Value of Insulation U (W/m2K) 0.221 Side 1 30.

6
Length L (m) 9 Side 2 30.6
Width W (m) 8.2 Side 3 27.88
Height H (m) 3.4 Side 4 27.88
Ambient Tempreature Ta © 48 Floor 73.8
Required room Tempreature Tr © 26 Roof 73.8
Transient time tT (h) 24 Volume 250.92
People P 8
Rate of Heat Loss from a Person Qp (W/hr) 270
Length of Working Hours tW (hr) 8
No of Lights NL 4
Rating of Lamp RL (W) 45
Changes in air CA 5

Transient Cooling Load (KWh/d) 30.87097728


People Cooling Load (KWh/d) 17.28
Lighting Cooling Load (KWh/d) 1.44
Infiltration Cooling Load (KWh/d) 7.667

Total Cooling Load (KWh/d) 57.25797728


Factor of Safety 1.5
Total Cooling Capacity (kW) 10.73587074
Total Cooling Capacity (Ton) 3.052564896