You are on page 1of 4

11/2/2022 1

Submittal AM240KXVANH/TL DVM S Latin America

Job Name UTP ATE Location LIMA


Purchaser NORDES Engineer ATL
Submitted to Reference Approval Construction

Specifications
Model AM240KXVANH/TL
Features Type DVM S
Power Voltage [Φ, #, V, Hz] 3,4,380-415,50/60
MCA [A] 55.00 (MCA)
MFA [A] 63.00
Performance HP 24.00
Cooling [kW] 67.20
Cooling [Btu/h] 229,300
Heating [kW] 75.60
Heating [Btu/h] 258,000
EER 3.93
COP 4.34
Power Input Cooling 1 [kW] 17.10
Heating 2 [kW] 17.42
Current Input (Nominal) Cooling 1 [A] 27.40
Heating 2 [A] 27.90 Compatibility
System Mode HEAT PUMP NASA DVM S indoor units , AHU kits (MXD-K***AN), and UCK (MCM-D211UN)
Construction
Compressor Type SSC Scroll x 2
The unit shall be galvanized steel with a baked on powder coated finish.
Output (kW x n) (6.39x2) Heat Exchanger
Oil Type PVE The heat exchanger shall be mechanically bonded fin to copper tube.
Inicial Charge [cc] 2200 The aluminum fins of the heat exchanger shall have a protective coating.
Salt spray test method: ASTM-B117-18 - the heat exchanger showed no unusual rust or
Refrigerant Type R410A
corrosion development to 2,280 hours.
Factory Charge [kg] 12.50 Controls
Installation Max. Distance Length [m] 200 The outdoor unit shall have a removable EEPROM that stores unit serial number, startup
Height [m] 110.0 information, system settings, system tag/name, and other information.
Control wiring shall be 16 AWG X 2 shielded wire.
Condenser Fan Fan Type Propeller
Refrigerant System
Output [CMM] 340 The compressors shall be Samsung hermetically sealed, inverter driven, direct flash
Output [CFM] 12007 injected, DC scroll type with soft-start capability.
Motor Output [W] 620.0 x 2 Flash injected compressors provide advanced low ambient heating performance.
Subcooling devices in system maintain capacity at extreme system refrigerant pipe
E.S.P Max. [mmAq] 8.00
lengths and minimize refrigerant noise.
E.S.P Max. [Pa] 78.45 Other Features
Piping Connections Liquid Pipe (Φ, mm) 15.88 Asymmetrical scroll design with rotating compressor operation/priority (where
Liquid Pipe (Φ, inch) 5/8" applicable).
Gas Pipe (Φ, mm)
Advanced oil recovery cycle logic (maximum duration in cool mode: 3 minutes, maximum
34.92
duration in heat mode: 6 minutes, defrost cycles lasting over 3 minutes are considered oil
Gas Pipe (Φ, inch) 1 3/8" recovery cycles). Oil recovery operation shall not interrupt heating or cooling operation.
Discharge (Φ,mm) - Optional night quiet modes to reduce outdoor unit sound (4 levels) with automatic
Discharge (Φ,inch) - activation or manual activation (with MIM-B14).
Sound Sound Pressure
Advanced intelligent defrost logic to significantly reduce defrost cycle frequency by
66.0
monitoring air resistance across the condenser coil during heating operation to
Sound Power 89.0 determine defrost operation initiation to prevent unnecessary defrost cycles.
Dimension Net Weight(kg) 333.0 Optional snow blowing logic to prevent snow accumulation on idle outdoor units
Shipping Weight (kg) 355.0 Maximum current control of outdoor unit(s) to limit current (50% - 100% of design
Net Dimensions (WxHxD) (mm) current) adjustable at outdoor unit or central control devices: DMS 2.5 (MIM-D01AN),
1,295 x 1,795 x 765
BACnet Gateway (MIM-B17BN), LON Gateway (MIM-B18BN).
Shipping Dimensions (WxHxD) (mm) 1,363 x 1,987 x 832 Energy savings options to reduce system energy consumption when average indoor room
Operating Cooling [°C] -5.0 ~ 48.0 temperatures are greater than average indoor set temperatures in heating mode or when
Temp. Range
Heating [°C] -25.0 ~ 24.0 average indoor room temperatures are lower than average indoor set temperatures in
cooling mode.
Samsung maintains a policy of ongoing development, specifications are subject to change
* Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75⁰F WB.
without notice.
* Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB.

* Restrictions apply. Design above 130% requires an engineering review for approval.
Refer to the Technical Data Book for more information.

English 1

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
11/2/2022 2

Submittal AM240KXVANH/TL DVM S Latin America

English 2

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
11/2/2022 3

Specifications

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.
11/2/2022 4

Specifications

Samsung maintains a policy of ongoing development, specifications are subject to change without notice.