0.18 6.16 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.38 1.76 3.14 48.23 0.77 26.37 Sub Total ==> -0.16 -0.31 23.66 Nom Vent 58 0
AHU Vent 58 0
Internal Loads Internal Loads Infil 18 0
Lights 0.66 0.16 0.82 12.60 0.66 22.60 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 1.07 0 1 16.44 0.58 19.86 People 0.00 0 0.00 Return 254 71
Misc 0.67 0.00 0.67 10.29 0.67 22.95 Misc 0.00 0.00 0.00 Exhaust 76 0
Sub Total ==> 2.40 0.16 2.56 39.32 1.91 65.41 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.25 -0.25 0.00 0.00 0.24 8.22 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.92 14.13 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.20 -0.20 -3.07 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 1.38 RA Preheat Diff. -0.53 40.46 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.56 42.75 % OA 24.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.09 -6.87 Lps/m² 3.54 1.06
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 36.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.21
W/m² 97.85 -11.19
Grand Total ==> 4.03 1.47 6.51 100.00 2.92 100.00 Grand Total ==> -0.19 -1.31 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 6.52 4.74 233 27.5 20.8 12.8 14.7 13.2 8.9 Floor 67 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 14 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 6.52 Roof 67 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 223 of 323
Room Checksums
By Trane
T3-phong truong khoa

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 9.41 0.19 13.67 Partition/Door -0.39 -0.39 0.00 Diffuser 168 51
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 168 51
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 168 51
Infiltration 0.27 0.27 13.37 0.06 4.32 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.46 0.00 0.46 22.77 0.25 17.99 Sub Total ==> -0.39 -0.39 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.21 0.05 0.26 12.87 0.21 15.11 Lights 0.00 0.00 0.00 MinStop/Rh 51 51
People 0.35 0 0 17.33 0.19 13.67 People 0.00 0 0.00 Return 174 51
Misc 0.67 0.00 0.67 33.17 0.67 48.20 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.23 0.05 1.28 63.37 1.07 76.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.07 5.04 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 13.37 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -2.48 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.06 2.97 RA Preheat Diff. -0.18 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.19 0.00 % OA 11.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 7.76 2.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.87
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.69
W/m² 93.53 -26.98
Grand Total ==> 1.75 -0.06 2.02 100.00 1.39 100.00 Grand Total ==> -0.40 -0.78 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.03 1.47 167 26.8 20.3 12.4 18.0 17.1 12.0 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 44 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.03 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 224 of 323
Room Checksums
By Trane
T3-phong truong khoa 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 29 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.8 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.8 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.62 0.62 21.09 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.24 0.06 0.30 10.20 0.33 20.25 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.06 0.06 2.04 0.06 3.68 Partition/Door -0.13 -0.13 0.00 Diffuser 195 59
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 195 59
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 195 59
Infiltration 0.28 0.28 9.52 0.04 2.45 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.58 0.68 1.26 42.86 0.43 26.38 Sub Total ==> -0.16 -0.22 0.00 Nom Vent 22 0
AHU Vent 22 0
Internal Loads Internal Loads Infil 7 0
Lights 0.25 0.06 0.31 10.54 0.25 15.34 Lights 0.00 0.00 0.00 MinStop/Rh 59 59
People 0.40 0 0 13.61 0.22 13.50 People 0.00 0 0.00 Return 202 59
Misc 0.67 0.00 0.67 22.79 0.67 41.10 Misc 0.00 0.00 0.00 Exhaust 28 0
Sub Total ==> 1.32 0.06 1.38 46.94 1.14 69.94 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.06 3.68 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.29 9.86 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.04 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.38 RA Preheat Diff. -0.20 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.22 0.00 % OA 11.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.04 0.00 Lps/m² 7.88 2.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.25
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.41
W/m² 118.84 -15.60
Grand Total ==> 1.98 0.60 2.94 100.00 1.63 100.00 Grand Total ==> -0.17 -0.60 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.95 2.33 190 27.0 20.4 12.4 18.0 16.3 10.9 Floor 25 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.95 Roof 25 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 225 of 323
Room Checksums
By Trane
T3-phong truong khoa 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.14 1.14 27.27 0.00 0.00 Roof Cond 0.00 -0.10 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.44 0.06 3.26 Partition/Door -0.13 -0.13 0.00 Diffuser 221 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 221 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 221 66
Infiltration 0.54 0.54 12.92 0.13 7.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 1.14 1.74 41.63 0.19 10.33 Sub Total ==> -0.13 -0.23 0.00 Nom Vent 39 0
AHU Vent 39 0
Internal Loads Internal Loads Infil 12 0
Lights 0.44 0.11 0.55 13.16 0.44 23.91 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.71 0 1 16.99 0.39 21.20 People 0.00 0 0.00 Return 234 66
Misc 0.67 0.00 0.67 16.03 0.67 36.41 Misc 0.00 0.00 0.00 Exhaust 51 0
Sub Total ==> 1.82 0.11 1.93 46.17 1.50 81.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.15 -0.15 0.00 0.00 0.15 8.15 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.55 13.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -2.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 1.91 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 17.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 0.00 Lps/m² 4.99 1.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -8.86
Grand Total ==> 2.57 0.98 4.18 100.00 1.84 100.00 Grand Total ==> -0.15 -0.64 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.19 3.07 221 27.2 20.6 12.6 18.0 15.6 10.1 Floor 44 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.19 Roof 44 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 226 of 323
Room Checksums
By Trane
T3-phong tu hoai

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.4 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.4 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.58 0.00 0.58 21.48 0.58 29.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.85 0.05 2.54 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.17 0.06 0.23 8.52 0.17 8.63 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 3.70 0.10 5.08 Partition/Door -0.13 -0.13 0.00 Diffuser 243 73
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 243 73
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 243 73
Infiltration 0.21 0.21 7.78 0.05 2.54 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.06 1.17 43.33 0.95 48.22 Sub Total ==> -0.16 -0.17 0.00 Nom Vent 24 0
AHU Vent 24 0
Internal Loads Internal Loads Infil 5 0
Lights 0.21 0.05 0.26 9.63 0.21 10.66 Lights 0.00 0.00 0.00 MinStop/Rh 73 73
People 0.43 0 0 15.93 0.22 11.17 People 0.00 0 0.00 Return 247 73
Misc 0.50 0.00 0.50 18.52 0.50 25.38 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.14 0.05 1.19 44.07 0.93 47.21 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.57 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.34 12.59 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -3.33 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.09 3.33 RA Preheat Diff. -0.33 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.35 0.00 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.02 0.00 Lps/m² 11.18 3.35
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 89.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.03
W/m² 124.50 -23.92
Grand Total ==> 2.34 -0.07 2.70 100.00 1.97 100.00 Grand Total ==> -0.17 -0.87 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.70 2.11 243 26.6 19.7 11.6 17.1 16.5 11.6 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.70 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 15 3 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 227 of 323
Room Checksums
By Trane
T3-phong xoa bop

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 8 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 25 / 20 OADB: 34 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.5 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 18.11 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.19 0.19 7.17 0.19 13.97 Partition/Door -0.26 -0.26 0.00 Diffuser 166 50
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 166 50
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 166 50
Infiltration 0.17 0.17 6.42 0.06 4.41 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.36 0.48 0.84 31.70 0.25 18.38 Sub Total ==> -0.26 -0.31 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.15 0.04 0.19 7.17 0.22 16.18 Lights 0.00 0.00 0.00 MinStop/Rh 50 50
People 0.42 0 0 15.85 0.25 18.38 People 0.00 0 0.00 Return 171 50
Misc 0.41 0.00 0.41 15.47 0.54 39.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 0.98 0.04 1.02 38.49 1.01 74.26 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 7.35 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.86 32.45 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -4.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 1.89 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.24 0.00 % OA 18.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.03 0.00 Lps/m² 7.50 2.25
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 62.52
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.34
W/m² 119.88 -22.69
Grand Total ==> 1.44 0.30 2.65 100.00 1.36 100.00 Grand Total ==> -0.27 -0.75 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.65 1.47 127 26.5 20.9 13.3 17.1 15.4 10.3 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.65 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 228 of 323
Room Checksums
By Trane
T3-phong y ta

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.7 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.7 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 9.22 0.13 12.15 Partition/Door -0.26 -0.26 0.00 Diffuser 129 39
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 129 39
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 129 39
Infiltration 0.14 0.14 9.93 0.03 2.80 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.27 0.00 0.27 19.15 0.16 14.95 Sub Total ==> -0.26 -0.26 0.00 Nom Vent 9 0
AHU Vent 9 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 9.93 0.11 10.28 Lights 0.00 0.00 0.00 MinStop/Rh 39 39
People 0.17 0 0 12.06 0.09 8.41 People 0.00 0 0.00 Return 132 39
Misc 0.67 0.00 0.67 47.52 0.67 62.62 Misc 0.00 0.00 0.00 Exhaust 12 0
Sub Total ==> 0.95 0.03 0.98 69.50 0.87 81.31 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.04 3.74 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 9.93 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -2.13 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 3.55 RA Preheat Diff. -0.13 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.14 0.00 % OA 7.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 11.92 3.58
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.67
W/m² 130.31 -37.73
Grand Total ==> 1.25 -0.03 1.41 100.00 1.07 100.00 Grand Total ==> -0.26 -0.54 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.41 1.12 128 26.8 20.2 12.2 18.0 17.3 12.2 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.41 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 229 of 323
Room Checksums
By Trane
T3-phong y ta nam

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 14 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 29 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.6 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.8 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 120 36
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 120 36
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 120 36
Infiltration 0.17 0.17 12.23 0.04 3.96 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.17 0.00 0.17 12.23 0.04 3.96 Sub Total ==> 0.00 0.00 0.00 Nom Vent 12 0
AHU Vent 12 0
Internal Loads Internal Loads Infil 4 0
Lights 0.13 0.03 0.16 11.51 0.13 12.87 Lights 0.00 0.00 0.00 MinStop/Rh 36 36
People 0.21 0 0 15.11 0.12 11.88 People 0.00 0 0.00 Return 124 36
Misc 0.67 0.00 0.67 48.20 0.67 66.34 Misc 0.00 0.00 0.00 Exhaust 15 0
Sub Total ==> 1.01 0.03 1.04 74.82 0.92 91.09 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.05 4.95 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.17 12.23 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -2.16 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.04 2.88 RA Preheat Diff. -0.13 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.13 0.00 % OA 9.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.00 Lps/m² 8.97 2.69
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 85.87
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.57
W/m² 104.44 -10.40
Grand Total ==> 1.22 -0.04 1.39 100.00 1.01 100.00 Grand Total ==> 0.00 -0.27 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.40 1.05 119 26.8 20.3 12.3 18.0 17.2 12.1 Floor 13 Main Htg -0.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.40 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 230 of 323
Room Checksums
By Trane
T3-phong y ta nu 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.3 21.0
Ra Plenum 26.9 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.14 1.14 27.27 0.00 0.00 Roof Cond 0.00 -0.10 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.06 0.06 1.44 0.06 3.26 Partition/Door -0.13 -0.13 0.00 Diffuser 221 66
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 221 66
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 221 66
Infiltration 0.54 0.54 12.92 0.13 7.07 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.60 1.14 1.74 41.63 0.19 10.33 Sub Total ==> -0.13 -0.23 0.00 Nom Vent 39 0
AHU Vent 39 0
Internal Loads Internal Loads Infil 12 0
Lights 0.44 0.11 0.55 13.16 0.44 23.91 Lights 0.00 0.00 0.00 MinStop/Rh 66 66
People 0.71 0 1 16.99 0.39 21.20 People 0.00 0 0.00 Return 234 66
Misc 0.67 0.00 0.67 16.03 0.67 36.41 Misc 0.00 0.00 0.00 Exhaust 51 0
Sub Total ==> 1.82 0.11 1.93 46.17 1.50 81.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.15 -0.15 0.00 0.00 0.15 8.15 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.55 13.16 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -2.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 1.91 RA Preheat Diff. -0.23 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 17.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 0.00 Lps/m² 4.99 1.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.60
W/m² 94.32 -8.86
Grand Total ==> 2.57 0.98 4.18 100.00 1.84 100.00 Grand Total ==> -0.15 -0.64 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.19 3.07 221 27.2 20.6 12.6 18.0 15.6 10.1 Floor 44 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.19 Roof 44 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 231 of 323
Room Checksums
By Trane
T3-tam bun

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.5 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 14.51 0.00 0.00 Roof Cond 0.00 -0.05 4.20
Glass Solar 0.55 0.00 0.55 14.25 0.55 22.54 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.11 0.00 0.11 2.85 0.11 4.51 Glass/Door Cond -0.02 -0.02 1.68
Cooling Heating
Wall Cond 0.46 0.16 0.62 16.06 0.46 18.85 Wall Cond -0.04 -0.06 5.04
Partition/Door 0.19 0.19 4.92 0.19 7.79 Partition/Door -0.26 -0.26 21.85 Diffuser 299 90
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 299 90
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 299 90
Infiltration 0.22 0.22 5.70 0.05 2.05 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.53 0.72 2.25 58.29 1.36 55.74 Sub Total ==> -0.32 -0.39 32.77 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 6.99 0.22 9.02 Lights 0.00 0.00 0.00 MinStop/Rh 90 90
People 0.44 0 0 11.40 0.24 9.84 People 0.00 0 0.00 Return 303 90
Misc 0.52 0.00 0.52 13.47 0.52 21.31 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.18 0.05 1.23 31.87 0.98 40.16 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 4.10 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 9.33 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -2.33 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.11 2.85 RA Preheat Diff. -0.41 34.45 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.43 36.13 % OA 8.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.04 -3.36 Lps/m² 13.51 4.05
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.20
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.71
W/m² 174.89 -34.30
Grand Total ==> 2.81 0.58 3.86 100.00 2.44 100.00 Grand Total ==> -0.33 -1.19 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.87 3.26 299 26.6 19.7 11.6 17.1 16.2 11.2 Floor 22 Main Htg -0.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.87 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 29 5 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 232 of 323
Room Checksums
By Trane
T3-tam ngam nuoc

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 17.4 21.0
Ra Plenum 26.5 20.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.5 20.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 12.07 0.00 0.00 Roof Cond 0.00 -0.05 3.40
Glass Solar 1.01 0.00 1.01 21.77 1.01 32.27 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.17 0.00 0.17 3.66 0.17 5.43 Glass/Door Cond -0.03 -0.03 2.04
Cooling Heating
Wall Cond 0.63 0.22 0.85 18.32 0.63 20.13 Wall Cond -0.07 -0.09 6.12
Partition/Door 0.19 0.19 4.09 0.19 6.07 Partition/Door -0.26 -0.26 17.69 Diffuser 383 115
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 383 115
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 383 115
Infiltration 0.22 0.22 4.74 0.05 1.60 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.22 0.78 3.00 64.66 2.05 65.50 Sub Total ==> -0.36 -0.43 29.25 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 5.82 0.22 7.03 Lights 0.00 0.00 0.00 MinStop/Rh 115 115
People 0.44 0 0 9.48 0.24 7.67 People 0.00 0 0.00 Return 388 115
Misc 0.52 0.00 0.52 11.21 0.52 16.61 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.18 0.05 1.23 26.51 0.98 31.31 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 3.19 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 7.76 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -1.94 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.14 3.02 RA Preheat Diff. -0.53 36.05 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.55 37.41 % OA 6.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.04 -2.72 Lps/m² 17.33 5.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.76
W/m² 210.02 -41.30
Grand Total ==> 3.50 0.64 4.64 100.00 3.13 100.00 Grand Total ==> -0.37 -1.47 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.64 4.03 383 26.6 19.6 11.5 17.1 16.3 11.4 Floor 22 Main Htg -0.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 29 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.64 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 44 8 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 233 of 323
Room Checksums
By Trane
T4-hanh lang 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 26.0 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 21.20 7.20 28.40 40.57 21.20 61.06 Wall Cond -2.48 -3.36 4.48
Partition/Door -6.67 -6.67 -9.53 -6.67 -19.21 Partition/Door -65.47 -65.47 87.35 Diffuser 3,188 956
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 3,188 956
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,188 956
Infiltration 8.80 8.80 12.57 1.68 4.84 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 23.33 7.20 30.53 43.61 16.21 46.69 Sub Total ==> -67.95 -68.83 91.83 Nom Vent 470 0
AHU Vent 470 0
Internal Loads Internal Loads Infil 231 0
Lights 8.30 2.07 10.37 14.81 8.30 23.91 Lights 0.00 0.00 0.00 MinStop/Rh 956 956
People 21.61 0 22 30.87 11.77 33.90 People 0.00 0 0.00 Return 3,419 956
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 702 0
Sub Total ==> 29.91 2.07 31.98 45.68 20.07 57.81 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -1.56 1.56 0.00 0.00 -1.56 -4.49 Ceiling Load 0.28 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 5.43 7.76 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.90 0.90 1.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 1.17 1.67 RA Preheat Diff. -3.87 5.16 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -3.64 4.86 % OA 14.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 1.39 -1.85 Lps/m² 3.79 1.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 45.52
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.00
W/m² 83.31 -84.87
Grand Total ==> 51.68 11.73 70.01 100.00 34.72 100.00 Grand Total ==> -67.67 -74.95 100.00 No. People 168

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 70.01 48.06 3,188 26.2 21.3 13.9 17.9 15.6 10.2 Floor 840 Main Htg -71.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 7,443 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 70.01 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,239 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -71.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 234 of 323
Room Checksums
By Trane
T4-hanh lang 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 39.67 0.00 39.67 41.30 40.58 60.58 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 7.27 0.00 7.27 7.57 7.15 10.67 Glass/Door Cond -2.08 -2.08 14.12
Cooling Heating
Wall Cond 6.17 7.61 13.78 14.35 5.55 8.28 Wall Cond -0.70 -1.57 10.66
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 6,603 1,981
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 6,603 1,981
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 6,603 1,981
Infiltration 6.14 6.14 6.39 1.26 1.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 59.25 7.61 66.86 69.60 54.54 81.42 Sub Total ==> -2.78 -3.65 24.78 Nom Vent 329 0
AHU Vent 329 0
Internal Loads Internal Loads Infil 162 0
Lights 5.76 1.44 7.20 7.50 5.76 8.60 Lights 0.00 0.00 0.00 MinStop/Rh 1,981 1,981
People 15.06 0 15 15.68 8.18 12.21 People 0.00 0 0.00 Return 6,764 1,981
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 491 0
Sub Total ==> 20.82 1.44 22.26 23.17 13.94 20.81 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -1.46 1.46 0.00 0.00 -1.49 -2.22 Ceiling Load 0.19 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 3.68 3.83 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.84 0.84 0.87 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 2.42 2.52 RA Preheat Diff. -6.51 44.20 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -6.07 41.21 % OA 5.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 1.50 -10.18 Lps/m² 11.24 3.37
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 68.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.12
W/m² 163.44 -14.74
Grand Total ==> 78.61 11.35 96.06 100.00 66.99 100.00 Grand Total ==> -2.59 -14.73 100.00 No. People 117

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 96.06 80.74 6,582 25.7 20.9 13.7 18.5 17.2 11.8 Floor 588 Main Htg -8.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 96.06 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,239 677 55 Opt Vent 0.0 0 0.0 0.0
Ext Door 279 0 0 Total -8.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 235 of 323
Room Checksums
By Trane
T4-phong bac si y ta 10

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.14 0.63 2.77 22.70 2.05 25.79 Wall Cond -0.14 -0.19 6.27
Partition/Door 0.49 0.49 4.02 0.49 6.16 Partition/Door -0.65 -0.65 21.45 Diffuser 1,239 372
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,239 372
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,239 372
Infiltration 1.10 1.10 9.02 0.29 3.65 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.73 0.63 4.36 35.74 2.83 35.60 Sub Total ==> -0.79 -0.84 27.72 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.08 0.27 1.35 11.07 1.08 13.58 Lights 0.00 0.00 0.00 MinStop/Rh 372 372
People 2.17 0 2 17.79 1.17 14.72 People 0.00 0 0.00 Return 1,263 372
Misc 2.50 0.00 2.50 20.49 2.56 32.20 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.75 0.27 6.02 49.34 4.81 60.50 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.32 -0.32 0.00 0.00 0.31 3.90 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.65 13.52 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.29 -0.29 -2.38 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.46 3.77 RA Preheat Diff. -1.22 40.26 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.14 37.62 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.61 Lps/m² 11.21 3.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 101.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.06
W/m² 110.30 -17.15
Grand Total ==> 9.80 0.29 12.20 100.00 7.95 100.00 Grand Total ==> -0.75 -3.03 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.19 9.24 1,238 25.8 19.4 11.6 18.5 16.8 11.4 Floor 111 Main Htg -1.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 74 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 236 of 323
Room Checksums
By Trane
T4-phong bac si y ta 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.14 0.63 2.77 22.70 2.05 25.79 Wall Cond -0.14 -0.19 6.27
Partition/Door 0.49 0.49 4.02 0.49 6.16 Partition/Door -0.65 -0.65 21.45 Diffuser 1,239 372
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,239 372
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,239 372
Infiltration 1.10 1.10 9.02 0.29 3.65 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.73 0.63 4.36 35.74 2.83 35.60 Sub Total ==> -0.79 -0.84 27.72 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.08 0.27 1.35 11.07 1.08 13.58 Lights 0.00 0.00 0.00 MinStop/Rh 372 372
People 2.17 0 2 17.79 1.17 14.72 People 0.00 0 0.00 Return 1,263 372
Misc 2.50 0.00 2.50 20.49 2.56 32.20 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.75 0.27 6.02 49.34 4.81 60.50 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.32 -0.32 0.00 0.00 0.31 3.90 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.65 13.52 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.29 -0.29 -2.38 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.46 3.77 RA Preheat Diff. -1.22 40.26 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.14 37.62 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.61 Lps/m² 11.21 3.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 101.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.06
W/m² 110.30 -17.15
Grand Total ==> 9.80 0.29 12.20 100.00 7.95 100.00 Grand Total ==> -0.75 -3.03 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.19 9.24 1,238 25.8 19.4 11.6 18.5 16.8 11.4 Floor 111 Main Htg -1.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 74 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 237 of 323
Room Checksums
By Trane
T4-phong bac si y ta 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.14 0.63 2.77 22.70 2.05 25.79 Wall Cond -0.14 -0.19 6.27
Partition/Door 0.49 0.49 4.02 0.49 6.16 Partition/Door -0.65 -0.65 21.45 Diffuser 1,239 372
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,239 372
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,239 372
Infiltration 1.10 1.10 9.02 0.29 3.65 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.73 0.63 4.36 35.74 2.83 35.60 Sub Total ==> -0.79 -0.84 27.72 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.08 0.27 1.35 11.07 1.08 13.58 Lights 0.00 0.00 0.00 MinStop/Rh 372 372
People 2.17 0 2 17.79 1.17 14.72 People 0.00 0 0.00 Return 1,263 372
Misc 2.50 0.00 2.50 20.49 2.56 32.20 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.75 0.27 6.02 49.34 4.81 60.50 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.32 -0.32 0.00 0.00 0.31 3.90 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.65 13.52 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.29 -0.29 -2.38 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.46 3.77 RA Preheat Diff. -1.22 40.26 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.14 37.62 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.61 Lps/m² 11.21 3.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 101.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.06
W/m² 110.30 -17.15
Grand Total ==> 9.80 0.29 12.20 100.00 7.95 100.00 Grand Total ==> -0.75 -3.03 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.19 9.24 1,238 25.8 19.4 11.6 18.5 16.8 11.4 Floor 111 Main Htg -1.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 74 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 238 of 323
Room Checksums
By Trane
T4-phong bac si y ta 8

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.14 0.63 2.77 22.70 2.05 25.79 Wall Cond -0.14 -0.19 6.27
Partition/Door 0.49 0.49 4.02 0.49 6.16 Partition/Door -0.65 -0.65 21.45 Diffuser 1,239 372
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,239 372
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,239 372
Infiltration 1.10 1.10 9.02 0.29 3.65 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.73 0.63 4.36 35.74 2.83 35.60 Sub Total ==> -0.79 -0.84 27.72 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.08 0.27 1.35 11.07 1.08 13.58 Lights 0.00 0.00 0.00 MinStop/Rh 372 372
People 2.17 0 2 17.79 1.17 14.72 People 0.00 0 0.00 Return 1,263 372
Misc 2.50 0.00 2.50 20.49 2.56 32.20 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.75 0.27 6.02 49.34 4.81 60.50 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.32 -0.32 0.00 0.00 0.31 3.90 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.65 13.52 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.29 -0.29 -2.38 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.46 3.77 RA Preheat Diff. -1.22 40.26 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.14 37.62 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.61 Lps/m² 11.21 3.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 101.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.06
W/m² 110.30 -17.15
Grand Total ==> 9.80 0.29 12.20 100.00 7.95 100.00 Grand Total ==> -0.75 -3.03 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.19 9.24 1,238 25.8 19.4 11.6 18.5 16.8 11.4 Floor 111 Main Htg -1.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 74 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 239 of 323
Room Checksums
By Trane
T4-phong bac si y ta 9

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.14 0.63 2.77 22.70 2.05 25.79 Wall Cond -0.14 -0.19 6.27
Partition/Door 0.49 0.49 4.02 0.49 6.16 Partition/Door -0.65 -0.65 21.45 Diffuser 1,239 372
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,239 372
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,239 372
Infiltration 1.10 1.10 9.02 0.29 3.65 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.73 0.63 4.36 35.74 2.83 35.60 Sub Total ==> -0.79 -0.84 27.72 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.08 0.27 1.35 11.07 1.08 13.58 Lights 0.00 0.00 0.00 MinStop/Rh 372 372
People 2.17 0 2 17.79 1.17 14.72 People 0.00 0 0.00 Return 1,263 372
Misc 2.50 0.00 2.50 20.49 2.56 32.20 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.75 0.27 6.02 49.34 4.81 60.50 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.32 -0.32 0.00 0.00 0.31 3.90 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.65 13.52 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.29 -0.29 -2.38 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.46 3.77 RA Preheat Diff. -1.22 40.26 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.14 37.62 % OA 9.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.61 Lps/m² 11.21 3.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 101.57
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.06
W/m² 110.30 -17.15
Grand Total ==> 9.80 0.29 12.20 100.00 7.95 100.00 Grand Total ==> -0.75 -3.03 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.19 9.24 1,238 25.8 19.4 11.6 18.5 16.8 11.4 Floor 111 Main Htg -1.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 74 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.19 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 240 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.39 0.40 1.79 15.62 1.39 18.01 Wall Cond -0.19 -0.25 8.14
Partition/Door 0.41 0.41 3.58 0.41 5.31 Partition/Door -0.82 -0.82 26.71 Diffuser 919 276
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 919 276
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 919 276
Infiltration 1.31 1.31 11.43 0.31 4.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.11 0.40 3.51 30.63 2.11 27.33 Sub Total ==> -1.01 -1.07 34.85 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.09 0.27 1.36 11.87 1.09 14.12 Lights 0.00 0.00 0.00 MinStop/Rh 276 276
People 1.78 0 2 15.53 0.97 12.56 People 0.00 0 0.00 Return 950 276
Misc 3.37 0.00 3.37 29.41 3.37 43.65 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.24 0.27 6.51 56.81 5.43 70.34 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 2.33 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.25 10.91 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -1.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.34 2.97 RA Preheat Diff. -1.12 36.48 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.05 34.20 % OA 10.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.54 Lps/m² 8.32 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.64
W/m² 103.70 -18.29
Grand Total ==> 9.53 0.34 11.46 100.00 7.72 100.00 Grand Total ==> -0.97 -3.07 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.46 8.75 919 26.1 20.1 12.3 17.9 16.8 11.6 Floor 111 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 241 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 10

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.57 0.00 2.57 17.10 2.57 23.84 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.24 0.00 0.24 1.60 0.24 2.23 Glass/Door Cond -0.05 -0.05 1.40
Cooling Heating
Wall Cond 1.74 0.66 2.40 15.97 1.74 16.14 Wall Cond -0.15 -0.22 6.15
Partition/Door 0.41 0.41 2.73 0.41 3.80 Partition/Door -0.82 -0.82 22.91 Diffuser 1,408 422
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,408 422
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,408 422
Infiltration 1.30 1.30 8.65 0.33 3.06 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.26 0.66 6.92 46.04 5.29 49.07 Sub Total ==> -1.02 -1.09 30.45 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.08 0.27 1.35 8.98 1.08 10.02 Lights 0.00 0.00 0.00 MinStop/Rh 422 422
People 1.77 0 2 11.78 0.96 8.91 People 0.00 0 0.00 Return 1,438 422
Misc 3.35 0.00 3.35 22.29 3.35 31.08 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.20 0.27 6.47 43.05 5.39 50.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 0.93 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.20 7.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.52 3.46 RA Preheat Diff. -1.39 38.83 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.29 36.03 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -5.31 Lps/m² 12.74 3.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 93.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.04 -20.68
Grand Total ==> 12.56 0.75 15.03 100.00 10.78 100.00 Grand Total ==> -0.98 -3.58 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.04 12.37 1,408 25.7 19.8 12.2 18.5 17.0 11.6 Floor 111 Main Htg -2.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 14 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 242 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.39 0.40 1.79 15.62 1.39 18.01 Wall Cond -0.19 -0.25 8.14
Partition/Door 0.41 0.41 3.58 0.41 5.31 Partition/Door -0.82 -0.82 26.71 Diffuser 919 276
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 919 276
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 919 276
Infiltration 1.31 1.31 11.43 0.31 4.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.11 0.40 3.51 30.63 2.11 27.33 Sub Total ==> -1.01 -1.07 34.85 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.09 0.27 1.36 11.87 1.09 14.12 Lights 0.00 0.00 0.00 MinStop/Rh 276 276
People 1.78 0 2 15.53 0.97 12.56 People 0.00 0 0.00 Return 950 276
Misc 3.37 0.00 3.37 29.41 3.37 43.65 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.24 0.27 6.51 56.81 5.43 70.34 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 2.33 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.25 10.91 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -1.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.34 2.97 RA Preheat Diff. -1.12 36.48 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.05 34.20 % OA 10.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.54 Lps/m² 8.32 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.64
W/m² 103.70 -18.29
Grand Total ==> 9.53 0.34 11.46 100.00 7.72 100.00 Grand Total ==> -0.97 -3.07 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.46 8.75 919 26.1 20.1 12.3 17.9 16.8 11.6 Floor 111 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 243 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.39 0.40 1.79 15.62 1.39 18.01 Wall Cond -0.19 -0.25 8.14
Partition/Door 0.41 0.41 3.58 0.41 5.31 Partition/Door -0.82 -0.82 26.71 Diffuser 919 276
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 919 276
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 919 276
Infiltration 1.31 1.31 11.43 0.31 4.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.11 0.40 3.51 30.63 2.11 27.33 Sub Total ==> -1.01 -1.07 34.85 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.09 0.27 1.36 11.87 1.09 14.12 Lights 0.00 0.00 0.00 MinStop/Rh 276 276
People 1.78 0 2 15.53 0.97 12.56 People 0.00 0 0.00 Return 950 276
Misc 3.37 0.00 3.37 29.41 3.37 43.65 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.24 0.27 6.51 56.81 5.43 70.34 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 2.33 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.25 10.91 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -1.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.34 2.97 RA Preheat Diff. -1.12 36.48 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.05 34.20 % OA 10.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.54 Lps/m² 8.32 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.64
W/m² 103.70 -18.29
Grand Total ==> 9.53 0.34 11.46 100.00 7.72 100.00 Grand Total ==> -0.97 -3.07 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.46 8.75 919 26.1 20.1 12.3 17.9 16.8 11.6 Floor 111 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 244 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.39 0.40 1.79 15.62 1.39 18.01 Wall Cond -0.19 -0.25 8.14
Partition/Door 0.41 0.41 3.58 0.41 5.31 Partition/Door -0.82 -0.82 26.71 Diffuser 919 276
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 919 276
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 919 276
Infiltration 1.31 1.31 11.43 0.31 4.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.11 0.40 3.51 30.63 2.11 27.33 Sub Total ==> -1.01 -1.07 34.85 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.09 0.27 1.36 11.87 1.09 14.12 Lights 0.00 0.00 0.00 MinStop/Rh 276 276
People 1.78 0 2 15.53 0.97 12.56 People 0.00 0 0.00 Return 950 276
Misc 3.37 0.00 3.37 29.41 3.37 43.65 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.24 0.27 6.51 56.81 5.43 70.34 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 2.33 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.25 10.91 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -1.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.34 2.97 RA Preheat Diff. -1.12 36.48 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.05 34.20 % OA 10.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.54 Lps/m² 8.32 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.64
W/m² 103.70 -18.29
Grand Total ==> 9.53 0.34 11.46 100.00 7.72 100.00 Grand Total ==> -0.97 -3.07 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.46 8.75 919 26.1 20.1 12.3 17.9 16.8 11.6 Floor 111 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 245 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.39 0.40 1.79 15.62 1.39 18.01 Wall Cond -0.19 -0.25 8.14
Partition/Door 0.41 0.41 3.58 0.41 5.31 Partition/Door -0.82 -0.82 26.71 Diffuser 919 276
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 919 276
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 919 276
Infiltration 1.31 1.31 11.43 0.31 4.02 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.11 0.40 3.51 30.63 2.11 27.33 Sub Total ==> -1.01 -1.07 34.85 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.09 0.27 1.36 11.87 1.09 14.12 Lights 0.00 0.00 0.00 MinStop/Rh 276 276
People 1.78 0 2 15.53 0.97 12.56 People 0.00 0 0.00 Return 950 276
Misc 3.37 0.00 3.37 29.41 3.37 43.65 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.24 0.27 6.51 56.81 5.43 70.34 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 2.33 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.25 10.91 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -1.31 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.34 2.97 RA Preheat Diff. -1.12 36.48 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.05 34.20 % OA 10.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -5.54 Lps/m² 8.32 2.50
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.17
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.64
W/m² 103.70 -18.29
Grand Total ==> 9.53 0.34 11.46 100.00 7.72 100.00 Grand Total ==> -0.97 -3.07 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.46 8.75 919 26.1 20.1 12.3 17.9 16.8 11.6 Floor 111 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 246 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.57 0.00 2.57 17.10 2.57 23.84 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.24 0.00 0.24 1.60 0.24 2.23 Glass/Door Cond -0.05 -0.05 1.40
Cooling Heating
Wall Cond 1.74 0.66 2.40 15.97 1.74 16.14 Wall Cond -0.15 -0.22 6.15
Partition/Door 0.41 0.41 2.73 0.41 3.80 Partition/Door -0.82 -0.82 22.91 Diffuser 1,408 422
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,408 422
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,408 422
Infiltration 1.30 1.30 8.65 0.33 3.06 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.26 0.66 6.92 46.04 5.29 49.07 Sub Total ==> -1.02 -1.09 30.45 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.08 0.27 1.35 8.98 1.08 10.02 Lights 0.00 0.00 0.00 MinStop/Rh 422 422
People 1.77 0 2 11.78 0.96 8.91 People 0.00 0 0.00 Return 1,438 422
Misc 3.35 0.00 3.35 22.29 3.35 31.08 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.20 0.27 6.47 43.05 5.39 50.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 0.93 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.20 7.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.52 3.46 RA Preheat Diff. -1.39 38.83 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.29 36.03 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -5.31 Lps/m² 12.74 3.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 93.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.04 -20.68
Grand Total ==> 12.56 0.75 15.03 100.00 10.78 100.00 Grand Total ==> -0.98 -3.58 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.04 12.37 1,408 25.7 19.8 12.2 18.5 17.0 11.6 Floor 111 Main Htg -2.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 14 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 247 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.57 0.00 2.57 17.10 2.57 23.84 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.24 0.00 0.24 1.60 0.24 2.23 Glass/Door Cond -0.05 -0.05 1.40
Cooling Heating
Wall Cond 1.74 0.66 2.40 15.97 1.74 16.14 Wall Cond -0.15 -0.22 6.15
Partition/Door 0.41 0.41 2.73 0.41 3.80 Partition/Door -0.82 -0.82 22.91 Diffuser 1,408 422
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,408 422
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,408 422
Infiltration 1.30 1.30 8.65 0.33 3.06 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.26 0.66 6.92 46.04 5.29 49.07 Sub Total ==> -1.02 -1.09 30.45 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.08 0.27 1.35 8.98 1.08 10.02 Lights 0.00 0.00 0.00 MinStop/Rh 422 422
People 1.77 0 2 11.78 0.96 8.91 People 0.00 0 0.00 Return 1,438 422
Misc 3.35 0.00 3.35 22.29 3.35 31.08 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.20 0.27 6.47 43.05 5.39 50.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 0.93 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.20 7.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.52 3.46 RA Preheat Diff. -1.39 38.83 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.29 36.03 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -5.31 Lps/m² 12.74 3.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 93.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.04 -20.68
Grand Total ==> 12.56 0.75 15.03 100.00 10.78 100.00 Grand Total ==> -0.98 -3.58 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.04 12.37 1,408 25.7 19.8 12.2 18.5 17.0 11.6 Floor 111 Main Htg -2.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 14 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 248 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 8

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.57 0.00 2.57 17.10 2.57 23.84 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.24 0.00 0.24 1.60 0.24 2.23 Glass/Door Cond -0.05 -0.05 1.40
Cooling Heating
Wall Cond 1.74 0.66 2.40 15.97 1.74 16.14 Wall Cond -0.15 -0.22 6.15
Partition/Door 0.41 0.41 2.73 0.41 3.80 Partition/Door -0.82 -0.82 22.91 Diffuser 1,408 422
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,408 422
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,408 422
Infiltration 1.30 1.30 8.65 0.33 3.06 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.26 0.66 6.92 46.04 5.29 49.07 Sub Total ==> -1.02 -1.09 30.45 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.08 0.27 1.35 8.98 1.08 10.02 Lights 0.00 0.00 0.00 MinStop/Rh 422 422
People 1.77 0 2 11.78 0.96 8.91 People 0.00 0 0.00 Return 1,438 422
Misc 3.35 0.00 3.35 22.29 3.35 31.08 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.20 0.27 6.47 43.05 5.39 50.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 0.93 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.20 7.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.52 3.46 RA Preheat Diff. -1.39 38.83 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.29 36.03 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -5.31 Lps/m² 12.74 3.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 93.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.04 -20.68
Grand Total ==> 12.56 0.75 15.03 100.00 10.78 100.00 Grand Total ==> -0.98 -3.58 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.04 12.37 1,408 25.7 19.8 12.2 18.5 17.0 11.6 Floor 111 Main Htg -2.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 14 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 249 of 323
Room Checksums
By Trane
T4-phong bac si, y ta 9

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.57 0.00 2.57 17.10 2.57 23.84 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.24 0.00 0.24 1.60 0.24 2.23 Glass/Door Cond -0.05 -0.05 1.40
Cooling Heating
Wall Cond 1.74 0.66 2.40 15.97 1.74 16.14 Wall Cond -0.15 -0.22 6.15
Partition/Door 0.41 0.41 2.73 0.41 3.80 Partition/Door -0.82 -0.82 22.91 Diffuser 1,408 422
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,408 422
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,408 422
Infiltration 1.30 1.30 8.65 0.33 3.06 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.26 0.66 6.92 46.04 5.29 49.07 Sub Total ==> -1.02 -1.09 30.45 Nom Vent 96 0
AHU Vent 96 0
Internal Loads Internal Loads Infil 30 0
Lights 1.08 0.27 1.35 8.98 1.08 10.02 Lights 0.00 0.00 0.00 MinStop/Rh 422 422
People 1.77 0 2 11.78 0.96 8.91 People 0.00 0 0.00 Return 1,438 422
Misc 3.35 0.00 3.35 22.29 3.35 31.08 Misc 0.00 0.00 0.00 Exhaust 126 0
Sub Total ==> 6.20 0.27 6.47 43.05 5.39 50.00 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 0.93 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.20 7.98 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.53 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.52 3.46 RA Preheat Diff. -1.39 38.83 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.29 36.03 % OA 6.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -5.31 Lps/m² 12.74 3.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 93.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.04 -20.68
Grand Total ==> 12.56 0.75 15.03 100.00 10.78 100.00 Grand Total ==> -0.98 -3.58 100.00 No. People 14

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.04 12.37 1,408 25.7 19.8 12.2 18.5 17.0 11.6 Floor 111 Main Htg -2.3 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.04 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 14 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.3

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 250 of 323
Room Checksums
By Trane
T4-phong bang ca

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.18 0.32 1.50 12.72 1.51 19.89 Wall Cond -0.19 -0.25 7.94
Partition/Door 0.62 0.62 5.26 0.62 8.17 Partition/Door -0.82 -0.82 26.03 Diffuser 1,183 355
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,183 355
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,183 355
Infiltration 1.33 1.33 11.28 0.28 3.69 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.13 0.32 3.45 29.26 2.41 31.75 Sub Total ==> -1.01 -1.07 33.97 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 0.92 0.23 1.15 9.75 1.09 14.36 Lights 0.00 0.00 0.00 MinStop/Rh 355 355
People 2.46 0 2 20.87 1.18 15.55 People 0.00 0 0.00 Return 1,207 355
Misc 2.66 0.00 2.66 22.56 2.59 34.12 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 6.04 0.23 6.27 53.18 4.86 64.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.29 -0.29 0.00 0.00 0.32 4.22 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.99 16.88 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.33 -0.33 -2.80 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.41 3.48 RA Preheat Diff. -1.17 37.14 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.09 34.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.18 -5.71 Lps/m² 10.70 3.21
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 100.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.38
W/m² 106.50 -18.64
Grand Total ==> 9.46 -0.07 11.79 100.00 7.59 100.00 Grand Total ==> -0.97 -3.15 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.77 7.99 1,106 25.7 19.5 11.8 18.5 16.7 11.2 Floor 111 Main Htg -2.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 251 of 323
Room Checksums
By Trane
T4-phong benh nhan 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.92 0.27 1.19 13.30 0.92 15.13 Wall Cond -0.20 -0.24 8.42
Partition/Door 0.13 0.13 1.45 0.13 2.14 Partition/Door -0.33 -0.33 11.58 Diffuser 723 217
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 723 217
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 723 217
Infiltration 1.00 1.00 11.17 0.24 3.95 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.05 0.27 2.32 25.92 1.29 21.22 Sub Total ==> -0.53 -0.57 20.00 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.37 0.53 8.72 Lights 0.00 0.00 0.00 MinStop/Rh 217 217
People 1.11 0 1 12.40 0.62 10.20 People 0.00 0 0.00 Return 746 217
Misc 3.50 0.00 3.50 39.11 3.50 57.57 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 58.88 4.65 76.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 2.30 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.22 13.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 3.02 RA Preheat Diff. -0.88 30.88 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.10 38.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.30 10.53 Lps/m² 8.56 2.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.83
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.45
W/m² 105.80 -20.74
Grand Total ==> 7.33 0.13 8.95 100.00 6.08 100.00 Grand Total ==> -0.65 -2.85 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 8.94 6.80 723 26.2 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 252 of 323
Room Checksums
By Trane
T4-phong benh nhan 10

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.24 0.37 1.61 17.60 1.42 21.98 Wall Cond -0.20 -0.24 8.08
Partition/Door 0.13 0.13 1.42 0.13 2.01 Partition/Door -0.33 -0.33 11.11 Diffuser 768 230
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 768 230
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 768 230
Infiltration 0.89 0.89 9.73 0.13 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.37 2.63 28.74 1.68 26.01 Sub Total ==> -0.53 -0.57 19.19 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.21 0.53 8.20 Lights 0.00 0.00 0.00 MinStop/Rh 230 230
People 1.11 0 1 12.13 0.62 9.60 People 0.00 0 0.00 Return 791 230
Misc 3.50 0.00 3.50 38.25 3.50 54.18 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.60 4.65 71.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 2.01 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.10 12.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.28 3.06 RA Preheat Diff. -0.93 31.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.16 39.06 % OA 12.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 10.44 Lps/m² 9.09 2.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.23
W/m² 108.26 -21.55
Grand Total ==> 7.53 0.24 9.15 100.00 6.46 100.00 Grand Total ==> -0.65 -2.97 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.15 7.09 752 26.0 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 253 of 323
Room Checksums
By Trane
T4-phong benh nhan 11

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.24 0.37 1.61 17.60 1.42 21.98 Wall Cond -0.20 -0.24 8.08
Partition/Door 0.13 0.13 1.42 0.13 2.01 Partition/Door -0.33 -0.33 11.11 Diffuser 768 230
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 768 230
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 768 230
Infiltration 0.89 0.89 9.73 0.13 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.37 2.63 28.74 1.68 26.01 Sub Total ==> -0.53 -0.57 19.19 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.21 0.53 8.20 Lights 0.00 0.00 0.00 MinStop/Rh 230 230
People 1.11 0 1 12.13 0.62 9.60 People 0.00 0 0.00 Return 791 230
Misc 3.50 0.00 3.50 38.25 3.50 54.18 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.60 4.65 71.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 2.01 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.10 12.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.28 3.06 RA Preheat Diff. -0.93 31.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.16 39.06 % OA 12.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 10.44 Lps/m² 9.09 2.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.23
W/m² 108.26 -21.55
Grand Total ==> 7.53 0.24 9.15 100.00 6.46 100.00 Grand Total ==> -0.65 -2.97 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.15 7.09 752 26.0 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 254 of 323
Room Checksums
By Trane
T4-phong benh nhan 12

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.24 0.37 1.61 17.60 1.42 21.98 Wall Cond -0.20 -0.24 8.08
Partition/Door 0.13 0.13 1.42 0.13 2.01 Partition/Door -0.33 -0.33 11.11 Diffuser 768 230
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 768 230
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 768 230
Infiltration 0.89 0.89 9.73 0.13 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.37 2.63 28.74 1.68 26.01 Sub Total ==> -0.53 -0.57 19.19 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.21 0.53 8.20 Lights 0.00 0.00 0.00 MinStop/Rh 230 230
People 1.11 0 1 12.13 0.62 9.60 People 0.00 0 0.00 Return 791 230
Misc 3.50 0.00 3.50 38.25 3.50 54.18 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.60 4.65 71.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 2.01 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.10 12.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.28 3.06 RA Preheat Diff. -0.93 31.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.16 39.06 % OA 12.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 10.44 Lps/m² 9.09 2.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.23
W/m² 108.26 -21.55
Grand Total ==> 7.53 0.24 9.15 100.00 6.46 100.00 Grand Total ==> -0.65 -2.97 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.15 7.09 752 26.0 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 255 of 323
Room Checksums
By Trane
T4-phong benh nhan 13

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.42 0.44 1.86 20.35 1.42 22.15 Wall Cond -0.20 -0.24 8.54
Partition/Door 0.13 0.13 1.42 0.13 2.03 Partition/Door -0.33 -0.33 11.74 Diffuser 837 251
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 837 251
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 837 251
Infiltration 0.75 0.75 8.21 0.13 2.03 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.30 0.44 2.74 29.98 1.68 26.21 Sub Total ==> -0.53 -0.57 20.28 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.22 0.53 8.27 Lights 0.00 0.00 0.00 MinStop/Rh 251 251
People 1.11 0 1 12.14 0.62 9.67 People 0.00 0 0.00 Return 860 251
Misc 3.50 0.00 3.50 38.29 3.50 54.60 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.66 4.65 72.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 1.25 Ceiling Load -0.13 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.90 9.85 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.31 3.39 RA Preheat Diff. -0.82 29.18 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.08 38.43 % OA 11.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.34 12.10 Lps/m² 9.90 2.97
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.49
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.24
W/m² 108.15 -20.58
Grand Total ==> 7.52 0.41 9.14 100.00 6.41 100.00 Grand Total ==> -0.66 -2.81 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.14 7.30 837 25.7 19.9 12.3 18.5 17.0 11.6 Floor 85 Main Htg -1.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 256 of 323
Room Checksums
By Trane
T4-phong benh nhan 14

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.42 0.44 1.86 20.35 1.42 22.15 Wall Cond -0.20 -0.24 8.54
Partition/Door 0.13 0.13 1.42 0.13 2.03 Partition/Door -0.33 -0.33 11.74 Diffuser 837 251
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 837 251
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 837 251
Infiltration 0.75 0.75 8.21 0.13 2.03 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.30 0.44 2.74 29.98 1.68 26.21 Sub Total ==> -0.53 -0.57 20.28 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.22 0.53 8.27 Lights 0.00 0.00 0.00 MinStop/Rh 251 251
People 1.11 0 1 12.14 0.62 9.67 People 0.00 0 0.00 Return 860 251
Misc 3.50 0.00 3.50 38.29 3.50 54.60 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.66 4.65 72.54 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 1.25 Ceiling Load -0.13 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.90 9.85 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.08 -0.08 -0.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.31 3.39 RA Preheat Diff. -0.82 29.18 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.08 38.43 % OA 11.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.34 12.10 Lps/m² 9.90 2.97
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.49
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.24
W/m² 108.15 -20.58
Grand Total ==> 7.52 0.41 9.14 100.00 6.41 100.00 Grand Total ==> -0.66 -2.81 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.14 7.30 837 25.7 19.9 12.3 18.5 17.0 11.6 Floor 85 Main Htg -1.7 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.14 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.7

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 257 of 323
Room Checksums
By Trane
T4-phong benh nhan 15

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 27 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.33 1.02 4.35 27.94 4.32 41.90 Wall Cond -0.49 -0.59 10.14
Partition/Door 0.65 0.65 4.17 0.65 6.30 Partition/Door -1.62 -1.62 27.84 Diffuser 1,344 403
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,344 403
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,344 403
Infiltration 1.47 1.47 9.44 0.06 0.58 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 5.45 1.02 6.47 41.55 5.03 48.79 Sub Total ==> -2.11 -2.21 37.97 Nom Vent 111 0
AHU Vent 111 0
Internal Loads Internal Loads Infil 27 0
Lights 1.04 0.26 1.30 8.35 1.51 14.65 Lights 0.00 0.00 0.00 MinStop/Rh 403 403
People 2.19 0 2 14.07 0.94 9.12 People 0.00 0 0.00 Return 1,371 403
Misc 3.50 0.00 3.50 22.48 2.63 25.51 Misc 0.00 0.00 0.00 Exhaust 138 0
Sub Total ==> 6.73 0.26 6.99 44.89 5.08 49.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.16 -0.16 0.00 0.00 0.20 1.94 Ceiling Load -0.25 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.77 11.37 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -0.96 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.49 3.15 RA Preheat Diff. -1.32 22.68 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.74 29.90 % OA 13.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.55 9.45 Lps/m² 8.09 2.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 86.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.68
W/m² 93.61 -24.63
Grand Total ==> 12.34 0.97 15.57 100.00 10.31 100.00 Grand Total ==> -2.36 -5.82 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.55 11.94 1,323 25.7 19.9 12.4 18.5 16.9 11.4 Floor 166 Main Htg -4.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.55 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 148 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -4.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 258 of 323
Room Checksums
By Trane
T4-phong benh nhan 16

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 27 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.33 1.02 4.35 27.94 4.32 41.90 Wall Cond -0.49 -0.59 10.14
Partition/Door 0.65 0.65 4.17 0.65 6.30 Partition/Door -1.62 -1.62 27.84 Diffuser 1,344 403
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,344 403
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,344 403
Infiltration 1.47 1.47 9.44 0.06 0.58 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 5.45 1.02 6.47 41.55 5.03 48.79 Sub Total ==> -2.11 -2.21 37.97 Nom Vent 111 0
AHU Vent 111 0
Internal Loads Internal Loads Infil 27 0
Lights 1.04 0.26 1.30 8.35 1.51 14.65 Lights 0.00 0.00 0.00 MinStop/Rh 403 403
People 2.19 0 2 14.07 0.94 9.12 People 0.00 0 0.00 Return 1,371 403
Misc 3.50 0.00 3.50 22.48 2.63 25.51 Misc 0.00 0.00 0.00 Exhaust 138 0
Sub Total ==> 6.73 0.26 6.99 44.89 5.08 49.27 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.16 -0.16 0.00 0.00 0.20 1.94 Ceiling Load -0.25 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.77 11.37 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.15 -0.15 -0.96 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.49 3.15 RA Preheat Diff. -1.32 22.68 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.74 29.90 % OA 13.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.55 9.45 Lps/m² 8.09 2.43
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 86.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.68
W/m² 93.61 -24.63
Grand Total ==> 12.34 0.97 15.57 100.00 10.31 100.00 Grand Total ==> -2.36 -5.82 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 15.55 11.94 1,323 25.7 19.9 12.4 18.5 16.9 11.4 Floor 166 Main Htg -4.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 15.55 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 148 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -4.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 259 of 323
Room Checksums
By Trane
T4-phong benh nhan 17

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 32 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.8 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 6.30 1.91 8.21 40.11 6.30 47.40 Wall Cond -0.97 -1.18 16.12
Partition/Door 0.65 0.65 3.18 0.65 4.89 Partition/Door -1.62 -1.62 22.13 Diffuser 1,733 520
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,733 520
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,733 520
Infiltration 1.89 1.89 9.23 0.40 3.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 8.84 1.91 10.75 52.52 7.35 55.30 Sub Total ==> -2.59 -2.80 38.25 Nom Vent 184 0
AHU Vent 184 0
Internal Loads Internal Loads Infil 46 0
Lights 1.04 0.26 1.30 6.35 1.04 7.83 Lights 0.00 0.00 0.00 MinStop/Rh 520 520
People 2.19 0 2 10.70 1.22 9.18 People 0.00 0 0.00 Return 1,779 520
Misc 3.50 0.00 3.50 17.10 3.50 26.34 Misc 0.00 0.00 0.00 Exhaust 230 0
Sub Total ==> 6.73 0.26 6.99 34.15 5.76 43.34 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 1.35 Ceiling Load -0.25 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.26 11.04 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.17 -0.17 -0.83 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.64 3.13 RA Preheat Diff. -1.71 23.36 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -2.24 30.60 % OA 10.6 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.57 7.79 Lps/m² 10.44 3.13
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 84.69
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.11
W/m² 123.19 -30.58
Grand Total ==> 15.75 1.82 20.47 100.00 13.29 100.00 Grand Total ==> -2.84 -7.32 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 20.46 16.26 1,733 25.8 20.0 12.3 18.5 16.9 11.4 Floor 166 Main Htg -5.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 20.46 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 295 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -5.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 260 of 323
Room Checksums
By Trane
T4-phong benh nhan 18

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.9 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 4.06 1.24 5.30 30.11 4.06 36.51 Wall Cond -0.49 -0.59 9.67
Partition/Door 0.65 0.65 3.69 0.65 5.85 Partition/Door -1.62 -1.62 26.56 Diffuser 1,451 435
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,451 435
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,451 435
Infiltration 1.96 1.96 11.14 0.47 4.23 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.67 1.24 7.91 44.94 5.18 46.58 Sub Total ==> -2.11 -2.21 36.23 Nom Vent 184 0
AHU Vent 184 0
Internal Loads Internal Loads Infil 46 0
Lights 1.04 0.26 1.30 7.39 1.04 9.35 Lights 0.00 0.00 0.00 MinStop/Rh 435 435
People 2.19 0 2 12.44 1.22 10.97 People 0.00 0 0.00 Return 1,497 435
Misc 3.50 0.00 3.50 19.89 3.50 31.47 Misc 0.00 0.00 0.00 Exhaust 230 0
Sub Total ==> 6.73 0.26 6.99 39.72 5.76 51.80 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 1.62 Ceiling Load -0.25 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.34 13.30 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.17 -0.17 -0.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.53 3.01 RA Preheat Diff. -1.43 23.44 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.87 30.66 % OA 12.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.59 9.67 Lps/m² 8.74 2.62
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.45
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.43
W/m² 105.94 -25.46
Grand Total ==> 13.58 1.15 17.60 100.00 11.12 100.00 Grand Total ==> -2.36 -6.10 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 17.59 13.39 1,451 25.9 20.0 12.4 18.5 16.9 11.4 Floor 166 Main Htg -4.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 17.59 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 148 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -4.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 261 of 323
Room Checksums
By Trane
T4-phong benh nhan 19

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 22.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.9 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 4.06 1.24 5.30 30.11 4.06 36.51 Wall Cond -0.49 -0.59 9.67
Partition/Door 0.65 0.65 3.69 0.65 5.85 Partition/Door -1.62 -1.62 26.56 Diffuser 1,451 435
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,451 435
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,451 435
Infiltration 1.96 1.96 11.14 0.47 4.23 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.67 1.24 7.91 44.94 5.18 46.58 Sub Total ==> -2.11 -2.21 36.23 Nom Vent 184 0
AHU Vent 184 0
Internal Loads Internal Loads Infil 46 0
Lights 1.04 0.26 1.30 7.39 1.04 9.35 Lights 0.00 0.00 0.00 MinStop/Rh 435 435
People 2.19 0 2 12.44 1.22 10.97 People 0.00 0 0.00 Return 1,497 435
Misc 3.50 0.00 3.50 19.89 3.50 31.47 Misc 0.00 0.00 0.00 Exhaust 230 0
Sub Total ==> 6.73 0.26 6.99 39.72 5.76 51.80 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 1.62 Ceiling Load -0.25 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 2.34 13.30 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.17 -0.17 -0.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.53 3.01 RA Preheat Diff. -1.43 23.44 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.87 30.66 % OA 12.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.59 9.67 Lps/m² 8.74 2.62
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.45
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.43
W/m² 105.94 -25.46
Grand Total ==> 13.58 1.15 17.60 100.00 11.12 100.00 Grand Total ==> -2.36 -6.10 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 17.59 13.39 1,451 25.9 20.0 12.4 18.5 16.9 11.4 Floor 166 Main Htg -4.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 17.59 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 148 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -4.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 262 of 323
Room Checksums
By Trane
T4-phong benh nhan 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.92 0.27 1.19 13.30 0.92 15.13 Wall Cond -0.20 -0.24 8.42
Partition/Door 0.13 0.13 1.45 0.13 2.14 Partition/Door -0.33 -0.33 11.58 Diffuser 723 217
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 723 217
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 723 217
Infiltration 1.00 1.00 11.17 0.24 3.95 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.05 0.27 2.32 25.92 1.29 21.22 Sub Total ==> -0.53 -0.57 20.00 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.37 0.53 8.72 Lights 0.00 0.00 0.00 MinStop/Rh 217 217
People 1.11 0 1 12.40 0.62 10.20 People 0.00 0 0.00 Return 746 217
Misc 3.50 0.00 3.50 39.11 3.50 57.57 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 58.88 4.65 76.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 2.30 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.22 13.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 3.02 RA Preheat Diff. -0.88 30.88 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.10 38.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.30 10.53 Lps/m² 8.56 2.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.83
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.45
W/m² 105.80 -20.74
Grand Total ==> 7.33 0.13 8.95 100.00 6.08 100.00 Grand Total ==> -0.65 -2.85 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 8.94 6.80 723 26.2 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 263 of 323
Room Checksums
By Trane
T4-phong benh nhan 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.92 0.27 1.19 13.30 0.92 15.13 Wall Cond -0.20 -0.24 8.42
Partition/Door 0.13 0.13 1.45 0.13 2.14 Partition/Door -0.33 -0.33 11.58 Diffuser 723 217
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 723 217
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 723 217
Infiltration 1.00 1.00 11.17 0.24 3.95 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.05 0.27 2.32 25.92 1.29 21.22 Sub Total ==> -0.53 -0.57 20.00 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.37 0.53 8.72 Lights 0.00 0.00 0.00 MinStop/Rh 217 217
People 1.11 0 1 12.40 0.62 10.20 People 0.00 0 0.00 Return 746 217
Misc 3.50 0.00 3.50 39.11 3.50 57.57 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 58.88 4.65 76.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 2.30 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.22 13.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 3.02 RA Preheat Diff. -0.88 30.88 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.10 38.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.30 10.53 Lps/m² 8.56 2.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.83
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.45
W/m² 105.80 -20.74
Grand Total ==> 7.33 0.13 8.95 100.00 6.08 100.00 Grand Total ==> -0.65 -2.85 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 8.94 6.80 723 26.2 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 264 of 323
Room Checksums
By Trane
T4-phong benh nhan 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.92 0.27 1.19 13.30 0.92 15.13 Wall Cond -0.20 -0.24 8.42
Partition/Door 0.13 0.13 1.45 0.13 2.14 Partition/Door -0.33 -0.33 11.58 Diffuser 723 217
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 723 217
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 723 217
Infiltration 1.00 1.00 11.17 0.24 3.95 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.05 0.27 2.32 25.92 1.29 21.22 Sub Total ==> -0.53 -0.57 20.00 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.37 0.53 8.72 Lights 0.00 0.00 0.00 MinStop/Rh 217 217
People 1.11 0 1 12.40 0.62 10.20 People 0.00 0 0.00 Return 746 217
Misc 3.50 0.00 3.50 39.11 3.50 57.57 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 58.88 4.65 76.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 2.30 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.22 13.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 3.02 RA Preheat Diff. -0.88 30.88 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.10 38.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.30 10.53 Lps/m² 8.56 2.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.83
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.45
W/m² 105.80 -20.74
Grand Total ==> 7.33 0.13 8.95 100.00 6.08 100.00 Grand Total ==> -0.65 -2.85 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 8.94 6.80 723 26.2 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 265 of 323
Room Checksums
By Trane
T4-phong benh nhan 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.2 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.92 0.27 1.19 13.30 0.92 15.13 Wall Cond -0.20 -0.24 8.42
Partition/Door 0.13 0.13 1.45 0.13 2.14 Partition/Door -0.33 -0.33 11.58 Diffuser 723 217
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 723 217
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 723 217
Infiltration 1.00 1.00 11.17 0.24 3.95 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.05 0.27 2.32 25.92 1.29 21.22 Sub Total ==> -0.53 -0.57 20.00 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.37 0.53 8.72 Lights 0.00 0.00 0.00 MinStop/Rh 217 217
People 1.11 0 1 12.40 0.62 10.20 People 0.00 0 0.00 Return 746 217
Misc 3.50 0.00 3.50 39.11 3.50 57.57 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 58.88 4.65 76.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 2.30 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.22 13.63 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.45 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 3.02 RA Preheat Diff. -0.88 30.88 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.10 38.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.30 10.53 Lps/m² 8.56 2.57
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.83
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.45
W/m² 105.80 -20.74
Grand Total ==> 7.33 0.13 8.95 100.00 6.08 100.00 Grand Total ==> -0.65 -2.85 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 8.94 6.80 723 26.2 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.94 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 266 of 323
Room Checksums
By Trane
T4-phong benh nhan 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 11 / 21 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 27 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.9 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.92 1.16 5.08 40.87 5.44 57.02 Wall Cond -0.69 -0.83 18.12
Partition/Door 0.13 0.13 1.05 0.13 1.36 Partition/Door -0.33 -0.33 7.21 Diffuser 1,134 340
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,134 340
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,134 340
Infiltration 0.75 0.75 6.03 0.04 0.42 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.80 1.16 5.96 47.95 5.61 58.81 Sub Total ==> -1.02 -1.16 25.33 Nom Vent 56 0
AHU Vent 56 0
Internal Loads Internal Loads Infil 14 0
Lights 0.53 0.13 0.66 5.31 0.79 8.28 Lights 0.00 0.00 0.00 MinStop/Rh 340 340
People 1.11 0 1 8.93 0.46 4.82 People 0.00 0 0.00 Return 1,148 340
Misc 3.50 0.00 3.50 28.16 2.52 26.42 Misc 0.00 0.00 0.00 Exhaust 70 0
Sub Total ==> 5.14 0.13 5.27 42.40 3.77 39.52 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.16 1.68 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.93 7.48 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -0.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.39 3.14 RA Preheat Diff. -1.38 30.13 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.72 37.55 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.32 6.99 Lps/m² 13.42 4.03
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 91.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.80
W/m² 147.06 -33.86
Grand Total ==> 10.07 1.04 12.43 100.00 9.54 100.00 Grand Total ==> -1.14 -4.58 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.43 10.59 1,065 25.9 19.9 12.2 17.9 16.9 11.7 Floor 85 Main Htg -2.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.43 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 208 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 267 of 323
Room Checksums
By Trane
T4-phong benh nhan 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.24 0.37 1.61 17.60 1.42 21.98 Wall Cond -0.20 -0.24 8.08
Partition/Door 0.13 0.13 1.42 0.13 2.01 Partition/Door -0.33 -0.33 11.11 Diffuser 768 230
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 768 230
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 768 230
Infiltration 0.89 0.89 9.73 0.13 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.37 2.63 28.74 1.68 26.01 Sub Total ==> -0.53 -0.57 19.19 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.21 0.53 8.20 Lights 0.00 0.00 0.00 MinStop/Rh 230 230
People 1.11 0 1 12.13 0.62 9.60 People 0.00 0 0.00 Return 791 230
Misc 3.50 0.00 3.50 38.25 3.50 54.18 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.60 4.65 71.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 2.01 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.10 12.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.28 3.06 RA Preheat Diff. -0.93 31.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.16 39.06 % OA 12.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 10.44 Lps/m² 9.09 2.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.23
W/m² 108.26 -21.55
Grand Total ==> 7.53 0.24 9.15 100.00 6.46 100.00 Grand Total ==> -0.65 -2.97 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.15 7.09 752 26.0 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 268 of 323
Room Checksums
By Trane
T4-phong benh nhan 8

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.24 0.37 1.61 17.60 1.42 21.98 Wall Cond -0.20 -0.24 8.08
Partition/Door 0.13 0.13 1.42 0.13 2.01 Partition/Door -0.33 -0.33 11.11 Diffuser 768 230
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 768 230
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 768 230
Infiltration 0.89 0.89 9.73 0.13 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.37 2.63 28.74 1.68 26.01 Sub Total ==> -0.53 -0.57 19.19 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.21 0.53 8.20 Lights 0.00 0.00 0.00 MinStop/Rh 230 230
People 1.11 0 1 12.13 0.62 9.60 People 0.00 0 0.00 Return 791 230
Misc 3.50 0.00 3.50 38.25 3.50 54.18 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.60 4.65 71.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 2.01 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.10 12.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.28 3.06 RA Preheat Diff. -0.93 31.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.16 39.06 % OA 12.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 10.44 Lps/m² 9.09 2.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.23
W/m² 108.26 -21.55
Grand Total ==> 7.53 0.24 9.15 100.00 6.46 100.00 Grand Total ==> -0.65 -2.97 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.15 7.09 752 26.0 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 269 of 323
Room Checksums
By Trane
T4-phong benh nhan 9

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 17 Mo/Hr: 11 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 22 OADB: 29 OADB: 19 SADB 18.2 22.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.0 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.24 0.37 1.61 17.60 1.42 21.98 Wall Cond -0.20 -0.24 8.08
Partition/Door 0.13 0.13 1.42 0.13 2.01 Partition/Door -0.33 -0.33 11.11 Diffuser 768 230
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 768 230
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 768 230
Infiltration 0.89 0.89 9.73 0.13 2.01 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.26 0.37 2.63 28.74 1.68 26.01 Sub Total ==> -0.53 -0.57 19.19 Nom Vent 94 0
AHU Vent 94 0
Internal Loads Internal Loads Infil 23 0
Lights 0.53 0.13 0.66 7.21 0.53 8.20 Lights 0.00 0.00 0.00 MinStop/Rh 230 230
People 1.11 0 1 12.13 0.62 9.60 People 0.00 0 0.00 Return 791 230
Misc 3.50 0.00 3.50 38.25 3.50 54.18 Misc 0.00 0.00 0.00 Exhaust 117 0
Sub Total ==> 5.14 0.13 5.27 57.60 4.65 71.98 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 2.01 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.10 12.02 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.13 -0.13 -1.42 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.28 3.06 RA Preheat Diff. -0.93 31.31 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.16 39.06 % OA 12.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 10.44 Lps/m² 9.09 2.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.23
W/m² 108.26 -21.55
Grand Total ==> 7.53 0.24 9.15 100.00 6.46 100.00 Grand Total ==> -0.65 -2.97 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 9.15 7.09 752 26.0 20.1 12.4 17.9 16.9 11.7 Floor 85 Main Htg -1.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.15 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 61 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 270 of 323
Room Checksums
By Trane
T4-phong bo bot chinh hinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.18 0.32 1.50 12.72 1.51 19.89 Wall Cond -0.19 -0.25 7.94
Partition/Door 0.62 0.62 5.26 0.62 8.17 Partition/Door -0.82 -0.82 26.03 Diffuser 1,183 355
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,183 355
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,183 355
Infiltration 1.33 1.33 11.28 0.28 3.69 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.13 0.32 3.45 29.26 2.41 31.75 Sub Total ==> -1.01 -1.07 33.97 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 0.92 0.23 1.15 9.75 1.09 14.36 Lights 0.00 0.00 0.00 MinStop/Rh 355 355
People 2.46 0 2 20.87 1.18 15.55 People 0.00 0 0.00 Return 1,207 355
Misc 2.66 0.00 2.66 22.56 2.59 34.12 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 6.04 0.23 6.27 53.18 4.86 64.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.29 -0.29 0.00 0.00 0.32 4.22 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.99 16.88 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.33 -0.33 -2.80 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.41 3.48 RA Preheat Diff. -1.17 37.14 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.09 34.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.18 -5.71 Lps/m² 10.70 3.21
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 100.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.38
W/m² 106.50 -18.64
Grand Total ==> 9.46 -0.07 11.79 100.00 7.59 100.00 Grand Total ==> -0.97 -3.15 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.77 7.99 1,106 25.7 19.5 11.8 18.5 16.7 11.2 Floor 111 Main Htg -2.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 271 of 323
Room Checksums
By Trane
T4-phong dieu tri

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.06 0.59 2.65 20.92 2.06 24.09 Wall Cond -0.14 -0.19 4.59
Partition/Door 0.97 0.97 7.66 0.97 11.35 Partition/Door -1.30 -1.30 31.40 Diffuser 1,195 359
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,195 359
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,195 359
Infiltration 1.10 1.10 8.68 0.28 3.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.13 0.59 4.72 37.25 3.31 38.71 Sub Total ==> -1.44 -1.49 35.99 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.09 0.27 1.36 10.73 1.09 12.75 Lights 0.00 0.00 0.00 MinStop/Rh 359 359
People 2.22 0 2 17.52 1.18 13.80 People 0.00 0 0.00 Return 1,219 359
Misc 2.59 0.00 2.59 20.44 2.59 30.29 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.90 0.27 6.17 48.70 4.86 56.84 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.38 -0.38 0.00 0.00 0.38 4.44 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.69 13.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.35 -0.35 -2.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.44 3.47 RA Preheat Diff. -1.45 35.02 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.37 33.09 % OA 10.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -4.11 Lps/m² 10.81 3.24
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.71
W/m² 114.76 -25.06
Grand Total ==> 10.41 0.13 12.67 100.00 8.55 100.00 Grand Total ==> -1.40 -4.14 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.69 9.72 1,195 26.1 19.5 11.6 17.9 16.7 11.5 Floor 111 Main Htg -2.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 272 of 323
Room Checksums
By Trane
T4-phong ky thuat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.06 0.59 2.65 20.92 2.06 24.09 Wall Cond -0.14 -0.19 4.59
Partition/Door 0.97 0.97 7.66 0.97 11.35 Partition/Door -1.30 -1.30 31.40 Diffuser 1,195 359
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,195 359
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,195 359
Infiltration 1.10 1.10 8.68 0.28 3.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.13 0.59 4.72 37.25 3.31 38.71 Sub Total ==> -1.44 -1.49 35.99 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.09 0.27 1.36 10.73 1.09 12.75 Lights 0.00 0.00 0.00 MinStop/Rh 359 359
People 2.22 0 2 17.52 1.18 13.80 People 0.00 0 0.00 Return 1,219 359
Misc 2.59 0.00 2.59 20.44 2.59 30.29 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.90 0.27 6.17 48.70 4.86 56.84 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.38 -0.38 0.00 0.00 0.38 4.44 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.69 13.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.35 -0.35 -2.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.44 3.47 RA Preheat Diff. -1.45 35.02 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.37 33.09 % OA 10.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -4.11 Lps/m² 10.81 3.24
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.71
W/m² 114.76 -25.06
Grand Total ==> 10.41 0.13 12.67 100.00 8.55 100.00 Grand Total ==> -1.40 -4.14 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.69 9.72 1,195 26.1 19.5 11.6 17.9 16.7 11.5 Floor 111 Main Htg -2.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 273 of 323
Room Checksums
By Trane
T4-phong thay do nam

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.65 0.65 9.12 0.65 12.22 Partition/Door -1.30 -1.30 47.62 Diffuser 633 190
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 633 190
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 633 190
Infiltration 0.70 0.70 9.82 0.17 3.20 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.35 0.00 1.35 18.93 0.82 15.41 Sub Total ==> -1.30 -1.30 47.62 Nom Vent 49 0
AHU Vent 49 0
Internal Loads Internal Loads Infil 15 0
Lights 0.55 0.14 0.69 9.68 0.55 10.34 Lights 0.00 0.00 0.00 MinStop/Rh 190 190
People 0.90 0 1 12.62 0.49 9.21 People 0.00 0 0.00 Return 648 190
Misc 3.37 0.00 3.37 47.27 3.37 63.35 Misc 0.00 0.00 0.00 Exhaust 64 0
Sub Total ==> 4.82 0.14 4.96 69.57 4.41 82.89 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 1.69 Ceiling Load 0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.66 9.26 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -0.98 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.23 3.23 RA Preheat Diff. -0.77 28.21 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.72 26.37 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.06 -2.20 Lps/m² 11.30 3.39
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 88.72
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.85
W/m² 127.29 -35.74
Grand Total ==> 6.26 -0.02 7.13 100.00 5.32 100.00 Grand Total ==> -1.28 -2.73 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.13 5.70 632 26.1 20.0 12.3 17.9 17.0 11.9 Floor 56 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.13 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 274 of 323
Room Checksums
By Trane
T4-phong thay do nu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.65 0.65 9.12 0.65 12.22 Partition/Door -1.30 -1.30 47.62 Diffuser 633 190
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 633 190
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 633 190
Infiltration 0.70 0.70 9.82 0.17 3.20 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.35 0.00 1.35 18.93 0.82 15.41 Sub Total ==> -1.30 -1.30 47.62 Nom Vent 49 0
AHU Vent 49 0
Internal Loads Internal Loads Infil 15 0
Lights 0.55 0.14 0.69 9.68 0.55 10.34 Lights 0.00 0.00 0.00 MinStop/Rh 190 190
People 0.90 0 1 12.62 0.49 9.21 People 0.00 0 0.00 Return 648 190
Misc 3.37 0.00 3.37 47.27 3.37 63.35 Misc 0.00 0.00 0.00 Exhaust 64 0
Sub Total ==> 4.82 0.14 4.96 69.57 4.41 82.89 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 1.69 Ceiling Load 0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.66 9.26 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -0.98 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.23 3.23 RA Preheat Diff. -0.77 28.21 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.72 26.37 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.06 -2.20 Lps/m² 11.30 3.39
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 88.72
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.85
W/m² 127.29 -35.74
Grand Total ==> 6.26 -0.02 7.13 100.00 5.32 100.00 Grand Total ==> -1.28 -2.73 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 7.13 5.70 632 26.1 20.0 12.3 17.9 17.0 11.9 Floor 56 Main Htg -2.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.13 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 275 of 323
Room Checksums
By Trane
T4-phong thua thuat huu khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.06 0.59 2.65 20.92 2.06 24.09 Wall Cond -0.14 -0.19 4.59
Partition/Door 0.97 0.97 7.66 0.97 11.35 Partition/Door -1.30 -1.30 31.40 Diffuser 1,195 359
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,195 359
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,195 359
Infiltration 1.10 1.10 8.68 0.28 3.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.13 0.59 4.72 37.25 3.31 38.71 Sub Total ==> -1.44 -1.49 35.99 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.09 0.27 1.36 10.73 1.09 12.75 Lights 0.00 0.00 0.00 MinStop/Rh 359 359
People 2.22 0 2 17.52 1.18 13.80 People 0.00 0 0.00 Return 1,219 359
Misc 2.59 0.00 2.59 20.44 2.59 30.29 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.90 0.27 6.17 48.70 4.86 56.84 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.38 -0.38 0.00 0.00 0.38 4.44 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.69 13.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.35 -0.35 -2.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.44 3.47 RA Preheat Diff. -1.45 35.02 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.37 33.09 % OA 10.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -4.11 Lps/m² 10.81 3.24
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.71
W/m² 114.76 -25.06
Grand Total ==> 10.41 0.13 12.67 100.00 8.55 100.00 Grand Total ==> -1.40 -4.14 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.69 9.72 1,195 26.1 19.5 11.6 17.9 16.7 11.5 Floor 111 Main Htg -2.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 276 of 323
Room Checksums
By Trane
T4-phong thua thuat vo khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.06 0.59 2.65 20.92 2.06 24.09 Wall Cond -0.14 -0.19 4.59
Partition/Door 0.97 0.97 7.66 0.97 11.35 Partition/Door -1.30 -1.30 31.40 Diffuser 1,195 359
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,195 359
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,195 359
Infiltration 1.10 1.10 8.68 0.28 3.27 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 4.13 0.59 4.72 37.25 3.31 38.71 Sub Total ==> -1.44 -1.49 35.99 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.09 0.27 1.36 10.73 1.09 12.75 Lights 0.00 0.00 0.00 MinStop/Rh 359 359
People 2.22 0 2 17.52 1.18 13.80 People 0.00 0 0.00 Return 1,219 359
Misc 2.59 0.00 2.59 20.44 2.59 30.29 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 5.90 0.27 6.17 48.70 4.86 56.84 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.38 -0.38 0.00 0.00 0.38 4.44 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.69 13.34 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.35 -0.35 -2.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.44 3.47 RA Preheat Diff. -1.45 35.02 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.37 33.09 % OA 10.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -4.11 Lps/m² 10.81 3.24
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.71
W/m² 114.76 -25.06
Grand Total ==> 10.41 0.13 12.67 100.00 8.55 100.00 Grand Total ==> -1.40 -4.14 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 12.69 9.72 1,195 26.1 19.5 11.6 17.9 16.7 11.5 Floor 111 Main Htg -2.8 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 12.69 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.8

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 277 of 323
Room Checksums
By Trane
T4-phong tiem cap cuu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.18 0.32 1.50 12.72 1.51 19.89 Wall Cond -0.19 -0.25 7.94
Partition/Door 0.62 0.62 5.26 0.62 8.17 Partition/Door -0.82 -0.82 26.03 Diffuser 1,183 355
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,183 355
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,183 355
Infiltration 1.33 1.33 11.28 0.28 3.69 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.13 0.32 3.45 29.26 2.41 31.75 Sub Total ==> -1.01 -1.07 33.97 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 0.92 0.23 1.15 9.75 1.09 14.36 Lights 0.00 0.00 0.00 MinStop/Rh 355 355
People 2.46 0 2 20.87 1.18 15.55 People 0.00 0 0.00 Return 1,207 355
Misc 2.66 0.00 2.66 22.56 2.59 34.12 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 6.04 0.23 6.27 53.18 4.86 64.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.29 -0.29 0.00 0.00 0.32 4.22 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.99 16.88 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.33 -0.33 -2.80 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.41 3.48 RA Preheat Diff. -1.17 37.14 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.09 34.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.18 -5.71 Lps/m² 10.70 3.21
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 100.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.38
W/m² 106.50 -18.64
Grand Total ==> 9.46 -0.07 11.79 100.00 7.59 100.00 Grand Total ==> -0.97 -3.15 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.77 7.99 1,106 25.7 19.5 11.8 18.5 16.7 11.2 Floor 111 Main Htg -2.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 278 of 323
Room Checksums
By Trane
T4-phong tiep nhan + y ta truc 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.2 21.0
Ra Plenum 25.9 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.9 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.1 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.33 0.00 2.33 15.70 2.33 21.84 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.28 0.00 0.28 1.89 0.28 2.62 Glass/Door Cond -0.05 -0.05 1.04
Cooling Heating
Wall Cond 1.39 0.53 1.92 12.94 1.39 13.03 Wall Cond -0.11 -0.16 3.31
Partition/Door 0.97 0.97 6.54 0.97 9.09 Partition/Door -1.30 -1.30 26.92 Diffuser 1,489 447
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,489 447
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,489 447
Infiltration 1.11 1.11 7.48 0.30 2.81 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.08 0.53 6.61 44.54 5.27 49.39 Sub Total ==> -1.46 -1.51 31.26 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.09 0.27 1.36 9.16 1.09 10.22 Lights 0.00 0.00 0.00 MinStop/Rh 447 447
People 2.27 0 2 15.30 1.24 11.62 People 0.00 0 0.00 Return 1,513 447
Misc 2.70 0.00 2.70 18.19 2.70 25.30 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 6.06 0.27 6.33 42.65 5.03 47.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.37 -0.37 0.00 0.00 0.37 3.47 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.69 11.39 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.34 -0.34 -2.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.55 3.71 RA Preheat Diff. -1.81 37.47 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.70 35.20 % OA 8.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -3.93 Lps/m² 13.47 4.04
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 100.28
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.44
W/m² 134.28 -28.27
Grand Total ==> 12.51 0.09 14.84 100.00 10.67 100.00 Grand Total ==> -1.42 -4.83 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 14.84 11.91 1,489 26.1 19.5 11.6 17.9 16.8 11.6 Floor 111 Main Htg -3.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 14.84 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 14 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -3.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 279 of 323
Room Checksums
By Trane
T4-phong tiep nhan + y ta truc 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.6 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.6 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.33 0.00 2.33 15.61 2.33 21.96 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.28 0.00 0.28 1.88 0.28 2.64 Glass/Door Cond -0.05 -0.05 1.12
Cooling Heating
Wall Cond 1.39 0.54 1.93 12.93 1.39 13.10 Wall Cond -0.11 -0.16 3.58
Partition/Door 0.97 0.97 6.50 0.97 9.14 Partition/Door -1.30 -1.30 29.08 Diffuser 1,652 496
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,652 496
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,652 496
Infiltration 1.11 1.11 7.43 0.30 2.83 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 6.08 0.54 6.62 44.34 5.27 49.67 Sub Total ==> -1.46 -1.51 33.78 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 1.09 0.27 1.36 9.11 1.09 10.27 Lights 0.00 0.00 0.00 MinStop/Rh 496 496
People 2.27 0 2 15.20 1.24 11.69 People 0.00 0 0.00 Return 1,676 496
Misc 2.70 0.00 2.70 18.08 2.70 25.45 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 6.06 0.27 6.33 42.40 5.03 47.41 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.31 -0.31 0.00 0.00 0.31 2.92 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.65 11.05 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.28 -0.28 -1.88 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.61 4.09 RA Preheat Diff. -1.63 36.47 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.52 34.00 % OA 7.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.19 -4.25 Lps/m² 14.95 4.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 110.61
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.40
W/m² 135.04 -26.63
Grand Total ==> 12.45 0.22 14.93 100.00 10.61 100.00 Grand Total ==> -1.42 -4.47 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 14.93 12.00 1,652 25.7 19.3 11.5 18.5 16.9 11.5 Floor 111 Main Htg -2.9 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 148 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 14.93 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 72 14 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.9

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 280 of 323
Room Checksums
By Trane
T4-phong tieu phau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 11 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 31 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 25.5 21.2
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 25.5 21.2
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 25.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.18 0.32 1.50 12.72 1.51 19.89 Wall Cond -0.19 -0.25 7.94
Partition/Door 0.62 0.62 5.26 0.62 8.17 Partition/Door -0.82 -0.82 26.03 Diffuser 1,183 355
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,183 355
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,183 355
Infiltration 1.33 1.33 11.28 0.28 3.69 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 3.13 0.32 3.45 29.26 2.41 31.75 Sub Total ==> -1.01 -1.07 33.97 Nom Vent 123 0
AHU Vent 123 0
Internal Loads Internal Loads Infil 24 0
Lights 0.92 0.23 1.15 9.75 1.09 14.36 Lights 0.00 0.00 0.00 MinStop/Rh 355 355
People 2.46 0 2 20.87 1.18 15.55 People 0.00 0 0.00 Return 1,207 355
Misc 2.66 0.00 2.66 22.56 2.59 34.12 Misc 0.00 0.00 0.00 Exhaust 147 0
Sub Total ==> 6.04 0.23 6.27 53.18 4.86 64.03 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.29 -0.29 0.00 0.00 0.32 4.22 Ceiling Load 0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.99 16.88 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.33 -0.33 -2.80 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.41 3.48 RA Preheat Diff. -1.17 37.14 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.09 34.60 % OA 13.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.18 -5.71 Lps/m² 10.70 3.21
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 100.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.38
W/m² 106.50 -18.64
Grand Total ==> 9.46 -0.07 11.79 100.00 7.59 100.00 Grand Total ==> -0.97 -3.15 100.00 No. People 22

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 11.77 7.99 1,106 25.7 19.5 11.8 18.5 16.7 11.2 Floor 111 Main Htg -2.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 93 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 11.77 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 93 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -2.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 281 of 323
Room Checksums
By Trane
T9-hanh lang

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.1 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.1 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.2 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 5.72 5.72 18.27 0.00 0.00 Roof Cond 0.00 -0.56 15.18
Glass Solar 8.00 0.00 8.00 25.55 8.18 48.92 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.40 0.00 1.40 4.47 1.37 8.19 Glass/Door Cond -0.42 -0.42 11.38
Cooling Heating
Wall Cond 1.19 1.33 2.52 8.05 1.07 6.40 Wall Cond -0.14 -0.29 7.86
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,637 491
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,637 491
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,637 491
Infiltration 2.47 2.47 7.89 0.50 2.99 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 13.06 7.05 20.11 64.23 11.12 66.51 Sub Total ==> -0.56 -1.27 34.42 Nom Vent 132 0
AHU Vent 132 0
Internal Loads Internal Loads Infil 65 0
Lights 2.32 0.58 2.90 9.26 2.32 13.88 Lights 0.00 0.00 0.00 MinStop/Rh 491 491
People 6.05 0 6 19.32 3.30 19.74 People 0.00 0 0.00 Return 1,701 491
Misc 0.00 0.00 0.00 0.00 0.00 0.00 Misc 0.00 0.00 0.00 Exhaust 197 0
Sub Total ==> 8.37 0.58 8.95 28.59 5.62 33.61 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 -0.02 -0.12 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 1.67 5.33 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.02 -0.02 -0.06 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.60 1.92 RA Preheat Diff. -1.49 40.38 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -1.54 41.73 % OA 8.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.61 -16.53 Lps/m² 6.95 2.09
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.24
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.51
W/m² 133.04 -9.09
Grand Total ==> 21.47 7.57 31.31 100.00 16.72 100.00 Grand Total ==> -0.60 -3.69 100.00 No. People 47

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 31.32 25.15 1,636 27.2 21.4 13.8 18.5 16.6 11.1 Floor 235 Main Htg -2.1 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 31.32 Roof 235 0 0 Humidif 0.0 0 0.0 0.0
Wall 248 135 55 Opt Vent 0.0 0 0.0 0.0
Ext Door 56 0 0 Total -2.1

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 282 of 323
Room Checksums
By Trane
T9-phong bac si y ta 10

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 14.37 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 14.07 0.47 22.38 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.80 0.06 2.86 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.38 0.28 13.33 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.22 0.22 6.59 0.06 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.58 1.71 51.20 0.97 46.19 Sub Total ==> -0.16 -0.22 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.08 0.22 10.48 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.45 0 0 13.47 0.25 11.90 People 0.00 0 0.00 Return 325 96
Misc 0.54 0.00 0.54 16.17 0.54 25.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 37.72 1.01 48.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.59 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.46 4.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.62
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.61
W/m² 151.14 -21.14
Grand Total ==> 2.46 0.40 3.34 100.00 2.10 100.00 Grand Total ==> -0.16 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.75 320 27.1 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 283 of 323
Room Checksums
By Trane
T9-phong bac si y ta 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 14.37 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 14.07 0.47 22.38 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.80 0.06 2.86 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.38 0.28 13.33 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.22 0.22 6.59 0.06 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.58 1.71 51.20 0.97 46.19 Sub Total ==> -0.16 -0.22 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.08 0.22 10.48 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.45 0 0 13.47 0.25 11.90 People 0.00 0 0.00 Return 325 96
Misc 0.54 0.00 0.54 16.17 0.54 25.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 37.72 1.01 48.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.59 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.46 4.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.62
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.61
W/m² 151.14 -21.14
Grand Total ==> 2.46 0.40 3.34 100.00 2.10 100.00 Grand Total ==> -0.16 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.75 320 27.1 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 284 of 323
Room Checksums
By Trane
T9-phong bac si y ta 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 14.37 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 14.07 0.47 22.38 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.80 0.06 2.86 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.38 0.28 13.33 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.22 0.22 6.59 0.06 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.58 1.71 51.20 0.97 46.19 Sub Total ==> -0.16 -0.22 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.08 0.22 10.48 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.45 0 0 13.47 0.25 11.90 People 0.00 0 0.00 Return 325 96
Misc 0.54 0.00 0.54 16.17 0.54 25.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 37.72 1.01 48.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.59 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.46 4.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.62
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.61
W/m² 151.14 -21.14
Grand Total ==> 2.46 0.40 3.34 100.00 2.10 100.00 Grand Total ==> -0.16 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.75 320 27.1 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 285 of 323
Room Checksums
By Trane
T9-phong bac si y ta 8

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 14.37 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 14.07 0.47 22.38 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.80 0.06 2.86 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.38 0.28 13.33 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.22 0.22 6.59 0.06 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.58 1.71 51.20 0.97 46.19 Sub Total ==> -0.16 -0.22 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.08 0.22 10.48 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.45 0 0 13.47 0.25 11.90 People 0.00 0 0.00 Return 325 96
Misc 0.54 0.00 0.54 16.17 0.54 25.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 37.72 1.01 48.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.59 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.46 4.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.62
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.61
W/m² 151.14 -21.14
Grand Total ==> 2.46 0.40 3.34 100.00 2.10 100.00 Grand Total ==> -0.16 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.75 320 27.1 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 286 of 323
Room Checksums
By Trane
T9-phong bac si y ta 9

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 14.37 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 14.07 0.47 22.38 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.80 0.06 2.86 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.38 0.28 13.33 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.10 0.10 2.99 0.10 4.76 Partition/Door -0.13 -0.13 0.00 Diffuser 320 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 320 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 320 96
Infiltration 0.22 0.22 6.59 0.06 2.86 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.58 1.71 51.20 0.97 46.19 Sub Total ==> -0.16 -0.22 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.08 0.22 10.48 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.45 0 0 13.47 0.25 11.90 People 0.00 0 0.00 Return 325 96
Misc 0.54 0.00 0.54 16.17 0.54 25.71 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 37.72 1.01 48.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.71 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.78 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.29 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.59 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.46 4.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 95.62
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.61
W/m² 151.14 -21.14
Grand Total ==> 2.46 0.40 3.34 100.00 2.10 100.00 Grand Total ==> -0.16 -0.76 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.34 2.75 320 27.1 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.34 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 287 of 323
Room Checksums
By Trane
T9-phong bac si, y ta 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.77 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.67 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.40 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.23 0.07 0.30 8.98 0.23 11.06 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.08 0.08 2.40 0.08 3.85 Partition/Door -0.16 -0.16 0.00 Diffuser 269 81
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 269 81
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 269 81
Infiltration 0.26 0.26 7.78 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.63 1.74 52.10 0.91 43.75 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.05 0.27 8.08 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 81 81
People 0.36 0 0 10.78 0.19 9.13 People 0.00 0 0.00 Return 275 81
Misc 0.67 0.00 0.67 20.06 0.67 32.21 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.25 0.05 1.30 38.92 1.08 51.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.33 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 8.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 12.18 3.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.59
W/m² 151.62 -20.93
Grand Total ==> 2.45 0.52 3.34 100.00 2.08 100.00 Grand Total ==> -0.20 -0.70 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.35 2.81 269 27.3 20.3 12.2 18.5 17.1 11.7 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.35 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 288 of 323
Room Checksums
By Trane
T9-phong bac si, y ta 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.77 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.67 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.40 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.23 0.07 0.30 8.98 0.23 11.06 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.08 0.08 2.40 0.08 3.85 Partition/Door -0.16 -0.16 0.00 Diffuser 269 81
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 269 81
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 269 81
Infiltration 0.26 0.26 7.78 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.63 1.74 52.10 0.91 43.75 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.05 0.27 8.08 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 81 81
People 0.36 0 0 10.78 0.19 9.13 People 0.00 0 0.00 Return 275 81
Misc 0.67 0.00 0.67 20.06 0.67 32.21 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.25 0.05 1.30 38.92 1.08 51.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.33 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 8.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 12.18 3.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.59
W/m² 151.62 -20.93
Grand Total ==> 2.45 0.52 3.34 100.00 2.08 100.00 Grand Total ==> -0.20 -0.70 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.35 2.81 269 27.3 20.3 12.2 18.5 17.1 11.7 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.35 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 289 of 323
Room Checksums
By Trane
T9-phong bac si, y ta 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.77 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.67 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.40 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.23 0.07 0.30 8.98 0.23 11.06 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.08 0.08 2.40 0.08 3.85 Partition/Door -0.16 -0.16 0.00 Diffuser 269 81
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 269 81
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 269 81
Infiltration 0.26 0.26 7.78 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.63 1.74 52.10 0.91 43.75 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.05 0.27 8.08 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 81 81
People 0.36 0 0 10.78 0.19 9.13 People 0.00 0 0.00 Return 275 81
Misc 0.67 0.00 0.67 20.06 0.67 32.21 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.25 0.05 1.30 38.92 1.08 51.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.33 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 8.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 12.18 3.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.59
W/m² 151.62 -20.93
Grand Total ==> 2.45 0.52 3.34 100.00 2.08 100.00 Grand Total ==> -0.20 -0.70 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.35 2.81 269 27.3 20.3 12.2 18.5 17.1 11.7 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.35 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 290 of 323
Room Checksums
By Trane
T9-phong bac si, y ta 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.77 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.67 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.40 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.23 0.07 0.30 8.98 0.23 11.06 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.08 0.08 2.40 0.08 3.85 Partition/Door -0.16 -0.16 0.00 Diffuser 269 81
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 269 81
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 269 81
Infiltration 0.26 0.26 7.78 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.63 1.74 52.10 0.91 43.75 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.05 0.27 8.08 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 81 81
People 0.36 0 0 10.78 0.19 9.13 People 0.00 0 0.00 Return 275 81
Misc 0.67 0.00 0.67 20.06 0.67 32.21 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.25 0.05 1.30 38.92 1.08 51.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.33 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 8.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 12.18 3.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.59
W/m² 151.62 -20.93
Grand Total ==> 2.45 0.52 3.34 100.00 2.08 100.00 Grand Total ==> -0.20 -0.70 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.35 2.81 269 27.3 20.3 12.2 18.5 17.1 11.7 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.35 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 291 of 323
Room Checksums
By Trane
T9-phong bac si, y ta 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.77 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.67 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.50 0.05 2.40 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.23 0.07 0.30 8.98 0.23 11.06 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.08 0.08 2.40 0.08 3.85 Partition/Door -0.16 -0.16 0.00 Diffuser 269 81
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 269 81
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 269 81
Infiltration 0.26 0.26 7.78 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.11 0.63 1.74 52.10 0.91 43.75 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.05 0.27 8.08 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 81 81
People 0.36 0 0 10.78 0.19 9.13 People 0.00 0 0.00 Return 275 81
Misc 0.67 0.00 0.67 20.06 0.67 32.21 Misc 0.00 0.00 0.00 Exhaust 25 0
Sub Total ==> 1.25 0.05 1.30 38.92 1.08 51.92 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 4.33 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 8.08 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.07 -0.07 -2.10 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.99 RA Preheat Diff. -0.24 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.25 0.00 % OA 7.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 12.18 3.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 80.26
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.59
W/m² 151.62 -20.93
Grand Total ==> 2.45 0.52 3.34 100.00 2.08 100.00 Grand Total ==> -0.20 -0.70 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.35 2.81 269 27.3 20.3 12.2 18.5 17.1 11.7 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.35 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 292 of 323
Room Checksums
By Trane
T9-phong bang ca

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.67 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.58 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.79 0.06 2.88 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.24 0.07 0.31 9.23 0.24 11.54 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.12 0.12 3.57 0.12 5.77 Partition/Door -0.16 -0.16 0.00 Diffuser 319 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 319 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 319 96
Infiltration 0.22 0.22 6.55 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.63 1.76 52.38 0.97 46.63 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.04 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.44 0 0 13.10 0.24 11.54 People 0.00 0 0.00 Return 323 96
Misc 0.52 0.00 0.52 15.48 0.52 25.00 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.18 0.05 1.23 36.61 0.98 47.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 6.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.37 11.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -3.57 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.57 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.41 4.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.54
W/m² 152.74 -23.04
Grand Total ==> 2.44 0.43 3.36 100.00 2.08 100.00 Grand Total ==> -0.20 -0.80 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.38 2.78 319 27.3 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.38 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 293 of 323
Room Checksums
By Trane
T9-phong benh nhan 1

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.43 0.43 15.75 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.49 0.00 0.49 17.95 0.53 30.29 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.83 0.04 2.29 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.13 0.05 0.18 6.59 0.12 6.86 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.10 0.03 1.71 Partition/Door -0.07 -0.07 0.00 Diffuser 226 68
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 226 68
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 226 68
Infiltration 0.20 0.20 7.33 0.04 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.90 0.48 1.38 50.55 0.76 43.43 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.13 0.11 6.29 Lights 0.00 0.00 0.00 MinStop/Rh 68 68
People 0.22 0 0 8.06 0.12 6.86 People 0.00 0 0.00 Return 230 68
Misc 0.70 0.00 0.70 25.64 0.70 40.00 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 38.83 0.93 53.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.06 3.43 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 9.89 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.93 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.36 4.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.22
W/m² 160.78 -26.21
Grand Total ==> 2.00 0.38 2.73 100.00 1.75 100.00 Grand Total ==> -0.15 -0.76 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.29 225 27.3 20.4 12.3 18.5 17.2 11.9 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 294 of 323
Room Checksums
By Trane
T9-phong benh nhan 10

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 295 of 323
Room Checksums
By Trane
T9-phong benh nhan 11

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 296 of 323
Room Checksums
By Trane
T9-phong benh nhan 12

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 297 of 323
Room Checksums
By Trane
T9-phong benh nhan 13

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 298 of 323
Room Checksums
By Trane
T9-phong benh nhan 14

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 299 of 323
Room Checksums
By Trane
T9-phong benh nhan 15

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 28 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.54 0.54 11.79 0.00 0.00 Roof Cond 0.00 -0.08 5.13
Glass Solar 1.02 0.00 1.02 22.27 1.17 37.50 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.31 0.04 1.28 Glass/Door Cond -0.04 -0.04 2.56
Cooling Heating
Wall Cond 0.50 0.19 0.69 15.07 0.50 16.03 Wall Cond -0.07 -0.09 5.77
Partition/Door 0.13 0.13 2.84 0.13 4.17 Partition/Door -0.32 -0.32 20.51 Diffuser 403 121
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 403 121
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 403 121
Infiltration 0.29 0.29 6.33 0.04 1.28 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.00 0.73 2.73 59.61 1.88 60.26 Sub Total ==> -0.43 -0.53 33.97 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 9 0
Lights 0.21 0.05 0.26 5.68 0.21 6.73 Lights 0.00 0.00 0.00 MinStop/Rh 121 121
People 0.44 0 0 9.61 0.24 7.69 People 0.00 0 0.00 Return 412 121
Misc 0.70 0.00 0.70 15.28 0.70 22.44 Misc 0.00 0.00 0.00 Exhaust 46 0
Sub Total ==> 1.35 0.05 1.40 30.57 1.15 36.86 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.09 2.88 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.40 8.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -1.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.14 3.06 RA Preheat Diff. -0.37 23.72 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.53 33.97 % OA 9.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.13 8.33 Lps/m² 12.13 3.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 87.87
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.24
W/m² 137.96 -30.98
Grand Total ==> 3.45 0.59 4.58 100.00 3.12 100.00 Grand Total ==> -0.50 -1.56 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.58 3.85 388 26.7 20.2 12.2 18.5 17.1 11.7 Floor 33 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.58 Roof 33 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 300 of 323
Room Checksums
By Trane
T9-phong benh nhan 16

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 28 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.54 0.54 11.79 0.00 0.00 Roof Cond 0.00 -0.08 5.13
Glass Solar 1.02 0.00 1.02 22.27 1.17 37.50 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.31 0.04 1.28 Glass/Door Cond -0.04 -0.04 2.56
Cooling Heating
Wall Cond 0.50 0.19 0.69 15.07 0.50 16.03 Wall Cond -0.07 -0.09 5.77
Partition/Door 0.13 0.13 2.84 0.13 4.17 Partition/Door -0.32 -0.32 20.51 Diffuser 403 121
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 403 121
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 403 121
Infiltration 0.29 0.29 6.33 0.04 1.28 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.00 0.73 2.73 59.61 1.88 60.26 Sub Total ==> -0.43 -0.53 33.97 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 9 0
Lights 0.21 0.05 0.26 5.68 0.21 6.73 Lights 0.00 0.00 0.00 MinStop/Rh 121 121
People 0.44 0 0 9.61 0.24 7.69 People 0.00 0 0.00 Return 412 121
Misc 0.70 0.00 0.70 15.28 0.70 22.44 Misc 0.00 0.00 0.00 Exhaust 46 0
Sub Total ==> 1.35 0.05 1.40 30.57 1.15 36.86 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.09 2.88 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.40 8.73 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.09 -0.09 -1.97 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.14 3.06 RA Preheat Diff. -0.37 23.72 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.53 33.97 % OA 9.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.13 8.33 Lps/m² 12.13 3.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 87.87
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.24
W/m² 137.96 -30.98
Grand Total ==> 3.45 0.59 4.58 100.00 3.12 100.00 Grand Total ==> -0.50 -1.56 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.58 3.85 388 26.7 20.2 12.2 18.5 17.1 11.7 Floor 33 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.58 Roof 33 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 301 of 323
Room Checksums
By Trane
T9-phong benh nhan 17

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 9 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.1 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.72 0.72 13.43 0.00 0.00 Roof Cond 0.00 -0.08 4.55
Glass Solar 0.93 0.00 0.93 17.35 1.09 32.06 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.10 0.00 0.10 1.87 0.07 2.06 Glass/Door Cond -0.04 -0.04 2.27
Cooling Heating
Wall Cond 0.85 0.26 1.11 20.71 0.82 24.12 Wall Cond -0.17 -0.21 11.93
Partition/Door 0.13 0.13 2.43 0.13 3.82 Partition/Door -0.32 -0.32 18.18 Diffuser 440 132
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 440 132
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 440 132
Infiltration 0.40 0.40 7.46 0.08 2.35 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.41 0.98 3.39 63.25 2.19 64.41 Sub Total ==> -0.53 -0.65 36.93 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 9 0
Lights 0.21 0.05 0.26 4.85 0.19 5.59 Lights 0.00 0.00 0.00 MinStop/Rh 132 132
People 0.44 0 0 8.21 0.23 6.76 People 0.00 0 0.00 Return 449 132
Misc 0.70 0.00 0.70 13.06 0.68 20.00 Misc 0.00 0.00 0.00 Exhaust 46 0
Sub Total ==> 1.35 0.05 1.40 26.12 1.10 32.35 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 3.24 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.52 9.70 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -2.05 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.16 2.99 RA Preheat Diff. -0.40 22.73 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.58 32.95 % OA 8.4 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.13 7.39 Lps/m² 13.26 3.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.20
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.20
W/m² 161.21 -35.39
Grand Total ==> 3.87 0.81 5.36 100.00 3.40 100.00 Grand Total ==> -0.60 -1.76 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.35 4.52 436 27.1 20.3 12.3 18.5 17.1 11.7 Floor 33 Main Htg -1.2 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.35 Roof 33 0 0 Humidif 0.0 0 0.0 0.0
Wall 59 5 9 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.2

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 302 of 323
Room Checksums
By Trane
T9-phong benh nhan 18

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.68 0.68 13.74 0.00 0.00 Roof Cond 0.00 -0.08 5.13
Glass Solar 1.07 0.00 1.07 21.62 1.07 34.52 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.09 0.00 0.09 1.82 0.09 2.90 Glass/Door Cond -0.04 -0.04 2.56
Cooling Heating
Wall Cond 0.50 0.19 0.69 13.94 0.50 16.13 Wall Cond -0.07 -0.09 5.77
Partition/Door 0.13 0.13 2.63 0.13 4.19 Partition/Door -0.32 -0.32 20.51 Diffuser 402 121
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 402 121
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 402 121
Infiltration 0.39 0.39 7.88 0.10 3.23 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.18 0.87 3.05 61.62 1.89 60.97 Sub Total ==> -0.43 -0.53 33.97 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 9 0
Lights 0.19 0.05 0.24 4.85 0.19 6.13 Lights 0.00 0.00 0.00 MinStop/Rh 121 121
People 0.43 0 0 8.69 0.23 7.42 People 0.00 0 0.00 Return 411 121
Misc 0.68 0.00 0.68 13.74 0.68 21.94 Misc 0.00 0.00 0.00 Exhaust 46 0
Sub Total ==> 1.30 0.05 1.35 27.27 1.10 35.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 3.55 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.51 10.30 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -2.22 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.15 3.03 RA Preheat Diff. -0.37 23.72 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.53 33.97 % OA 9.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.13 8.33 Lps/m² 12.11 3.63
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.06
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.69
W/m² 149.33 -30.96
Grand Total ==> 3.59 0.70 4.95 100.00 3.10 100.00 Grand Total ==> -0.50 -1.56 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.96 4.12 402 27.0 20.3 12.3 18.5 17.1 11.7 Floor 33 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.96 Roof 33 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 303 of 323
Room Checksums
By Trane
T9-phong benh nhan 19

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 14 Mo/Hr: 8 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.68 0.68 13.74 0.00 0.00 Roof Cond 0.00 -0.08 5.13
Glass Solar 1.07 0.00 1.07 21.62 1.07 34.52 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.09 0.00 0.09 1.82 0.09 2.90 Glass/Door Cond -0.04 -0.04 2.56
Cooling Heating
Wall Cond 0.50 0.19 0.69 13.94 0.50 16.13 Wall Cond -0.07 -0.09 5.77
Partition/Door 0.13 0.13 2.63 0.13 4.19 Partition/Door -0.32 -0.32 20.51 Diffuser 402 121
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 402 121
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 402 121
Infiltration 0.39 0.39 7.88 0.10 3.23 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 2.18 0.87 3.05 61.62 1.89 60.97 Sub Total ==> -0.43 -0.53 33.97 Nom Vent 37 0
AHU Vent 37 0
Internal Loads Internal Loads Infil 9 0
Lights 0.19 0.05 0.24 4.85 0.19 6.13 Lights 0.00 0.00 0.00 MinStop/Rh 121 121
People 0.43 0 0 8.69 0.23 7.42 People 0.00 0 0.00 Return 411 121
Misc 0.68 0.00 0.68 13.74 0.68 21.94 Misc 0.00 0.00 0.00 Exhaust 46 0
Sub Total ==> 1.30 0.05 1.35 27.27 1.10 35.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 3.55 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.51 10.30 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -2.22 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.15 3.03 RA Preheat Diff. -0.37 23.72 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.53 33.97 % OA 9.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.13 8.33 Lps/m² 12.11 3.63
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.06
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.69
W/m² 149.33 -30.96
Grand Total ==> 3.59 0.70 4.95 100.00 3.10 100.00 Grand Total ==> -0.50 -1.56 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 4.96 4.12 402 27.0 20.3 12.3 18.5 17.1 11.7 Floor 33 Main Htg -1.0 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.96 Roof 33 0 0 Humidif 0.0 0 0.0 0.0
Wall 30 5 18 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -1.0

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 304 of 323
Room Checksums
By Trane
T9-phong benh nhan 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.43 0.43 15.75 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.49 0.00 0.49 17.95 0.53 30.29 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.83 0.04 2.29 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.13 0.05 0.18 6.59 0.12 6.86 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.10 0.03 1.71 Partition/Door -0.07 -0.07 0.00 Diffuser 226 68
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 226 68
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 226 68
Infiltration 0.20 0.20 7.33 0.04 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.90 0.48 1.38 50.55 0.76 43.43 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.13 0.11 6.29 Lights 0.00 0.00 0.00 MinStop/Rh 68 68
People 0.22 0 0 8.06 0.12 6.86 People 0.00 0 0.00 Return 230 68
Misc 0.70 0.00 0.70 25.64 0.70 40.00 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 38.83 0.93 53.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.06 3.43 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 9.89 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.93 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.36 4.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.22
W/m² 160.78 -26.21
Grand Total ==> 2.00 0.38 2.73 100.00 1.75 100.00 Grand Total ==> -0.15 -0.76 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.29 225 27.3 20.4 12.3 18.5 17.2 11.9 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 305 of 323
Room Checksums
By Trane
T9-phong benh nhan 3

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.43 0.43 15.75 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.49 0.00 0.49 17.95 0.53 30.29 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.83 0.04 2.29 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.13 0.05 0.18 6.59 0.12 6.86 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.10 0.03 1.71 Partition/Door -0.07 -0.07 0.00 Diffuser 226 68
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 226 68
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 226 68
Infiltration 0.20 0.20 7.33 0.04 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.90 0.48 1.38 50.55 0.76 43.43 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.13 0.11 6.29 Lights 0.00 0.00 0.00 MinStop/Rh 68 68
People 0.22 0 0 8.06 0.12 6.86 People 0.00 0 0.00 Return 230 68
Misc 0.70 0.00 0.70 25.64 0.70 40.00 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 38.83 0.93 53.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.06 3.43 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 9.89 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.93 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.36 4.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.22
W/m² 160.78 -26.21
Grand Total ==> 2.00 0.38 2.73 100.00 1.75 100.00 Grand Total ==> -0.15 -0.76 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.29 225 27.3 20.4 12.3 18.5 17.2 11.9 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 306 of 323
Room Checksums
By Trane
T9-phong benh nhan 4

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.43 0.43 15.75 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.49 0.00 0.49 17.95 0.53 30.29 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.83 0.04 2.29 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.13 0.05 0.18 6.59 0.12 6.86 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.10 0.03 1.71 Partition/Door -0.07 -0.07 0.00 Diffuser 226 68
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 226 68
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 226 68
Infiltration 0.20 0.20 7.33 0.04 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.90 0.48 1.38 50.55 0.76 43.43 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.13 0.11 6.29 Lights 0.00 0.00 0.00 MinStop/Rh 68 68
People 0.22 0 0 8.06 0.12 6.86 People 0.00 0 0.00 Return 230 68
Misc 0.70 0.00 0.70 25.64 0.70 40.00 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 38.83 0.93 53.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.06 3.43 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 9.89 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.93 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.36 4.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.22
W/m² 160.78 -26.21
Grand Total ==> 2.00 0.38 2.73 100.00 1.75 100.00 Grand Total ==> -0.15 -0.76 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.29 225 27.3 20.4 12.3 18.5 17.2 11.9 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 307 of 323
Room Checksums
By Trane
T9-phong benh nhan 5

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 32 OADB: 19 SADB 18.8 22.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.43 0.43 15.75 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.49 0.00 0.49 17.95 0.53 30.29 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.83 0.04 2.29 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.13 0.05 0.18 6.59 0.12 6.86 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.10 0.03 1.71 Partition/Door -0.07 -0.07 0.00 Diffuser 226 68
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 226 68
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 226 68
Infiltration 0.20 0.20 7.33 0.04 2.29 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.90 0.48 1.38 50.55 0.76 43.43 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.13 0.11 6.29 Lights 0.00 0.00 0.00 MinStop/Rh 68 68
People 0.22 0 0 8.06 0.12 6.86 People 0.00 0 0.00 Return 230 68
Misc 0.70 0.00 0.70 25.64 0.70 40.00 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 38.83 0.93 53.14 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.06 3.43 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.27 9.89 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.06 -0.06 -2.20 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.93 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 8.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.36 4.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 83.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.22
W/m² 160.78 -26.21
Grand Total ==> 2.00 0.38 2.73 100.00 1.75 100.00 Grand Total ==> -0.15 -0.76 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.72 2.29 225 27.3 20.4 12.3 18.5 17.2 11.9 Floor 17 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.72 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 308 of 323
Room Checksums
By Trane
T9-phong benh nhan 6

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 21 Mo/Hr: 11 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 25 / 20 OADB: 28 OADB: 19 SADB 18.8 22.0
Ra Plenum 27.7 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.7 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.38 0.38 11.21 0.00 0.00 Roof Cond 0.00 -0.04 3.88
Glass Solar 0.35 0.00 0.35 10.32 0.38 16.59 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.02 0.00 0.02 0.59 0.02 0.87 Glass/Door Cond -0.02 -0.02 1.94
Cooling Heating
Wall Cond 1.01 0.30 1.31 38.64 0.99 43.23 Wall Cond -0.13 -0.15 14.56
Partition/Door 0.03 0.03 0.88 0.03 1.31 Partition/Door -0.07 -0.07 6.80 Diffuser 295 88
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 295 88
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 295 88
Infiltration 0.08 0.08 2.36 0.01 0.44 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.49 0.68 2.17 64.01 1.43 62.45 Sub Total ==> -0.22 -0.28 27.18 Nom Vent 11 0
AHU Vent 11 0
Internal Loads Internal Loads Infil 3 0
Lights 0.16 0.04 0.20 5.90 0.15 6.55 Lights 0.00 0.00 0.00 MinStop/Rh 88 88
People 0.15 0 0 4.42 0.10 4.37 People 0.00 0 0.00 Return 297 88
Misc 0.50 0.00 0.50 14.75 0.53 23.14 Misc 0.00 0.00 0.00 Exhaust 14 0
Sub Total ==> 0.81 0.04 0.85 25.07 0.78 34.06 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.08 -0.08 0.00 0.00 0.08 3.49 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.31 9.14 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.47 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.11 3.24 RA Preheat Diff. -0.27 26.21 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.39 37.86 % OA 3.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.09 8.74 Lps/m² 17.43 5.23
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 86.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.98
W/m² 200.85 -37.31
Grand Total ==> 2.38 0.59 3.39 100.00 2.29 100.00 Grand Total ==> -0.25 -1.03 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.40 2.99 291 27.6 20.5 12.3 18.5 17.5 12.2 Floor 17 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.40 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 42 3 7 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 309 of 323
Room Checksums
By Trane
T9-phong benh nhan 7

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 310 of 323
Room Checksums
By Trane
T9-phong benh nhan 8

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 311 of 323
Room Checksums
By Trane
T9-phong benh nhan 9

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 11 / 17 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 19 SADB 18.8 22.0
Ra Plenum 26.6 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.6 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 26.7 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.28 0.28 10.94 0.00 0.00 Roof Cond 0.00 -0.04 0.00
Glass Solar 0.51 0.00 0.51 19.92 0.62 34.07 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 1.17 0.02 1.10 Glass/Door Cond -0.02 -0.02 0.00
Cooling Heating
Wall Cond 0.19 0.08 0.27 10.55 0.16 8.79 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.03 0.03 1.17 0.03 1.65 Partition/Door -0.07 -0.07 0.00 Diffuser 236 71
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 236 71
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 236 71
Infiltration 0.15 0.15 5.86 0.02 1.10 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.91 0.36 1.27 49.61 0.85 46.70 Sub Total ==> -0.12 -0.17 0.00 Nom Vent 19 0
AHU Vent 19 0
Internal Loads Internal Loads Infil 5 0
Lights 0.11 0.03 0.14 5.47 0.11 6.04 Lights 0.00 0.00 0.00 MinStop/Rh 71 71
People 0.22 0 0 8.59 0.12 6.59 People 0.00 0 0.00 Return 240 71
Misc 0.70 0.00 0.70 27.34 0.70 38.46 Misc 0.00 0.00 0.00 Exhaust 23 0
Sub Total ==> 1.03 0.03 1.06 41.41 0.93 51.10 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.05 -0.05 0.00 0.00 0.04 2.20 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.20 7.81 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.05 -0.05 -1.95 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 3.13 RA Preheat Diff. -0.21 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.31 0.00 % OA 8.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 0.00 Lps/m² 13.94 4.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 92.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.34 -26.98
Grand Total ==> 1.99 0.29 2.56 100.00 1.82 100.00 Grand Total ==> -0.15 -0.77 100.00 No. People 2

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 2.56 2.19 228 26.7 20.1 12.2 18.5 17.2 11.9 Floor 17 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 6 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.56 Roof 17 0 0 Humidif 0.0 0 0.0 0.0
Wall 12 3 22 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 312 of 323
Room Checksums
By Trane
T9-phong bo bot chinh hinh

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.67 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.58 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.79 0.06 2.88 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.24 0.07 0.31 9.23 0.24 11.54 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.12 0.12 3.57 0.12 5.77 Partition/Door -0.16 -0.16 0.00 Diffuser 319 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 319 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 319 96
Infiltration 0.22 0.22 6.55 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.63 1.76 52.38 0.97 46.63 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.04 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.44 0 0 13.10 0.24 11.54 People 0.00 0 0.00 Return 323 96
Misc 0.52 0.00 0.52 15.48 0.52 25.00 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.18 0.05 1.23 36.61 0.98 47.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 6.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.37 11.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -3.57 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.57 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.41 4.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.54
W/m² 152.74 -23.04
Grand Total ==> 2.44 0.43 3.36 100.00 2.08 100.00 Grand Total ==> -0.20 -0.80 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.38 2.78 319 27.3 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.38 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 313 of 323
Room Checksums
By Trane
T9-phong dieu tri

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 13.99 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 13.70 0.47 21.46 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.75 0.06 2.74 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.08 0.28 12.79 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 5.54 0.19 8.68 Partition/Door -0.26 -0.26 0.00 Diffuser 335 100
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 335 100
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 335 100
Infiltration 0.22 0.22 6.41 0.06 2.74 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.22 0.58 1.80 52.48 1.06 48.40 Sub Total ==> -0.29 -0.35 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 7.87 0.22 10.05 Lights 0.00 0.00 0.00 MinStop/Rh 100 100
People 0.45 0 0 13.12 0.25 11.42 People 0.00 0 0.00 Return 339 100
Misc 0.54 0.00 0.54 15.74 0.54 24.66 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 36.73 1.01 46.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.48 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.50 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.21 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.50 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 0.00 % OA 7.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 15.14 4.54
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.42
W/m² 155.79 -27.65
Grand Total ==> 2.55 0.40 3.43 100.00 2.19 100.00 Grand Total ==> -0.29 -0.92 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.44 2.85 335 27.0 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.44 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 314 of 323
Room Checksums
By Trane
T9-phong giao ban SHK

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 7 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.4 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 10.87 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 9.13 0.47 16.04 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 0.97 0.05 1.71 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.77 0.22 0.99 19.22 0.77 26.28 Wall Cond -0.09 -0.12 0.00
Partition/Door 0.08 0.08 1.55 0.08 2.73 Partition/Door -0.16 -0.16 0.00 Diffuser 379 114
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 379 114
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 379 114
Infiltration 0.27 0.27 5.24 0.06 2.05 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.64 0.78 2.42 46.99 1.43 48.81 Sub Total ==> -0.26 -0.34 0.00 Nom Vent 61 0
AHU Vent 61 0
Internal Loads Internal Loads Infil 6 0
Lights 0.22 0.05 0.27 5.24 0.22 7.51 Lights 0.00 0.00 0.00 MinStop/Rh 114 114
People 0.95 0 1 18.45 0.52 17.75 People 0.00 0 0.00 Return 385 114
Misc 0.67 0.00 0.67 13.01 0.67 22.87 Misc 0.00 0.00 0.00 Exhaust 67 0
Sub Total ==> 1.84 0.05 1.89 36.70 1.41 48.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.09 -0.09 0.00 0.00 0.09 3.07 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.88 17.09 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.18 -0.18 -3.50 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.14 2.72 RA Preheat Diff. -0.34 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.36 0.00 % OA 16.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.06 0.00 Lps/m² 17.15 5.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.39
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.28
W/m² 233.58 -28.30
Grand Total ==> 3.57 0.56 5.15 100.00 2.93 100.00 Grand Total ==> -0.26 -0.98 100.00 No. People 7

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 5.16 3.93 379 27.4 20.6 12.5 18.5 17.1 11.7 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.16 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 48 3 6 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 315 of 323
Room Checksums
By Trane
T9-phong giao ban SHK 2

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 15 Mo/Hr: 7 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 29 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 12.09 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.45 0.00 0.45 11.34 0.45 17.58 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 1.26 0.05 1.95 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.78 0.21 0.99 24.94 0.78 30.47 Wall Cond -0.08 -0.11 0.00
Partition/Door 0.10 0.10 2.52 0.10 3.91 Partition/Door -0.13 -0.13 0.00 Diffuser 393 118
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 393 118
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 393 118
Infiltration 0.23 0.23 5.79 0.06 2.34 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.61 0.69 2.30 57.93 1.44 56.25 Sub Total ==> -0.22 -0.30 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 6.80 0.22 8.59 Lights 0.00 0.00 0.00 MinStop/Rh 118 118
People 0.45 0 0 11.34 0.25 9.77 People 0.00 0 0.00 Return 398 118
Misc 0.54 0.00 0.54 13.60 0.54 21.09 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 31.74 1.01 39.45 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 4.30 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.38 9.57 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -2.77 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.14 3.53 RA Preheat Diff. -0.36 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.37 0.00 % OA 6.2 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.06 0.00 Lps/m² 17.80 5.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 98.76
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.55
W/m² 180.13 -26.97
Grand Total ==> 2.93 0.52 3.97 100.00 2.56 100.00 Grand Total ==> -0.22 -0.97 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.98 3.37 393 27.0 19.7 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 15 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.98 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 44 3 6 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 316 of 323
Room Checksums
By Trane
T9-phong ky thuat

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 13.99 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 13.70 0.47 21.46 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.75 0.06 2.74 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.08 0.28 12.79 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 5.54 0.19 8.68 Partition/Door -0.26 -0.26 0.00 Diffuser 335 100
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 335 100
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 335 100
Infiltration 0.22 0.22 6.41 0.06 2.74 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.22 0.58 1.80 52.48 1.06 48.40 Sub Total ==> -0.29 -0.35 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 7.87 0.22 10.05 Lights 0.00 0.00 0.00 MinStop/Rh 100 100
People 0.45 0 0 13.12 0.25 11.42 People 0.00 0 0.00 Return 339 100
Misc 0.54 0.00 0.54 15.74 0.54 24.66 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 36.73 1.01 46.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.48 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.50 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.21 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.50 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 0.00 % OA 7.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 15.14 4.54
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.42
W/m² 155.79 -27.65
Grand Total ==> 2.55 0.40 3.43 100.00 2.19 100.00 Grand Total ==> -0.29 -0.92 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.44 2.85 335 27.0 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.44 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 317 of 323
Room Checksums
By Trane
T9-phong thay do nam

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.29 0.29 17.06 0.00 0.00 Roof Cond 0.00 -0.03 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 7.65 0.13 12.04 Partition/Door -0.26 -0.26 0.00 Diffuser 141 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 141 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 141 42
Infiltration 0.13 0.13 7.65 0.03 2.78 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.26 0.29 0.55 32.35 0.16 14.81 Sub Total ==> -0.26 -0.29 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 8.24 0.11 10.19 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.18 0 0 10.59 0.10 9.26 People 0.00 0 0.00 Return 144 42
Misc 0.67 0.00 0.67 39.41 0.67 62.04 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.96 0.03 0.99 58.24 0.88 81.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.70 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 8.24 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.94 RA Preheat Diff. -0.13 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.13 0.00 % OA 6.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 0.00 Lps/m² 12.54 3.76
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.75
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.47 -35.16
Grand Total ==> 1.26 0.25 1.70 100.00 1.08 100.00 Grand Total ==> -0.26 -0.53 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.70 1.42 141 27.3 20.3 12.2 18.5 17.2 11.9 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.70 Roof 11 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 318 of 323
Room Checksums
By Trane
T9-phong thay do nu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.29 0.29 17.06 0.00 0.00 Roof Cond 0.00 -0.03 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.13 0.13 7.65 0.13 12.04 Partition/Door -0.26 -0.26 0.00 Diffuser 141 42
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 141 42
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 141 42
Infiltration 0.13 0.13 7.65 0.03 2.78 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 0.26 0.29 0.55 32.35 0.16 14.81 Sub Total ==> -0.26 -0.29 0.00 Nom Vent 10 0
AHU Vent 10 0
Internal Loads Internal Loads Infil 3 0
Lights 0.11 0.03 0.14 8.24 0.11 10.19 Lights 0.00 0.00 0.00 MinStop/Rh 42 42
People 0.18 0 0 10.59 0.10 9.26 People 0.00 0 0.00 Return 144 42
Misc 0.67 0.00 0.67 39.41 0.67 62.04 Misc 0.00 0.00 0.00 Exhaust 13 0
Sub Total ==> 0.96 0.03 0.99 58.24 0.88 81.48 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 3.70 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.14 8.24 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.03 -0.03 -1.76 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.05 2.94 RA Preheat Diff. -0.13 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.13 0.00 % OA 6.9 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.02 0.00 Lps/m² 12.54 3.76
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 82.75
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.60
W/m² 151.47 -35.16
Grand Total ==> 1.26 0.25 1.70 100.00 1.08 100.00 Grand Total ==> -0.26 -0.53 100.00 No. People 1

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 1.70 1.42 141 27.3 20.3 12.2 18.5 17.2 11.9 Floor 11 Main Htg -0.4 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 1.70 Roof 11 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.4

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 319 of 323
Room Checksums
By Trane
T9-phong thua thuat huu khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 13.99 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 13.70 0.47 21.46 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.75 0.06 2.74 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.08 0.28 12.79 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 5.54 0.19 8.68 Partition/Door -0.26 -0.26 0.00 Diffuser 335 100
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 335 100
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 335 100
Infiltration 0.22 0.22 6.41 0.06 2.74 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.22 0.58 1.80 52.48 1.06 48.40 Sub Total ==> -0.29 -0.35 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 7.87 0.22 10.05 Lights 0.00 0.00 0.00 MinStop/Rh 100 100
People 0.45 0 0 13.12 0.25 11.42 People 0.00 0 0.00 Return 339 100
Misc 0.54 0.00 0.54 15.74 0.54 24.66 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 36.73 1.01 46.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.48 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.50 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.21 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.50 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 0.00 % OA 7.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 15.14 4.54
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.42
W/m² 155.79 -27.65
Grand Total ==> 2.55 0.40 3.43 100.00 2.19 100.00 Grand Total ==> -0.29 -0.92 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.44 2.85 335 27.0 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.44 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 320 of 323
Room Checksums
By Trane
T9-phong thua thuat vo khuan

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 34 / 28 / 23 OADB: 34 OADB: 19 SADB 18.8 21.0
Ra Plenum 26.9 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.9 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.0 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.48 0.48 13.99 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.47 0.00 0.47 13.70 0.47 21.46 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.75 0.06 2.74 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.28 0.10 0.38 11.08 0.28 12.79 Wall Cond -0.02 -0.03 0.00
Partition/Door 0.19 0.19 5.54 0.19 8.68 Partition/Door -0.26 -0.26 0.00 Diffuser 335 100
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 335 100
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 335 100
Infiltration 0.22 0.22 6.41 0.06 2.74 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.22 0.58 1.80 52.48 1.06 48.40 Sub Total ==> -0.29 -0.35 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 7.87 0.22 10.05 Lights 0.00 0.00 0.00 MinStop/Rh 100 100
People 0.45 0 0 13.12 0.25 11.42 People 0.00 0 0.00 Return 339 100
Misc 0.54 0.00 0.54 15.74 0.54 24.66 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.21 0.05 1.26 36.73 1.01 46.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 5.48 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.36 10.50 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.11 -0.11 -3.21 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.50 RA Preheat Diff. -0.30 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.32 0.00 % OA 7.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 15.14 4.54
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 97.11
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.42
W/m² 155.79 -27.65
Grand Total ==> 2.55 0.40 3.43 100.00 2.19 100.00 Grand Total ==> -0.29 -0.92 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.44 2.85 335 27.0 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.6 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 30 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.44 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 14 3 19 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.6

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 321 of 323
Room Checksums
By Trane
T9-phong tiem cap cuu

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.67 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.58 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.79 0.06 2.88 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.24 0.07 0.31 9.23 0.24 11.54 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.12 0.12 3.57 0.12 5.77 Partition/Door -0.16 -0.16 0.00 Diffuser 319 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 319 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 319 96
Infiltration 0.22 0.22 6.55 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.63 1.76 52.38 0.97 46.63 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.04 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.44 0 0 13.10 0.24 11.54 People 0.00 0 0.00 Return 323 96
Misc 0.52 0.00 0.52 15.48 0.52 25.00 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.18 0.05 1.23 36.61 0.98 47.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 6.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.37 11.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -3.57 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.57 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.41 4.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.54
W/m² 152.74 -23.04
Grand Total ==> 2.44 0.43 3.36 100.00 2.08 100.00 Grand Total ==> -0.20 -0.80 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.38 2.78 319 27.3 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.38 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 322 of 323
Room Checksums
By Trane
T9-phong tieu phau

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 33 / 28 / 23 OADB: 33 OADB: 19 SADB 18.8 21.0
Ra Plenum 27.2 20.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 27.2 20.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 27.3 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.56 0.56 16.67 0.00 0.00 Roof Cond 0.00 -0.05 0.00
Glass Solar 0.49 0.00 0.49 14.58 0.49 23.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.06 0.00 0.06 1.79 0.06 2.88 Glass/Door Cond -0.01 -0.01 0.00
Cooling Heating
Wall Cond 0.24 0.07 0.31 9.23 0.24 11.54 Wall Cond -0.03 -0.04 0.00
Partition/Door 0.12 0.12 3.57 0.12 5.77 Partition/Door -0.16 -0.16 0.00 Diffuser 319 96
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 319 96
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 319 96
Infiltration 0.22 0.22 6.55 0.06 2.88 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 1.13 0.63 1.76 52.38 0.97 46.63 Sub Total ==> -0.20 -0.26 0.00 Nom Vent 25 0
AHU Vent 25 0
Internal Loads Internal Loads Infil 5 0
Lights 0.22 0.05 0.27 8.04 0.22 10.58 Lights 0.00 0.00 0.00 MinStop/Rh 96 96
People 0.44 0 0 13.10 0.24 11.54 People 0.00 0 0.00 Return 323 96
Misc 0.52 0.00 0.52 15.48 0.52 25.00 Misc 0.00 0.00 0.00 Exhaust 29 0
Sub Total ==> 1.18 0.05 1.23 36.61 0.98 47.12 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 6.25 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.37 11.01 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat -0.12 -0.12 -3.57 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.12 3.57 RA Preheat Diff. -0.29 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat -0.30 0.00 % OA 7.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 0.00 Lps/m² 14.41 4.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 94.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.54
W/m² 152.74 -23.04
Grand Total ==> 2.44 0.43 3.36 100.00 2.08 100.00 Grand Total ==> -0.20 -0.80 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 3.38 2.78 319 27.3 19.8 11.5 18.5 16.9 11.5 Floor 22 Main Htg -0.5 0 -17.8 -17.8
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 19 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.38 Roof 22 0 0 Humidif 0.0 0 0.0 0.0
Wall 19 3 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.5

Project Name: Benh vien quan y 887 TRACE® 700 v6.2.4 calculated at 10:51 AM on 01/22/2022
Dataset Name: DATN-BV87.TRC Alternative - 1 System Checksums Report Page 323 of 323

You might also like