Room Checksums

By Trane
2-3-4 FLOOR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 10 Mo/Hr: 3 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 21 SADB 13.4 21.1
Ra Plenum 28.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 23.0 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 23.4 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 51.00 0.00 51.00 28.55 51.00 38.08 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 2.08 0.00 2.08 1.16 2.08 1.55 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 34.41 8.02 42.43 23.75 34.41 25.69 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 11,165 11,165
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 11,165 11,165
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 11,165 11,165
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 87.49 8.02 95.51 53.46 87.49 65.33 Sub Total ==> 0.00 0.00 0.00 Nom Vent 813 0
AHU Vent 813 0
Internal Loads Internal Loads Infil 0 0
Lights 14.56 3.64 18.20 10.19 14.56 10.87 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 21.42 0 21 11.99 11.90 8.89 People 0.00 0 0.00 Return 11,165 11,165
Misc 7.80 0.00 7.80 4.37 7.80 5.82 Misc 0.00 0.00 0.00 Exhaust 813 0
Sub Total ==> 43.78 3.64 47.42 26.54 34.26 25.58 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 12.18 -12.18 0.00 0.00 12.18 9.09 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 35.73 20.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 7.82 0
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -7.82 0 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0 % OA 7.3 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.59 8.59
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0 Lps/kW 62.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0 m²/kW 7.28
W/m² 137.38 0.00
Grand Total ==> 143.45 -0.52 178.66 100.00 133.93 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 162

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 178.67 139.35 11,165 23.4 17.2 9.6 13.4 12.4 8.5 Floor 1,300 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 178.67 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 495 79 16 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: TRACE® 700 v6.2.5 calculated at 04:22 PM on 02/05/2015


Dataset Name: AC LOAR LXR.trc Alternative - 1 System Checksums Report Page 1 of 5
Room Checksums
By Trane
5 FLOOR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 10 Mo/Hr: 3 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 21 SADB 13.0 21.1
Ra Plenum 28.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 23.0 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 23.6 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 23.70 0.00 23.70 19.13 23.70 27.24 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.97 0.00 0.97 0.78 0.97 1.11 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 27.90 5.96 33.86 27.34 27.90 32.07 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 6,968 6,968
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 6,968 6,968
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 6,968 6,968
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 52.57 5.96 58.53 47.25 52.57 60.42 Sub Total ==> 0.00 0.00 0.00 Nom Vent 664 0
AHU Vent 664 0
Internal Loads Internal Loads Infil 0 0
Lights 10.42 2.60 13.02 10.51 10.42 11.98 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 17.52 0 18 14.15 9.73 11.18 People 0.00 0 0.00 Return 6,968 6,968
Misc 5.58 0.00 5.58 4.51 5.58 6.41 Misc 0.00 0.00 0.00 Exhaust 664 0
Sub Total ==> 33.52 2.60 36.12 29.16 25.73 29.57 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 8.71 -8.71 0.00 0.00 8.71 10.01 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 29.21 23.58 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 6.72 0
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -6.72 0 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0 % OA 9.5 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.49 7.49
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0 Lps/kW 56.24
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0 m²/kW 7.51
W/m² 133.12 0.00
Grand Total ==> 94.80 -0.15 123.86 100.00 87.01 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 133

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 123.85 91.70 6,968 23.6 17.4 9.9 13.0 12.1 8.4 Floor 930 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 123.85 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 368 37 10 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: TRACE® 700 v6.2.5 calculated at 04:22 PM on 02/05/2015


Dataset Name: AC LOAR LXR.trc Alternative - 1 System Checksums Report Page 2 of 5
Room Checksums
By Trane
6 FLOOR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 11 Mo/Hr: 3 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 30 / 27 / 22 OADB: 29 OADB: 21 SADB 14.0 21.1
Ra Plenum 28.4 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 23.0 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 23.4 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 30.73 0.00 30.73 30.26 36.29 44.97 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.76 0.00 1.76 1.73 1.35 1.67 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 26.04 5.95 31.99 31.50 23.41 29.01 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 7,115 7,115
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 7,115 7,115
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 7,115 7,115
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 58.53 5.95 64.48 63.50 61.05 75.65 Sub Total ==> 0.00 0.00 0.00 Nom Vent 344 0
AHU Vent 344 0
Internal Loads Internal Loads Infil 0 0
Lights 6.16 1.54 7.70 7.58 6.16 7.63 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 9.06 0 9 8.92 5.04 6.25 People 0.00 0 0.00 Return 7,115 7,115
Misc 3.30 0.00 3.30 3.25 3.30 4.09 Misc 0.00 0.00 0.00 Exhaust 344 0
Sub Total ==> 18.52 1.54 20.06 19.75 14.50 17.97 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 5.33 -5.33 0.00 0.00 5.15 6.38 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 17.01 16.75 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 3.08 0
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -3.08 0 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0 % OA 4.8 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 12.94 12.94
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0 Lps/kW 70.04
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0 m²/kW 5.42
W/m² 184.57 0.00
Grand Total ==> 82.38 2.16 101.55 100.00 80.70 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 69

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 101.56 83.69 7,115 23.4 16.9 9.4 14.0 12.7 8.6 Floor 550 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 101.56 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 368 55 15 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: TRACE® 700 v6.2.5 calculated at 04:22 PM on 02/05/2015


Dataset Name: AC LOAR LXR.trc Alternative - 1 System Checksums Report Page 3 of 5
Room Checksums
By Trane
G FLOOR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 11 Mo/Hr: 3 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 30 / 27 / 22 OADB: 29 OADB: 21 SADB 13.1 21.1
Ra Plenum 28.4 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 23.0 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 23.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 17.27 0.00 17.27 11.04 22.99 20.78 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.21 0.00 1.21 0.77 0.94 0.85 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 41.73 8.57 50.30 32.16 40.26 36.39 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 8,921 8,921
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 8,921 8,921
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 8,921 8,921
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 60.21 8.57 68.78 43.97 64.19 58.02 Sub Total ==> 0.00 0.00 0.00 Nom Vent 813 0
AHU Vent 813 0
Internal Loads Internal Loads Infil 0 0
Lights 14.56 3.64 18.20 11.64 14.56 13.16 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 21.42 0 21 13.69 11.90 10.76 People 0.00 0 0.00 Return 8,921 8,921
Misc 7.80 0.00 7.80 4.99 7.80 7.05 Misc 0.00 0.00 0.00 Exhaust 813 0
Sub Total ==> 43.78 3.64 47.42 30.32 34.26 30.97 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 12.60 -12.60 0.00 0.00 12.18 11.01 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 40.21 25.71 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 8.15 0
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -8.15 0 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0 % OA 9.1 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 6.86 6.86
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0 Lps/kW 57.01
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0 m²/kW 8.31
W/m² 120.27 0.00
Grand Total ==> 116.59 -0.39 156.41 100.00 110.63 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 162

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 156.42 114.18 8,921 23.7 17.5 9.9 13.1 12.3 8.5 Floor 1,300 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 156.42 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 510 36 7 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: TRACE® 700 v6.2.5 calculated at 04:22 PM on 02/05/2015


Dataset Name: AC LOAR LXR.trc Alternative - 1 System Checksums Report Page 4 of 5
Room Checksums
By Trane
M FLOOR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 10 Mo/Hr: 3 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 21 OADB: 29 OADB: 21 SADB 13.2 21.1
Ra Plenum 28.2 21.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 23.0 21.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 23.5 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.0 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 30.91 0.00 30.91 19.38 30.91 26.88 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.26 0.00 1.26 0.79 1.26 1.10 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 36.39 7.78 44.17 27.69 36.39 31.64 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 9,335 9,335
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 9,335 9,335
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0 Main Fan 9,335 9,335
Infiltration 0.00 0.00 0.00 0.00 0.00 Infiltration 0.00 0.00 0.00 Sec Fan 0 0
Sub Total ==> 68.56 7.78 76.34 47.87 68.56 59.62 Sub Total ==> 0.00 0.00 0.00 Nom Vent 813 0
AHU Vent 813 0
Internal Loads Internal Loads Infil 0 0
Lights 14.56 3.64 18.20 11.41 14.56 12.66 Lights 0.00 0.00 0.00 MinStop/Rh 0 0
People 21.42 0 21 13.43 11.90 10.35 People 0.00 0 0.00 Return 9,335 9,335
Misc 7.80 0.00 7.80 4.89 7.80 6.78 Misc 0.00 0.00 0.00 Exhaust 813 0
Sub Total ==> 43.78 3.64 47.42 29.73 34.26 29.79 Sub Total ==> 0.00 0.00 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 12.18 -12.18 0.00 0.00 12.18 10.59 Ceiling Load 0.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 35.73 22.40 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 8.09 0
Sup. Fan Heat 0.00 0.00 RA Preheat Diff. -8.09 0 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0 % OA 8.7 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 7.18 7.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0 Lps/kW 58.51
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0 m²/kW 8.15
W/m² 122.63 0.00
Grand Total ==> 124.52 -0.76 159.49 100.00 115.00 100.00 Grand Total ==> 0.00 0.00 100.00 No. People 162

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
kW kW L/s °C °C g/kg °C °C g/kg m² (%) kW L/s °C °C
Main Clg 159.49 120.17 9,335 23.5 17.3 9.8 13.2 12.2 8.4 Floor 1,300 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.00 0.00 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 159.49 Roof 0 0 0 Humidif 0.0 0 0.0 0.0
Wall 480 48 10 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: TRACE® 700 v6.2.5 calculated at 04:22 PM on 02/05/2015


Dataset Name: AC LOAR LXR.trc Alternative - 1 System Checksums Report Page 5 of 5