You are on page 1of 21

Zone Checksums

By BIP INGENIERIAS SC
Zone - 001 RESIDENCIA DE MEDICOS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 6 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 83 / 66 / 91 OADB: 87 OADB: 44 SADB 55.0 78.4
Ra Plenum 77.4 66.8
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 77.8 66.8
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 78.9 61.7
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 5,544 5,544 15 0 0 Roof Cond 0 -4,723 20.49
Glass Solar 5,388 0 5,388 15 7,757 30 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 1,343 0 1,343 4 1,600 6 Glass/Door Cond -2,828 -2,828 12.27
Cooling Heating
Wall Cond 3,386 717 4,102 11 3,265 12 Wall Cond -4,154 -5,169 22.42
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 1,494 1,494
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 1,494 1,494
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 1,494 1,494
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 10,117 6,261 16,378 44 12,622 48 Sub Total ==> -6,981 -12,720 55.18 Nom Vent 334 340
AHU Vent 334 340
Internal Loads Internal Loads Infil 0 0
Lights 8,811 0 8,811 24 8,107 31 Lights 0 0 0.00 MinStop/Rh 0 0
People 6,077 0 6,077 16 2,501 10 People 0 0 0.00 Return 1,494 1,494
Misc 924 0 924 3 924 4 Misc 0 0 0.00 Exhaust 334 340
Sub Total ==> 15,811 0 15,811 43 11,532 44 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1,425 -1,425 0 0 2,040 8 Ceiling Load -1,350 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 5,678 15 0 0 Ventilation Load 0 -8,037 34.87 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -3,293 -3,293 14.29
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 999 -4.34 ENGINEERING CKS
Exhaust Heat -1,164 -1,164 -3 OA Preheat Diff. 0 0.00
Sup. Fan Heat 221 1 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 22.4 22.8
Duct Heat Pkup 0 0 0 System Plenum Heat 0 0.00 cfm/ft² 1.12 1.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 485.63
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 434.82
Btu/hr·ft² 27.60 -17.23
Grand Total ==> 27,354 3,672 36,924 100.00 26,194 100.00 Grand Total ==> -11,624 -23,050 100.00 No. People 15

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 3.1 36.9 32.2 1,494 78.9 59.9 62.5 54.8 50.3 58.1 Floor 1,338 Main Htg -23.1 1,494 61.7 78.4
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.1 36.9 Roof 1,338 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,444 121 8 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -23.1

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 1 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 002 CIRUGIA

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 21 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 81 OADB: 44 SADB 55.2 59.0
Ra Plenum 78.8 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 60.8 59.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 84.2 44.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.3 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.9 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 812 812 0 0 0 Roof Cond 0 -1,124 2.73
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 471 -36 435 0 1,772 11 Wall Cond -501 -641 1.55
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 3,059 3,059
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 3,059 3,059
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 3,059 3,059
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 471 776 1,247 1 1,772 11 Sub Total ==> -501 -1,765 4.28 Nom Vent 3,059 3,059
AHU Vent 3,059 3,059
Internal Loads Internal Loads Infil 0 0
Lights 5,966 0 5,966 3 5,966 38 Lights 5,966 5,966 -14.48 MinStop/Rh 0 0
People 2,000 0 2,000 1 1,000 6 People 1,000 1,000 -2.43 Return 3,059 3,059
Misc 2,983 0 2,983 2 2,983 19 Misc 2,983 2,983 -7.24 Exhaust 3,059 3,059
Sub Total ==> 10,949 0 10,949 6 9,949 63 Sub Total ==> 9,949 9,949 -24.14 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,486 -2,486 0 0 4,014 26 Ceiling Load 240 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 178,185 92 0 0 Ventilation Load 0 -41,208 100.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 3,626 2 RA Preheat Diff. -9,689 23.51 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 100.0 100.0
Duct Heat Pkup 0 0 0 System Plenum Heat 1,504 -3.65 cfm/ft² 7.00 7.00
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 189.22
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 27.03
Btu/hr·ft² 443.94 -94.29
Grand Total ==> 13,906 -1,710 194,006 100.00 15,734 100.00 Grand Total ==> 9,689 -41,208 100.00 No. People 4

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 16.2 194.0 80.8 3,059 84.2 68.6 102.0 53.9 45.7 41.7 Floor 437 Main Htg -41.2 3,059 44.4 59.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -26.9 3,059 44.4 53.9
ExFlr 0
Total 16.2 194.0 Roof 437 0 0 Humidif 0.0 0 0.0 0.0
Wall 273 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -41.2

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 2 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 003 HOSPITALIZACION

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 84 OADB: 44 SADB 55.0 70.0
Ra Plenum 78.8 67.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 78.0 67.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 81.0 55.9
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 10,503 10,503 11 0 0 Roof Cond 0 -5,984 20.15
Glass Solar 470 0 470 1 469 1 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 219 0 219 0 185 0 Glass/Door Cond -332 -332 1.12
Cooling Heating
Wall Cond 3,817 793 4,610 5 4,127 10 Wall Cond -3,175 -3,890 13.10
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,276 2,276
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,276 2,276
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,276 2,276
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 4,506 11,296 15,802 17 4,782 12 Sub Total ==> -3,507 -10,207 34.37 Nom Vent 1,126 1,126
AHU Vent 1,126 1,126
Internal Loads Internal Loads Infil 0 0
Lights 11,440 0 11,440 12 11,440 29 Lights 11,440 11,440 -38.53 MinStop/Rh 0 0
People 8,550 0 8,550 9 4,750 12 People 4,750 4,750 -16.00 Return 2,276 2,276
Misc 2,860 0 2,860 3 2,860 7 Misc 2,860 2,860 -9.63 Exhaust 1,126 1,126
Sub Total ==> 22,850 0 22,850 25 19,050 48 Sub Total ==> 19,050 19,050 -64.15 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,568 -2,568 0 0 3,060 8 Ceiling Load -1,554 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 42,557 46 0 0 Ventilation Load 0 -26,589 89.54 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 13,004 13,004 14 13,004 33 Exhaust Heat 3,039 -10.24 ENGINEERING CKS
Exhaust Heat -2,594 -2,594 -3 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,349 1 RA Preheat Diff. -13,989 47.11 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 49.5 49.5
Duct Heat Pkup 0 0 0 System Plenum Heat -999 3.37 cfm/ft² 1.36 1.36
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 293.77
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 216.33
Btu/hr·ft² 55.47 -17.72
Grand Total ==> 42,928 6,133 92,967 100.00 39,895 100.00 Grand Total ==> 13,989 -29,694 100.00 No. People 19

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 7.8 93.0 57.2 2,276 81.0 62.2 70.8 54.4 46.2 43.0 Floor 1,676 Main Htg -29.7 2,276 55.9 70.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 7.8 93.0 Roof 1,676 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,006 14 1 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -29.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 3 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 004 LABORATORIO

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 19 Mo/Hr: 6 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 87 / 59 / 46 OADB: 87 OADB: 44 SADB 55.0 70.0
Ra Plenum 79.3 67.6
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 79.3 67.6
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 79.3 67.6
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 9,768 9,768 21 0 0 Roof Cond 0 -4,505 107.95
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 1,847 1,847
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 1,847 1,847
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 1,847 1,847
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 9,768 9,768 21 0 0 Sub Total ==> 0 -4,505 107.95 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 0 0
Lights 16,870 0 16,870 37 16,870 52 Lights 16,870 16,870 -404.21 MinStop/Rh 0 0
People 10,000 0 10,000 22 5,000 15 People 5,000 5,000 -119.80 Return 1,847 1,847
Misc 8,435 0 8,435 18 8,435 26 Misc 8,435 8,435 -202.11 Exhaust 0 0
Sub Total ==> 35,305 0 35,305 76 30,305 94 Sub Total ==> 30,305 30,305 -726.13 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,078 -2,078 0 0 2,078 6 Ceiling Load -959 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 0 0 0 0 Ventilation Load 0 0 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,095 2 RA Preheat Diff. -29,346 703.15 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 0.0 0.0
Duct Heat Pkup 0 0 0 System Plenum Heat -627 15.02 cfm/ft² 1.49 1.49
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 480.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 321.19
Btu/hr·ft² 37.36 0.00
Grand Total ==> 37,383 7,689 46,167 100.00 32,383 100.00 Grand Total ==> 29,346 -4,173 100.00 No. People 20

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 3.9 46.2 41.2 1,847 79.3 57.4 50.1 54.4 47.1 46.5 Floor 1,236 Main Htg 0.0 0 0.0 0.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 3.9 46.2 Roof 1,236 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total 0.0

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 4 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 005 GOBIERNO

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 9 / 12 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 83 / 66 / 91 OADB: 80 OADB: 44 SADB 56.0 74.4
Ra Plenum 77.5 67.4
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 76.9 67.4
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 77.7 64.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 5,757 5,757 16 0 0 Roof Cond 0 -4,184 30.99
Glass Solar 5,186 0 5,186 15 7,985 33 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 581 0 581 2 134 1 Glass/Door Cond -1,601 -1,601 11.86
Cooling Heating
Wall Cond 580 155 735 2 -33 0 Wall Cond -1,112 -1,422 10.54
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 1,463 1,463
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 1,463 1,463
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 1,463 1,463
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 6,347 5,912 12,259 35 8,085 33 Sub Total ==> -2,712 -7,207 53.38 Nom Vent 189 189
AHU Vent 189 189
Internal Loads Internal Loads Infil 0 0
Lights 7,891 0 7,891 23 7,891 32 Lights 0 0 0.00 MinStop/Rh 0 0
People 10,800 0 10,800 31 6,000 25 People 0 0 0.00 Return 1,463 1,463
Misc 1,945 0 1,945 6 1,864 8 Misc 0 0 0.00 Exhaust 189 189
Sub Total ==> 20,637 0 20,637 59 15,755 65 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1,270 -1,270 0 0 521 2 Ceiling Load -959 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 2,413 7 0 0 Ventilation Load 0 -4,473 33.13 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -2,280 -2,280 16.88
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 458 -3.39 ENGINEERING CKS
Exhaust Heat -624 -624 -2 OA Preheat Diff. 0 0.00
Sup. Fan Heat 217 1 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 12.9 12.9
Duct Heat Pkup 0 0 0 System Plenum Heat 0 0.00 cfm/ft² 1.27 1.27
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 503.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 397.47
Btu/hr·ft² 30.19 -11.68
Grand Total ==> 28,253 4,018 34,902 100.00 24,361 100.00 Grand Total ==> -5,951 -13,502 100.00 No. People 24

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 2.9 34.9 29.7 1,463 77.7 62.1 75.9 55.8 53.4 69.7 Floor 1,156 Main Htg -13.5 1,463 64.4 74.4
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.9 34.9 Roof 1,156 0 0 Humidif 0.0 0 0.0 0.0
Wall 431 68 16 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -13.5

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 5 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 006 CONSULTA EXTERNA

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 10 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 82 / 67 / 96 OADB: 82 OADB: 44 SADB 56.0 74.9
Ra Plenum 76.8 67.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 76.7 67.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 77.2 65.9
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 22,580 22,580 13 0 0 Roof Cond 0 -16,494 25.48
Glass Solar 62,678 0 62,678 35 66,475 51 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 3,082 0 3,082 2 3,082 2 Glass/Door Cond -8,870 -8,870 13.70
Cooling Heating
Wall Cond 447 115 562 0 583 0 Wall Cond -941 -1,254 1.94
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 7,832 7,832
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 7,832 7,832
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 7,832 7,832
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 66,207 22,695 88,902 50 70,141 54 Sub Total ==> -9,811 -26,617 41.12 Nom Vent 643 643
AHU Vent 643 643
Internal Loads Internal Loads Infil 0 0
Lights 30,463 0 30,463 17 30,463 23 Lights 0 0 0.00 MinStop/Rh 0 0
People 33,750 0 33,750 19 18,750 14 People 0 0 0.00 Return 7,832 7,832
Misc 7,594 0 7,594 4 7,594 6 Misc 0 0 0.00 Exhaust 643 643
Sub Total ==> 71,807 0 71,807 40 56,807 44 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 3,892 -3,892 0 0 3,116 2 Ceiling Load -3,015 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 14,111 8 0 0 Ventilation Load 0 -15,182 23.46 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -22,578 -22,578 34.88
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 1,264 -1.95 ENGINEERING CKS
Exhaust Heat -1,642 -1,642 -1 OA Preheat Diff. 0 0.00
Sup. Fan Heat 4,641 3 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 8.2 8.2
Duct Heat Pkup 0 0 0 System Plenum Heat -1,615 2.49 cfm/ft² 1.75 1.75
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 528.51
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 301.16
Btu/hr·ft² 39.85 -14.50
Grand Total ==> 141,906 17,161 177,819 100.00 130,063 100.00 Grand Total ==> -35,404 -64,727 100.00 No. People 75

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 14.8 177.8 153.8 7,832 77.2 61.2 72.1 55.4 52.8 67.7 Floor 4,463 Main Htg -64.7 7,832 65.9 74.9
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 14.8 177.8 Roof 4,463 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,527 1,208 79 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -64.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 6 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 007 INGRESO URGENCIAS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 10 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 82 / 67 / 96 OADB: 82 OADB: 44 SADB 56.0 71.8
Ra Plenum 76.4 68.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 76.4 68.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 76.7 66.8
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 8,435 8,435 9 0 0 Roof Cond 0 -6,202 28.76
Glass Solar 50,769 0 50,769 52 53,536 68 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 2,359 0 2,359 2 2,360 3 Glass/Door Cond -6,790 -6,790 31.49
Cooling Heating
Wall Cond 0 28 28 0 0 0 Wall Cond 0 -75 0.35
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 4,730 4,730
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 4,730 4,730
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 4,730 4,730
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 53,128 8,464 61,592 63 55,896 71 Sub Total ==> -6,790 -13,067 60.59 Nom Vent 250 250
AHU Vent 250 250
Internal Loads Internal Loads Infil 0 0
Lights 11,344 0 11,344 12 11,344 14 Lights 0 0 0.00 MinStop/Rh 0 0
People 13,500 0 13,500 14 7,500 10 People 0 0 0.00 Return 4,730 4,730
Misc 2,836 0 2,836 3 2,836 4 Misc 0 0 0.00 Exhaust 250 250
Sub Total ==> 27,681 0 27,681 28 21,681 28 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1,260 -1,260 0 0 975 1 Ceiling Load -1,003 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 6,001 6 0 0 Ventilation Load 0 -5,898 27.35 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 439 -2.04 ENGINEERING CKS
Exhaust Heat -551 -551 -1 OA Preheat Diff. 0 0.00
Sup. Fan Heat 2,803 3 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 5.3 5.3
Duct Heat Pkup 0 0 0 System Plenum Heat -3,039 14.09 cfm/ft² 2.85 2.85
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 581.99
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 204.49
Btu/hr·ft² 58.68 -12.98
Grand Total ==> 82,069 6,653 97,525 100.00 78,552 100.00 Grand Total ==> -7,793 -21,566 100.00 No. People 30

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 8.1 97.5 87.4 4,730 76.7 60.5 69.0 55.4 52.7 67.4 Floor 1,662 Main Htg -21.6 4,730 66.8 71.8
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 8.1 97.5 Roof 1,662 0 0 Humidif 0.0 0 0.0 0.0
Wall 945 925 98 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -21.6

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 7 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 008 COMEDOR

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 19 Mo/Hr: 6 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 78 / 63 / 79 OADB: 87 OADB: 44 SADB 55.0 72.7
Ra Plenum 77.5 68.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 77.5 68.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 77.6 63.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 4,152 4,152 13 0 0 Roof Cond 0 -2,274 21.61
Glass Solar 7,162 0 7,162 23 6,856 32 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 333 0 333 1 825 4 Glass/Door Cond -1,416 -1,416 13.46
Cooling Heating
Wall Cond 751 191 941 3 1,076 5 Wall Cond -988 -1,271 12.08
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 1,230 1,230
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 1,230 1,230
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 1,230 1,230
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 8,245 4,343 12,588 40 8,756 41 Sub Total ==> -2,405 -4,962 47.16 Nom Vent 238 238
AHU Vent 238 238
Internal Loads Internal Loads Infil 0 0
Lights 3,647 0 3,647 12 3,647 17 Lights 0 0 0.00 MinStop/Rh 0 0
People 7,403 0 7,403 23 3,091 14 People 0 0 0.00 Return 1,230 1,230
Misc 156 0 156 0 156 1 Misc 0 0 0.00 Exhaust 238 238
Sub Total ==> 11,207 0 11,207 35 6,894 32 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 672 -672 0 0 776 4 Ceiling Load -393 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 2,714 9 0 0 Ventilation Load 0 -5,628 53.50 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -243 -243 2.31
Ov/Undr Sizing 5,131 5,131 16 5,131 24 Exhaust Heat 445 -4.23 ENGINEERING CKS
Exhaust Heat -769 -769 -2 OA Preheat Diff. 0 0.00
Sup. Fan Heat 729 2 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 19.4 19.4
Duct Heat Pkup 0 0 0 System Plenum Heat -133 1.27 cfm/ft² 2.01 2.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 467.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 232.58
Btu/hr·ft² 51.59 -17.18
Grand Total ==> 25,256 2,901 31,600 100.00 21,558 100.00 Grand Total ==> -3,040 -10,521 100.00 No. People 18

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 2.6 31.6 25.6 1,230 77.6 60.9 70.0 54.4 51.2 62.8 Floor 612 Main Htg -10.5 1,230 63.4 72.7
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 2.6 31.6 Roof 612 0 0 Humidif 0.0 0 0.0 0.0
Wall 383 60 16 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -10.5

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 8 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 009 MANTENIMIENTO

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 7 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 83 / 66 / 91 OADB: 92 OADB: 44 SADB 55.1 70.7
Ra Plenum 76.9 68.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 76.9 68.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 78.2 62.7
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 627 627 19 0 0 Roof Cond 0 -388 52.18
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 100 100
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 100 100
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 100 100
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 627 627 19 0 0 Sub Total ==> 0 -388 52.18 Nom Vent 22 22
AHU Vent 22 22
Internal Loads Internal Loads Infil 0 0
Lights 713 0 713 22 713 41 Lights 0 0 0.00 MinStop/Rh 0 0
People 1,350 0 1,350 42 750 43 People 0 0 0.00 Return 100 100
Misc 178 0 178 5 178 10 Misc 0 0 0.00 Exhaust 22 22
Sub Total ==> 2,241 0 2,241 69 1,641 94 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 95 -95 0 0 112 6 Ceiling Load -67 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 379 12 0 0 Ventilation Load 0 -530 71.39 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 42 -5.65 ENGINEERING CKS
Exhaust Heat -59 -59 -2 OA Preheat Diff. 0 0.00
Sup. Fan Heat 59 2 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 22.4 22.4
Duct Heat Pkup 0 0 0 System Plenum Heat 133 -17.93 cfm/ft² 0.96 0.96
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 370.84
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 385.83
Btu/hr·ft² 31.10 -7.12
Grand Total ==> 2,336 473 3,247 100.00 1,753 100.00 Grand Total ==> -67 -743 100.00 No. People 3

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 0.3 3.3 2.5 100 78.2 62.9 79.2 54.4 50.9 61.4 Floor 104 Main Htg -0.7 100 62.7 70.7
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 0.3 3.3 Roof 104 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -0.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 9 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 010 MORTUORIO

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 84 OADB: 44 SADB 55.0 80.7
Ra Plenum 78.2 58.6
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 74.0 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 84.2 44.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 396 396 1 0 0 Roof Cond 0 -745 4.29
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 781 62 843 3 2,992 33 Wall Cond -3,270 -3,724 21.45
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 519 519
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 519 519
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 519 519
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 781 458 1,239 4 2,992 33 Sub Total ==> -3,270 -4,469 25.75 Nom Vent 519 519
AHU Vent 519 519
Internal Loads Internal Loads Infil 0 0
Lights 2,270 0 2,270 8 2,121 23 Lights 0 0 0.00 MinStop/Rh 0 0
People 3,600 0 3,600 12 1,895 21 People 0 0 0.00 Return 519 519
Misc 522 0 522 2 418 5 Misc 0 0 0.00 Exhaust 519 519
Sub Total ==> 6,392 0 6,392 22 4,434 49 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 441 -441 0 0 1,663 18 Ceiling Load -1,199 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 21,611 74 0 0 Ventilation Load 0 -12,247 70.56 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -642 -642 3.70
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 77 0 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 100.0 100.0
Duct Heat Pkup 0 0 0 System Plenum Heat 0 0.00 cfm/ft² 1.56 1.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 212.22
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 136.13
Btu/hr·ft² 88.15 -52.19
Grand Total ==> 7,614 17 29,319 100.00 9,089 100.00 Grand Total ==> -5,111 -17,358 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 2.4 29.3 11.0 519 84.2 68.6 101.8 54.8 48.7 51.8 Floor 333 Main Htg -17.4 519 44.4 80.7
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -5.0 519 44.4 54.8
ExFlr 0
Total 2.4 29.3 Roof 333 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,018 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -17.4

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 10 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 011 CONSULTORIOS EXTERNOS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 9 / 11 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 92 / 63 / 55 OADB: 77 OADB: 44 SADB 56.0 77.1
Ra Plenum 77.3 67.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 77.2 67.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 79.0 65.0
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 11,178 11,178 16 0 0 Roof Cond 0 -7,392 22.38
Glass Solar 4,085 0 4,085 6 19,850 40 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 3,339 0 3,339 5 197 0 Glass/Door Cond -5,436 -5,436 16.46
Cooling Heating
Wall Cond 4,517 1,185 5,702 8 699 1 Wall Cond -5,094 -6,475 19.60
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,952 2,952
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,952 2,952
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,952 2,952
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 11,941 12,363 24,304 35 20,747 42 Sub Total ==> -10,530 -19,302 58.43 Nom Vent 360 360
AHU Vent 360 360
Internal Loads Internal Loads Infil 0 0
Lights 13,652 0 13,652 20 13,652 28 Lights 0 0 0.00 MinStop/Rh 0 0
People 21,600 0 21,600 31 12,000 24 People 0 0 0.00 Return 2,952 2,952
Misc 3,166 0 3,166 5 2,784 6 Misc 0 0 0.00 Exhaust 360 360
Sub Total ==> 38,417 0 38,417 56 28,435 58 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,083 -2,083 0 0 -162 0 Ceiling Load -1,351 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 5,593 8 0 0 Ventilation Load 0 -8,503 25.74 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -7,551 -7,551 22.86
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 708 -2.14 ENGINEERING CKS
Exhaust Heat -985 -985 -1 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,749 3 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 12.2 12.2
Duct Heat Pkup 0 0 0 System Plenum Heat 1,615 -4.89 cfm/ft² 1.48 1.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 512.75
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 347.42
Btu/hr·ft² 34.54 -16.52
Grand Total ==> 52,442 9,295 69,079 100.00 49,020 100.00 Grand Total ==> -19,432 -33,034 100.00 No. People 48

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 5.8 69.1 58.3 2,952 79.0 62.2 74.3 55.4 53.7 71.7 Floor 2,000 Main Htg -33.0 2,952 65.0 77.1
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 5.8 69.1 Roof 2,000 0 0 Humidif 0.0 0 0.0 0.0
Wall 1,875 232 12 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -33.0

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 11 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 012 CONSULTORIOS LABS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 92 / 63 / 55 OADB: 92 OADB: 44 SADB 55.0 71.3
Ra Plenum 79.0 67.6
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 79.1 67.6
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 79.6 66.7
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 15,080 15,080 26 0 0 Roof Cond 0 -7,378 77.24
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,294 2,294
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,294 2,294
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,294 2,294
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 15,080 15,080 26 0 0 Sub Total ==> 0 -7,378 77.24 Nom Vent 81 81
AHU Vent 81 81
Internal Loads Internal Loads Infil 0 0
Lights 22,086 0 22,086 38 22,086 55 Lights 16,546 16,546 -173.22 MinStop/Rh 0 0
People 10,200 0 10,200 17 5,250 13 People 3,750 3,750 -39.26 Return 2,294 2,294
Misc 9,658 0 9,658 16 9,658 24 Misc 8,273 8,273 -86.61 Exhaust 81 81
Sub Total ==> 41,945 0 41,945 72 36,995 92 Sub Total ==> 28,570 28,570 -299.09 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 3,209 -3,209 0 0 3,209 8 Ceiling Load -1,570 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 557 1 0 0 Ventilation Load 0 -1,916 20.06 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -29,638 -29,638 310.28
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 183 -1.92 ENGINEERING CKS
Exhaust Heat -384 -384 -1 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,359 2 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 3.5 3.5
Duct Heat Pkup 0 0 0 System Plenum Heat 627 -6.56 cfm/ft² 1.13 1.13
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 470.00
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 414.70
Btu/hr·ft² 28.94 -4.72
Grand Total ==> 45,154 11,488 58,557 100.00 40,204 100.00 Grand Total ==> -2,638 -9,552 100.00 No. People 21

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 4.9 58.6 54.1 2,294 79.6 59.3 58.5 54.4 49.2 54.5 Floor 2,024 Main Htg -9.6 2,294 66.7 71.3
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.9 58.6 Roof 2,024 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -9.6

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 12 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 013 URGENCIAS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 92 OADB: 44 SADB 55.0 73.0
Ra Plenum 77.1 68.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 76.3 68.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 80.6 55.1
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 14,315 14,315 13 0 0 Roof Cond 0 -8,692 18.83
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 1,489 290 1,779 2 1,895 4 Wall Cond -2,936 -3,616 7.83
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,803 2,803
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,803 2,803
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,803 2,803
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 1,489 14,604 16,094 14 1,895 4 Sub Total ==> -2,936 -12,308 26.66 Nom Vent 1,532 1,532
AHU Vent 1,532 1,532
Internal Loads Internal Loads Infil 0 0
Lights 15,900 0 15,900 14 15,900 32 Lights 0 0 0.00 MinStop/Rh 0 0
People 9,000 0 9,000 8 5,000 10 People 0 0 0.00 Return 2,803 2,803
Misc 3,714 0 3,714 3 3,714 8 Misc 0 0 0.00 Exhaust 1,532 1,532
Sub Total ==> 28,614 0 28,614 25 24,614 50 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,291 -2,291 0 0 2,460 5 Ceiling Load -1,406 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 49,539 43 0 0 Ventilation Load 0 -36,186 78.39 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -3,400 -3,400 7.36
Ov/Undr Sizing 20,166 20,166 18 20,166 41 Exhaust Heat 2,693 -5.83 ENGINEERING CKS
Exhaust Heat -2,176 -2,176 -2 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,661 1 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 54.7 54.7
Duct Heat Pkup 0 0 0 System Plenum Heat 3,039 -6.58 cfm/ft² 1.20 1.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 295.31
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 245.41
Btu/hr·ft² 48.90 -19.82
Grand Total ==> 52,560 10,138 113,898 100.00 49,135 100.00 Grand Total ==> -7,742 -46,162 100.00 No. People 20

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 9.5 113.9 76.0 2,803 80.6 63.6 79.2 54.4 48.4 51.3 Floor 2,329 Main Htg -46.2 2,803 55.1 73.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 9.5 113.9 Roof 2,329 0 0 Humidif 0.0 0 0.0 0.0
Wall 914 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -46.2

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 13 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 014 REC POSTQUIRURGICA

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 84 OADB: 44 SADB 55.0 70.0
Ra Plenum 78.8 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 72.3 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 84.2 44.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.3 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.9 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 2,721 2,721 2 0 0 Roof Cond 0 -3,491 5.88
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 486 -18 468 0 2,346 6 Wall Cond -1,992 -2,310 3.89
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,513 2,513
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,513 2,513
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,513 2,513
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 486 2,703 3,189 2 2,346 6 Sub Total ==> -1,992 -5,801 9.77 Nom Vent 2,513 2,513
AHU Vent 2,513 2,513
Internal Loads Internal Loads Infil 0 0
Lights 18,530 0 18,530 12 18,530 46 Lights 18,530 18,530 -31.22 MinStop/Rh 0 0
People 4,000 0 4,000 3 2,000 5 People 2,000 2,000 -3.37 Return 2,513 2,513
Misc 9,265 0 9,265 6 9,265 23 Misc 9,265 9,265 -15.61 Exhaust 2,513 2,513
Sub Total ==> 31,795 0 31,795 21 29,795 74 Sub Total ==> 29,795 29,795 -50.20 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,710 -2,710 0 0 7,960 20 Ceiling Load -3,985 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 114,063 75 0 0 Ventilation Load 0 -59,354 100.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 2,978 2 RA Preheat Diff. -23,818 40.13 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 100.0 100.0
Duct Heat Pkup 0 0 0 System Plenum Heat -176 0.30 cfm/ft² 1.85 1.85
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 198.35
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 107.14
Btu/hr·ft² 112.00 -43.73
Grand Total ==> 34,991 -6 152,026 100.00 40,101 100.00 Grand Total ==> 23,818 -59,354 100.00 No. People 8

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 12.7 152.0 63.5 2,513 84.2 68.6 102.0 53.7 47.0 47.0 Floor 1,357 Main Htg -59.4 2,513 44.4 70.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -21.6 2,513 44.4 53.7
ExFlr 0
Total 12.7 152.0 Roof 1,357 0 0 Humidif 0.0 0 0.0 0.0
Wall 620 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -59.4

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 14 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 015 CEYE

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 92 OADB: 44 SADB 58.5 73.3
Ra Plenum 79.2 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 74.0 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 83.8 45.5
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.3 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.9 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 5,406 5,406 3 0 0 Roof Cond 0 -5,787 6.24
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 3,606 3,606
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 3,606 3,606
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 3,606 3,606
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 5,406 5,406 3 0 0 Sub Total ==> 0 -5,787 6.24 Nom Vent 3,457 3,457
AHU Vent 3,457 3,457
Internal Loads Internal Loads Infil 0 0
Lights 22,064 0 22,064 12 22,064 43 Lights 13,909 13,909 -15.01 MinStop/Rh 0 0
People 9,550 0 9,550 5 5,000 10 People 3,500 3,500 -3.78 Return 3,606 3,606
Misc 8,689 0 8,689 5 8,870 17 Misc 6,831 6,831 -7.37 Exhaust 3,457 3,457
Sub Total ==> 40,303 0 40,303 23 35,935 70 Sub Total ==> 24,240 24,240 -26.16 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 3,690 -3,690 0 0 11,077 21 Ceiling Load -6,605 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 123,287 69 0 0 Ventilation Load 0 -81,647 88.10 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -28,662 -28,662 30.93
Ov/Undr Sizing 4,613 4,613 3 4,613 9 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 4,274 2 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 95.9 95.9
Duct Heat Pkup 0 0 0 System Plenum Heat -819 0.88 cfm/ft² 1.60 1.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 243.25
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 151.76
Btu/hr·ft² 79.07 -41.19
Grand Total ==> 48,606 1,716 177,883 100.00 51,624 100.00 Grand Total ==> -11,027 -92,674 100.00 No. People 20

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 14.8 177.9 82.5 3,606 83.8 68.2 100.1 57.2 51.2 58.0 Floor 2,250 Main Htg -92.7 3,606 45.5 73.3
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -39.1 3,606 45.5 57.2
ExFlr 0
Total 14.8 177.9 Roof 2,250 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -92.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 15 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 016 SALA DE EXPULSION

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 87 OADB: 44 SADB 67.0 70.0
Ra Plenum 78.8 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 71.6 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 84.2 44.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.3 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.9 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 945 945 1 0 0 Roof Cond 0 -1,072 1.56
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,916 2,916
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,916 2,916
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,916 2,916
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 945 945 1 0 0 Sub Total ==> 0 -1,072 1.56 Nom Vent 2,916 2,916
AHU Vent 2,916 2,916
Internal Loads Internal Loads Infil 0 0
Lights 5,687 0 5,687 4 5,687 46 Lights 5,687 5,687 -8.26 MinStop/Rh 0 0
People 2,500 0 2,500 2 1,250 10 People 1,250 1,250 -1.81 Return 2,916 2,916
Misc 2,843 0 2,843 2 2,843 23 Misc 2,843 2,843 -4.13 Exhaust 2,916 2,916
Sub Total ==> 11,030 0 11,030 8 9,780 79 Sub Total ==> 9,780 9,780 -14.20 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 944 -944 0 0 2,564 21 Ceiling Load -1,223 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 127,791 89 0 0 Ventilation Load 0 -68,874 100.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 3,456 2 RA Preheat Diff. -8,557 12.42 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 100.0 100.0
Duct Heat Pkup 0 0 0 System Plenum Heat -152 0.22 cfm/ft² 7.00 7.00
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 244.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 34.90
Btu/hr·ft² 343.82 -165.34
Grand Total ==> 11,975 1 143,222 100.00 12,344 100.00 Grand Total ==> 8,557 -68,874 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 11.9 143.2 48.1 2,916 84.2 68.6 102.0 65.7 52.0 47.7 Floor 417 Main Htg -68.9 2,916 44.4 70.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -57.4 2,916 44.4 65.7
ExFlr 0
Total 11.9 143.2 Roof 417 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -68.9

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 16 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 017 TOCOCIRUGIA

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 87 OADB: 44 SADB 55.0 70.0
Ra Plenum 78.8 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 71.6 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 84.2 44.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.3 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.9 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 2,230 2,230 2 0 0 Roof Cond 0 -2,528 5.92
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 1,807 1,807
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 1,807 1,807
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 1,807 1,807
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 2,230 2,230 2 0 0 Sub Total ==> 0 -2,528 5.92 Nom Vent 1,807 1,807
AHU Vent 1,807 1,807
Internal Loads Internal Loads Infil 0 0
Lights 13,416 0 13,416 13 13,416 48 Lights 13,416 13,416 -31.44 MinStop/Rh 0 0
People 3,000 0 3,000 3 1,500 5 People 1,500 1,500 -3.51 Return 1,807 1,807
Misc 6,708 0 6,708 6 6,708 24 Misc 6,708 6,708 -15.72 Exhaust 1,807 1,807
Sub Total ==> 23,125 0 23,125 22 21,625 78 Sub Total ==> 21,625 21,625 -50.67 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2,228 -2,228 0 0 6,048 22 Ceiling Load -2,886 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 78,708 74 0 0 Ventilation Load 0 -42,679 100.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 2,142 2 RA Preheat Diff. -18,739 43.91 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 100.0 100.0
Duct Heat Pkup 0 0 0 System Plenum Heat -358 0.84 cfm/ft² 1.84 1.84
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 204.16
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 111.04
Btu/hr·ft² 108.07 -43.43
Grand Total ==> 25,353 2 106,204 100.00 27,673 100.00 Grand Total ==> 18,739 -42,679 100.00 No. People 6

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 8.9 106.2 47.0 1,807 84.2 68.6 102.0 53.7 47.8 50.0 Floor 983 Main Htg -42.7 1,807 44.4 70.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -15.5 1,807 44.4 53.7
ExFlr 0
Total 8.9 106.2 Roof 983 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -42.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 17 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 018 PASILLOS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 92 / 63 / 55 OADB: 92 OADB: 44 SADB 55.0 72.1
Ra Plenum 79.3 67.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 79.3 67.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 80.8 64.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 18,622 18,622 37 0 0 Roof Cond 0 -9,617 75.91
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 991 198 1,189 2 988 3 Wall Cond -974 -1,189 9.39
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 1,771 1,771
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 1,771 1,771
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 1,771 1,771
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 991 18,820 19,811 40 988 3 Sub Total ==> -974 -10,806 85.30 Nom Vent 212 212
AHU Vent 212 212
Internal Loads Internal Loads Infil 0 0
Lights 18,383 0 18,383 37 18,383 59 Lights 5,408 5,408 -42.69 MinStop/Rh 0 0
People 4,500 0 4,500 9 2,500 8 People 750 750 -5.92 Return 1,771 1,771
Misc 4,596 0 4,596 9 4,596 15 Misc 1,352 1,352 -10.67 Exhaust 212 212
Sub Total ==> 27,479 0 27,479 55 25,479 82 Sub Total ==> 7,510 7,510 -59.28 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 4,488 -4,488 0 0 4,569 15 Ceiling Load -2,497 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 2,435 5 0 0 Ventilation Load 0 -4,998 39.45 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -7,500 -7,500 59.20
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 571 -4.51 ENGINEERING CKS
Exhaust Heat -1,027 -1,027 -2 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,049 2 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 12.0 12.0
Duct Heat Pkup 0 0 0 System Plenum Heat 2,554 -20.16 cfm/ft² 0.66 0.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 427.08
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 649.63
Btu/hr·ft² 18.47 -4.70
Grand Total ==> 32,958 13,305 49,748 100.00 31,036 100.00 Grand Total ==> -3,462 -12,669 100.00 No. People 10

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 4.2 49.8 48.8 1,771 80.8 60.1 60.8 54.4 49.2 54.4 Floor 2,693 Main Htg -12.7 1,771 64.4 72.1
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.2 49.8 Roof 2,693 0 0 Humidif 0.0 0 0.0 0.0
Wall 303 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -12.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 18 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 019 ENCAMADOS

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 17 Mo/Hr: 10 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 82 / 67 / 96 OADB: 82 OADB: 44 SADB 56.0 70.0
Ra Plenum 76.9 67.1
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 76.9 67.1
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 77.3 65.3
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.1 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.4 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 5,055 5,055 11 0 0 Roof Cond 0 -5,147 53.36
Glass Solar 16,042 0 16,042 33 16,042 43 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 1,357 0 1,357 3 1,357 4 Glass/Door Cond -3,939 -3,939 40.83
Cooling Heating
Wall Cond 1,636 406 2,042 4 1,866 5 Wall Cond -2,457 -3,150 32.66
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,244 2,244
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,244 2,244
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,244 2,244
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 19,036 5,461 24,497 51 19,266 52 Sub Total ==> -6,396 -12,235 126.85 Nom Vent 171 171
AHU Vent 171 171
Internal Loads Internal Loads Infil 0 0
Lights 9,838 0 9,838 20 9,838 26 Lights 9,838 9,838 -102.00 MinStop/Rh 0 0
People 7,650 0 7,650 16 4,250 11 People 4,250 4,250 -44.06 Return 2,244 2,244
Misc 2,460 0 2,460 5 2,460 7 Misc 2,460 2,460 -25.50 Exhaust 171 171
Sub Total ==> 19,948 0 19,948 42 16,548 44 Sub Total ==> 16,548 16,548 -171.56 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1,336 -1,336 0 0 1,448 4 Ceiling Load -1,336 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 2,702 6 0 0 Ventilation Load 0 -4,050 41.99 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 463 -4.80 ENGINEERING CKS
Exhaust Heat -475 -475 -1 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,330 3 RA Preheat Diff. -8,816 91.40 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 7.6 7.6
Duct Heat Pkup 0 0 0 System Plenum Heat -1,555 16.12 cfm/ft² 1.56 1.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 560.91
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 360.31
Btu/hr·ft² 33.30 -6.69
Grand Total ==> 40,320 3,650 48,001 100.00 37,262 100.00 Grand Total ==> 8,816 -9,645 100.00 No. People 17

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 4.0 48.0 43.2 2,244 77.3 60.8 69.8 55.4 52.8 67.9 Floor 1,441 Main Htg -9.7 2,244 65.3 70.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 4.0 48.0 Roof 1,441 0 0 Humidif 0.0 0 0.0 0.0
Wall 975 168 17 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -9.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 19 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 020

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 6 / 17 Mo/Hr: 6 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 92 / 63 / 55 OADB: 92 OADB: 44 SADB 56.0 75.7
Ra Plenum 82.9 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 74.0 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 75.6 67.8
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 8,979 8,979 7 0 0 Roof Cond 0 -8,249 18.45
Glass Solar 39,996 0 39,996 33 40,974 40 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 4,054 0 4,054 3 5,151 5 Glass/Door Cond -11,372 -11,372 25.43
Cooling Heating
Wall Cond 3,609 195 3,805 3 3,688 4 Wall Cond -7,256 -8,716 19.50
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 6,116 6,116
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 6,116 6,116
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 6,116 6,116
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 47,659 9,174 56,833 46 49,814 49 Sub Total ==> -18,628 -28,337 63.38 Nom Vent 528 528
AHU Vent 528 528
Internal Loads Internal Loads Infil 0 0
Lights 21,798 0 21,798 18 21,798 21 Lights 0 0 0.00 MinStop/Rh 0 0
People 29,426 0 29,426 24 16,446 16 People 0 0 0.00 Return 6,116 6,116
Misc 5,020 0 5,020 4 5,020 5 Misc 0 0 0.00 Exhaust 528 528
Sub Total ==> 56,243 0 56,243 46 43,263 43 Sub Total ==> 0 0 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 9,065 -9,065 0 0 8,500 8 Ceiling Load -9,554 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 8,463 7 0 0 Ventilation Load 0 -12,481 27.92 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -4,046 -4,046 9.05
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 906 1 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 8.6 8.6
Duct Heat Pkup 0 0 0 System Plenum Heat 154 -0.35 cfm/ft² 1.90 1.90
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 599.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 315.94
Btu/hr·ft² 37.98 -13.87
Grand Total ==> 112,968 108 122,446 100.00 101,577 100.00 Grand Total ==> -32,228 -44,710 100.00 No. People 67

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 10.2 122.5 106.0 6,116 75.6 60.4 70.4 55.8 52.9 67.4 Floor 3,224 Main Htg -44.7 6,116 67.8 75.7
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat 0.0 0 0.0 0.0
ExFlr 0
Total 10.2 122.5 Roof 3,224 0 0 Humidif 0.0 0 0.0 0.0
Wall 2,865 485 17 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -44.7

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 20 de 21
Zone Checksums
By BIP INGENIERIAS SC
Zone - 021

COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 15 Mo/Hr: 6 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 84 / 69 / 102 OADB: 87 OADB: 44 SADB 56.0 70.8
Ra Plenum 79.4 60.7
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 72.1 70.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 84.2 44.4
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.0 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 825 825 1 0 0 Roof Cond 0 -975 1.71
Glass Solar 0 0 0 0 0 0 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 0 0 0 0 0 0 Glass/Door Cond 0 0 0.00
Cooling Heating
Wall Cond 0 0 0 0 0 0 Wall Cond 0 0 0.00
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 2,341 2,341
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 2,341 2,341
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 2,341 2,341
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 0 825 825 1 0 0 Sub Total ==> 0 -975 1.71 Nom Vent 2,341 2,341
AHU Vent 2,341 2,341
Internal Loads Internal Loads Infil 0 0
Lights 4,460 0 4,460 3 4,460 13 Lights 3,718 3,718 -6.52 MinStop/Rh 0 0
People 2,450 0 2,450 2 1,250 4 People 1,000 1,000 -1.75 Return 2,341 2,341
Misc 2,026 0 2,026 1 2,044 6 Misc 1,859 1,859 -3.26 Exhaust 2,341 2,341
Sub Total ==> 8,936 0 8,936 7 7,754 22 Sub Total ==> 6,577 6,577 -11.53 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 860 -860 0 0 2,327 7 Ceiling Load -1,129 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 101,734 75 0 0 Ventilation Load 0 -55,298 96.96 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -7,182 -7,182 12.59
Ov/Undr Sizing 24,578 24,578 18 24,578 71 Exhaust Heat 0 0.00 ENGINEERING CKS
Exhaust Heat 0 0 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 347 0 RA Preheat Diff. 0 0.00 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 100.0 100.0
Duct Heat Pkup 0 0 0 System Plenum Heat -154 0.27 cfm/ft² 6.14 6.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 205.94
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 33.52
Btu/hr·ft² 358.02 -149.67
Grand Total ==> 34,374 -35 136,420 100.00 34,660 100.00 Grand Total ==> -1,735 -57,032 100.00 No. People 5

COOLING COIL SELECTION AREAS HEATING COIL SELECTION


Total Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Capacity Coil Airflow Ent Lvg
ton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) MBh cfm °F °F
Main Clg 11.4 136.4 59.7 2,341 84.2 68.6 102.0 55.8 48.0 47.5 Floor 381 Main Htg -57.0 2,341 44.4 70.8
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Part 0 Aux Htg 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Int Door 0 Preheat -24.7 2,341 44.4 55.8
ExFlr 0
Total 11.4 136.4 Roof 381 0 0 Humidif 0.0 0 0.0 0.0
Wall 0 0 0 Opt Vent 0.0 0 0.0 0.0
Ext Door 0 0 0 Total -57.0

Project Name: TRACE® 700 v6.3.4 calculated at 03:43 PM on 08/06/2020


Dataset Name: HOSPIOCOTLAN.trc Alternative - 1 System Checksums Report Página 21 de 21

You might also like