You are on page 1of 2

6/8/2020 1

Submittal AM076FNHDCH/AA HSP DUCT Latin America

Job Name SUBMITTALS Location SUBMITTALS


Purchaser SUBMITTALS Engineer SUBMITTALS
Submitted to Reference Approval Construction

Specifications
Model AM076FNHDCH/AA
Features Type HSP DUCT
Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,208-230,60
Capacity Cooling [kW] 22.51

Specifications
Cooling [Btu/h] 76,800
Heating [kW] 24.97
Heating [Btu/h] 85,200 • Compatible with Samsung DVM S, DVM S Water, and DVM Eco systems
Current Input (Nominal) Cooling 1 [A] 3.80 (AM*********/**).
Heating 2 [A] 3.80
• The indoor unit shall have an internal condensate pump as standard with
System Mode HP/HR float switch (maximum 29" lift from bottom of unit).
Power Input (Nominal) Cooling 1 [W] 530.00
Heating 2 [W] 530.00 • High-voltage terminal block temperature sensor to disable unit in the event
overheating of power connection.
Fan Type Sirocco Fan
Motor (Output) [W] 400 x 1 • Discharge air temperature sensor with target discharge temperature control
Air Flow Rate (High / Mid / Low) [CFM] 2048/1836/1660 capability
Air Flow Rate (High / Mid / Low) [CMM] 57.99/51.99/47.00
Construction
Air Flow Rate (High/Mid/Low) [L/S] 966.51/866.46/783.40
The unit shall be constructed of insulated, galvanized steel
External Static Pressure (Min / Std / Max) [in H20] 0.2/0.59/0.98
External Static Pressure (Min / Std / Max) [mmAq] 5.08/14.99/24.89 Heat Exchanger
External Static Pressure (Min / Std / Max) [Pa] 49.82/146.96/244.11 The heat exchanger shall be mechanically bonded fin to copper tube
Piping Connections Liquid Pipe (Φ, mm) 9.52
Indoor Fan
Liquid Pipe (Φ, inch) 3/8" Indoor fan is a centrifugal type with a single fan motor
Gas Pipe (Φ, mm) 19.05
Gas Pipe (Φ, inch) 3/4" Three fan speed settings and auto setting
Drain Pipe (Φ,mm) VP25 (OD 32,ID 25)
Fan output can be configured during commissioning for variousexternal static
Field Wiring Power Source Wire AWG 14 pressure ranges
Transmission Cable 2 X 16 AWG SHIELDED
Refrigerant Type R410A Controls
Control Method
The unit shall be operated via a wireless or wired remote control with DDC
EEV INCLUDED
type signal
Sound Sound Pressure 45.0/43.0/41.0
Sound Power - The unit shall integrate with the Samsung NASA Controls Network Solution
External Dimension (Indoor Unit) Net Weight(kg) 89.00
Shipping Weight (kg) Controls shall integrate with a BMS system
99.00
Net Dimensions (WxHxD) (mm) 1240 x 470 x 1040 Control wiring shall be 2 X 16 AWG shielded wire
Shipping Dimensions (WxHxD) (mm) 1507 x 558 x 1155
Panel Size Panel model - Air Filtration
Panel Net Weight (kg) The unit shall ship with basic filtration as standard
-
Shipping Weight (kg) - Pressure drop across the filter must be factored into the total ESP.
Net Dimensions (WxHxD) (mm) -
Shipping Dimensions (WxHxD) (mm) -
Additional Accessories Drain Pump MDP-N047SNC1D
Drain Pump Max. Lifting Height/Displacement -
Air Filter Removable / Washable

* Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75⁰F WB.
* Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB.

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
6/8/2020 2

Submittal AM076FNHDCH/AA HSP DUCT Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.

You might also like