ACCA Climate Data

ACCA Climate Data and Cover Sheet Design Address


4069 Borneo St.
Bay St. Louis

Form J1 Abridged Verson of Manual J, 8th Edition

FORM J1AE ? ABRIDGED VERSION of MANUAL J, 8TH EDITION


Project Design State & City Mississippi Biloxi, Keesler AFB
Indoor Design Heating db 70 @ Outdoor (Winter) 99% db 35 HTD 35
Indoor Design Cooling db 75 @ Outdoor (Summer) 1% db 91 CTD 16
Indoor Design Cooling RH 0.5 Grains Difference 63 Daily Range Medium
Latitude 30 Elevation 26 ACF 1

Page 1
Heat Loss and Gain

Manual J as Prepared Per ACCA Manual J Spreadsheets

Summer Outdoor 91 Summer Indoor 75 Design Grains 63 Daily Range Medium


Winter Outdoor 35 Winder Indoor 70 Cooling RH 50.00% Elevation 26

Cooling Loads Heating Loads


Name Area Sensible Latent Name Area Heat Loss
Windows & Glass Doors 242 5091 Windows & Glass Doors 242 3836
Skylights 0 0 Skylights 0 0
Doors 189 1988 Doors 189 1980
Walls 2410 9190 Walls 2410 4264
Floors 1463 2901 Floors 1463 3045
Ceiling 1600 2675 Ceiling 1600 1801
Ventilation 0 0 Ventilation 0 0
Infiltration 0 3312 2308 Infiltration 0 2292
Internal 0 2405 2172 Internal 0 0
Duct 0 3647 2308 Duct 0 1325
Blower Heat 0 0 Blower Heat 0 0
AED Excursion 0 0 AED Excursion 0 0
Total 5904 31210 6787 Total 5904 18544

Page 2
Manual S

Equipment Selection as Per Manual S ACCA Spreadsheet

BTUH Nom.Tons Design Temp Outdoor Indoor


Total Heat Loss 18544 Winter 35 70
Total Heat Gain 37997 3.2 Summer 91 75
Sensible Heat Gain 31210 ID design RH 50.00% 63F WB
Latent Heat Gain 6787 Altitude 26
Sensible/Total Ratio 0.82
Target Cooling TD 21

Manufacturer's Equipment Specification


Equipment Manufacturer
Model No. BTU output
Furnace 20000 Cooling Capacity @ OD Design Temp
Boiler Total Sensible Latent
Heat Pump/AC 3.5 Ton Unit 42000 35000 7000
Evaporator
Air Handler
Total Capacity with Altitude Correction 20000 42000 35000 7000
Selected Equipment Size OK OK OK OK

Page 3
Manual D

Manual D Duct Sizing Per ACCA Spreadsheet

Total Sq ft Tonnage of Unit CFM per ton Total CFM


CFM/Sq Ft
1,881 3.5000 400 1400 0.74
CPL ASP
Longest Supply Longest Return
1400 700 467 Total Heat Loss Total Heat Gain
Index # - 0.1 0.05 0.05 0.05 18,544 37997
Room Name Sq Feet Req CFM Supply Ducts Return Duct
Return Duct
Return
if 2 DuctRoom
if 3 Heat Loss Room Heat Gain

Bed 2 137 102 7 in 20 18 16 1,350.63 2,767.43


Bath 1 50 37 5 in 492.93 1,010.01
Bed 1 150 112 8 in 1,478.79 3,030.03
Living Room 221 164 9 in 2,178.75 4,464.24
Kitchen 158 118 8 in 1,557.66 3,191.63
Pantry 43 32 5 in 423.92 868.61
Master 168 125 8 in 1,656.25 3,393.63
Hall 77 57 6 in 759.11 1,555.42
Closet 55 41 6 in 542.22 1,111.01
Master Bath 83 62 6 in 818.26 1,676.62
Bath 1 27 20 5 in 266.18 545.41
Bath 2 27 20 5 in 266.18 545.41
Loft 225 167 9 in 2,218.19 4,545.04
Loft 2 460 342 11 in 4,534.96 9,292.09

Page 4