You are on page 1of 27

Page 1 of 27

Project Summary
Location and Weather
Project Project Name
Address
Calculation Time Wednesday, June 1, 2022 10:28 PM
Report Type Detailed
Latitude 31.41°
Longitude 73.11°
Summer Dry Bulb 104 °F
Summer Wet Bulb 86 °F
Winter Dry Bulb 70 °F
Mean Daily Range 92 °F

Building Summary
Inputs
Building Type Manufacturing
Area (SF) 44,941
Volume (CF) 880,898.85
Calculated Results
Peak Cooling Total Load (Btu/h) 3,302,111.5
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 3,000,067.2
Peak Cooling Latent Load (Btu/h) 302,044.3
Maximum Cooling Capacity (Btu/h) 3,273,731.6
Peak Cooling Airflow (CFM) 145,692
Peak Heating Load (Btu/h) -524,571.8
Peak Heating Airflow (CFM) 3,266
Checksums
Cooling Load Density (Btu/(h·ft²)) 73.48
Cooling Flow Density (CFM/SF) 3.24
Cooling Flow / Load (CFM/ton) 529.45
Cooling Area / Load (SF/ton) 163.32
Heating Load Density (Btu/(h·ft²)) -11.67
Heating Flow Density (CFM/SF) 0.07

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 2 of 27

Level Summary - Level 1


Inputs
Area (SF) 44,941
Volume (CF) 880,898.85
Calculated Results
Peak Cooling Total Load (Btu/h) 2,928,445.9
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 2,818,811.9
Peak Cooling Latent Load (Btu/h) 109,634.0
Peak Cooling Airflow (CFM) 143,888
Peak Heating Load (Btu/h) -524,571.8
Peak Heating Airflow (CFM) 3,266
Checksums
Cooling Load Density (Btu/(h·ft²)) 65.16
Cooling Flow Density (CFM/SF) 3.20
Cooling Flow / Load (CFM/ton) 589.61
Cooling Area / Load (SF/ton) 184.15
Heating Load Density (Btu/(h·ft²)) -11.67
Heating Flow Density (CFM/SF) 0.07

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 3 of 27

Zone Summary - 5
Inputs
Area (SF) 34,187
Volume (CF) 752,121.14
Cooling Setpoint 74 °F
Heating Setpoint 70 °F
Supply Air Temperature 54 °F
Number of People 80
Infiltration (CFM) 761
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 75 °F
Cooling Coil Entering Wet-Bulb Temperature 61 °F
Cooling Coil Leaving Dry-Bulb Temperature 51 °F
Cooling Coil Leaving Wet-Bulb Temperature 51 °F
Mixed Air Dry-Bulb Temperature 75 °F
Calculated Results
Peak Cooling Total Load (Btu/h) 2,496,742.9
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 2,266,523.6
Peak Cooling Latent Load (Btu/h) 230,219.4
Peak Cooling Airflow (CFM) 108,734
Peak Heating Load (Btu/h) -404,692.3
Peak Heating Airflow (CFM) 2,448
Peak Ventilation Airflow (CFM) 2,448
Checksums
Cooling Load Density (Btu/(h·ft²)) 73.03
Cooling Flow Density (CFM/SF) 3.18
Cooling Flow / Load (CFM/ton) 522.61
Cooling Area / Load (SF/ton) 164.31
Heating Load Density (Btu/(h·ft²)) -11.84
Heating Flow Density (CFM/SF) 0.07
Ventilation Density (CFM/SF) 0.07
Ventilation / Person (CFM) 31

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -43,762.8 -1.75% 0.0 0.0 0.0 0.0 -8,376.5 -9,333.7 -14,280.4 -11,772.2
Window 2,486.4 0.10% 0.0 0.0 0.0 0.0 0.0 2,486.4 0.0 0.0
Door -6,399.3 -0.26% 0.0 0.0 0.0 0.0 -968.2 -189.5 -5,241.7 0.0
Roof 1,792,935.5 71.81% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 66,196.0 2.65% - - - - - - - -
Ventilation 216,158.0 8.66% - - - - - - - -
Lighting 125,975.0 5.05% - - - - - - - -
Power 213,188.5 8.54% - - - - - - - -
People 65,528.8 2.62% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Fan Heat 64,436.8 2.58% - - - - - - - -
Reheat 0.0 0.00% - - - - - - - -
Total 2,496,742.9 100% 0.0 0.0 0.0 0.0 -9,344.7 -7,036.7 -19,522.1 -11,772.2
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 4 of 27

Roof 0.0 0.00% - - - - - - - -


Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Ventilation 0.0 0.00% - - - - - - - -
Lighting -125,975.0 -31.13% - - - - - - - -
Power -213,188.5 -52.68% - - - - - - - -
People -65,528.8 -16.19% - - - - - - - -
Total -404,692.3 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

5 Spaces
Peak Cooling Cooling Airflow Peak Heating Heating Airflow
Space Name Area (SF) Volume (CF)
Load (Btu/h) (CFM) Load (Btu/h) (CFM)
16 Laundry Area 34,187 752,121.14 2,216,148.1 108,734 -404,692.3 2,448

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 5 of 27

Zone Summary - Equipment Room


Inputs
Area (SF) 2,095
Volume (CF) 25,145.83
Cooling Setpoint 74 °F
Heating Setpoint 70 °F
Supply Air Temperature 54 °F
Number of People 5
Infiltration (CFM) 75
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 75 °F
Cooling Coil Entering Wet-Bulb Temperature 61 °F
Cooling Coil Leaving Dry-Bulb Temperature 51 °F
Cooling Coil Leaving Wet-Bulb Temperature 51 °F
Mixed Air Dry-Bulb Temperature 75 °F
Calculated Results
Peak Cooling Total Load (Btu/h) 160,886.3
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 145,157.3
Peak Cooling Latent Load (Btu/h) 15,729.0
Peak Cooling Airflow (CFM) 6,974
Peak Heating Load (Btu/h) -24,805.3
Peak Heating Airflow (CFM) 150
Peak Ventilation Airflow (CFM) 150
Checksums
Cooling Load Density (Btu/(h·ft²)) 76.78
Cooling Flow Density (CFM/SF) 3.33
Cooling Flow / Load (CFM/ton) 520.14
Cooling Area / Load (SF/ton) 156.30
Heating Load Density (Btu/(h·ft²)) -11.84
Heating Flow Density (CFM/SF) 0.07
Ventilation Density (CFM/SF) 0.07
Ventilation / Person (CFM) 30

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -3,792.5 -2.36% 0.0 0.0 0.0 0.0 -1,293.6 -1,442.3 -471.4 -585.2
Window 497.3 0.31% 0.0 0.0 0.0 0.0 0.0 497.3 0.0 0.0
Door -860.4 -0.53% 0.0 0.0 0.0 0.0 -416.5 -189.5 0.0 -254.5
Roof 116,353.5 72.32% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 6,501.3 4.04% - - - - - - - -
Ventilation 13,249.2 8.24% - - - - - - - -
Lighting 7,721.5 4.80% - - - - - - - -
Power 13,067.2 8.12% - - - - - - - -
People 4,016.5 2.50% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Fan Heat 4,132.6 2.57% - - - - - - - -
Reheat 0.0 0.00% - - - - - - - -
Total 160,886.3 100% 0.0 0.0 0.0 0.0 -1,710.1 -1,134.5 -471.4 -839.7
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 6 of 27

Roof 0.0 0.00% - - - - - - - -


Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Ventilation 0.0 0.00% - - - - - - - -
Lighting -7,721.5 -31.13% - - - - - - - -
Power -13,067.2 -52.68% - - - - - - - -
People -4,016.5 -16.19% - - - - - - - -
Total -24,805.3 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Equipment Room Spaces


Peak Cooling Cooling Airflow Peak Heating Heating Airflow
Space Name Area (SF) Volume (CF)
Load (Btu/h) (CFM) Load (Btu/h) (CFM)
1 equipment Room 350 4,197.17 24,815.0 1,206 -4,140.3 25
2 equipment Room 301 3,617.08 20,936.8 1,017 -3,568.1 22
3 equipment Room 439 5,262.58 30,346.9 1,475 -5,191.3 31
4 equipment Room 1,006 12,069.00 67,405.7 3,276 -11,905.6 72

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 7 of 27

Zone Summary - Office zone


Inputs
Area (SF) 8,658
Volume (CF) 103,631.89
Cooling Setpoint 74 °F
Heating Setpoint 70 °F
Supply Air Temperature 54 °F
Number of People 21
Infiltration (CFM) 117
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 75 °F
Cooling Coil Entering Wet-Bulb Temperature 61 °F
Cooling Coil Leaving Dry-Bulb Temperature 51 °F
Cooling Coil Leaving Wet-Bulb Temperature 52 °F
Mixed Air Dry-Bulb Temperature 75 °F
Calculated Results
Peak Cooling Total Load (Btu/h) 644,482.3
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 588,386.3
Peak Cooling Latent Load (Btu/h) 56,096.0
Peak Cooling Airflow (CFM) 28,180
Peak Heating Load (Btu/h) -95,074.2
Peak Heating Airflow (CFM) 668
Peak Ventilation Airflow (CFM) 668
Checksums
Cooling Load Density (Btu/(h·ft²)) 74.44
Cooling Flow Density (CFM/SF) 3.25
Cooling Flow / Load (CFM/ton) 524.70
Cooling Area / Load (SF/ton) 161.21
Heating Load Density (Btu/(h·ft²)) -10.98
Heating Flow Density (CFM/SF) 0.08
Ventilation Density (CFM/SF) 0.08
Ventilation / Person (CFM) 32

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -6,889.4 -1.07% 0.0 0.0 0.0 0.0 -1,948.8 -1,398.9 -327.2 -3,214.5
Window 497.3 0.08% 0.0 0.0 0.0 0.0 0.0 497.3 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 469,903.4 72.91% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 10,207.8 1.58% - - - - - - - -
Ventilation 58,989.3 9.15% - - - - - - - -
Lighting 29,698.8 4.61% - - - - - - - -
Power 49,438.2 7.67% - - - - - - - -
People 15,937.2 2.47% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Fan Heat 16,699.6 2.59% - - - - - - - -
Reheat 0.0 0.00% - - - - - - - -
Total 644,482.3 100% 0.0 0.0 0.0 0.0 -1,948.8 -901.6 -327.2 -3,214.5
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 8 of 27

Roof 0.0 0.00% - - - - - - - -


Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Ventilation 0.0 0.00% - - - - - - - -
Lighting -29,698.8 -31.24% - - - - - - - -
Power -49,438.2 -52.00% - - - - - - - -
People -15,937.2 -16.76% - - - - - - - -
Total -95,074.2 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Office zone Spaces


Peak Cooling Cooling Airflow Peak Heating Heating Airflow
Space Name Area (SF) Volume (CF)
Load (Btu/h) (CFM) Load (Btu/h) (CFM)
13 Office 994 11,932.00 57,687.2 2,853 -2,584.8 77
15 Office 131 1,311.11 1,592.0 74 -1,401.9 10
9 Office 77 929.17 5,665.8 280 -956.4 6
10 Office 78 936.92 5,726.5 283 -964.4 6
5 office 480 5,761.33 32,826.2 1,626 -5,683.3 37
6 Office 554 6,647.83 37,725.5 1,869 -6,557.8 43
2 Office 95 1,137.50 6,880.2 340 -1,170.8 7
3 Office 79 942.50 5,770.2 285 -970.1 6
4 Office 81 975.00 6,090.1 302 -961.8 6
1 Office 492 5,902.83 33,619.9 1,666 -5,822.9 38
8 Office 1,346 16,148.52 89,440.4 4,423 -16,621.5 104
11 Office 888 10,650.33 59,428.4 2,940 -10,962.3 68
12 Office 1,179 14,146.33 78,787.1 3,897 -14,560.7 91
14 Office 2,184 26,210.50 148,206.6 7,343 -25,855.6 169

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 9 of 27

Space Summary - 16 Laundry Area


Input Data
Area (SF) 34,187
Volume (CF) 752,121.14
Wall Area (SF) 20,037
Roof Area (SF) 34,596
Door Area (SF) 766
Partition Area (SF) 0
Window Area (SF) 60
Skylight Area (SF) 0
Lighting Load (VA) 44,444
Power Load (VA) 75,212
Number of People 80
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 761
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 2,216,148.1
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 2,130,143.5
Peak Cooling Latent Load (Btu/h) 86,004.6
Peak Cooling Airflow (CFM) 108,734
Peak Heating Load (Btu/h) -404,692.3
Peak Heating Airflow (CFM) 2,448

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -43,762.8 -1.97% 0.0 0.0 0.0 0.0 -8,376.5 -9,333.7 -14,280.4 -11,772.2
Window 2,486.4 0.11% 0.0 0.0 0.0 0.0 0.0 2,486.4 0.0 0.0
Door -6,399.3 -0.29% 0.0 0.0 0.0 0.0 -968.2 -189.5 -5,241.7 0.0
Roof 1,792,935.5 80.90% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 66,196.0 2.99% - - - - - - - -
Lighting 125,975.0 5.68% - - - - - - - -
Power 213,188.5 9.62% - - - - - - - -
People 65,528.8 2.96% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 2,216,148.1 100% 0.0 0.0 0.0 0.0 -9,344.7 -7,036.7 -19,522.1 -11,772.2
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -125,975.0 -31.13% - - - - - - - -
Power -213,188.5 -52.68% - - - - - - - -
People -65,528.8 -16.19% - - - - - - - -
Total -404,692.3 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 10 of 27

Space Summary - 1 equipment Room


Input Data
Area (SF) 350
Volume (CF) 4,197.17
Wall Area (SF) 492
Roof Area (SF) 375
Door Area (SF) 75
Partition Area (SF) 0
Window Area (SF) 12
Skylight Area (SF) 0
Lighting Load (VA) 455
Power Load (VA) 769
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 19
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 24,815.0
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 23,308.3
Peak Cooling Latent Load (Btu/h) 1,506.7
Peak Cooling Airflow (CFM) 1,206
Peak Heating Load (Btu/h) -4,140.3
Peak Heating Airflow (CFM) 25

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -1,008.1 -4.06% 0.0 0.0 0.0 0.0 -18.2 -428.4 0.0 -561.5
Window 497.3 2.00% 0.0 0.0 0.0 0.0 0.0 497.3 0.0 0.0
Door -443.9 -1.79% 0.0 0.0 0.0 0.0 0.0 -189.5 0.0 -254.5
Roof 20,005.4 80.62% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 1,624.0 6.54% - - - - - - - -
Lighting 1,288.8 5.19% - - - - - - - -
Power 2,181.1 8.79% - - - - - - - -
People 670.4 2.70% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 24,815.0 100% 0.0 0.0 0.0 0.0 -18.2 -120.6 0.0 -816.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -1,288.8 -31.13% - - - - - - - -
Power -2,181.1 -52.68% - - - - - - - -
People -670.4 -16.19% - - - - - - - -
Total -4,140.3 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 11 of 27

Space Summary - 2 equipment Room


Input Data
Area (SF) 301
Volume (CF) 3,617.08
Wall Area (SF) 225
Roof Area (SF) 324
Door Area (SF) 21
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 392
Power Load (VA) 663
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 9
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 20,936.8
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 20,071.8
Peak Cooling Latent Load (Btu/h) 865.0
Peak Cooling Airflow (CFM) 1,017
Peak Heating Load (Btu/h) -3,568.1
Peak Heating Airflow (CFM) 22

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -433.8 -2.07% 0.0 0.0 0.0 0.0 -17.7 -416.1 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 17,057.7 81.47% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 744.9 3.56% - - - - - - - -
Lighting 1,110.7 5.31% - - - - - - - -
Power 1,879.6 8.98% - - - - - - - -
People 577.8 2.76% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 20,936.8 100% 0.0 0.0 0.0 0.0 -17.7 -416.1 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -1,110.7 -31.13% - - - - - - - -
Power -1,879.6 -52.68% - - - - - - - -
People -577.8 -16.19% - - - - - - - -
Total -3,568.1 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 12 of 27

Space Summary - 3 equipment Room


Input Data
Area (SF) 439
Volume (CF) 5,262.58
Wall Area (SF) 543
Roof Area (SF) 467
Door Area (SF) 40
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 570
Power Load (VA) 965
Number of People 2
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 21
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 30,346.9
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 28,617.4
Peak Cooling Latent Load (Btu/h) 1,729.5
Peak Cooling Airflow (CFM) 1,475
Peak Heating Load (Btu/h) -5,191.3
Peak Heating Airflow (CFM) 31

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -977.9 -3.22% 0.0 0.0 0.0 0.0 -356.5 -597.8 0.0 -23.7
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door -208.2 -0.69% 0.0 0.0 0.0 0.0 -208.2 0.0 0.0 0.0
Roof 24,546.6 80.89% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 1,795.1 5.92% - - - - - - - -
Lighting 1,616.0 5.33% - - - - - - - -
Power 2,734.7 9.01% - - - - - - - -
People 840.6 2.77% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 30,346.9 100% 0.0 0.0 0.0 0.0 -564.7 -597.8 0.0 -23.7
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -1,616.0 -31.13% - - - - - - - -
Power -2,734.7 -52.68% - - - - - - - -
People -840.6 -16.19% - - - - - - - -
Total -5,191.3 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 13 of 27

Space Summary - 4 equipment Room


Input Data
Area (SF) 1,006
Volume (CF) 12,069.00
Wall Area (SF) 707
Roof Area (SF) 1,041
Door Area (SF) 40
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 1,307
Power Load (VA) 2,213
Number of People 3
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 27
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 67,405.7
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 64,617.4
Peak Cooling Latent Load (Btu/h) 2,788.3
Peak Cooling Airflow (CFM) 3,276
Peak Heating Load (Btu/h) -11,905.6
Peak Heating Airflow (CFM) 72

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -1,372.7 -2.04% 0.0 0.0 0.0 0.0 -901.3 0.0 -471.4 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door -208.2 -0.31% 0.0 0.0 0.0 0.0 -208.2 0.0 0.0 0.0
Roof 54,743.8 81.22% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 2,337.3 3.47% - - - - - - - -
Lighting 3,706.0 5.50% - - - - - - - -
Power 6,271.7 9.30% - - - - - - - -
People 1,927.8 2.86% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 67,405.7 100% 0.0 0.0 0.0 0.0 -1,109.5 0.0 -471.4 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -3,706.0 -31.13% - - - - - - - -
Power -6,271.7 -52.68% - - - - - - - -
People -1,927.8 -16.19% - - - - - - - -
-
Total 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
11,905.6

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 14 of 27

Space Summary - 13 Office


Input Data
Area (SF) 994
Volume (CF) 11,932.00
Wall Area (SF) 317
Roof Area (SF) 1,038
Door Area (SF) 17
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 278
Power Load (VA) 199
Number of People 3
Sensible Heat Gain / Person (Btu/h) 250.0
Latent Heat Gain / Person (Btu/h) 200.0
Infiltration Airflow (CFM) 12
Space Type Office Common Activity Areas - Inactive Storage
Calculated Results
Peak Cooling Total Load (Btu/h) 57,687.2
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 56,715.3
Peak Cooling Latent Load (Btu/h) 971.9
Peak Cooling Airflow (CFM) 2,853
Peak Heating Load (Btu/h) -2,584.8
Peak Heating Airflow (CFM) 77

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -511.9 -0.89% 0.0 0.0 0.0 0.0 0.0 -511.9 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 54,829.4 95.05% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 810.3 1.40% - - - - - - - -
Lighting 835.2 1.45% - - - - - - - -
Power 596.6 1.03% - - - - - - - -
People 1,127.6 1.95% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 57,687.2 100% 0.0 0.0 0.0 0.0 0.0 -511.9 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -839.8 -32.49% - - - - - - - -
Power -599.9 -23.21% - - - - - - - -
People -1,145.2 -44.30% - - - - - - - -
Total -2,584.8 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 15 of 27

Space Summary - 15 Office


Input Data
Area (SF) 131
Volume (CF) 1,311.11
Wall Area (SF) 140
Roof Area (SF) 0
Door Area (SF) 17
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 170
Power Load (VA) 288
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 5
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 1,592.0
Peak Cooling Month and Hour June 9:00 AM
Peak Cooling Sensible Load (Btu/h) 1,114.6
Peak Cooling Latent Load (Btu/h) 477.5
Peak Cooling Airflow (CFM) 74
Peak Heating Load (Btu/h) -1,401.9
Peak Heating Airflow (CFM) 10

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -199.9 -12.56% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 -199.9
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 462.5 29.05% - - - - - - - -
Lighting 401.4 25.21% - - - - - - - -
Power 679.3 42.67% - - - - - - - -
People 248.8 15.63% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 1,592.0 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 -199.9
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -431.1 -30.75% - - - - - - - -
Power -729.5 -52.03% - - - - - - - -
People -241.4 -17.22% - - - - - - - -
-
Total 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1,401.9

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 16 of 27

Space Summary - 9 Office


Input Data
Area (SF) 77
Volume (CF) 929.17
Wall Area (SF) 23
Roof Area (SF) 89
Door Area (SF) 17
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 101
Power Load (VA) 170
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 1
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 5,665.8
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 5,537.4
Peak Cooling Latent Load (Btu/h) 128.4
Peak Cooling Airflow (CFM) 280
Peak Heating Load (Btu/h) -956.4
Peak Heating Airflow (CFM) 6

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -49.3 -0.87% 0.0 0.0 0.0 0.0 0.0 0.0 -18.7 -30.5
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 4,708.5 83.10% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 59.7 1.05% - - - - - - - -
Lighting 296.0 5.22% - - - - - - - -
Power 500.9 8.84% - - - - - - - -
People 149.9 2.65% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 5,665.8 100% 0.0 0.0 0.0 0.0 0.0 0.0 -18.7 -30.5
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -299.2 -31.29% - - - - - - - -
Power -506.4 -52.95% - - - - - - - -
People -150.8 -15.76% - - - - - - - -
Total -956.4 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 17 of 27

Space Summary - 10 Office


Input Data
Area (SF) 78
Volume (CF) 936.92
Wall Area (SF) 0
Roof Area (SF) 90
Door Area (SF) 17
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 102
Power Load (VA) 172
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 0
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 5,726.5
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 5,630.2
Peak Cooling Latent Load (Btu/h) 96.3
Peak Cooling Airflow (CFM) 283
Peak Heating Load (Btu/h) -964.4
Peak Heating Airflow (CFM) 6

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 4,771.8 83.33% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting 298.4 5.21% - - - - - - - -
Power 505.1 8.82% - - - - - - - -
People 151.2 2.64% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 5,726.5 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -301.7 -31.29% - - - - - - - -
Power -510.6 -52.95% - - - - - - - -
People -152.0 -15.76% - - - - - - - -
Total -964.4 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 18 of 27

Space Summary - 5 office


Input Data
Area (SF) 480
Volume (CF) 5,761.33
Wall Area (SF) 244
Roof Area (SF) 510
Door Area (SF) 50
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 624
Power Load (VA) 1,056
Number of People 2
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 9
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 32,826.2
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 31,700.7
Peak Cooling Latent Load (Btu/h) 1,125.5
Peak Cooling Airflow (CFM) 1,626
Peak Heating Load (Btu/h) -5,683.3
Peak Heating Airflow (CFM) 37

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -472.8 -1.44% 0.0 0.0 0.0 0.0 -472.8 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 26,810.4 81.67% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 805.3 2.45% - - - - - - - -
Lighting 1,769.1 5.39% - - - - - - - -
Power 2,993.9 9.12% - - - - - - - -
People 920.3 2.80% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 32,826.2 100% 0.0 0.0 0.0 0.0 -472.8 0.0 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -1,769.1 -31.13% - - - - - - - -
Power -2,993.9 -52.68% - - - - - - - -
People -920.3 -16.19% - - - - - - - -
Total -5,683.3 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 19 of 27

Space Summary - 6 Office


Input Data
Area (SF) 554
Volume (CF) 6,647.83
Wall Area (SF) 308
Roof Area (SF) 585
Door Area (SF) 33
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 720
Power Load (VA) 1,219
Number of People 2
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 12
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 37,725.5
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 36,368.9
Peak Cooling Latent Load (Btu/h) 1,356.6
Peak Cooling Airflow (CFM) 1,869
Peak Heating Load (Btu/h) -6,557.8
Peak Heating Airflow (CFM) 43

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -608.6 -1.61% 0.0 0.0 0.0 0.0 -543.7 -17.6 0.0 -47.3
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 30,759.7 81.54% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 1,016.7 2.69% - - - - - - - -
Lighting 2,041.4 5.41% - - - - - - - -
Power 3,454.6 9.16% - - - - - - - -
People 1,061.9 2.81% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 37,725.5 100% 0.0 0.0 0.0 0.0 -543.7 -17.6 0.0 -47.3
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -2,041.4 -31.13% - - - - - - - -
Power -3,454.6 -52.68% - - - - - - - -
People -1,061.9 -16.19% - - - - - - - -
Total -6,557.8 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 20 of 27

Space Summary - 2 Office


Input Data
Area (SF) 95
Volume (CF) 1,137.50
Wall Area (SF) 0
Roof Area (SF) 108
Door Area (SF) 38
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 123
Power Load (VA) 209
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 0
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 6,880.2
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 6,763.2
Peak Cooling Latent Load (Btu/h) 117.0
Peak Cooling Airflow (CFM) 340
Peak Heating Load (Btu/h) -1,170.8
Peak Heating Airflow (CFM) 7

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 5,721.1 83.15% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting 362.3 5.27% - - - - - - - -
Power 613.2 8.91% - - - - - - - -
People 183.6 2.67% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 6,880.2 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -366.3 -31.29% - - - - - - - -
Power -619.9 -52.95% - - - - - - - -
People -184.6 -15.76% - - - - - - - -
-
Total 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1,170.8

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 21 of 27

Space Summary - 3 Office


Input Data
Area (SF) 79
Volume (CF) 942.50
Wall Area (SF) 0
Roof Area (SF) 91
Door Area (SF) 21
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 102
Power Load (VA) 173
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 0
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 5,770.2
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 5,673.3
Peak Cooling Latent Load (Btu/h) 96.9
Peak Cooling Airflow (CFM) 285
Peak Heating Load (Btu/h) -970.1
Peak Heating Airflow (CFM) 6

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 4,809.8 83.36% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting 300.2 5.20% - - - - - - - -
Power 508.1 8.80% - - - - - - - -
People 152.1 2.64% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 5,770.2 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -303.5 -31.29% - - - - - - - -
Power -513.7 -52.95% - - - - - - - -
People -152.9 -15.76% - - - - - - - -
Total -970.1 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 22 of 27

Space Summary - 4 Office


Input Data
Area (SF) 81
Volume (CF) 975.00
Wall Area (SF) 140
Roof Area (SF) 94
Door Area (SF) 21
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 106
Power Load (VA) 179
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 5
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 6,090.1
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 5,683.3
Peak Cooling Latent Load (Btu/h) 406.8
Peak Cooling Airflow (CFM) 302
Peak Heating Load (Btu/h) -961.8
Peak Heating Airflow (CFM) 6

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -271.9 -4.46% 0.0 0.0 0.0 0.0 -271.9 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 4,937.1 81.07% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 463.0 7.60% - - - - - - - -
Lighting 299.4 4.92% - - - - - - - -
Power 506.7 8.32% - - - - - - - -
People 155.7 2.56% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 6,090.1 100% 0.0 0.0 0.0 0.0 -271.9 0.0 0.0 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -299.4 -31.13% - - - - - - - -
Power -506.7 -52.68% - - - - - - - -
People -155.7 -16.19% - - - - - - - -
Total -961.8 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 23 of 27

Space Summary - 1 Office


Input Data
Area (SF) 492
Volume (CF) 5,902.83
Wall Area (SF) 286
Roof Area (SF) 522
Door Area (SF) 84
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 639
Power Load (VA) 1,082
Number of People 2
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 11
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 33,619.9
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 32,386.5
Peak Cooling Latent Load (Btu/h) 1,233.3
Peak Cooling Airflow (CFM) 1,666
Peak Heating Load (Btu/h) -5,822.9
Peak Heating Airflow (CFM) 38

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -570.8 -1.70% 0.0 0.0 0.0 0.0 -484.6 -17.6 -21.2 -47.3
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 27,421.5 81.56% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 946.2 2.81% - - - - - - - -
Lighting 1,812.6 5.39% - - - - - - - -
Power 3,067.5 9.12% - - - - - - - -
People 942.9 2.80% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 33,619.9 100% 0.0 0.0 0.0 0.0 -484.6 -17.6 -21.2 -47.3
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -1,812.6 -31.13% - - - - - - - -
Power -3,067.5 -52.68% - - - - - - - -
People -942.9 -16.19% - - - - - - - -
Total -5,822.9 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 24 of 27

Space Summary - 8 Office


Input Data
Area (SF) 1,346
Volume (CF) 16,148.52
Wall Area (SF) 44
Roof Area (SF) 1,381
Door Area (SF) 33
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 1,749
Power Load (VA) 2,961
Number of People 4
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 2
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 89,440.4
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 87,718.6
Peak Cooling Latent Load (Btu/h) 1,721.8
Peak Cooling Airflow (CFM) 4,423
Peak Heating Load (Btu/h) -16,621.5
Peak Heating Airflow (CFM) 104

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -89.6 -0.10% 0.0 0.0 0.0 0.0 0.0 0.0 -89.6 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 72,963.5 81.58% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 111.7 0.12% - - - - - - - -
Lighting 5,143.8 5.75% - - - - - - - -
Power 8,704.9 9.73% - - - - - - - -
People 2,606.0 2.91% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 89,440.4 100% 0.0 0.0 0.0 0.0 0.0 0.0 -89.6 0.0
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -5,200.6 -31.29% - - - - - - - -
Power -8,800.9 -52.95% - - - - - - - -
People -2,620.0 -15.76% - - - - - - - -
-
Total 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
16,621.5

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 25 of 27

Space Summary - 11 Office


Input Data
Area (SF) 888
Volume (CF) 10,650.33
Wall Area (SF) 73
Roof Area (SF) 919
Door Area (SF) 0
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 1,154
Power Load (VA) 1,953
Number of People 3
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 3
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 59,428.4
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 58,230.5
Peak Cooling Latent Load (Btu/h) 1,197.9
Peak Cooling Airflow (CFM) 2,940
Peak Heating Load (Btu/h) -10,962.3
Peak Heating Airflow (CFM) 68

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -140.2 -0.24% 0.0 0.0 0.0 0.0 -34.0 -29.5 -37.5 -39.2
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 48,529.3 81.66% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 187.0 0.31% - - - - - - - -
Lighting 3,392.5 5.71% - - - - - - - -
Power 5,741.1 9.66% - - - - - - - -
People 1,718.7 2.89% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 59,428.4 100% 0.0 0.0 0.0 0.0 -34.0 -29.5 -37.5 -39.2
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -3,429.9 -31.29% - - - - - - - -
Power -5,804.4 -52.95% - - - - - - - -
People -1,728.0 -15.76% - - - - - - - -
-
Total 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10,962.3

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 26 of 27

Space Summary - 12 Office


Input Data
Area (SF) 1,179
Volume (CF) 14,146.33
Wall Area (SF) 73
Roof Area (SF) 1,218
Door Area (SF) 17
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 1,533
Power Load (VA) 2,593
Number of People 3
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 3
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 78,787.1
Peak Cooling Month and Hour May 2:00 PM
Peak Cooling Sensible Load (Btu/h) 77,229.7
Peak Cooling Latent Load (Btu/h) 1,557.3
Peak Cooling Airflow (CFM) 3,897
Peak Heating Load (Btu/h) -14,560.7
Peak Heating Airflow (CFM) 91

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -140.2 -0.18% 0.0 0.0 0.0 0.0 -34.0 -29.5 -37.5 -39.2
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 64,325.7 81.65% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 187.0 0.24% - - - - - - - -
Lighting 4,506.1 5.72% - - - - - - - -
Power 7,625.7 9.68% - - - - - - - -
People 2,282.9 2.90% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 78,787.1 100% 0.0 0.0 0.0 0.0 -34.0 -29.5 -37.5 -39.2
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -4,555.8 -31.29% - - - - - - - -
Power -7,709.7 -52.95% - - - - - - - -
People -2,295.2 -15.76% - - - - - - - -
-
Total 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
14,560.7

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022
Page 27 of 27

Space Summary - 14 Office


Input Data
Area (SF) 2,184
Volume (CF) 26,210.50
Wall Area (SF) 1,442
Roof Area (SF) 2,259
Door Area (SF) 17
Partition Area (SF) 0
Window Area (SF) 12
Skylight Area (SF) 0
Lighting Load (VA) 2,839
Power Load (VA) 4,805
Number of People 6
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 55
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Total Load (Btu/h) 148,206.6
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 142,358.7
Peak Cooling Latent Load (Btu/h) 5,847.8
Peak Cooling Airflow (CFM) 7,343
Peak Heating Load (Btu/h) -25,855.6
Peak Heating Airflow (CFM) 169

Cooling Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall -3,513.1 -2.37% 0.0 0.0 0.0 0.0 -104.9 -683.9 -98.6 -2,625.7
Window 497.3 0.34% 0.0 0.0 0.0 0.0 0.0 497.3 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 120,604.3 81.38% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Infiltration 4,762.5 3.21% - - - - - - - -
Lighting 8,048.5 5.43% - - - - - - - -
Power 13,620.5 9.19% - - - - - - - -
People 4,186.6 2.82% - - - - - - - -
Plenum 0.0 0.00% - - - - - - - -
Total 148,206.6 100% 0.0 0.0 0.0 0.0 -104.9 -186.6 -98.6 -2,625.7
Heating Total North South East West Northeast Southeast Northwest Southwest
Percentage
Components (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h) (Btu/h)
Wall 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Window 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Door 0.0 0.00% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Roof 0.0 0.00% - - - - - - - -
Partition 0.0 0.00% - - - - - - - -
Skylight 0.0 0.00% - - - - - - - -
Infiltration 0.0 0.00% - - - - - - - -
Lighting -8,048.5 -31.13% - - - - - - - -
Power -13,620.5 -52.68% - - - - - - - -
People -4,186.6 -16.19% - - - - - - - -
Total -25,855.6 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/25ae6ebc-40f7-4c7b-8f87-87... 6/1/2022