CoolPack COOLING DEMAND FOR A COLD ROOM

HEAT TRANSFER THOUGH BUILDING PARTS


Calculate
k-value [W/(m²·K)] T [°C] L [m] : 22.39 W [m] : 11.4 H [m] : 3.1 QTRANS : 11.562 [kW]
Save inputs WALL 1 2.3 38.0 3
Volume : 791.3 [m ]
Load inputs WALL 2 2.3 28.0 WALL 2 (L = length)

WALL 1 (W = width)
Help WALL 3 2.3 38.0

WALL 3
TROOM [°C] : 22.0
WALL 4 2.3 28.0
Print
RHROOM [%] : 85
FLOOR 2.3 26.0

CIELING 2.3 30.0 WALL 4


AIR CHANGE (natural infiltration only)
TAIR,IN [°C] : 38.0 RHAIR,IN [%] : 80 Air Change Factor (ACF) 9 QINFILT : 6.077 [kW]
3
ACF : 9.0 [room vol. pr 24 hour] (ACF recommended : 2.5 ) Volume flow : 296.7 [m /h]

COOLING AND FREEZING OF GOODS


Quantity [kg] TIN [°C]  COOL [h] Type QMAX [kW] QAVG [kW] QMAX : 4.990 [kW]

1 8000 28.0 22 Diary products 4.990 2.121 QAVG : 2.121 [kW]

2 0 26.0 22 Diary products 0.000 0.000

AUXILIARY LOADS
© 1999 - 2001 No. of persons [-] : 50 Work type : Light q : 39 [W/person] at TROOM : 22.0 [°C] QAUX : 12.255 [kW]
Department of
Mechanical Engineering Fans [kW] : 1.200 Lights : 20 [W/m²] Other equipment [kW] : 4.000
Technical University
of Denmark Heat of respiration [W] : 0 Hours of operation per 24 h [h] : 16

Version 1.48
Maximum cooling demand : 52.324 [kW] at SHR : 91 [%] Average cooling demand : 48.022 [kW] at SHR : 91 [%]
TOOL A.9