Unidad De Cuidados Intensivos HNAAA

HVAC Load Analysis


for

Hospital Almanzor Aguinaga Asenjo


Plaza de la Seguridad Social S/N Chiclay
Chiclayo, Lambayeque, Peru

Prepared By:

Rober Alberto Roque Sandoval


NITCON SAC
Av. 10 De Junio 1010
SMP, Lima, Peru

martes, 19 de Diciembre de 2023


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 2

Building Summary Loads


Building peaks in January at 8am.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 0 0 0.00 0 0 0 0.00
Wall 64 790 11.64 0 2,025 2,025 4.10
Glass 29 412 6.07 0 3,761 3,761 7.61
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 1,202 17.71 0 5,786 5,786 11.71
Lighting 131 0 0.00 0 490 490 0.99
Equipment 131 0 0.00 0 490 490 0.99
People 2 0 0.00 352 440 792 1.60
Partition 443 4,150 61.15 0 4,582 4,582 9.27
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 761 0 0.00 30,662 4,181 34,843 70.52
Heat. Vent. 95 1,434 21.14 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 2,321 2,321 4.70
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 107 107 0.22
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 6,786 100.00 31,014 18,398 49,411 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 1,434 21.14 30,662 4,181 34,843 70.52
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 5,351 78.86 352 11,895 12,247 24.79
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 2,321 2,321 4.70
Building Totals 6,786 100.00 31,014 18,398 49,411 100.00

Check Figures
Total Building Supply Air (based on a 17° TD): 761 CFM
Total Building Vent. Air (100.00% of Supply): 761 CFM
Total Conditioned Air Space: 87 Sq.ft
Supply Air Per Unit Area: 8.7473 CFM/Sq.ft
Area Per Cooling Capacity: 21.1385 Sq.ft/Ton
Cooling Capacity Per Area: 0.0473 Tons/Sq.ft
Heating Capacity Per Area: 77.96 Btuh/Sq.ft
Total Heating Required With Outside Air: 6,786 Btuh
Total Cooling Required With Outside Air: 4.12 Tons

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI


martes, 19 de Diciembre
HNAAA.chvde 2023, 10:42 a. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 3

Air Handler #1 - Ue-1 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 UCI-1 87 5,351 11,898 440 100% 100%
8am January 2 95 762 0 0 0
783 1.09 8.75 0 95 762
Zone Peak Totals: 87 5,351 11,898 440
Total Zones: 1 2 95 762 0 0 0
Unique Zones: 1 783 1.09 8.75 0 95 762

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI


martes, 19 de Diciembre
HNAAA.chvde 2023, 10:42 a. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 4

Air Handler #1 - Ue-1 - Total Load Summary


Air Handler Description: Ue-1 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.92 HP
Fan Input: 85% motor and fan efficiency with 6.5 in. water across the fan
Sensible Heat Ratio: 0.98 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8am in January.
Outdoor Conditions: 76° DB, 73° WB, 118.20 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 5,351 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 1,434 Btuh 95 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 6,786 Btuh
Heating Supply Air: 5,351 / (.998 X 1.08 X 52) = 95 CFM
Winter Vent Outside Air (100.0% of supply) = 95 CFM
Zone space sensible gain: 11,788 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 2,321 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 107 Btuh
Total sensible gain on supply side of coil: 14,216 Btuh
Cooling Supply Air: 14,216 / (.998 X 1.1 X 17) = 761 CFM
Summer Vent Outside Air (100.0% of supply) = 761 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,181 Btuh 761 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 4,181 Btuh
Total sensible gain on air handling system: 18,398 Btuh
Zone space latent gain: 352 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 30,662 Btuh
Total latent gain on air handling system: 31,014 Btuh
Total system sensible and latent gain: 49,411 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 761 CFM
Total Air Handler Vent. Air (100.00% of Supply): 761 CFM
Total Conditioned Air Space: 87 Sq.ft
Supply Air Per Unit Area: 8.7473 CFM/Sq.ft
Area Per Cooling Capacity: 21.1385 Sq.ft/Ton
Cooling Capacity Per Area: 0.0473 Tons/Sq.ft
Heating Capacity Per Area: 77.96 Btuh/Sq.ft
Total Heating Required With Outside Air: 6,786 Btuh
Total Cooling Required With Outside Air: 4.12 Tons

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI


martes, 19 de Diciembre
HNAAA.chvde 2023, 10:42 a. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 5

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-UCI-1 peaks (sensible) in January at 8am, Air Handler 1 (Ue-1), Group 1, 6.8 x 12.8, Construction
Type: 1 (Light)
Wall-3-SE-G-M 64 0.83 35.9 0.800 1,841 11.200 718
Partition-1-1 93.5 12/0 0.350 393 0.000 0
Partition-2-2 349.3 12/12 0.900 3,772 10.800 3,772
Gls-SE-1-90-Tran 29.4 1.000 3 0.900 69 12.740 375
0%S-0-WS-Solar 29.4 0.700 220 0.740 3,350
Lights-Prof=2 131 1.000 445
Equipment-Prof=2 131 1.000 445 0
People-Prof=2 2.0 1.000 500 400
Sub-total 10,816 400 4,865
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 11,898 440 5,351

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI


martes, 19 de Diciembre
HNAAA.chvde 2023, 10:42 a. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 6

Air System #1 (Ue-1) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 57.765 55.000
Draw-Thru Fan 2,321 2.776 124
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 352 0.681 11,788 14.097 631
Sensible Reserve 107 0.128 6
Zone Condition 352 58.446 14,216 72.000 761
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 761 CFM 30,662 57.675 4,181 5.000
Blow-Thru Fan 0 0.000
Entering Coil Condition 31,014 116.121 18,398 77.000 761

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.998 x 1.10 x 761 x( 77.000 - 55.000 )= 18,397 Btuh


TLH = 0.998 x 0.68 x 761 x( 116.121 - 57.765 )= 30,167 Btuh
----------
SUM = 48,564 Btuh
GTH = 0.998 x 4.50 x 761 x( 36.651 - 22.159 )= 49,578 Btuh
Total System Load = 49,411 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 49,578 / ( 10.00 x 500 ) = 9.9 GPM
Heating GPM = 6,786 / ( 20.00 x 500 ) = 0.7 GPM
Steam Req. = 6,786 / 970 = 7.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 77.00 Dry bulb temperature: 58.00
Wet bulb temperature: 73.01
Relative humidity: 82.96
Enthalpy: 36.65 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 124.24
Wet bulb temperature: 53.29
Relative humidity: 89.75
Enthalpy: 22.16 Btu/lbm

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI


martes, 19 de Diciembre
HNAAA.chvde 2023, 10:42 a. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 7

Air System #1 (Ue-1) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Cooling process could not be added.

Results out of range.

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI


martes, 19 de Diciembre
HNAAA.chvde 2023, 10:42 a. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Unidad De Cuidados Intensivos HNAAA
Hell Page 8

Air Handler #1 - Ue-1 - Pie Charts


Air Handler #1 peaks in January at 8am.

Reserve Cap. - 0.22%


Wall - 4.10% Draw-Thru Fan - 4.70%
Glass - 7.61%
Lighting - 0.99%
Equipment - 0.99%
People - 1.60%

Partition - 9.27%

Air Handler
#1
Net Gain
49,411
Btuh

Cool. Vent. - 70.52%

Wall - 11.64%
Heat. Vent. - 21.14%

Glass - 6.07%

Air Handler
#1
Loss 6,786
Btuh

Partition - 61.15%

C:\Users\PSI\Documents\AIRLAN\HOSPITAL 2\06. IIMM\06.03 MEMORIA DE CÁLCULO\NATIVOS\UCI