Professional Documents
Culture Documents
By .
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: Sum of Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 91 / 70 / 101 OADB: Peaks OADB: 29 SADB 54.0 76.4
Plenum 75.0 70.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 75.0 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 76.5 66.3
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.0 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 57,829 0 57,829 5 57,829 6 Roof Cond -37,907 -37,907 8.08
Glass Solar 69,828 0 69,828 6 74,756 8 Glass Solar 0 0 0.00
Glass Cond 17,172 0 17,172 1 17,172 2 Glass Cond -43,881 -43,881 9.36
Wall Cond 47,317 0 47,317 4 52,246 5 Wall Cond -53,330 -53,330 11.37 AIRFLOWS
Partition 75,557 75,557 6 75,557 8 Partition -43,670 -43,670 9.31
Cooling Heating
Exposed Floor 177,464 177,464 15 177,464 18 Exposed Floor -117,772 -117,772 25.11
Vent 4,673 4,673
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00
Infil 0 0
Sub Total ==> 445,166 0 445,166 36 455,024 47 Sub Total ==> -296,560 -296,560 63.24 Supply 51,490 51,490
MinStop/Rh 0 0
Internal Loads Internal Loads Return 51,490 51,490
Lights 100,604 0 100,604 8 98,921 10 Lights 0 0 0.00 Exhaust 4,673 4,673
People 230,172 230,172 19 121,594 13 People 0 0 0.00 Rm Exh 0 0
Misc 296,668 0 296,668 24 295,078 30 Misc 0 0 0.00 Auxiliary 0 0
Sub Total ==> 627,444 0 627,444 51 515,593 53 Sub Total ==> 0 0 0.00
Grand Total ==> 1,072,610 3 1,221,258 100.00 970,617 100.00 Grand Total ==> -296,560 -468,947 100.00 No. People 539