You are on page 1of 5

Customer report

Date: 20/5/2022

Project : F and M - Design Support

Selection : PU-01
by Rashid Husain

50FC280 - Assembly B2
Air cooled rooftop, Standard. Economizer, 2 dampers

Seasonal Efficiency
Allowed applications for CE mark:
SEER | ηs cool | Energy Class 4.54 | 178.6 % | B
SCOP | ηs heat | Energy Class 3.37 | 131.8 % | B

SEER/SCOP values are calculated for each outdoor fan technology

Operating conditions
Non contractual picture
Mode Cooling Heating
Indoor conditions (Temp. / Rel. Performance
24 / 55 20 / 50
Humidity) °C / % Mode Cooling Heating
Outdoor conditions (Temp. / Rel. Gross thermodynamic capacity kW 241.75 292.15
46 / 31.8 6 / 90
Humidity) °C / %
Sensible thermodynamic capacity kW 174.93 292.15
Supply air flow m3/h 32400
Total capacity output kW 237.32 296.58
Fresh air flow m3/h 5904
Sensible capacity output kW 170.5 296.58
Fresh air ratio % 18.22222222222222
Compressor consumption kW 99.55 74.56
Available pressure (supply) Pa 500
Consumption (compressors + fans) kW 122.07 97.58
Mixing conditions (Temp. / Rel. 28.07 / 17.46 /
Net capacity kW 238.41 295.49
Humidity) °C / % 50.86 55.64
Gross EER compressor kW 2.43 -
Evaporator / Condenser outlet (Temp. / 11.49 / 43.95 /
Gross COP compressor kW - 3.92
Rel. Hum.) °C / % 100 12.26
Net EER kW 2.08 -
11.89 / 44.39 /
Supply (Temp. / Rel. Hum.) Net COP kW - 3.29
°C / % 97.43 11.98
Radiated Sound Power Level (LwA) dBA 92.99
Unit information Radiated sound pressure level (LpA) dBA 65.01 (at 5m)

Refrigerant type / GWP R410A / 2088 Discharge sound level (LwA) dBA 83.43

Refrigerant kg / tCO2Equ 75 / 156.60 Intake sound level (LwA) dBA 66.83

Number of refrigerant Circuit 2


Documentation
Number of compressor 4
Capacity control 100-75-50-25-0 % PSD (.PDF)

Dimensions Drawing (.DWG)


Electric data
Revit (.PDF)
400V / 3ph + N /
Unit voltage Revit (.RFA)
V / Ph / Hz 50Hz
Start Up Current A 448.39
Current for cable selection (excluding
223.40
electrical heater) A

Short circuit current kA 15

ECAT EMEA Rooftop builder - v3.32.0-0


Customer report

50FC 0280 A 4 A B2 LL 000 S N G H M 00A 0000 0000 0 0 BA00 A0 A00 000 AA00 0000 0003 00

50FC0280A4AB2LL000SNGHM00A0000
000000BA00A0A00000AA000000000300

Selected mounting

Return - Discharge
I / S = Discharge C (Cross flow)
R = Return B2: (Cross flow)
Air Extraction Air direction 3: Lateral supply and lateral return
N / F = Fresh Air

Non contractual picture

Supply fans Outdoor fan


Technology EC plug-fan Technology EcElectronic
Number and type 6 * R3G500RA2866 Number of fans 4.00
Fan material Polypropylene (PP) Total fans consumption (cooling) kW 11.50
Total motor(s) power kW 18.3 Total fans consumption (heating) kW 12.00
Total fan consumption kW 11.02 Rotation speed rpm 1070.00
Rotation speed rpm 1508.33
Maximum available pressure Pa 864.31 Dimensions
Supply available pressure Pa 500 Length mm 6350
Supply air flow m3/h 32400 Width mm 2257
SFP kW / (m3/s) 1.22 Height mm 2494
Weight

Weight (empty) Unit kg 3235

Weight (empty) Rotary Wheel kg 0

Weight (empty) Roofcurb kg 0

Weight (empty) TOTAL kg 3235

Weight (operation) TOTAL kg 3235

Weight with all options selected included (given at +/- 10%).

ECAT EMEA Rooftop builder - v3.32.0-0


Customer report

Configuration
Designation
B2 50FC280
Supply fan R3G500RA2866
EC electronic axial fan(s)
G4 filters + F7 folded filters
1 temp + humidity sensor RS485
Condensate drain pan in stainless steel
Aluminium - Aluminium
400V / 3ph + N / 50Hz
Thermal economizer management
Insulation M0 with double wall (50mm)
Graphic terminal installed in the electrical cabinet
Unit configuration: stand-alone

As per our general sales conditions in your possession.


Validity of prices: 1 month.
As part of our policy of continual improvement, we reserve the right to make any technical modifications we feel necessary without prior notice.

ECAT EMEA Rooftop builder - v3.32.0-0