Air System Design Load Summary for FF- AHU-04 w heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:34AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 49.2 C / 29.9 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 33 m 5298 - 33 m - -
Wall Transmission 182 m 3042 - 182 m 977 -
Roof Transmission 337 m 9935 - 337 m 2099 -
Window Transmission 33 m 2845 - 33 m 1001 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 19 m 322 - 19 m 0 -
Partitions 174 m 3454 - 174 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 8399 W 7538 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6300 W 6012 - 0 0 -
People 58 3632 3485 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 6312 523 0% 0 0
>> Total Zone Loads - 48391 4007 - 4077 0
Zone Conditioning - 52919 4007 - 2810 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4674 L/s 0 - 586 L/s 0 -
Ventilation Load 534 L/s 16607 15551 67 L/s 628 0
Supply Fan Load 4674 L/s 2619 - 586 L/s -787 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 484 - 1% 41 -
>> Total System Loads - 72629 19558 - 2691 0
Central Cooling Coil - 74186 19558 - -4202 0
Central Heating Coil - -1557 - - 0 -
Humidification Load - - 0 - - 0
Terminal Reheat Coils - 0 - - 6892 -
>> Total Conditioning - 72629 19558 - 2691 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.3 Page 1 of 1