Submittal AM200JXVANH/TL DVM S Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model AM200JXVANH/TL
Features Type DVM S
Power Voltage [Φ, #, V, Hz] 3,4,380-415,50/60
MCA [A] 42.50 (MCA)
MFA [A] 63.00
Performance HP 20.00
Cooling [kW] 56.00
Cooling [Btu/h] 191,100
Heating [kW] 63.00
Heating [Btu/h] 215,000

Specifications
EER 3.84
COP 4.53
Power Input Cooling 1 [kW] 14.59
Heating 2 [kW] 13.90
Current Input (Nominal) Cooling 1 [A] 23.40
Heating 2 [A] 22.30 Compatibility
System Mode HEAT PUMP NASA DVM S indoor units , AHU kits (MXD-K***AN), and UCK (MCM-D211UN)
Compressor Type Construction
SSC Scroll x 2
The unit shall be galvanized steel with a baked on powder coated finish.
Output (kW x n) (6.39x2)
Heat Exchanger
Oil Type PVE The heat exchanger shall be mechanically bonded fin to copper tube.
Inicial Charge [cc] 2200 The aluminum fins of the heat exchanger shall have a protective coating.
Refrigerant Type R410A Salt spray test method: ASTM-B117-18 - the heat exchanger showed no unusual rust or
Factory Charge [kg] corrosion development to 2,280 hours.
8.40
Controls
Installation Max. Distance Length [m] 200
The outdoor unit shall have a removable EEPROM that stores unit serial number, startup
Height [m] 110.0 information, system settings, system tag/name, and other information.
Condenser Fan Fan Type Propeller Control wiring shall be 16 AWG X 2 shielded wire.
Output [CMM] 290 Refrigerant System
Output [CFM] 10241
The compressors shall be Samsung hermetically sealed, inverter driven, direct flash
injected, DC scroll type with soft-start capability.
Motor Output [W] 620.0 x 2
Flash injected compressors provide advanced low ambient heating performance.
E.S.P Max. [mmAq] 8.00 Subcooling devices in system maintain capacity at extreme system refrigerant pipe
E.S.P Max. [Pa] 78.45 lengths and minimize refrigerant noise.
Piping Connections Liquid Pipe (Φ, mm) 15.88 Other Features
Liquid Pipe (Φ, inch) 5/8" Asymmetrical scroll design with rotating compressor operation/priority (where
applicable).
Gas Pipe (Φ, mm) 28.58
Advanced oil recovery cycle logic (maximum duration in cool mode: 3 minutes, maximum
Gas Pipe (Φ, inch) 1 1/8" duration in heat mode: 6 minutes, defrost cycles lasting over 3 minutes are considered
Discharge (Φ,mm) - oil recovery cycles). Oil recovery operation shall not interrupt heating or cooling
Discharge (Φ,inch) - operation.
Sound Sound Pressure 65.0 Optional night quiet modes to reduce outdoor unit sound (4 levels) with automatic
Sound Power activation or manual activation (with MIM-B14).
87.0
Advanced intelligent defrost logic to significantly reduce defrost cycle frequency by
Dimension Net Weight(kg) 307.0 monitoring air resistance across the condenser coil during heating operation to
Shipping Weight (kg) 326.0 determine defrost operation initiation to prevent unnecessary defrost cycles.
Net Dimensions (WxHxD) (mm) 1,295 x 1,695 x 765 Optional snow blowing logic to prevent snow accumulation on idle outdoor units
Shipping Dimensions (WxHxD) (mm) 1,363 x 1,887 x 832 Maximum current control of outdoor unit(s) to limit current (50% - 100% of design
Operating Cooling [°C] current) adjustable at outdoor unit or central control devices: DMS 2.5 (MIM-D01AN),
-5.0 ~ 48.0
Temp. Range BACnet Gateway (MIM-B17BN), LON Gateway (MIM-B18BN).
Heating [°C] -25.0 ~ 24.0
Energy savings options to reduce system energy consumption when average indoor room
temperatures are greater than average indoor set temperatures in heating mode or when
* Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75⁰F WB. average indoor room temperatures are lower than average indoor set temperatures in
* Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB. cooling mode.
Samsung maintains a policy of ongoing development, specifications are subject to change
without notice.

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 2

Submittal AM200JXVANH/TL DVM S Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 1

Submittal AM048KNMDCH/AZ MSP DUCT Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model AM048KNMDCH/AZ
Features Type
MSP DUCT

Power Supply (Indoor Unit) [Φ, #, V, Hz] 1,2,208-230,60


Capacity Cooling [kW]

Specifications
14.07
Cooling [Btu/h] 48,000
Heating [kW] 15.83
Heating [Btu/h] 54,000 • Compatible with Samsung DVM S, DVM S Water, and DVM Eco
Current Input (Nominal) Cooling 1 [A] 2.45 systems (AM*********/**).
Heating 2 [A] 2.45
• The indoor unit shall have an internal condensate pump as standard
System Mode HP/HR with float switch (maximum 29" lift from bottom of unit).
Power Input (Nominal) Cooling 1 [W] 430.00
Heating 2 [W] 430.00 • High-voltage terminal block temperature sensor to disable unit in the
Fan Type Sirocco Fan event overheating of power connection.
Motor (Output) [W] 218 x 1
• Discharge air temperature sensor with target discharge temperature
Air Flow Rate (High / Mid / Low) [CFM] 1236/1165/1059 control capability
Air Flow Rate (High / Mid / Low) [CMM] 35.00/32.99/29.99
Air Flow Rate (High/Mid/Low) [L/S] 583.33/549.83/499.83 Construction
External Static Pressure (Min / Std / Max) [in H20] 0.24/0.31/0.39 The unit shall be constructed of insulated, galvanized steel
External Static Pressure (Min / Std / Max) [mmAq] 6.10/7.87/9.91
Heat Exchanger
External Static Pressure (Min / Std / Max) [Pa] 59.82/77.18/97.18 The heat exchanger shall be mechanically bonded fin to copper tube
Piping Connections Liquid Pipe (Φ, mm) 9.52
Liquid Pipe (Φ, inch) 3/8" Indoor Fan
Gas Pipe (Φ, mm) 15.88 Indoor fan is a centrifugal type with a single fan motor
Gas Pipe (Φ, inch) 5/8"
Three fan speed settings and auto setting
Drain Pipe (Φ,mm) VP25 (OD 32,ID 25)
Field Wiring Power Source Wire AWG 14 Fan output can be configured during commissioning for variousexternal
Transmission Cable 2 X 16 AWG SHIELDED static pressure ranges
Refrigerant Type R410A
Control Method Controls
EEV INCLUDED
The unit shall be operated via a wireless or wired remote control with
Sound Sound Pressure 42.0/39.0/36.0 DDC type signal
Sound Power 62.0
External Dimension (Indoor Unit) Net Weight(kg) 48.50 The unit shall integrate with the Samsung NASA Controls Network
Shipping Weight (kg) 57.00 Solution
Net Dimensions (WxHxD) (mm) 1200 x 360 x 650
Controls shall integrate with a BMS system
Shipping Dimensions (WxHxD) (mm) 1456 x 434 x 778
Panel Size Panel model - Control wiring shall be 2 X 16 AWG shielded wire
Panel Net Weight (kg) -
Shipping Weight (kg) - Air Filtration
Net Dimensions (WxHxD) (mm) The unit shall ship with basic filtration as standard
-
Shipping Dimensions (WxHxD) (mm) - Pressure drop across the filter must be factored into the total ESP.
Additional Accessories Drain Pump MDP-M075SGU2D
Drain Pump Max. Lifting Height/Displacement -
Air Filter Removable / Washable

* Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75⁰F WB.
* Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB.

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 2

Submittal AM048KNMDCH/AZ MSP DUCT Latin America

Specifications

English 2
Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 1

Submittal MWR-SH11N Wired remote controller Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model MWR-SH11N
Features Type Wired remote controller

Features
• Internal temperature sensor

• Backlight

• Built-in infrared receiver to allow control of indoor unit wirelessly with AR-EH03U or AR-KH03U wireless controllers

• Indoor unit operation ON/OFF, operation mode, set temperature, louver position (cassette, ceiling, wall units), and fan
speed settings

Specifications
Specifications
• Error display
• Compatible with Samsung DVM S Systems (AM****X****/**,
AM0***XMDCH/**) and CAC systems (AC0***X**CH/**) only.
• Filter replacement alarm display and reset
• Can connect and control up to 16 indoor units on a single system or
across multiple systems (group control)
• Single indoor unit control or multiple unit control (maximum 16 units)
• 2 Conductor connection
• DC 12V power supplied by indoor unit
• All button lock (option)
• PLC (power line communication) is done on F3/F4 terminals.
• MWR-SH11N has screw terminals for all wiring connections, wire is
• Partial controller button lock (ON/OFF, temperature setting, fan speed, timer function, louver swing, sleep function, quiet
not included
function, outing function, and operation mode buttons)
• 16 AWG X 2 shielded cable is necessary for proper operation
• Maximum wire length: 328' from MWR-SH11N to farthest indoor unit.
• Upper and lower temperature setting restriction

• Heat, cool, dry, fan, and auto mode skip options (skips specified mode on wired controller)

• Restrict wireless controller signal (optional)

• Single event timer function (ON/OFF control, 30 minutes - 24 hours timer setting options)

• System/indoor unit function and operation indication (defrost, error, restricted controller, central control, and SPi status)

• Service mode for connected indoor unit operation monitoring, addressing, and setup

• Can be used to specify "Mode Master" while connected to a single indoor unit when used with heat pump systems to control
system mode (heating or cooling)

• Outing function to keep a minimum heating (61~72°F) and cooling (77~86°F) temperature while you are away. When Outing
mode is activated, the unit will operate at the specified Outing temperature.
If indoor temperature is 9°F difference from desired Outing temperature, the indoor unit will turn on. If indoor temperature is
the same as desired Outing temperature, the indoor unit will turn off automatically. This is repeated depending on indoor
temperature for 12 hours. After 12 hours, Outing mode is released /canceled.

• Wind-FreeTM Control (applies to supported models when using


the Wind-FreeTM fascia panel)

• Long Reach Function (applies to supported models when using


the Wind-FreeTM fascia panel)

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 2

Submittal MWR-SH11N Wired remote controller Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 1

Submittal MXJ-YA2815M Y-joint Latin America

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction

Specifications
Model MXJ-YA2815M
Features Type Y-joint

• Required component for Samsung DVM S and DVM Eco systems (AM****X****/**) with multiple evaporators and/or Mode
Change Units (MCU)
• Constructed of brazed copper or brass and copper
• Indoor unit Y-joint models include both liquid and suction fittings, insulation, and ties to secure insulation
• Heat recovery (HR) Y-joint models are required for branching the hot gas pipe throughout heat recovery systems (HR
systems only)
• Included insulation shall be polystyrene certified to UL94 V0, 5/8" wall thickness
• Inlet pipe shall be adjustable to facilitate different pipe sizes without having to braze additional fittings MW
• Each model shall include adjustable reducers as noted in the table below

Specifications

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
03/11/2023 2

Submittal MXJ-YA2815M Y-joint Latin America

Specifications

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.