Prepared By:
Clima Tech
Check Figures
Total Building Supply Air (based on a 20° TD): 4,398 CFM
Total Building Vent. Air (100.04% of Supply): 4,400 CFM
Total Conditioned Air Space: 914 Sq.ft
Supply Air Per Unit Area: 4.8097 CFM/Sq.ft
Area Per Cooling Capacity: 104.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0096 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 8.75 Tons
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,399 CFM
Total Air Handler Vent. Air (100.06% of Supply): 1,400 CFM
Total Conditioned Air Space: 235 Sq.ft
Supply Air Per Unit Area: 5.9498 CFM/Sq.ft
Area Per Cooling Capacity: 81.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0123 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.88 Tons
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,500 CFM
Total Air Handler Vent. Air (100.03% of Supply): 1,500 CFM
Total Conditioned Air Space: 362 Sq.ft
Supply Air Per Unit Area: 4.1389 CFM/Sq.ft
Area Per Cooling Capacity: 113.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0088 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.19 Tons
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,500 CFM
Total Air Handler Vent. Air (100.02% of Supply): 1,500 CFM
Total Conditioned Air Space: 317 Sq.ft
Supply Air Per Unit Area: 4.7307 CFM/Sq.ft
Area Per Cooling Capacity: 118.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0084 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 2.67 Tons
Room 2-Quirofanos ST - Air Handler 2 (Uma-03,04,05,06), Zone 0 peaks (sensible) in August at 12am.
Lights-Prof=2 399 1.000 449 911 1,360
Equipment-Prof=3 1,000 1.000 2,730 682 3,412 0
People-Prof=2 8.0 1.000 880 1,320 2,200 2,200
Sub-total 6,972 2,200 0
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,669 2,420 0
Room 3-Quirofano H. Dia - Air Handler 3 (Uma-03), Zone 0 peaks (sensible) in August at 12am.
Lights-Prof=2 349 1.000 393 797 1,190
Equipment-Prof=2 1,000 1.000 2,730 682 3,412 0
People-Prof=2 8.0 1.000 880 1,320 2,200 2,200
Sub-total 6,802 2,200 0
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,482 2,420 0
Room 2-Quirofanos ST peaks (sensible) in August at 12am, Air Handler 2 (Uma-03,04,05,06), Zone 0,
23.3 x 15.6, Construction Type: 1 (Exterior, Light Construction, With Carpet, 10% Glass)
Lights-Prof=2 399 1.000 449 911 1,360
Equipment-Prof=3 1,000 1.000 2,730 682 3,412 0
People-Prof=2 8.0 1.000 880 1,320 2,200 2,200
Sub-total 6,972 2,200 0
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,669 2,420 0
Room 3-Quirofano H. Dia peaks (sensible) in August at 12am, Air Handler 3 (Uma-03), Zone 0, 20.0 x
15.9, Construction Type: 1 (Exterior, Light Construction, With Carpet, 10% Glass)
Lights-Prof=2 349 1.000 393 797 1,190
Equipment-Prof=2 1,000 1.000 2,730 682 3,412 0
People-Prof=2 8.0 1.000 880 1,320 2,200 2,200
Sub-total 6,802 2,200 0
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 7,482 2,420 0