You are on page 1of 4

Project Summary

Location and Weather


Project Project Name
Address
Calculation Time Saturday, June 6, 2020 11:45 AM
Report Type Standard
Latitude 26.28°
Longitude 80.20°
Summer Dry Bulb 43 °C
Summer Wet Bulb 29 °C
Winter Dry Bulb 7 °C
Mean Daily Range 10 °C

Building Summary
Inputs
Building Type Office
Area (m²) 30
Volume (m³) 92.07
Calculated Results
Peak Cooling Total Load (W) 6,520
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (W) 5,401
Peak Cooling Latent Load (W) 1,120
Maximum Cooling Capacity (W) 6,520
Peak Cooling Airflow (L/s) 371.2
Peak Heating Load (W) 668
Peak Heating Airflow (L/s) 98.6
Checksums
Cooling Load Density (W/m²) 215.87
Cooling Flow Density (L/(s·m²)) 12.29
Cooling Flow / Load (L/(s·kW)) 56.92
Cooling Area / Load (m²/kW) 4.63
Heating Load Density (W/m²) 22.12
Heating Flow Density (L/(s·m²)) 3.26

Zone Summary - Default


Inputs
Area (m²) 30
Volume (m³) 92.07
Cooling Setpoint 23 °C
Heating Setpoint 21 °C
Supply Air Temperature 12 °C
Number of People 8
Infiltration (L/s) 0.0
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 25 °C
Cooling Coil Entering Wet-Bulb Temperature 17 °C
Cooling Coil Leaving Dry-Bulb Temperature 10 °C
Cooling Coil Leaving Wet-Bulb Temperature 10 °C
Mixed Air Dry-Bulb Temperature 25 °C
Calculated Results
Peak Cooling Load (W) 6,520
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (W) 5,401
Peak Cooling Latent Load (W) 1,120
Peak Cooling Airflow (L/s) 371.2
Peak Heating Load (W) 668
Peak Heating Airflow (L/s) 98.6
Peak Ventilation Airflow (L/s) 28.1
Checksums
Cooling Load Density (W/m²) 215.87
Cooling Flow Density (L/(s·m²)) 12.29
Cooling Flow / Load (L/(s·kW)) 56.92
Cooling Area / Load (m²/kW) 4.63
Heating Load Density (W/m²) 22.12
Heating Flow Density (L/(s·m²)) 3.26
Ventilation Density (L/(s·m²)) 0.93
Ventilation / Person (L/s) 3.5

Cooling Heating
Components Percentage of Percentage of
Loads (W) Loads (W)
Total Total
Wall 1,168 17.92% 858 24.73%
Window 81 1.24% 34 0.97%
Door 165 2.53% 103 2.97%
Roof 2,207 33.85% 597 17.19%
Skylight 0 0.00% 0 0.00%
Partition 0 0.00% 0 0.00%
Infiltration 0 0.00% 0 0.00%
Ventilation 1,356 20.80% 478 13.77%
Lighting 398 6.11% -398 -11.47%
Power 244 3.75% -244 -7.04%
People 759 11.65% -759 -21.87%
Plenum 0 0.00%
Fan Heat 141 2.16%
Reheat 0 0.00%
Total 6,520 100% 668 100%

Default Spaces
Space Area Volume Peak Cooling Load Cooling Airflow Peak Heating Load Heating Airflow
Name (m²) (m³) (W) (L/s) (W) (L/s)
1 Space 30 92.07 5,023 371.2 190 98.6

Space Summary - 1 Space

Inputs

Area (m²) 30
Volume (m³) 92.07
Wall Area (m²) 77
Roof Area (m²) 33
Door Area (m²) 2
Partition Area (m²) 0
Window Area (m²) 1
Skylight Area (m²) 0
Lighting Load (W) 530
Power Load (W) 325
Number of People 8
Sensible Heat Gain / Person (W) 73
Latent Heat Gain / Person (W) 59
Infiltration Airflow (L/s) 0.0
Space Type Audience/Seating Area - Auditorium
Calculated Results
Peak Cooling Load (W) 5,023
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (W) 4,648
Peak Cooling Latent Load (W) 375
Peak Cooling Airflow (L/s) 371.2
Peak Heating Load (W) 190
Peak Heating Airflow (L/s) 98.6

Cooling Heating
Components Percentage of Percentage of
Loads (W) Loads (W)
Total Total
Wall 1,168 23.26% 858 28.67%
Window 81 1.61% 34 1.12%
Door 165 3.28% 103 3.45%
Roof 2,207 43.94% 597 19.93%
Skylight 0 0.00% 0 0.00%
Partition 0 0.00% 0 0.00%
Infiltration 0 0.00% 0 0.00%
Lighting 398 7.93% -398 -13.30%
Power 244 4.86% -244 -8.16%
People 759 15.12% -759 -25.37%
Plenum 0 0.00%
Total 5,023 100% 190 100%