You are on page 1of 1

System Checksums

By .

QUERETARO Fan Coil

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 5 / 17 Mo/Hr: Sum of Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 91 / 70 / 101 OADB: Peaks OADB: 29 SADB 54.0 76.4
Plenum 75.0 70.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 75.0 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 76.5 66.3
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.0 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 57,829 0 57,829 5 57,829 6 Roof Cond -37,907 -37,907 8.08
Glass Solar 69,828 0 69,828 6 74,756 8 Glass Solar 0 0 0.00
Glass Cond 17,172 0 17,172 1 17,172 2 Glass Cond -43,881 -43,881 9.36
Wall Cond 47,317 0 47,317 4 52,246 5 Wall Cond -53,330 -53,330 11.37 AIRFLOWS
Partition 75,557 75,557 6 75,557 8 Partition -43,670 -43,670 9.31
Cooling Heating
Exposed Floor 177,464 177,464 15 177,464 18 Exposed Floor -117,772 -117,772 25.11
Vent 4,673 4,673
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00
Infil 0 0
Sub Total ==> 445,166 0 445,166 36 455,024 47 Sub Total ==> -296,560 -296,560 63.24 Supply 51,490 51,490
MinStop/Rh 0 0
Internal Loads Internal Loads Return 51,490 51,490
Lights 100,604 0 100,604 8 98,921 10 Lights 0 0 0.00 Exhaust 4,673 4,673
People 230,172 230,172 19 121,594 13 People 0 0 0.00 Rm Exh 0 0
Misc 296,668 0 296,668 24 295,078 30 Misc 0 0 0.00 Auxiliary 0 0
Sub Total ==> 627,444 0 627,444 51 515,593 53 Sub Total ==> 0 0 0.00

Ceiling Load 0 0 0 0 0 0 Ceiling Load 0 0 0.00


ENGINEERING CKS
Ventilation Load 0 0 148,643 12 0 0 Ventilation Load 0 -172,388 36.76
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0 Cooling Heating
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00 % OA 9.1 9.1
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0 cfm/ft2 1.56 1.56
Sup. Fan Heat 3 0 RA Preheat Diff. 0 0 cfm/ton 505.94
Ret. Fan Heat 3 3 0 Additional Reheat 0 0
Duct Heat Pkup 0 0 0 ft2/ton 323.87
Reheat at Design 0 0 Btu/hr-ft2 37.05 -14.23

Grand Total ==> 1,072,610 3 1,221,258 100.00 970,617 100.00 Grand Total ==> -296,560 -468,947 100.00 No. People 539

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm F F gr/lb F F gr/lb ft2 (%) MBh cfm F F
Main Clg 101.8 1,221.3 1,033.6 51,490.2 76.5 60.7 73.0 54.0 51.6 66.9 Floor 32,960 Main Htg -469.0 51,490.2 66.3 76.4
Aux Clg 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Part 51,882 Aux Htg 0.0 0 0 0
Opt Vent 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 32,116 Preheat 0.0 0 0 0
Roof 16,632 0 0
Total 101.8 1,221.3 Wall 16,456 3,882 24 Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -469.0

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 System Checksums Report Página 1 de 1