You are on page 1of 2

Design Cooling Load Summary

By Trane
Clean room BV Pharma
Hochiminh-Vietnam

System - System - 001


Type - Displacement Ventilation VAV

Coil Location - System


Coil Peak Calculation Time: May, hour 15
Ambient DB/WB/HR: 33 / 30 / 26

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


kW kW kW of Total

Solar Gain 0.00 0.00 0.0% Coil Entering Air (DB / WB) 32.7 / 30.0 °C
Glass Transmission 0.02 0.02 0.0% Coil Entering Humidity Ratio 25.91 g/kg
Wall Transmission 0.24 0.24 0.1% Coil Leaving Air (DB / WB) 18.3 / 11.2 °C
Roof Transmission 0.00 0.00 0.0% Coil Leaving Humidity Ratio 5.35 g/kg
Floor Transmission 0.00 0.00 0.0% Coil Sensible Load 54.65 kW
Adj Floor Transmission 0 0.00 0.0% Coil Total Load 228.09 kW
Partition Transmission 0.00 0.00 0.0% Cooling Supply Air Temperature 18.33 °C
Net Ceiling Load 0.00 0.00 0.0% Total Cooling Airflow 2,767.11 L/s
Lighting 0.65 0.65 0.3% Resulting Room Relative Humidity 35.00 %
People 1.05 2.09 3.14 1.4%
Misc. Equipment Loads 10.00 0.00 10.00 4.4%
Cooling Infiltration 0.00 0.00 0.00 0.0%
Sub-Total ==> 11.96 2.09 14.05 6.2% General Engineering Checks
Ventilation Load 37.21 171.34 208.55 91.9% Total Cooling Load 228.1 kW
Exhaust Heat -13.81 0.00 -13.81 -6.1% Area / Load 0.65 m²/kW
Supply Fan Load 0.00 0.00 0.0% Total Floor Area 148 m²
Return Fan Load 0.00 0.00 0.0% Cooling Airflow 18.80 Lps/m²
Net Duct Heat Pickup 0.00 0.00 0.0% Airflow / Load 12.20 Lps/kW
Wall Load to Plenum 0.36 0.36 0.2% Percent Outdoor Air 100.0 %
Roof Load to Plenum 6.50 6.50 2.9% Cooling Load Methodology TETD-TA1
Adj Floor to Plenum 0 0 0.0%
Lighting Load to Plenum 0.98 0.98 0.4%
Misc. Equip. Load to Plenum 10.00 0.00 10.00 4.4%
Glass Transmission to Plenum 0.02 0.02 0.0%
Glass Solar to Plenum 0.00 0.00 0.0%
Over/Under Sizing 0.39 0.39 0.2%
Reheat at Design 0.00 0.00 0.00 0.0%
Underfloor Sup Heat Pickup 0 0 0.0%
Supply Air Leakage 0 0 0 0.0%
Total Cooling Loads 53.61 173.43 227.04 100.0 %

Project Name: Clean room BV Pharma TRACE® 700 v6.2.5 calculated at 03:37 PM on 08/08/2021
Dataset Name: BV Pharma.trc Alternative - 1 Design Cooling Load Report Page 1 of 2
Design Cooling Load Summary
By Trane
Clean room BV Pharma
Hochiminh-Vietnam

System - System - 002


Type - Displacement Ventilation VAV

Coil Location - System


Coil Peak Calculation Time: May, hour 15
Ambient DB/WB/HR: 33 / 30 / 26

COOLING COIL LOAD INFORMATION COOLING COIL SELECTION

Load Component Sensible Latent Total Percent Coil Selection Parameters


kW kW kW of Total

Solar Gain 0.00 0.00 0.0% Coil Entering Air (DB / WB) 32.7 / 30.0 °C
Glass Transmission 0.00 0.00 0.0% Coil Entering Humidity Ratio 25.91 g/kg
Wall Transmission 0.06 0.06 0.2% Coil Leaving Air (DB / WB) 18.3 / 16.6 °C
Roof Transmission 0.00 0.00 0.0% Coil Leaving Humidity Ratio 11.02 g/kg
Floor Transmission 0.00 0.00 0.0% Coil Sensible Load 8.59 kW
Adj Floor Transmission 0 0.00 0.0% Coil Total Load 27.80 kW
Partition Transmission 0.00 0.00 0.0% Cooling Supply Air Temperature 18.33 °C
Net Ceiling Load 0.00 0.00 0.0% Total Cooling Airflow 428.93 L/s
Lighting 0.13 0.13 0.5% Resulting Room Relative Humidity 70.00 %
People 0.16 0.32 0.48 1.7%
Misc. Equipment Loads 1.50 0.00 1.50 5.4%
Cooling Infiltration 0.00 0.00 0.00 0.0%
Sub-Total ==> 1.85 0.32 2.17 7.9% General Engineering Checks
Ventilation Load 5.77 18.89 24.66 89.2% Total Cooling Load 27.8 kW
Exhaust Heat -2.57 0.00 -2.57 -9.3% Area / Load 1.08 m²/kW
Supply Fan Load 0.00 0.00 0.0% Total Floor Area 30 m²
Return Fan Load 0.00 0.00 0.0% Cooling Airflow 19.00 Lps/m²
Net Duct Heat Pickup 0.00 0.00 0.0% Airflow / Load 20.50 Lps/kW
Wall Load to Plenum 0.09 0.09 0.3% Percent Outdoor Air 100.0 %
Roof Load to Plenum 1.59 1.59 5.8% Cooling Load Methodology TETD-TA1
Adj Floor to Plenum 0 0 0.0%
Lighting Load to Plenum 0.20 0.20 0.7%
Misc. Equip. Load to Plenum 1.50 0.00 1.50 5.4%
Glass Transmission to Plenum 0.00 0.00 0.0%
Glass Solar to Plenum 0.00 0.00 0.0%
Over/Under Sizing 0.00 0.00 0.0%
Reheat at Design 0.00 0.00 0.00 0.0%
Underfloor Sup Heat Pickup 0 0 0.0%
Supply Air Leakage 0 0 0 0.0%
Total Cooling Loads 8.43 19.21 27.64 100.0 %

Project Name: Clean room BV Pharma TRACE® 700 v6.2.5 calculated at 03:37 PM on 08/08/2021
Dataset Name: BV Pharma.trc Alternative - 1 Design Cooling Load Report Page 2 of 2

You might also like