Sheet prepared by:- COOLING & DEHUMIDIFYING, HEATING LOAD ESTIMATE Date:- 2-24-2024
DHIREN
Sheet no: 1
Job Name :- Gurugram
. Floor:- Ground Floor _
Space Used For :- Conf. Room
Estimated By :-
SEASON SUMMER MONSOON WINTER
COND DB WB RH GR/LB DB WB RH GR/LB DB RH
Outside 110 75 70 90 83 152 45 70
Inside 72 55 68 72 55 68 80
Difference 38 2 18 84 35
SENSIBLE HEAT FACTOR DEHUMIDIFIED RISE
0.9 X (Rm Temp- ADP) = 18
SHF = 72552 RSH = 0.98
73909 RTH DEHUMIDIFIED CFM
SUMMER = 3732
Ind ADP Selc ADP 52 MONSOON = 2663
Equipment: 250 Watts Cfm/per : 5 F.Air = 3460 CUFT X ACPH = 0
Occupancy: 6 Nos ACPH : 1 60
Light : 2.5 Watts/sft F.Air = 60 PER X CFM/PER = 30
AREA 346 sft X ht 10 = 3460 cuft
SENSIBLE HEAT
AREA SUN GAIN/TEM DIFF FACTOR BTU/HOUR
SUMMER MONSOON WINTER SUMMER MONSOON WINTER SUMMER MONSOON WINTER
N-glass 14 0.560 0 0 -
NE-glass 140 12 0.560 1101 1101 -
E-glass 12 0.560 0 0 -
SE-glass 260 12 0.560 2044 2044 -
S-glass 12 0.560 0 0 -
SW-glass 140 100 0.560 5962 5962 -
W-glass 164 0.560 0 0 -
NW-glass 260 123 0.560 13620 13620 -
Horizontal 123 1.000 0 0 -
Poly-Carbo 60 1.000 0 0 -