Air System Sizing Summary for Chambre froide

Project Name: BATIMENT2 10/02/2022


Prepared by: ingenios 01:33

Air System Information


Air System Name: Chambre froide Number of zones: 1
Air System Type: Single Zone CAV Floor Area: 11,9 sqm
Location: Abidjan, Ivory Coast

Sizing Calculation Information


Calculation Months: Jan to Dec Calculation method: Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load: 28,7 kW Load occurs at: Jun 1500
Total coil load: 28,7 kW OA DB / WB: 32,2/28,3
Sensible coil load: 10,5 kW Entering DB / WB: 32,2/28,3
Coil airflow: 453 L/s Leaving DB / WB: 13,0/13,0
Sensible heat ratio: 0,366 Coil ADP: 10,8 C
Area per unit load: 0,4 sqm/kW Bypass Factor: 0,100
Load per unit area: 2413,2 W/sqm Resulting RH: 91 %
Design supply temp: 10,0 C

Supply Fan Sizing Data


Actual max airflow: 453 L/s Fan motor BHP: 0,00 BHP
Standard airflow: 452 L/s Fan motor kW: 0,00 kW
Actual max airflow per unit area: 38,10 L/(s-sqm) Fan static: 0,00 Pa

Outdoor Ventilation Air Data


Design airflow: 453 L/s Airflow per person: 226,53 L/s/person
Airflow per unit floor area: 38,10 L/(s-sqm)

Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Chambre froide 1,0 453 Jul 1600 0,0 11,9 38,10

Block Load 4.15 Page 1 of 3


System Design Load Summary for Chambre froide
Project Name: BATIMENT2 10/02/2022
Prepared by: ingenios 01:33

DESIGN COOLING DESIGN HEATING


Jun 1500 Design Heating Day
OA DB / WB 32,2 C / 28,3 C OA DB / WB 19,4 C / 13,3 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 0 sqm 0 - 0 sqm - -
Wall Transmission 56 sqm 281 - 56 sqm 0 -
Roof Transmission 12 sqm 462 - 12 sqm 0 -
Window Transmission 0 sqm 0 - 0 sqm 0 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 2 sqm 19 - 2 sqm 0 -
Floor Transmission 12 sqm 0 - 12 sqm 0 -
Partitions/Ceilings 0 sqm 0 - 0 sqm 0 -
Overhead Lighting 24 W 24 - 0W 0 -
Electric Equipment 0W 0 - 0W 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>>Total Zone Loads - 959 267 - 0 0
Thermostat and Pulldown Adjustment - 43 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 453 L/s 9507 17922 453 L/s -4608 0
Supply Fan Load 453 L/s 0 - 453 L/s 0 -
>> Total System Loads - 10509 18189 - -4608 0
Central Cooling Coil - 10509 18189 - -4608 0
>> Total Coil Loads - 10509 18189 - -4608 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 3


System PsychrometricsforChambre froide
Project Name: BATIMENT2 10/02/2022
Prepared by: ingenios 01:33

Location: Abidjan, Ivory Coast


Altitude: 19,8 m
Data for: Jun DESIGN COOLING DAY, 1500
0,025
1. Outdoor Air
2.CentralCoolingCoilOutlet
3. Supply Fan Outlet
4. Room Air
1

0,020

Specific Humidity ( kg/kg )


0,015

4
0,010
3
2

0,005

0,000
0 10 20 30
Temperature (C)

Block Load 4.15 Page 3 of 3