COOLING PERFORMANCE
Total capacity 25,4 [kW] Sensible capacity 17,5 [kW]
Sensible/Total ratio 0,69 hs,C (calculated) * 149,2
Total power Input 8,5 [kW] SEER* 3,81
* figure calculated as per Commision Regulation (EU) 2016/2281 - Ecodesign
INDOOR AIR
Air temperature 24,0 [°C] Relative humidity 47 [%]
OUTDOOR AIR
Air temperature 42,0 [°C] Relative humidity 50 [%]
Inlet mixing air
Air temperature 29,4 [°C] Relative humidity 54 [%]
Outlet mixing air
Air temperature 16,6 [°C] Relative humidity 100 [%]
Economizer 30 [%] Air flow 1.290 [m³/h]
Working Range (Full Load / Partial Load) [°C] -10°C ~ 46°C / -10°C ~ 52°C
HEATING PERFORMANCE
Total capacity 23,4 [kW] hs,H (calculated) * 115,20
Total power Input 6,90 [kW] SCOP* 2,96
* figure calculated as per Commision Regulation (EU) 2016/2281 - Ecodesign
INDOOR AIR
Air temperature 20,0 [°C] Relative humidity 50 [%]
OUTDOOR AIR
Air temperature 7,0 [°C] Relative humidity 87 [%]
Inlet mixing air
Air temperature 16,1 [°C] Relative humidity 59 [%]
Outlet mixing air
Air temperature 32,3 [°C] Relative humidity 22 [%]
NOTE:
· In order to maintain data updated, YORK reserves the rights to change specification without prior notice.
· For more detailed information, please refer to the technical guides
· STAR spreadsheet only includes reference values that might require confirmation using technical guide information
· Prices need to be confirmed with your JCI contact person or with the corresponding customer service.
SUPPLY FANS
Number 1 [n°]
Power input 0,2 [kW] Available static pressure 210[Pa]
Air flow rate 4.500 [m³/h] Total pressure drop 210[Pa]
CONDENSER FANS
Number 1 [n°]
Power input 0,6 [kW]
Air flow rate 8.000 [m³/h]
COMPRESSORS
Number 1 [n°] Power input in cooling mode 7,2[kW]
Power input in heat pump mode 4,1[kW]
EVAPORATORS
Number 1 [n°]
Row number 4 [n°] Frontal section 0,87 [m²]
ELECTRICAL DATA
Voltage 400/3N/50 [V/ph/Hz] Max power input 11,0 [kW]
Max absorbed current 21,0 [A] Startup current 95,0 [A]
NOTE:
· In order to maintain data updated, YORK reserves the rights to change specification without prior notice.
· For more detailed information, please refer to the technical guides
· STAR spreadsheet only includes reference values that might require confirmation using technical guide information
· Prices need to be confirmed with your JCI contact person or with the corresponding customer service.
Psychrometric chart
Economizer–Cooling mode
P0 42,0 °C 50,0 %
P1 29,4 °C 54,4 %
Indoor coil–Cooling mode
P1 29,4 °C 54,4 %
P2 16,6 °C 100,0 %
Economizer–Heating mode
P4 7,0 °C 87,0 %
P5 16,1 °C 59,0 %
Indoor coil–Heating mode
P5 16,1 °C 59,0 %
P6 32,3 °C 22,4 %
KJ/Kg
NOTE:
· In order to maintain data updated, YORK reserves the rights to change specification without prior notice.
· For more detailed information, please refer to the technical guides
· STAR spreadsheet only includes reference values that might require confirmation using technical guide information
· Prices need to be confirmed with your JCI contact person or with the corresponding customer service.
Thermal/Acoustic Insulation
The inside of the evaporator area and the heating supply/accessory area are fully insulated.
The insulation protects the outside surface with a sheet of reinforced aluminium, with M1 fire resistance rating in line with
UNE 23727. This aluminium surface keeps friction for air passage to a minimum and
is easy to clean.
Unit base
The base of the unit is made with fixed beams that provide a solid foundation. Openings on the front of these beams can
be used to attach a crane for hoisting the unit into position during the installation
process.
The beams also have openings on the bottom to place the unit on dampers, if required.
Duct Connection
The entire range of units is prepared for connecting air supply and return ducts for downward or sideways flow.
Air filters
All units have standard filters with metal frame and average filtering of 48 mm available in zig-zag.
Gravimetric efficiency is 90%, G4, complying with EN779 and fire resistance is F1 in accordance with DIN 53438.
Optionally, high opacimetric efficiency filters, classes F6 and F7 are available according to EN779. These filters are easily
installed behind the standard filters.
NOTE:
· In order to maintain data updated, YORK reserves the rights to change specification without prior notice.
· For more detailed information, please refer to the technical guides
· STAR spreadsheet only includes reference values that might require confirmation using technical guide information
· Prices need to be confirmed with your JCI contact person or with the corresponding customer service.
Cooling circuit
There are several refrigerant circuit configurations depending on the size of the ACTIVA rooftops. Only the smaller
ACTIVA Rooftops, size 17 and 20, use 1 refrigerant circuit with one compressor. In models 32 to 90 Rooftop ACTIVA
units have 1 cooling circuit equipped with 2 compressors in tandem . This makes for better performance when the unit is
not running at full capacity, which is usually the case. It also improves unit operations at extreme temperatures, as it does
not jam and continues operating at partial capacity, using the entire surface of the exchangers. Based on the
accumulated operating hours of each compressor, a control circuit determines the order of operation, thus lengthening
their working life. Finally, the ACTIVA rooftops 100 to 175 works with two refrigerant circuits using two tandem scroll
compressor in each of those circuits increasing the flexibility of those models to work at partial loads.
Compressors
Vertical hermetic scroll-type compressor, with internal motor protection and standard crankcase exterior heater.
The compressors have dampers to reduce operating noise and vibrations.
Cooling circuit protection
All cooling circuits are supplied as standard with high and low-pressure switches, dehydrator filter on the liquid line,
discharge temperature cut-out switch and temperature probes for supply air, suction liquid and outdoor air.
Service connections
In order to make the connections with a minimum amount of work, electrical and control cables can be pulled into the unit
at the side or through the base.
Electrical panel
The electrical panel of the unit complies with the standards EN60204-1 and EN60439-1. The main circuit breaker with
drive lever is a standard element in all units. The electric motors are protected with specific thermal magnetic switches
and motor protection relays.
The unit is fitted with a sequence and phase fault sensor: where a non R-S-T phase sequence is detected or where, once
the unit is running, there is a phase fault, the sensor will disconnect the power supply to the main board of the unit,
preventing it from starting.
Noise emissions
All units operate with extremely low noise emission levels. The compressors have anti-vibration mounts as well as
vertical discharge fans that direct noise upwards, away from surrounding buildings and property.
NOTE:
· In order to maintain data updated, YORK reserves the rights to change specification without prior notice.
· For more detailed information, please refer to the technical guides
· STAR spreadsheet only includes reference values that might require confirmation using technical guide information
· Prices need to be confirmed with your JCI contact person or with the corresponding customer service.