Professional Documents
Culture Documents
PROTECTION
Dr. Attaullah Khidran
1
Overcurrent protection
Protection against excess current / overload
Non unit protection
Relay coordination can be achieved by using either
Time
Current
Combination of both time and current
2
Discrimination by time
3
Discrimination by currents
The fault currents varies with the location of faults.
5
Relay characteristics
Instantaneous
Definite time
Inverse Definite Minimum
Time (IDMT)
Very inverse time
Extremely inverse time
GOOGLE
Equation
IEEE vs IEC
6
IDMT Relay Adjustments
→Current Setting
Relay Setting Current (RSI)
aka Pick Up Current.
Current value that will initiate relay operation.
Standard relay rating : 1 A or 5 A.
o 5 A relay will operate when the current is 5 A.
• The RSI is 5 A
o 1 A relay will operate when the current is 1 A.
• The RSI is 1 A
7
Current Setting
Relay Setting Current (RSI)
Line is connected to relay via CT.
o We can express normal RSI in term of line current.
5 A relay paired with 400/5 CT.
400
o The RSI will be 5 × 5
= 400 A.
5 A relay paired with 400/1 CT.
400
o The RSI will be 5 × = 2000 A.
1
1 A relay paired with 400/1 CT.
400
o The RSI will be 1 × = 400 A.
1
9
Current Setting
Plug Setting.
Tapping in the relay coil
Range between 50 % to 200% in steps of ie. 25%
1 A relay paired with 400/1 CT.
o Plug setting of 100% will give RSI of 400 A.
o Plug setting of 125% will give RSI of 400 A × (125/100) = 500 A.
𝑃𝑆
𝑅𝑆𝐼 = 𝑅𝑒𝑙𝑎𝑦 𝑟𝑎𝑡𝑖𝑛𝑔 × 𝐶𝑇 𝑟𝑎𝑡𝑖𝑜 × .
100
𝑃𝑆
𝑅𝑆𝐼 = 𝐶𝑇 𝑟𝑎𝑡𝑖𝑜 × 100
.
If relay rating = CT secondary
10
Current Setting
Selecting PS for overcurrent protection
Relay should not trip when the line is carrying full load
current (IN)
oIN < RSI
𝑃𝑆
𝑅𝑆𝐼 = 𝐶𝑇 𝑟𝑎𝑡𝑖𝑜 ×
100
𝑃𝑆
𝐼𝑁 < 𝐶𝑇 𝑟𝑎𝑡𝑖𝑜 ×
100
𝐼𝑁
𝑃𝑆 > × 100.
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
11
IDMT Relay Adjustments
→Time Setting
Plug Setting Multiplier (PSM)
Relay will trip when line is carrying current (fault current -
FC) greater than RSI
This fault current can be expressed in term of ratio of its
value to RSI
𝐹𝐶
𝑃𝑆𝑀 =
𝑅𝑆𝐼
o How many times the FC is larger than RSI
12
Time Setting
The relay characteristic curve indicate the operation
time of the relay for a specific PSM.
Relay Characteristic Operating Time (RCOT)
𝑅𝐶𝑂𝑇 = 𝑓(𝑃𝑆𝑀)
E.g. PSM of X will give RCOT of XX
RCOT might be different from the desired relay
operating time (ROT). How do we make the relay trip
at YY for PSM of X?
Use another feature of the relay – Time Setting Multiplier
(TSM).
13
Time Setting
IDMT curve
14
Time Setting
Time Setting Multiplier
Setting (multiplier) that will make the relay trip faster
In case where ROT is specified
𝑅𝑂𝑇
o 𝑇𝑆𝑀 =
𝑅𝐶𝑂𝑇
In case where TSM is specified
o 𝑅𝑂𝑇 = 𝑇𝑆𝑀 × 𝑅𝐶𝑂𝑇
15
Discrimination Time
Fault to the right side of relay A can be seen by both Relay A
and Relay B.
Relay A tripped – CB A opened – section A will be interrupted.
Relay B tripped – CB A opened – section A and B will be
interrupted.
ROTB > ROTA
ROTB = ROTA + DT
16
Factors Affecting Discrimination Time
Errors
All measuring devices, including the relay, are subject to
manufacturer's error. A tolerance must be allowed.
CB operating time
The circuit breaker must interrupt the fault current completely before
the back up relay ceases to be energized.
Overshoot time
When the driving torque is removed, the relay disc continues to
rotate. The time of rotation after the relay is de-energised is called the
overshoot time.
Final margin
Some extra allowance is required to ensure that a satisfactory
operation of the relay is obtained. This is also called safety margin.
17
Recommended
Discrimination Time
0.5 s – Conservative setting.
0.4 s – With faster breaker, lower relay overshoot
time.
0.35 s – Under best / favourable conditions
Variable time – google it
18
Example
PS range between 50 % to 200% in steps of 25%
TSM range between 0.1 to 1 in step of 0.01
DT = 0.4s
19
Example – PS of all relays
𝐼𝑁
𝑃𝑆 > × 100.
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
𝑃𝑆
𝑅𝑆𝐼 = 𝐶𝑇 𝑟𝑎𝑡𝑖𝑜 ×
100
22
Example – time setting of Relay C
23
Example – time setting of Relay D
24
25
Problem 1
Determine the relay
settings at A, B and C:
Max load at each feeder
of the 415 V bus is 750 A
When fault occur near C,
relay C will operate at
0.25 s while relay B and
A will operate with 0.4 s
delay
Fault current at 415 V is
23.68 kA
26
Problem 1
At C 𝑃𝑆𝑀 =
23680
= 29.6. > 21
800
Max load = 750 A
CT ratio = 800/5
𝑅𝐶𝑂𝑇 = 2.2𝑠
0.25
FC = 23.68 kA 𝑇𝑆𝑀 = = 0.11
2.2
ROT = 0.25s
750
𝑃𝑆 > × 100 = 93.75
800
∴ PS = 100
100
𝑅𝑆𝐼 = 800 × = 800𝐴
100
28
Problem 1
At B – LV side 𝑃𝑆𝑀 =
23680
= 14.8
1600
Max load = transformer
rating 𝑅𝐶𝑂𝑇 = 2.5𝑠
𝟏𝑴 0.65
= = 1391A 𝑇𝑆𝑀𝐵 = = 0.26
3×415 2.5
CT ratio = 1600/5
FC = 23.68 kA
ROT = 0.25 + 0.4 = 0.65𝑠
1391
𝑃𝑆 > × 100 = 87
1600
∴ PS = 100%
100
𝑅𝑆𝐼 = 1600 × =
100
1600𝐴
29
Problem 1
At A – HV side 𝑃𝑆𝑀 =
893
= 15.9
56.25
Max load = transformer
rating 𝑅𝐶𝑂𝑇 = 2.5𝑠
1𝑀 0.65
= = 52.49A 𝑇𝑆𝑀 = = 0.26
3×11𝑘 2.5
CT ratio = 75/5
415
FC =23.68k × = 0.893kA
11𝑘
ROT = 0.25 + 0.4 = 0.65𝑠
52.49
𝑃𝑆 > × 100 = 70
75
∴ PS = 75%
75
𝑅𝑆𝐼 = 75 × = 56.25𝐴
100
30
Test 1 201620172
Test 1 201720181
31
32
Problem 2
10 MVA 4 MVA
100 MVA 34.5/13.2 kV
34.5 kV R3
Z = 20 % Z = 1.5 pu
R7 R5 R4 3 MVA
R2
R6
2 MVA
2 MVA
R1
Relay R7 R6 R5 R4 R3, R2, R1
CT Ratio 200/5 50/5 200/5 400/5 200/5
33
Problem 2
Propose the relay setting (nearest value of PS and TSM) for all relays in the
network.
PS : 50 % to 200% in step of 25%
TSM : 0.05 to 1.0 in step of 0.01
Choose the discrimination time (DT) equal to 0.4 second in your
calculation.
Assume that relays R1, R2 and R3 will operate with 0.36 second when a
three-phase fault occurs downstream close to the relay while R6 will
operate with 0.22 second when a three-phase fault occurs downstream
close to the relay.
Use IDMT relay characteristic given by Figure Q.2(b) in your calculation.
All impedance values are referred to its own rating. The impedance of the
transmission line is 1.5 pu with base of 100 MVA, 13.2 kV. Assume that all
impedances are pure reactance..
34
Relay CT ratio Max load Max load Plug Setting RSI
(MVA) current (A) (A)
1 200/5 2 87.48 50 100
2 200/5 3 131.22 75 150
3 200/5 4 174.95 100 200
4 400/5 2+3+4 = 9 393.65 100 400
5 200/5 10 (Tx rating) 167.35 100 200
6 50/5 2 33.47 75 37.5
7 200/5 2+ 10 = 12 200.82 125 250
35
Relay RSI (A) Maximum fault
current (A)
1 100
2 150
3 200
4 400
5 200
6 37.5
7 250
36
Problem 2 – Fault Analysis
34.5𝑘 2
𝑍𝑠 = 100𝑀
= j11.90Ω
34.5𝑘 2
𝑍𝑠,𝑏𝑎𝑠𝑒 = = j11.90Ω
100𝑀
11.9
𝑍𝑠,𝑝𝑢 = 11.9 = 1.0pu
100
𝑍𝑇,𝑝𝑢 = 0.2 × 10 = 2.0pu
𝑍𝐿,𝑝𝑢 = 1.5pu
37
Problem 2 – Fault Analysis
Maximum fault current of R1,R2 and R3
1
• 𝐼𝐹,𝑝𝑢 = = 0.2222
1.0+2.0+1.5
100𝑀
• 𝐼𝐹 = 0.2222 × 3×13.2𝑘 = 972 A
Maximum fault current of R4
1
• 𝐼𝐹,𝑝𝑢 = 1.0+2.0 = 0.3333
100𝑀
• 𝐼𝐹,𝑠𝑒𝑐 = 0.3333 × 3×13.2𝑘
= 1458 A
100𝑀
• 𝐼𝐹,𝑝𝑟𝑖 = 0.3333 × 3×34.5𝑘
= 558 A
Maximum fault current of R5,R6 and R7
1
• 𝐼𝐹,𝑝𝑢 = =1
1.0
100𝑀
• 𝐼𝐹 = 1 × 3×34.5𝑘
= 1673 A
38
Relay RSI (A) Maximum fault Fault current of
current (A) downstream relay (A)
1 100 972 -
2 150 972 -
3 200 972 -
4 400 1458 972
5 200 1673 558 (1458 on sec)
6 37.5 1673 -
7 250 1673 1673
39
Problem 2 – TSM setting (R1)
Fault downstream of R1
R1 can see 972 A.
𝐹𝐶 972
𝑃𝑆𝑀 = = = 9.72
𝑅𝑆𝐼1 100
𝑅𝐶𝑂𝑇 = 𝑓 9.72 = 3s
𝑅𝑂𝑇1 0.36
𝑇𝑆𝑀1 = = = 0.12
𝑅𝐶𝑂𝑇 3
40
Problem 2 – TSM setting (R2)
Fault downstream of R2
R2 can see 972 A.
𝐹𝐶 972
𝑃𝑆𝑀 = = = 6.48
𝑅𝑆𝐼2 150
𝑅𝐶𝑂𝑇 = 𝑓 6.48 = 3.7s
𝑅𝑂𝑇2 0.36
𝑇𝑆𝑀2 = = = 0.09 0.1
𝑅𝐶𝑂𝑇 3.7
Minimum TSM is 0.1 for this relay
41
Problem 2 – TSM setting (R3)
Fault downstream of R3
R3 can see 972 A.
𝐹𝐶 972
𝑃𝑆𝑀 = = = 4.86
𝑅𝑆𝐼3 200
𝑅𝐶𝑂𝑇 = 𝑓 4.86 = 4.4s
𝑅𝑂𝑇3 0.36
𝑇𝑆𝑀3 = = = 0.08
𝑅𝐶𝑂𝑇 4.4
42
Problem 2 – TSM setting (R4)
Fault downstream of R1,2,3 Fault downstream of R4
R4 can see 972 A. R4 can see 1458 A.
(maximum current (maximum current
downstream of downstream of R4)
R1,R2,R3) 𝐹𝐶 1458
𝑃𝑆𝑀 = = = 3.65
𝐹𝐶 972 𝑅𝑆𝐼4 400
𝑃𝑆𝑀 = = = 2.43
𝑅𝑆𝐼4 400 𝑅𝐶𝑂𝑇 = 𝑓 3.65 = 5.3s
𝑅𝐶𝑂𝑇 = 𝑓 2.43 = 7.8s 𝑅𝑂𝑇 = 𝑇𝑆𝑀4 × 𝑅𝐶𝑂𝑇
𝑅𝑂𝑇 = 0.36 + 0.4 = 0.76s = 0.1 × 5.3 = 0.53s
𝑅𝑂𝑇 0.76
𝑇𝑆𝑀4 = = = 0.1
𝑅𝐶𝑂𝑇 7.8
43
Problem 2 – TSM setting (R5)
Fault downstream of R4 Fault downstream of R5
R5 can see 558 A. R5 can see 1673 A.
(maximum current (maximum current
downstream of R4 - downstream of R5)
1458 A on the LV side) 𝐹𝐶 1673
𝑃𝑆𝑀 = = = 8.37
𝐹𝐶 558 𝑅𝑆𝐼5 200
𝑃𝑆𝑀 = = = 2.79
𝑅𝑆𝐼5 200 𝑅𝐶𝑂𝑇 = 𝑓 8.37 = 3.2s
𝑅𝐶𝑂𝑇 = 𝑓 2.79 = 6.8s 𝑅𝑂𝑇 = 𝑇𝑆𝑀5 × 𝑅𝐶𝑂𝑇
𝑅𝑂𝑇 = 0.53 + 0.4 = 0.94s = 0.14 × 3.2 = 0.45s
𝑅𝑂𝑇 0.94
𝑇𝑆𝑀5 = = = 0.14
𝑅𝐶𝑂𝑇 6.8
44
Problem 2 – TSM setting (R6)
Fault downstream of R6
R6 can see 1673 A.
𝐹𝐶 1673
𝑃𝑆𝑀 = = = 44.6
𝑅𝑆𝐼6 37.2
𝑅𝐶𝑂𝑇 = 𝑓 22 = 2.2s
𝑅𝑂𝑇6 0.22
𝑇𝑆𝑀6 = = = 0.1
𝑅𝐶𝑂𝑇 2.2
45
Problem 2 – TSM setting (R7)
Fault downstream of R5,6
R7 can see 1673 A. (maximum current downstream of
R5,R6)
𝐹𝐶 1673
𝑃𝑆𝑀 = = = 6.69
𝑅𝑆𝐼7 250
𝑅𝐶𝑂𝑇 = 𝑓 6.69 = 3.6s
𝑅𝑂𝑇 = max(𝑅𝑂𝑇5 , 𝑅𝑂𝑇6 ) + 0.4 = max 0.45,0.22 + 0.4 =
0.85s
𝑅𝑂𝑇 0.85
𝑇𝑆𝑀7 = = = 0.24
𝑅𝐶𝑂𝑇 3.6
46
Final 201620172
Test 1 201720181
47
Directional Overcurrent Relay
Fault at point X
Fault current?
Breaker to open?
Set faster breaker to isolate X
Fault at point Y
Fault current?
Breaker to open?
Isolated sections?
We need directional relay
48
Earth Fault Protection
Normal overcurrent protection can cater for earth fault
provided the minimum earth fault current has sufficient
magnitude.
At distribution circuit – provide separate relay at each phase
or at two phase – the second scheme is sufficient for solidly
earthed system.
Relay can be set independent from load current and setting
below load current – (10%-40%)
49
Instantaneous high-set relay
Combined with IDMT relay.
For long transmission line or
transformer feeder where
source impedance is small
compared to circuit
impedance.
Instantaneous high set relay
reduce tripping time at
maximum short circuit
current and shorten grading
margin time between circuit
breakers
50
It is given that fault current level at 33 kV side is 2,700 A, CT
ratio at 33 kV side is 200 : 1 and 132 kV side is 100 : 1. If both
relays R1 and R2 are set for 100% plug setting, determine the
operation time for both relays when time grading margin of
0.6 second is given and TSM for relay R1 is 0.15. Calculate also
TSM for R2.
SPACE KL 30.9.12
33kV
132kV
100/1 132/33kV 200/1
IF = 2700A
R2 R1
51