You are on page 1of 16

Zone Load Summary Analytical Space 2 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 65.83 Btu/hr-ft2
Time at Peak: 7/21 15:15:00
Floor Area per Capacity: 15.1903 ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.32 %
DB: 95.3 F Airflow per Floor Area: 2.995417
HR: 0.0149 lb/lb ft3/min-ft2
WB: 76.1 F Airflow per Capacity: 546.015673
ft3/min-ton
Zone Number of People: 1.0
DB: 75.0 F
HR: 0.0090 lb/lb
RH: 48.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 3,004 - 3,004 63.4
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 36 - - 36 0.8
Glass - Solar - 115 - 115 2.4
Door - 4 - 4 0.1
Wall - 62 - 62 1.3
Below-grade Wall - 0 - 0 0.0
Partition - 88 - 88 1.9
Other - Wall - 0 - 0 0.0
Exterior Floor - -150 - -150 -3.2
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 53 - 68 121 2.6
Subtotal 88 3,122 68 3,279 69.2

Internal Gains
People 175 76 200 451 9.5
Lights 246 0 - 246 5.2
Return Air - Lights 0 - - 0 0.0
Equipment 319 0 0 319 6.7
Subtotal 740 76 200 1,016 21.4

Systems
Zone Ventilation 197 - 256 453 9.6
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 197 0 256 453 9.6

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -8 - -8 -0.2
Grand Total 1,026 3,190 525 4,741 100.0
Zone Load Summary Zone 3 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 57.28 Btu/hr-ft2
Time at Peak: 7/21 15:15:00
Floor Area per Capacity: 17.4567 ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.41 %
DB: 95.3 F Airflow per Floor Area: 2.697411
HR: 0.0149 lb/lb ft3/min-ft2
WB: 76.1 F Airflow per Capacity: 565.056881
ft3/min-ton
Zone Number of People: 1.0
DB: 75.0 F
HR: 0.0088 lb/lb
RH: 47.9 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 6,414 - 6,414 71.8
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 53 - - 53 0.6
Glass - Solar - 197 - 197 2.2
Door - -28 - -28 -0.3
Wall - 73 - 73 0.8
Below-grade Wall - 0 - 0 0.0
Partition - 46 - 46 0.5
Other - Wall - 0 - 0 0.0
Exterior Floor - -401 - -401 -4.5
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 79 - 105 184 2.1
Subtotal 132 6,300 105 6,537 73.1

Internal Gains
People 175 103 200 478 5.3
Lights 532 0 - 532 6.0
Return Air - Lights 0 - - 0 0.0
Equipment 692 0 0 692 7.7
Subtotal 1,399 103 200 1,702 19.0

Systems
Zone Ventilation 304 - 405 709 7.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 304 0 405 709 7.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -10 - -10 -0.1
Grand Total 1,835 6,393 710 8,938 100.0
Zone Load Summary Analytical Space 1 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 76.21 Btu/hr-ft2
Time at Peak: 7/21 14:45:00
Floor Area per Capacity: 13.1219 ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.38 %
DB: 95.5 F Airflow per Floor Area: 3.433839
HR: 0.0149 lb/lb ft3/min-ft2
WB: 76.1 F Airflow per Capacity: 540.703118
ft3/min-ton
Zone Number of People: 1.0
DB: 75.0 F
HR: 0.0090 lb/lb
RH: 48.9 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 2,399 - 2,399 56.9
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 70 - - 70 1.7
Glass - Solar - 268 - 268 6.4
Door - -15 - -15 -0.3
Wall - 194 - 194 4.6
Below-grade Wall - 0 - 0 0.0
Partition - 2 - 2 0.0
Other - Wall - 0 - 0 0.0
Exterior Floor - -117 - -117 -2.8
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 59 - 76 136 3.2
Subtotal 129 2,731 76 2,936 69.6

Internal Gains
People 175 76 200 451 10.7
Lights 189 0 - 189 4.5
Return Air - Lights 0 - - 0 0.0
Equipment 245 0 0 245 5.8
Subtotal 609 76 200 885 21.0

Systems
Zone Ventilation 176 - 227 403 9.6
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 176 0 227 403 9.6

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -9 - -9 -0.2
Grand Total 915 2,798 503 4,216 100.0
Zone Load Summary Zone 7 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 73.40 Btu/hr-ft2
Time at Peak: 7/21 15:30:00
Floor Area per Capacity: 13.6248 ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.57 %
DB: 95.1 F Airflow per Floor Area: 3.290853
HR: 0.0149 lb/lb ft3/min-ft2
WB: 76.0 F Airflow per Capacity: 538.047777
ft3/min-ton
Zone Number of People: 1.0
DB: 75.0 F
HR: 0.0091 lb/lb
RH: 49.1 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 2,418 - 2,418 59.6
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -3 - -3 -0.1
Wall - 209 - 209 5.1
Below-grade Wall - 0 - 0 0.0
Partition - 142 - 142 3.5
Other - Wall - 0 - 0 0.0
Exterior Floor - -118 - -118 -2.9
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 59 - 76 135 3.3
Subtotal 59 2,648 76 2,783 68.5

Internal Gains
People 175 70 200 445 11.0
Lights 189 0 - 189 4.6
Return Air - Lights 0 - - 0 0.0
Equipment 245 0 0 245 6.0
Subtotal 609 70 200 879 21.7

Systems
Zone Ventilation 175 - 226 401 9.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 175 0 226 401 9.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -4 - -4 -0.1
Grand Total 843 2,715 502 4,060 100.0
Zone Load Summary Zone 6 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 54.05 Btu/hr-ft2
Time at Peak: 7/21 15:30:00
Floor Area per Capacity: 18.5000
Outside ft2/kBtu-hr
DB: 95.1 F Outdoor Air Percentage: 3.60 %
HR: 0.0149 lb/lb Airflow per Floor Area: 2.564660
WB: 76.0 F ft3/min-ft2
Airflow per Capacity: 569.354101
Zone ft3/min-ton
DB: 75.0 F Number of People: 1.0
HR: 0.0088 lb/lb
RH: 47.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 6,442 - 6,442 77.1
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -50 - -50 -0.6
Wall - 0 - 0 0.0
Below-grade Wall - 0 - 0 0.0
Partition - -128 - -128 -1.5
Other - Wall - 0 - 0 0.0
Exterior Floor - -387 - -387 -4.6
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 0 - 0 0 0.0
Subtotal 0 5,876 0 5,876 70.4

Internal Gains
People 175 188 200 563 6.7
Lights 527 0 - 527 6.3
Return Air - Lights 0 - - 0 0.0
Equipment 685 0 0 685 8.2
Subtotal 1,387 188 200 1,775 21.3

Systems
Zone Ventilation 300 - 404 705 8.4
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 300 0 404 705 8.4

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -4 - -4 -0.1
Grand Total 1,688 6,059 604 8,351 100.0
Zone Load Summary Zone 4 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 66.10 Btu/hr-ft2
Time at Peak: 7/21 15:15:00
Floor Area per Capacity: 15.1292 ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.54 %
DB: 95.3 F Airflow per Floor Area: 3.004623
HR: 0.0149 lb/lb ft3/min-ft2
WB: 76.1 F Airflow per Capacity: 545.491838
ft3/min-ton
Zone Number of People: 2.0
DB: 75.0 F
HR: 0.0090 lb/lb
RH: 48.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 6,063 - 6,063 60.6
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 78 - - 78 0.8
Glass - Solar - 343 - 343 3.4
Door - -43 - -43 -0.4
Wall - 213 - 213 2.1
Below-grade Wall - 0 - 0 0.0
Partition - -30 - -30 -0.3
Other - Wall - 0 - 0 0.0
Exterior Floor - -328 - -328 -3.3
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 212 - 275 487 4.9
Subtotal 290 6,218 275 6,783 67.8

Internal Gains
People 350 114 400 864 8.6
Lights 693 0 - 693 6.9
Return Air - Lights 0 - - 0 0.0
Equipment 901 0 0 901 9.0
Subtotal 1,943 114 400 2,458 24.6

Systems
Zone Ventilation 340 - 442 783 7.8
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 340 0 442 783 7.8

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -15 - -15 -0.2
Grand Total 2,574 6,317 1,117 10,008 100.0
Zone Load Summary Zone 5 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 61.04 Btu/hr-ft2
Time at Peak: 7/21 15:00:00
Floor Area per Capacity: 16.3826 ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.06 %
DB: 95.5 F Airflow per Floor Area: 2.810985
HR: 0.0149 lb/lb ft3/min-ft2
WB: 76.1 F Airflow per Capacity: 552.616734
ft3/min-ton
Zone Number of People: 2.0
DB: 75.0 F
HR: 0.0089 lb/lb
RH: 48.4 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 6,050 - 6,050 67.3
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 108 - - 108 1.2
Glass - Solar - 466 - 466 5.2
Door - -27 - -27 -0.3
Wall - 379 - 379 4.2
Below-grade Wall - 0 - 0 0.0
Partition - -80 - -80 -0.9
Other - Wall - 0 - 0 0.0
Exterior Floor - -330 - -330 -3.7
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 111 - 146 257 2.9
Subtotal 219 6,458 146 6,823 75.9

Internal Gains
People 350 107 400 856 9.5
Lights 306 0 - 306 3.4
Return Air - Lights 0 - - 0 0.0
Equipment 398 0 0 398 4.4
Subtotal 1,053 107 400 1,560 17.4

Systems
Zone Ventilation 269 - 352 621 6.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 269 0 352 621 6.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -14 - -14 -0.2
Grand Total 1,542 6,551 898 8,991 100.0
Zone Load Summary Zone 8 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 71.14 Btu/hr-ft2
Time at Peak: 7/21 15:45:00
Floor Area per Capacity: 14.0573 ft2/kBtu-hr
Outside Outdoor Air Percentage: 2.64 %
DB: 94.9 F Airflow per Floor Area: 3.301701
HR: 0.0149 lb/lb ft3/min-ft2
WB: 75.9 F Airflow per Capacity: 556.958708
ft3/min-ton
Zone Number of People: 4.0
DB: 75.0 F
HR: 0.0089 lb/lb
RH: 48.3 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 10,197 - 10,197 54.8
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 538 - - 538 2.9
Glass - Solar - 2,415 - 2,415 13.0
Door - 285 - 285 1.5
Wall - 805 - 805 4.3
Below-grade Wall - 0 - 0 0.0
Partition - -198 - -198 -1.1
Other - Wall - 0 - 0 0.0
Exterior Floor - -107 - -107 -0.6
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 219 - 292 511 2.7
Subtotal 757 13,397 292 14,446 77.6

Internal Gains
People 700 98 800 1,598 8.6
Lights 633 0 - 633 3.4
Return Air - Lights 0 - - 0 0.0
Equipment 823 0 0 823 4.4
Subtotal 2,156 98 800 3,054 16.4

Systems
Zone Ventilation 476 - 636 1,112 6.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 476 0 636 1,112 6.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -6 - -6 -0.0
Grand Total 3,388 13,489 1,728 18,606 100.0
Zone Load Summary Analytical Space 2 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -63.85 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.32 %
DB: 8.4 F Airflow per Floor Area: 1.670601
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0048 lb/lb
RH: 30.8 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -3,421 - -3,421 74.4
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -162 - - -162 3.5
Glass - Solar - 0 - 0 0.0
Door - -13 - -13 0.3
Wall - -241 - -241 5.2
Below-grade Wall - 0 - 0 0.0
Partition - -91 - -91 2.0
Other - Wall - 0 - 0 0.0
Exterior Floor - -25 - -25 0.6
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -187 - -48 -235 5.1
Subtotal -349 -3,792 -48 -4,189 91.1

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -324 - -83 -408 8.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -324 0 -83 -408 8.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 0.0
Grand Total -673 -3,794 -131 -4,598 100.0
Zone Load Summary Zone 3 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -59.06 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.41 %
DB: 8.4 F Airflow per Floor Area: 1.546725
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0048 lb/lb
RH: 30.9 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -7,300 - -7,300 79.2
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -317 - - -317 3.4
Glass - Solar - 0 - 0 0.0
Door - 11 - 11 -0.1
Wall - -336 - -336 3.6
Below-grade Wall - 0 - 0 0.0
Partition - -5 - -5 0.1
Other - Wall - 0 - 0 0.0
Exterior Floor - -26 - -26 0.3
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -280 - -72 -352 3.8
Subtotal -598 -7,657 -72 -8,327 90.4

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -703 - -180 -883 9.6
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -703 0 -180 -883 9.6

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -4 - -4 0.0
Grand Total -1,301 -7,661 -252 -9,214 100.0
Zone Load Summary Analytical Space 1 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -70.18 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.38 %
DB: 8.4 F Airflow per Floor Area: 1.832791
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0048 lb/lb
RH: 30.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -2,784 - -2,784 71.7
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -165 - - -165 4.3
Glass - Solar - 0 - 0 0.0
Door - -7 - -7 0.2
Wall - -276 - -276 7.1
Below-grade Wall - 0 - 0 0.0
Partition - -50 - -50 1.3
Other - Wall - 0 - 0 0.0
Exterior Floor - -21 - -21 0.5
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -210 - -54 -264 6.8
Subtotal -376 -3,138 -54 -3,568 91.9

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -249 - -64 -313 8.1
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -249 0 -64 -313 8.1

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 0.0
Grand Total -625 -3,140 -117 -3,882 100.0
Zone Load Summary Zone 7 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -68.72 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.57 %
DB: 8.4 F Airflow per Floor Area: 1.793565
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0047 lb/lb
RH: 30.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -2,793 - -2,793 73.5
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -8 - -8 0.2
Wall - -305 - -305 8.0
Below-grade Wall - 0 - 0 0.0
Partition - -94 - -94 2.5
Other - Wall - 0 - 0 0.0
Exterior Floor - -22 - -22 0.6
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -210 - -54 -264 6.9
Subtotal -210 -3,223 -54 -3,487 91.7

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -249 - -63 -313 8.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -249 0 -63 -313 8.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 0.0
Grand Total -460 -3,225 -117 -3,802 100.0
Zone Load Summary Zone 6 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -53.50 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.60 %
DB: 8.4 F Airflow per Floor Area: 1.409256
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0048 lb/lb
RH: 31.2 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -7,340 - -7,340 88.8
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -14 - -14 0.2
Wall - 0 - 0 0.0
Below-grade Wall - 0 - 0 0.0
Partition - 11 - 11 -0.1
Other - Wall - 0 - 0 0.0
Exterior Floor - -42 - -42 0.5
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 0 - 0 0 0.0
Subtotal 0 -7,386 0 -7,386 89.4

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -696 - -181 -877 10.6
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -696 0 -181 -877 10.6

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -3 - -3 0.0
Grand Total -696 -7,388 -181 -8,266 100.0
Zone Load Summary Zone 4 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -63.38 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.54 %
DB: 8.4 F Airflow per Floor Area: 1.651872
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 2.0
Zone
DB: 70.0 F
HR: 0.0047 lb/lb
RH: 30.6 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -6,924 - -6,924 72.2
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -465 - - -465 4.8
Glass - Solar - 0 - 0 0.0
Door - 22 - 22 -0.2
Wall - -718 - -718 7.5
Below-grade Wall - 0 - 0 0.0
Partition - 37 - 37 -0.4
Other - Wall - 0 - 0 0.0
Exterior Floor - -25 - -25 0.3
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -753 - -191 -944 9.8
Subtotal -1,217 -7,609 -191 -9,018 94.0

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -457 - -116 -574 6.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -457 0 -116 -574 6.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -4 - -4 0.0
Grand Total -1,675 -7,613 -307 -9,596 100.0
Zone Load Summary Zone 5 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -60.18 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 3.06 %
DB: 8.4 F Airflow per Floor Area: 1.592097
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 2.0
Zone
DB: 70.0 F
HR: 0.0049 lb/lb
RH: 31.4 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -6,959 - -6,959 78.5
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -466 - - -466 5.3
Glass - Solar - 0 - 0 0.0
Door - 11 - 11 -0.1
Wall - -720 - -720 8.1
Below-grade Wall - 0 - 0 0.0
Partition - 52 - 52 -0.6
Other - Wall - 0 - 0 0.0
Exterior Floor - -25 - -25 0.3
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -395 - -104 -498 5.6
Subtotal -861 -7,642 -104 -8,607 97.1

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -202 - -53 -255 2.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -202 0 -53 -255 2.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 0.0
Grand Total -1,063 -7,644 -157 -8,864 100.0
Zone Load Summary Zone 8 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -62.36 Btu/hr-ft2
Time at Peak: 1/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 2.64 %
DB: 8.4 F Airflow per Floor Area: 1.652457
HR: 0.0012 lb/lb ft3/min-ft2
WB: 8.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 4.0
Zone
DB: 70.0 F
HR: 0.0049 lb/lb
RH: 31.5 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -12,734 - -12,734 78.1
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction -1,058 - - -1,058 6.5
Glass - Solar - 0 - 0 0.0
Door - -277 - -277 1.7
Wall - -1,124 - -1,124 6.9
Below-grade Wall - 0 - 0 0.0
Partition - 143 - 143 -0.9
Other - Wall - 0 - 0 0.0
Exterior Floor - 2 - 2 -0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -787 - -207 -995 6.1
Subtotal -1,845 -13,990 -207 -16,043 98.4

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -209 - -55 -264 1.6
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -209 0 -55 -264 1.6

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -4 - -4 0.0
Grand Total -2,054 -13,994 -262 -16,310 100.0

You might also like