HVAC Load Analysis


for

Tienda Juliaca

Prepared By:

ISSC
ISSC

miércoles, 10 de Marzo de 2021


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Tienda Juliaca
Hell Page 2

Building Summary Loads


Building peaks in November at 8pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 532 11,437 47.83 0 1,002 1,002 5.09
Wall 204 979 4.10 0 -62 -62 -0.31
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 12,416 51.93 0 941 941 4.77
Lighting 585 0 0.00 0 2,294 2,294 11.64
Equipment 797 0 0.00 0 3,128 3,128 15.88
People 10 0 0.00 2,300 2,875 5,175 26.26
Partition 1,450 8,079 33.79 0 5,386 5,386 27.33
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 0 0 0.00 0 0 0 0.00
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 1,252 1,252 6.35
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 2,277 9.52 0 1,019 1,019 5.17
Return Duct 0 1,139 4.76 0 509 509 2.59
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 23,910 100.00 2,300 17,404 19,704 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 0 0 0 0.00
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 20,494 85.71 2,300 14,624 16,924 85.89
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 3,416 14.29 0 2,780 2,780 14.11
Building Totals 23,910 100.00 2,300 17,404 19,704 100.00

Check Figures
Total Building Supply Air (based on a 17° TD): 1,490 CFM
Total Building Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 532 Sq.ft
Supply Air Per Unit Area: 2.8025 CFM/Sq.ft
Area Per Cooling Capacity: 323.6957 Sq.ft/Ton
Cooling Capacity Per Area: 0.0031 Tons/Sq.ft
Total Heating Required With Outside Air: 23,910 Btuh
Total Cooling Required With Outside Air: 1.64 Tons

D:\TIENDAS - JULIACA Y CUSCO\JULIACA\TIENDA JULIACA.CHV miércoles, 10 de Marzo de 2021, 3:21 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Tienda Juliaca
Hell Page 3

Air Handler #1 - Tienda - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Tienda 532 20,494 14,624 2,300 None None
8pm November 10 1,696 1,490 0 0 0
8,717 3.19 2.80 0 0 0
Zone Peak Totals: 532 20,494 14,624 2,300
Total Zones: 1 10 1,696 1,490 0 0 0
Unique Zones: 1 8,717 3.19 2.80 0 0 0

D:\TIENDAS - JULIACA Y CUSCO\JULIACA\TIENDA JULIACA.CHV miércoles, 10 de Marzo de 2021, 3:21 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Tienda Juliaca
Hell Page 4

Air Handler #1 - Tienda - Total Load Summary


Air Handler Description: Tienda Variable Air Volume
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.79 HP
Fan Input: 65% motor and fan efficiency with 2.2 in. water across the fan
Sensible Heat Ratio: 0.88 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 8pm in November.
Outdoor Conditions: 58° DB, 32° WB, 3.26 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 20,494 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 2,277 Btuh
Return Duct sensible loss: 1,139 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 23,910 Btuh
Heating Supply Air: 22,772 / (.622 X 1.08 X 20) = 1,696 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 14,624 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,252 Btuh
Supply duct sensible gain: 1,019 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 16,894 Btuh
Cooling Supply Air: 16,894 / (.622 X 1.1 X 17) = 1,490 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 509 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 509 Btuh
Total sensible gain on air handling system: 17,404 Btuh
Zone space latent gain: 2,300 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 2,300 Btuh
Total system sensible and latent gain: 19,704 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 1,490 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 532 Sq.ft
Supply Air Per Unit Area: 2.8025 CFM/Sq.ft
Area Per Cooling Capacity: 323.6957 Sq.ft/Ton
Cooling Capacity Per Area: 0.0031 Tons/Sq.ft
Total Heating Required With Outside Air: 23,910 Btuh
Total Cooling Required With Outside Air: 1.64 Tons

D:\TIENDAS - JULIACA Y CUSCO\JULIACA\TIENDA JULIACA.CHV miércoles, 10 de Marzo de 2021, 3:21 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Tienda Juliaca
Hell Page 5

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Tienda peaks (sensible) in November at 8pm, Air Handler 1 (Tienda), Group 0, 531.5 x 1.0,
Construction Type: 1 (Light)
Roof-1-8-No.Clg-L 532 0.50 5.0 0.327 872 18.711 9,945
Wall-6-N-D-M 204 0.83 -3.6 0.073 -54 4.177 852
Partition-1-2 567.112 10/15 0.323 1,832 4.845 2,748
Partition-2-2 163.508 10/15 0.323 528 4.845 792
Partition-3-2 576.296 10/15 0.323 1,861 4.845 2,792
Partition-4-2 64.452 10/15 0.323 208 4.845 312
Partition-5-2 78.556 10/15 0.323 254 4.845 381
Lights-Prof=1 585 1.000 1,995
Equipment-Prof=1 797 1.000 2,720 0
People-Prof=3 10.0 1.000 2,500 2,000
Sub-total 12,717 2,000 17,821
Safety factors: +15% +15% +15%
--------- --------- ---------
Total w/ safety factors: 14,624 2,300 20,494