Design Cooling Load Summary

By .

System - QUERETARO
Zone - QRO EDIF A BB L1 COFFE
Room - QRO EDIF A BB L1 COFFE

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 75.2 / 58.1 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 62 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 50.2 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 61 gr/lb
Floor Transmission 286 286 2.6 % Coil Sensible Load 11 MBh
Partition Transmission 452 452 4.2 % Coil Total Load 11 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 152 152 1.4 % Total Cooling Airflow 551 cfm
People 223 200 423 3.9 % Resulting Room Relative Humidity 38 %
Misc. Equipment Loads 9,276 0 9,276 85.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 10,389 200 10,589 97.2 %
General Engineering Checks
Ventilation Load 120 182 302 2.8 % Total Cooling Load 0.9 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 58 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 52 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 11 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 607 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 1.5 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 10,509 382 10,890 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 1 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 KITCHENETTE 160
Room - QRO EDIF A BB L1 KITCHENETTE 160

Coil Location - Room


Coil Peak Calculation Time: May, hour 12
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 6,454 6,454 11.5 % Coil Entering Air (DB / WB) 76.4 / 60.6 F
Glass Transmission 784 784 1.4 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 4,075 4,075 7.3 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 7,885 7,885 14.1 % Coil Sensible Load 48 MBh
Partition Transmission 1,744 1,744 3.1 % Coil Total Load 56 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 3,764 3,764 6.7 % Total Cooling Airflow 2,367 cfm
People 5,194 4,800 9,994 17.9 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 14,718 0 14,718 26.3 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 44,618 4,800 49,418 88.3 %
General Engineering Checks
Ventilation Load 2,987 3,536 6,523 11.7 % Total Cooling Load 4.7 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 296 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 1,382 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 508 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.6 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 47,606 8,336 55,942 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 2 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 LOUD LOUNGE 161
Room - QRO EDIF A BB L1 LOUD LOUNGE 161

Coil Location - Room


Coil Peak Calculation Time: May, hour 12
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 4,774 4,774 8.0 % Coil Entering Air (DB / WB) 76.3 / 60.5 F
Glass Transmission 1,173 1,173 2.0 % Coil Entering Humidity Ratio 72 gr/lb
Wall Transmission 8,723 8,723 14.7 % Coil Leaving Air (DB / WB) 54.0 / 51.5 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 8,284 8,284 13.9 % Coil Sensible Load 51 MBh
Partition Transmission 1,191 1,191 2.0 % Coil Total Load 59 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 3,937 3,937 6.6 % Total Cooling Airflow 2,545 cfm
People 5,186 4,800 9,986 16.8 % Resulting Room Relative Humidity 43 %
Misc. Equipment Loads 14,707 0 14,707 24.7 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 47,975 4,800 52,775 88.7 %
General Engineering Checks
Ventilation Load 3,049 3,661 6,710 11.3 % Total Cooling Load 5.0 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 293 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 1,452 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 513 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 51,025 8,461 59,486 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 3 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 MEETING ROOM 152
Room - QRO EDIF A BB L1 MEETING ROOM 152

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 1,165 1,165 11.2 % Coil Entering Air (DB / WB) 76.5 / 61.0 F
Glass Transmission 389 389 3.7 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 768 768 7.4 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 736 736 7.1 % Coil Sensible Load 9 MBh
Partition Transmission 511 511 4.9 % Coil Total Load 10 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 400 400 3.8 % Total Cooling Airflow 425 cfm
People 1,346 1,200 2,546 24.5 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 2,704 0 2,704 26.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 8,020 1,200 9,220 88.6 %
General Engineering Checks
Ventilation Load 561 621 1,182 11.4 % Total Cooling Load 0.9 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 155 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 135 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 491 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.0 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 8,580 1,821 10,402 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 4 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 OF 153 A 155
Room - QRO EDIF A BB L1 OF 153 A 155

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 583 583 10.1 % Coil Entering Air (DB / WB) 76.5 / 60.9 F
Glass Transmission 195 195 3.4 % Coil Entering Humidity Ratio 74 gr/lb
Wall Transmission 805 805 13.9 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 583 583 10.1 % Coil Sensible Load 5 MBh
Partition Transmission 468 468 8.1 % Coil Total Load 6 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 313 313 5.4 % Total Cooling Airflow 240 cfm
People 671 600 1,271 21.9 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 900 0 900 15.5 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 4,515 600 5,115 88.4 %
General Engineering Checks
Ventilation Load 315 358 673 11.6 % Total Cooling Load 0.5 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 221 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 107 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 497 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.9 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 4,830 958 5,789 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 5 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 OPEN OFICE 151
Room - QRO EDIF A BB L1 OPEN OFICE 151

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.7 / 60.9 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 74 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 2,277 2,277 17.3 % Coil Sensible Load 11 MBh
Partition Transmission 1,734 1,734 13.1 % Coil Total Load 13 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 1,259 1,259 9.5 % Total Cooling Airflow 544 cfm
People 1,357 1,200 2,557 19.4 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 3,620 0 3,620 27.4 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 10,247 1,200 11,447 86.8 %
General Engineering Checks
Ventilation Load 809 938 1,748 13.2 % Total Cooling Load 1.1 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 379 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 416 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 494 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 11,057 2,138 13,195 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 6 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 PANTRY 159
Room - QRO EDIF A BB L1 PANTRY 159

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 75.8 / 59.5 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 68 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.1 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 65 gr/lb
Floor Transmission 550 550 7.4 % Coil Sensible Load 7 MBh
Partition Transmission 724 724 9.7 % Coil Total Load 7 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 295 295 4.0 % Total Cooling Airflow 346 cfm
People 447 400 847 11.3 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 4,499 0 4,499 60.3 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 6,516 400 6,916 92.7 %
General Engineering Checks
Ventilation Load 236 312 548 7.3 % Total Cooling Load 0.6 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 162 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 101 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 556 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 4.6 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 6,752 712 7,464 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 7 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L1 RECEPTION 150
Room - QRO EDIF A BB L1 RECEPTION 150

Coil Location - Room


Coil Peak Calculation Time: May, hour 12
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 3,797 3,797 21.6 % Coil Entering Air (DB / WB) 76.0 / 59.9 F
Glass Transmission 583 583 3.3 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 3,718 3,718 21.1 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 1,530 1,530 8.7 % Coil Sensible Load 16 MBh
Partition Transmission 538 538 3.1 % Coil Total Load 18 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 748 748 4.2 % Total Cooling Airflow 788 cfm
People 1,290 1,200 2,490 14.1 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 2,642 0 2,642 15.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 14,845 1,200 16,045 91.1 %
General Engineering Checks
Ventilation Load 689 870 1,559 8.9 % Total Cooling Load 1.5 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 191 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 280 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 537 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 5.9 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 15,534 2,070 17,604 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 8 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L2 QUIET LOUNGE 250
Room - QRO EDIF A BB L2 QUIET LOUNGE 250

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 5,882 5,882 6.1 % Coil Entering Air (DB / WB) 76.7 / 61.1 F
Glass Transmission 1,570 1,570 1.6 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 1,843 1,843 1.9 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 7,062 7,062 7.4 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 13,419 13,419 14.0 % Coil Sensible Load 79 MBh
Partition Transmission 2,212 2,212 2.3 % Coil Total Load 96 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 7,462 7,462 7.8 % Total Cooling Airflow 3,896 cfm
People 11,341 10,000 21,341 22.3 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 22,655 0 22,655 23.6 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 73,444 10,000 83,444 87.0 %
General Engineering Checks
Ventilation Load 5,848 6,583 12,431 13.0 % Total Cooling Load 8.0 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 307 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 2,454 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 488 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.2 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 79,293 16,583 95,876 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 9 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L2 SLEEP ROOM 254
Room - QRO EDIF A BB L2 SLEEP ROOM 254

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.3 / 60.1 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 173 173 4.5 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 409 409 10.6 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 800 800 20.9 % Coil Sensible Load 3 MBh
Partition Transmission 563 563 14.7 % Coil Total Load 4 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 416 416 10.8 % Total Cooling Airflow 169 cfm
People 223 200 423 11.0 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 599 0 599 15.6 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 3,182 200 3,382 88.1 %
General Engineering Checks
Ventilation Load 200 256 456 11.9 % Total Cooling Load 0.3 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 446 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 143 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 528 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.0 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 3,382 456 3,838 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 10 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A BB L2 SLEEP ROOM 255 AL 258
Room - QRO EDIF A BB L2 SLEEP ROOM 255 AL 258

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.3 / 60.1 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 409 409 10.6 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 800 800 20.8 % Coil Sensible Load 3 MBh
Partition Transmission 734 734 19.1 % Coil Total Load 4 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 421 421 10.9 % Total Cooling Airflow 169 cfm
People 224 200 424 11.0 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 600 0 600 15.6 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 3,188 200 3,388 88.1 %
General Engineering Checks
Ventilation Load 200 256 456 11.9 % Total Cooling Load 0.3 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 446 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 143 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 528 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.0 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 3,387 456 3,844 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 11 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 ACCOUNTING 106
Room - QRO EDIF A L1 ACCOUNTING 106

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.5 / 60.6 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 5,982 5,982 18.9 % Coil Sensible Load 27 MBh
Partition Transmission 2,061 2,061 6.5 % Coil Total Load 32 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 3,429 3,429 10.8 % Total Cooling Airflow 1,336 cfm
People 2,758 2,400 5,158 16.3 % Resulting Room Relative Humidity 43 %
Misc. Equipment Loads 10,952 0 10,952 34.6 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 25,182 2,400 27,582 87.1 %
General Engineering Checks
Ventilation Load 1,850 2,221 4,071 12.9 % Total Cooling Load 2.6 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 415 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 1,094 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 506 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.4 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 27,032 4,621 31,652 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 12 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 COFFE
Room - QRO EDIF A L1 COFFE

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.3 / 60.6 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 777 777 9.3 % Coil Sensible Load 7 MBh
Partition Transmission 824 824 9.8 % Coil Total Load 8 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 422 422 5.0 % Total Cooling Airflow 354 cfm
People 898 800 1,698 20.2 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 3,757 0 3,757 44.8 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 6,679 800 7,479 89.2 %
General Engineering Checks
Ventilation Load 420 489 909 10.8 % Total Cooling Load 0.7 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 203 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 142 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 507 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 7,099 1,289 8,388 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 13 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 COMPUTER ROOM 131
Room - QRO EDIF A L1 COMPUTER ROOM 131

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 3,752 3,752 28.7 % Coil Entering Air (DB / WB) 75.8 / 59.7 F
Glass Transmission 392 392 3.0 % Coil Entering Humidity Ratio 69 gr/lb
Wall Transmission 1,046 1,046 8.0 % Coil Leaving Air (DB / WB) 54.0 / 51.2 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 65 gr/lb
Floor Transmission 259 259 2.0 % Coil Sensible Load 12 MBh
Partition Transmission 642 642 4.9 % Coil Total Load 13 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 560 560 4.3 % Total Cooling Airflow 596 cfm
People 925 800 1,725 13.2 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 3,663 0 3,663 28.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 11,239 800 12,039 92.1 %
General Engineering Checks
Ventilation Load 450 582 1,032 7.9 % Total Cooling Load 1.1 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 162 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 176 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 547 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 5.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 11,689 1,382 13,071 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 14 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 DRIVER TRAINING 137
Room - QRO EDIF A L1 DRIVER TRAINING 137

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 6,099 6,099 12.4 % Coil Entering Air (DB / WB) 76.4 / 60.6 F
Glass Transmission 782 782 1.6 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 3,224 3,224 6.6 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 5,827 5,827 11.9 % Coil Sensible Load 42 MBh
Partition Transmission 1,458 1,458 3.0 % Coil Total Load 49 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 3,320 3,320 6.8 % Total Cooling Airflow 2,075 cfm
People 5,043 4,400 9,443 19.2 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 13,366 0 13,366 27.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 39,119 4,400 43,519 88.7 %
General Engineering Checks
Ventilation Load 2,561 3,011 5,572 11.3 % Total Cooling Load 4.1 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 260 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 1,066 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 507 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.4 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 41,680 7,411 49,091 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 15 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 DRIVER WAITING 130
Room - QRO EDIF A L1 DRIVER WAITING 130

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.4 / 60.1 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 2,777 2,777 16.0 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 3,908 3,908 22.6 % Coil Sensible Load 15 MBh
Partition Transmission 2,241 2,241 12.9 % Coil Total Load 17 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 2,154 2,154 12.4 % Total Cooling Airflow 764 cfm
People 904 800 1,704 9.8 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 2,412 0 2,412 13.9 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 14,395 800 15,195 87.7 %
General Engineering Checks
Ventilation Load 926 1,200 2,125 12.3 % Total Cooling Load 1.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 495 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 715 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 529 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.2 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 15,321 2,000 17,321 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 16 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 LUNCH ROOM 105
Room - QRO EDIF A L1 LUNCH ROOM 105

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 2,671 2,671 4.3 % Coil Entering Air (DB / WB) 77.2 / 62.1 F
Glass Transmission 1,118 1,118 1.8 % Coil Entering Humidity Ratio 80 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 52.1 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 69 gr/lb
Floor Transmission 5,509 5,509 8.8 % Coil Sensible Load 48 MBh
Partition Transmission 1,599 1,599 2.5 % Coil Total Load 63 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 3,178 3,178 5.1 % Total Cooling Airflow 2,328 cfm
People 11,523 10,000 21,523 34.3 % Resulting Room Relative Humidity 47 %
Misc. Equipment Loads 18,283 0 18,283 29.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 43,881 10,000 53,881 85.8 %
General Engineering Checks
Ventilation Load 4,570 4,368 8,938 14.2 % Total Cooling Load 5.2 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 192 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 1,008 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 445 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 13.3 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 48,452 14,368 62,820 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 17 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 MEETENG ROOM 118
Room - QRO EDIF A L1 MEETENG ROOM 118

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 1,009 1,009 6.2 % Coil Entering Air (DB / WB) 76.3 / 60.6 F
Glass Transmission 337 337 2.1 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 2,713 2,713 16.5 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 1,195 1,195 7.3 % Coil Sensible Load 14 MBh
Partition Transmission 643 643 3.9 % Coil Total Load 16 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 636 636 3.9 % Total Cooling Airflow 695 cfm
People 1,782 1,600 3,382 20.6 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 4,789 0 4,789 29.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 13,104 1,600 14,704 89.7 %
General Engineering Checks
Ventilation Load 782 909 1,691 10.3 % Total Cooling Load 1.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 160 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 219 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 509 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 7.6 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 13,886 2,509 16,395 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 18 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 MEETING ROOM 102
Room - QRO EDIF A L1 MEETING ROOM 102

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 2,034 2,034 5.2 % Coil Entering Air (DB / WB) 76.6 / 60.9 F
Glass Transmission 698 698 1.8 % Coil Entering Humidity Ratio 74 gr/lb
Wall Transmission 1,813 1,813 4.6 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 4,826 4,826 12.4 % Coil Sensible Load 33 MBh
Partition Transmission 1,418 1,418 3.6 % Coil Total Load 39 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 2,746 2,746 7.0 % Total Cooling Airflow 1,606 cfm
People 4,582 4,000 8,582 22.0 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 12,147 0 12,147 31.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 30,265 4,000 34,265 87.7 %
General Engineering Checks
Ventilation Load 2,252 2,558 4,809 12.3 % Total Cooling Load 3.3 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 271 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 883 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 493 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.5 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 32,517 6,558 39,074 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 19 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 OFFICE 107 A 110 122 A 126
Room - QRO EDIF A L1 OFFICE 107 A 110 122 A 126

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 471 471 9.0 % Coil Entering Air (DB / WB) 76.7 / 61.2 F
Glass Transmission 195 195 3.7 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 568 568 10.9 % Coil Leaving Air (DB / WB) 54.0 / 51.8 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 68 gr/lb
Floor Transmission 614 614 11.8 % Coil Sensible Load 4 MBh
Partition Transmission 525 525 10.1 % Coil Total Load 5 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 310 310 6.0 % Total Cooling Airflow 210 cfm
People 671 600 1,271 24.4 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 600 0 600 11.5 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 3,954 600 4,554 87.4 %
General Engineering Checks
Ventilation Load 314 345 659 12.6 % Total Cooling Load 0.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 243 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 105 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 483 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.2 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 4,268 945 5,213 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 20 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 OFFICE 119 AL 121
Room - QRO EDIF A L1 OFFICE 119 AL 121

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 583 583 9.6 % Coil Entering Air (DB / WB) 76.4 / 60.7 F
Glass Transmission 195 195 3.2 % Coil Entering Humidity Ratio 74 gr/lb
Wall Transmission 1,292 1,292 21.4 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 614 614 10.1 % Coil Sensible Load 5 MBh
Partition Transmission 525 525 8.7 % Coil Total Load 6 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 305 305 5.0 % Total Cooling Airflow 253 cfm
People 666 600 1,266 20.9 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 598 0 598 9.9 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 4,777 600 5,377 88.8 %
General Engineering Checks
Ventilation Load 314 362 676 11.2 % Total Cooling Load 0.5 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 209 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 105 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 502 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.4 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 5,091 962 6,053 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 21 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 OFICINA
Room - QRO EDIF A L1 OFICINA

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 583 583 5.6 % Coil Entering Air (DB / WB) 76.6 / 61.1 F
Glass Transmission 195 195 1.9 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 2,255 2,255 21.7 % Coil Leaving Air (DB / WB) 54.0 / 51.8 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 895 895 8.6 % Coil Sensible Load 9 MBh
Partition Transmission 392 392 3.8 % Coil Total Load 10 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 480 480 4.6 % Total Cooling Airflow 421 cfm
People 1,340 1,200 2,540 24.5 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 1,799 0 1,799 17.3 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 7,939 1,200 9,139 88.1 %
General Engineering Checks
Ventilation Load 586 647 1,233 11.9 % Total Cooling Load 0.9 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 189 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 164 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 487 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.5 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 8,525 1,847 10,372 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 22 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 OPEN OFFICE 117
Room - QRO EDIF A L1 OPEN OFFICE 117

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.9 / 61.1 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 20,305 20,305 21.7 % Coil Sensible Load 78 MBh
Partition Transmission 3,820 3,820 4.1 % Coil Total Load 94 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 11,859 11,859 12.7 % Total Cooling Airflow 3,787 cfm
People 9,732 8,400 18,132 19.4 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 25,673 0 25,673 27.5 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 71,388 8,400 79,788 85.3 %
General Engineering Checks
Ventilation Load 6,372 7,339 13,710 14.7 % Total Cooling Load 7.8 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 477 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 3,714 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 486 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 11.4 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 77,760 15,739 93,499 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 23 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L1 RECEPTION AREA 101
Room - QRO EDIF A L1 RECEPTION AREA 101

Coil Location - Room


Coil Peak Calculation Time: May, hour 14
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 4,421 4,421 8.9 % Coil Entering Air (DB / WB) 76.4 / 60.1 F
Glass Transmission 1,620 1,620 3.3 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 10,890 10,890 21.9 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 11,173 11,173 22.4 % Coil Sensible Load 44 MBh
Partition Transmission 1,413 1,413 2.8 % Coil Total Load 50 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 5,953 5,953 12.0 % Total Cooling Airflow 2,187 cfm
People 2,671 2,400 5,071 10.2 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 3,090 0 3,090 6.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 41,231 2,400 43,631 87.6 %
General Engineering Checks
Ventilation Load 2,688 3,465 6,153 12.4 % Total Cooling Load 4.2 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 493 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 2,043 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 527 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.3 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 43,919 5,865 49,784 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 24 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 COFFE
Room - QRO EDIF A L2 COFFE

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 75.8 / 59.4 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 68 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.1 F
Roof Transmission 792 792 4.7 % Coil Leaving Humidity Ratio 64 gr/lb
Floor Transmission 1,512 1,512 9.0 % Coil Sensible Load 15 MBh
Partition Transmission 1,433 1,433 8.5 % Coil Total Load 17 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 816 816 4.9 % Total Cooling Airflow 783 cfm
People 896 800 1,696 10.1 % Resulting Room Relative Humidity 41 %
Misc. Equipment Loads 9,306 0 9,306 55.4 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 14,754 800 15,554 92.5 %
General Engineering Checks
Ventilation Load 539 720 1,259 7.5 % Total Cooling Load 1.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 197 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 277 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 559 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 4.7 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 15,293 1,520 16,813 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 25 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 PRINT 216
Room - QRO EDIF A L2 PRINT 216

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 75.6 / 59.3 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 68 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.0 F
Roof Transmission 198 198 2.6 % Coil Leaving Humidity Ratio 64 gr/lb
Floor Transmission 52 52 0.7 % Coil Sensible Load 7 MBh
Partition Transmission 513 513 6.7 % Coil Total Load 8 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 204 204 2.6 % Total Cooling Airflow 362 cfm
People 448 400 848 11.0 % Resulting Room Relative Humidity 41 %
Misc. Equipment Loads 5,404 0 5,404 70.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 6,818 400 7,218 93.7 %
General Engineering Checks
Ventilation Load 208 278 486 6.3 % Total Cooling Load 0.6 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 108 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 69 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 5 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 563 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 3.9 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 7,026 678 7,704 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 26 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 EXECUTIVE LUNCH ROOM 202
Room - QRO EDIF A L2 EXECUTIVE LUNCH ROOM 202

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 1,141 1,141 3.8 % Coil Entering Air (DB / WB) 76.8 / 61.5 F
Glass Transmission 389 389 1.3 % Coil Entering Humidity Ratio 77 gr/lb
Wall Transmission 220 220 0.7 % Coil Leaving Air (DB / WB) 54.0 / 51.9 F
Roof Transmission 1,427 1,427 4.8 % Coil Leaving Humidity Ratio 68 gr/lb
Floor Transmission 2,719 2,719 9.1 % Coil Sensible Load 24 MBh
Partition Transmission 1,076 1,076 3.6 % Coil Total Load 30 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 1,496 1,496 5.0 % Total Cooling Airflow 1,168 cfm
People 4,516 4,000 8,516 28.5 % Resulting Room Relative Humidity 46 %
Misc. Equipment Loads 9,041 0 9,041 30.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 22,025 4,000 26,025 87.0 %
General Engineering Checks
Ventilation Load 1,911 1,994 3,905 13.0 % Total Cooling Load 2.5 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 199 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 497 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 468 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 11.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 23,937 5,994 29,931 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 27 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 EXECUTIVE MEETING ROOM 210
Room - QRO EDIF A L2 EXECUTIVE MEETING ROOM 210

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 1,826 1,826 6.7 % Coil Entering Air (DB / WB) 76.8 / 61.3 F
Glass Transmission 782 782 2.9 % Coil Entering Humidity Ratio 76 gr/lb
Wall Transmission 352 352 1.3 % Coil Leaving Air (DB / WB) 54.0 / 51.8 F
Roof Transmission 1,948 1,948 7.1 % Coil Leaving Humidity Ratio 68 gr/lb
Floor Transmission 0 0 0.0 % Coil Sensible Load 22 MBh
Partition Transmission 0 0 0.0 % Coil Total Load 27 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 2,086 2,086 7.7 % Total Cooling Airflow 1,080 cfm
People 3,655 3,200 6,855 25.2 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 9,702 0 9,702 35.6 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 20,349 3,200 23,549 86.4 %
General Engineering Checks
Ventilation Load 1,774 1,924 3,698 13.6 % Total Cooling Load 2.3 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 297 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 675 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 475 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 11.2 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 22,123 5,124 27,248 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 28 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 EXECUTIVE OFFICE 213
Room - QRO EDIF A L2 EXECUTIVE OFFICE 213

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 1,365 1,365 4.9 % Coil Entering Air (DB / WB) 76.5 / 60.7 F
Glass Transmission 585 585 2.1 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 293 293 1.1 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 2,176 2,176 7.8 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 4,138 4,138 14.9 % Coil Sensible Load 24 MBh
Partition Transmission 1,242 1,242 4.5 % Coil Total Load 28 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 2,294 2,294 8.2 % Total Cooling Airflow 1,170 cfm
People 2,718 2,400 5,118 18.4 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 7,245 0 7,245 26.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 22,055 2,400 24,455 87.9 %
General Engineering Checks
Ventilation Load 1,552 1,830 3,381 12.1 % Total Cooling Load 2.3 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 326 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 757 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 504 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.0 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 23,607 4,230 27,836 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 29 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 EXECUTIVE RECEPTION 209
Room - QRO EDIF A L2 EXECUTIVE RECEPTION 209

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.7 / 60.8 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 73 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 1,530 1,530 11.6 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 2,913 2,913 22.1 % Coil Sensible Load 11 MBh
Partition Transmission 1,558 1,558 11.8 % Coil Total Load 13 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 1,607 1,607 12.2 % Total Cooling Airflow 549 cfm
People 1,130 1,000 2,130 16.2 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 1,607 0 1,607 12.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 10,346 1,000 11,346 86.0 %
General Engineering Checks
Ventilation Load 839 1,001 1,840 14.0 % Total Cooling Load 1.1 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 485 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 533 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 499 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.4 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 11,185 2,001 13,186 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 30 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 LOUNGE 201
Room - QRO EDIF A L2 LOUNGE 201

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 7,737 7,737 13.2 % Coil Entering Air (DB / WB) 76.3 / 59.9 F
Glass Transmission 2,673 2,673 4.6 % Coil Entering Humidity Ratio 69 gr/lb
Wall Transmission 1,292 1,292 2.2 % Coil Leaving Air (DB / WB) 54.0 / 51.2 F
Roof Transmission 6,781 6,781 11.6 % Coil Leaving Humidity Ratio 65 gr/lb
Floor Transmission 12,860 12,860 22.0 % Coil Sensible Load 52 MBh
Partition Transmission 702 702 1.2 % Coil Total Load 58 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 7,232 7,232 12.4 % Total Cooling Airflow 2,606 cfm
People 2,735 2,400 5,135 8.8 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 7,122 0 7,122 12.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 49,132 2,400 51,532 88.3 %
General Engineering Checks
Ventilation Load 2,961 3,896 6,857 11.7 % Total Cooling Load 4.9 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 483 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 2,352 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 536 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 7.7 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 52,093 6,296 58,389 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 31 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 MEETING ROOM 228
Room - QRO EDIF A L2 MEETING ROOM 228

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.7 / 61.3 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 76 gr/lb
Wall Transmission 229 229 1.8 % Coil Leaving Air (DB / WB) 54.0 / 51.8 F
Roof Transmission 539 539 4.2 % Coil Leaving Humidity Ratio 68 gr/lb
Floor Transmission 1,030 1,030 8.1 % Coil Sensible Load 10 MBh
Partition Transmission 603 603 4.8 % Coil Total Load 13 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 551 551 4.3 % Total Cooling Airflow 506 cfm
People 1,785 1,600 3,385 26.7 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 4,793 0 4,793 37.8 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 9,531 1,600 11,131 87.7 %
General Engineering Checks
Ventilation Load 755 809 1,564 12.3 % Total Cooling Load 1.1 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 178 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 188 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 478 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 10,286 2,409 12,695 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 32 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 OFICINA 219
Room - QRO EDIF A L2 OFICINA 219

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 583 583 10.5 % Coil Entering Air (DB / WB) 76.6 / 61.0 F
Glass Transmission 195 195 3.5 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 346 346 6.2 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 324 324 5.8 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 618 618 11.1 % Coil Sensible Load 5 MBh
Partition Transmission 327 327 5.9 % Coil Total Load 6 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 326 326 5.9 % Total Cooling Airflow 227 cfm
People 666 600 1,266 22.8 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 896 0 896 16.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 4,280 600 4,880 87.8 %
General Engineering Checks
Ventilation Load 321 360 680 12.2 % Total Cooling Load 0.5 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 244 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 113 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 490 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.6 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 4,600 960 5,560 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 33 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 OFICINA 220 AL 227
Room - QRO EDIF A L2 OFICINA 220 AL 227

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 583 583 11.2 % Coil Entering Air (DB / WB) 76.7 / 61.2 F
Glass Transmission 195 195 3.7 % Coil Entering Humidity Ratio 76 gr/lb
Wall Transmission 110 110 2.1 % Coil Leaving Air (DB / WB) 54.0 / 51.8 F
Roof Transmission 324 324 6.2 % Coil Leaving Humidity Ratio 68 gr/lb
Floor Transmission 618 618 11.9 % Coil Sensible Load 4 MBh
Partition Transmission 503 503 9.7 % Coil Total Load 5 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 330 330 6.3 % Total Cooling Airflow 208 cfm
People 669 600 1,269 24.4 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 599 0 599 11.5 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 3,929 600 4,529 87.1 %
General Engineering Checks
Ventilation Load 321 351 672 12.9 % Total Cooling Load 0.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 261 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 113 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 481 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.5 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 4,249 951 5,201 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 34 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 OFICINA 229 AL 233
Room - QRO EDIF A L2 OFICINA 229 AL 233

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 583 583 11.2 % Coil Entering Air (DB / WB) 76.7 / 61.2 F
Glass Transmission 195 195 3.7 % Coil Entering Humidity Ratio 76 gr/lb
Wall Transmission 110 110 2.1 % Coil Leaving Air (DB / WB) 54.0 / 51.8 F
Roof Transmission 324 324 6.2 % Coil Leaving Humidity Ratio 68 gr/lb
Floor Transmission 618 618 11.9 % Coil Sensible Load 4 MBh
Partition Transmission 503 503 9.7 % Coil Total Load 5 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 330 330 6.3 % Total Cooling Airflow 208 cfm
People 669 600 1,269 24.4 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 599 0 599 11.5 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 3,929 600 4,529 87.1 %
General Engineering Checks
Ventilation Load 321 351 672 12.9 % Total Cooling Load 0.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 261 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 113 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 481 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 10.5 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 4,249 951 5,201 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 35 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 OPEN OFFICE 218
Room - QRO EDIF A L2 OPEN OFFICE 218

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 15,526 15,526 7.1 % Coil Entering Air (DB / WB) 76.4 / 60.5 F
Glass Transmission 1,556 1,556 0.7 % Coil Entering Humidity Ratio 72 gr/lb
Wall Transmission 1,098 1,098 0.5 % Coil Leaving Air (DB / WB) 54.0 / 51.6 F
Roof Transmission 29,232 29,232 13.3 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 36,548 36,548 16.6 % Coil Sensible Load 189 MBh
Partition Transmission 3,871 3,871 1.8 % Coil Total Load 220 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 19,701 19,701 8.9 % Total Cooling Airflow 9,377 cfm
People 18,803 16,800 35,603 16.2 % Resulting Room Relative Humidity 43 %
Misc. Equipment Loads 50,428 0 50,428 22.9 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 176,763 16,800 193,563 87.9 %
General Engineering Checks
Ventilation Load 12,087 14,574 26,661 12.1 % Total Cooling Load 18.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 364 ft2/ton
Supply Fan Load 1 1 0.0 % Total Floor Area 6,684 ft2
Return Fan Load 1 1 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 511 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 8.8 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 188,851 31,374 220,225 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 36 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIF A L2 RECAMARA
Room - QRO EDIF A L2 RECAMARA

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.3 / 59.9 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 451 451 10.5 % Coil Leaving Humidity Ratio 65 gr/lb
Floor Transmission 860 860 20.1 % Coil Sensible Load 4 MBh
Partition Transmission 679 679 15.9 % Coil Total Load 4 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 468 468 10.9 % Total Cooling Airflow 190 cfm
People 225 200 425 9.9 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 902 0 902 21.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 3,584 200 3,784 88.5 %
General Engineering Checks
Ventilation Load 213 277 489 11.5 % Total Cooling Load 0.4 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 442 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 157 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 534 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 7.6 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 3,797 477 4,274 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 37 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B LUNCH ROOM 206 PA
Room - QRO EDIFICIO B LUNCH ROOM 206 PA

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 77.6 / 62.4 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 80 gr/lb
Wall Transmission 916 916 2.6 % Coil Leaving Air (DB / WB) 54.0 / 52.1 F
Roof Transmission 2,781 2,781 7.9 % Coil Leaving Humidity Ratio 69 gr/lb
Floor Transmission 5,312 5,312 15.0 % Coil Sensible Load 27 MBh
Partition Transmission 2,077 2,077 5.9 % Coil Total Load 35 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 2,890 2,890 8.2 % Total Cooling Airflow 1,274 cfm
People 6,291 5,600 11,891 33.7 % Resulting Room Relative Humidity 48 %
Misc. Equipment Loads 3,758 0 3,758 10.6 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 24,024 5,600 29,624 83.9 %
General Engineering Checks
Ventilation Load 2,919 2,751 5,670 16.1 % Total Cooling Load 2.9 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 330 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 971 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 1 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 433 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 15.6 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 26,943 8,351 35,294 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 38 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B OFFICE 209 Y 210 PA
Room - QRO EDIFICIO B OFFICE 209 Y 210 PA

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.0 / 60.0 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 70 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 375 375 4.4 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 1,414 1,414 16.8 % Coil Sensible Load 7 MBh
Partition Transmission 3,631 3,631 43.0 % Coil Total Load 8 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 386 386 4.6 % Total Cooling Airflow 375 cfm
People 672 600 1,272 15.1 % Resulting Room Relative Humidity 43 %
Misc. Equipment Loads 600 0 600 7.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 7,077 600 7,677 91.0 %
General Engineering Checks
Ventilation Load 336 422 758 9.0 % Total Cooling Load 0.7 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 186 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 131 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 534 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 6.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 7,414 1,022 8,436 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 39 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B PARTS COUNTER 106 PB
Room - QRO EDIFICIO B PARTS COUNTER 106 PB

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.2 / 60.1 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 71 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.3 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 66 gr/lb
Floor Transmission 1,295 1,295 13.1 % Coil Sensible Load 9 MBh
Partition Transmission 4,472 4,472 45.3 % Coil Total Load 10 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 857 857 8.7 % Total Cooling Airflow 436 cfm
People 680 600 1,280 13.0 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 906 0 906 9.2 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 8,210 600 8,810 89.2 %
General Engineering Checks
Ventilation Load 470 596 1,066 10.8 % Total Cooling Load 0.8 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 343 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 283 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 529 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 7.3 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 8,680 1,196 9,876 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 40 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B SERVICE COUNTER PB
Room - QRO EDIFICIO B SERVICE COUNTER PB

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 75.6 / 59.2 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 67 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 50.9 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 64 gr/lb
Floor Transmission 2,931 2,931 14.8 % Coil Sensible Load 18 MBh
Partition Transmission 12,275 12,275 61.9 % Coil Total Load 20 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 823 823 4.2 % Total Cooling Airflow 942 cfm
People 906 800 1,706 8.6 % Resulting Room Relative Humidity 41 %
Misc. Equipment Loads 819 0 819 4.1 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 17,754 800 18,554 93.6 %
General Engineering Checks
Ventilation Load 534 730 1,264 6.4 % Total Cooling Load 1.7 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 164 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 271 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 3 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 570 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 3.9 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 18,289 1,530 19,819 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 41 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B SUPERVISOR OFFICE 102 PB
Room - QRO EDIFICIO B SUPERVISOR OFFICE 102 PB

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.5 / 60.8 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 74 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 700 700 11.6 % Coil Sensible Load 5 MBh
Partition Transmission 2,354 2,354 39.0 % Coil Total Load 6 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 383 383 6.4 % Total Cooling Airflow 250 cfm
People 676 600 1,276 21.2 % Resulting Room Relative Humidity 44 %
Misc. Equipment Loads 602 0 602 10.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 4,716 600 5,316 88.1 %
General Engineering Checks
Ventilation Load 334 383 717 11.9 % Total Cooling Load 0.5 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 255 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 128 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 498 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.1 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 5,050 983 6,033 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 42 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B TRAINING ROOM PA
Room - QRO EDIFICIO B TRAINING ROOM PA

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 0 0 0.0 % Coil Entering Air (DB / WB) 76.0 / 59.7 F
Glass Transmission 0 0 0.0 % Coil Entering Humidity Ratio 69 gr/lb
Wall Transmission 0 0 0.0 % Coil Leaving Air (DB / WB) 54.0 / 51.2 F
Roof Transmission 750 750 6.6 % Coil Leaving Humidity Ratio 65 gr/lb
Floor Transmission 716 716 6.3 % Coil Sensible Load 10 MBh
Partition Transmission 5,864 5,864 51.8 % Coil Total Load 11 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 781 781 6.9 % Total Cooling Airflow 514 cfm
People 675 600 1,275 11.3 % Resulting Room Relative Humidity 42 %
Misc. Equipment Loads 903 0 903 8.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 9,688 600 10,288 90.8 %
General Engineering Checks
Ventilation Load 452 590 1,042 9.2 % Total Cooling Load 0.9 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 277 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 262 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 544 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 6.0 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 10,140 1,190 11,330 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 43 de 44
Design Cooling Load Summary
By .

System - QUERETARO
Zone - QRO EDIFICIO B VESTIBULE 100 PB
Room - QRO EDIFICIO B VESTIBULE 100 PB

Coil Location - Room


Coil Peak Calculation Time: May, hour 17
Ambient DB/WB/HR: 91 / 70 / 101

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


Btu/h Btu/h Btu/h of Total

Solar Gain 1,137 1,137 7.6 % Coil Entering Air (DB / WB) 76.5 / 61.0 F
Glass Transmission 380 380 2.5 % Coil Entering Humidity Ratio 75 gr/lb
Wall Transmission 598 598 4.0 % Coil Leaving Air (DB / WB) 54.0 / 51.7 F
Roof Transmission 0 0 0.0 % Coil Leaving Humidity Ratio 67 gr/lb
Floor Transmission 1,577 1,577 10.5 % Coil Sensible Load 12 MBh
Partition Transmission 3,443 3,443 23.0 % Coil Total Load 15 MBh
Net Ceiling Load 0 0 0.0 % Cooling Supply Air Temperature 54 F
Lighting 843 843 5.6 % Total Cooling Airflow 613 cfm
People 1,784 1,600 3,384 22.6 % Resulting Room Relative Humidity 45 %
Misc. Equipment Loads 1,797 0 1,797 12.0 %
Cooling Infiltration 0 0 0 0.0 %
Sub-Total ==> 11,559 1,600 13,159 88.0 %
General Engineering Checks
Ventilation Load 844 950 1,793 12.0 % Total Cooling Load 1.3 ton
Exhaust Heat 0 0 0 0.0 % Area / Load 232 ft2/ton
Supply Fan Load 0 0 0.0 % Total Floor Area 288 ft2
Return Fan Load 0 0 0.0 % Cooling Airflow 2 cfm/ft2
Net Duct Heat Pickup 0 0 0.0 % Airflow / Load 492 cfm/ton
Wall Load to Plenum 0 0 0.0 % Percent Outdoor Air 9.3 %
Roof Load to Plenum 0 0 0.0 % Cooling Load Methodology CLTD-CLF (ASHRAE TFM)
Lighting Load to Plenum 0 0 0.0 %
Misc. Equip. Load to Plenum 0 0 0 0.0 %
Glass Transmission to Plenum 0 0 0.0 %
Glass Solar to Plenum 0 0 0.0 %
Over/Under Sizing 0 0 0.0 %
Reheat at Design 0 0 0 0.0 %

Total Cooling Loads 12,402 2,550 14,952 100.0 %

Project Name: TRACE® 700 v6.1.2 calculated at 09:57 PM on 09/28/2023


Dataset Name: C:\CDS\TRACE700\Projects\QUERETARO SEP 2023.trc Alternative - 1 Design Cooling Load Report Página 44 de 44