SDPWS
Special Design Provisions for Wind & Seismic
2015 EDITION
ANSI/AWC SDPWS-2015
Approval date September 8, 2014
Updates and Errata
While every precaution has been taken to
ensure the accuracy of this document, errors
may have occurred during development.
Updates or Errata are posted to the American
Wood Council website at www.awc.org.
Technical inquiries may be addressed to
info@awc.org.
The American Wood Council (AWC) is the voice of North American traditional and engineered wood
products. From a renewable resource that absorbs and sequesters carbon, the wood products industry
makes products that are essential to everyday life. AWC’s engineers, technologists, scientists, and
building code experts develop state-of-the-art engineering data, technology, and standards on structural
wood products for use by design professionals, building officials, and wood products manufacturers to
assure the safe and efficient design and use of wood structural components.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
SDPWS
Special Design Provisions for Wind & Seismic
2015 EDITION
Dedicated to the memory of James E. Russell, who passed away on February 14, 2013.
As Chairman of AWC’s Wind & Seismic Task Committee since its inception in 2005,
Jim gave generously of his time, expertise, and leadership. He was a gifted Committee
Chair, advisor, and friend to all at AWC and will be missed immensely.
ISBN 978-1-940383-04-0
Copyright Permission
American Wood Council
222 Catoctin Circle, SE, Suite 201
Leesburg, VA 20175
info@awc.org
TABLE OF CONTENTS
Chapter/Title Page Chapter/Title Page
LIST OF TABLES
3.1.1.1 Wall Stud Repetitive Member Factors ............ 8 4.3A Nominal Unit Shear Capacities for Wood-
Frame Shear Walls (Wood-based Panels) ..... 35
3.2.1 Nominal Uniform Load Capacities (psf) for
Wall Sheathing Resisting Out-of-Plane Wind 4.3B Nominal Unit Shear Capacities for Wood-
Loads ............................................................... 9 Frame Shear Walls (Wood Structural Panels
Applied over 1/2" or 5/8" Gypsum
3.2.2 Nominal Uniform Load Capacities (psf)
Wallboard or Gypsum Sheathing Board) ..... 36
for Roof Sheathing Resisting Out-of-Plane
Wind Loads ................................................... 10 4.3C Nominal Unit Shear Capacities for Wood-
Frame Shear Walls (Gypsum and Portland
4.2.4 Maximum Diaphragm Aspect Ratios
Cement Plaster) ............................................ 37
(Horizontal or Sloped Diaphragms) ............. 16
4.3D Nominal Unit Shear Capacities for Wood-
4.2A Nominal Unit Shear Capacities for Wood-
Frame Shear Walls (Lumber Shear Walls) ... 38
Frame Diaphragms (Blocked Wood
Structural Panel Diaphragms) ...................... 21 4.4.1 Nominal Uplift Capacity of 7/16" (Nominal)
Minimum Wood Structural Panel Sheathing
4.2B Nominal Unit Shear Capacities for Wood-
or Siding When Used for Both Shear Walls
Frame Diaphragms (Blocked Wood
and Wind Uplift Simultaneously over
Structural Panel Diaphragms Utilizing
Framing with a Specific Gravity of 0.42 or
Multiple Rows of Fasteners (High Load
Greater ........................................................... 43
Diaphragms)) ................................................ 22
4.4.1.6 Maximum Anchor Bolt Spacing (inches) for
4.2C Nominal Unit Shear Capacities for Wood-
Combined Shear and Wind Uplift ................. 43
Frame Diaphragms (Unblocked Wood
Structural Panel Diaphragms) ...................... 23 4.4.2 Nominal Uplift Capacity of 3/8" (Nominal)
Minimum Wood Structural Panel Sheathing or
4.2D Nominal Unit Shear Capacities for Wood-
Siding When Used for Wind Uplift Only over
Frame Diaphragms (Lumber Diaphragms) .. 24
Framing with a Specific Gravity of 0.42 or
4.3.3.2 Unblocked Shear Wall Adjustment Greater ........................................................... 44
Factor, Cub ...................................................... 26
A1 Standard, Common, Box, and Sinker Nails .. 46
4.3.3.5 Shear Capacity Adjustment Factor, Co .......... 28
A2 Standard Cut Washers ................................... 46
4.3.4 Maximum Shear Wall Aspect Ratios............. 28
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
iv SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC
LIST OF FIGURES
4A Examples of Open Front Structures ................... 17 4F Panel Attachment ............................................... 40
4B High Load Diaphragm........................................ 20 4G Panel Splice Occurring over Horizontal
Framing Member................................................ 41
4C Typical Shear Wall Height-to-Width Ratio for
Perforated Shear Walls ....................................... 29 4H Panel Splice Occurring across Studs .................. 41
4D Typical Individual Full-Height Wall Segments 4I Sheathing Splice Plate (Alternate Detail) ......... 42
Height-to-Width Ratio........................................ 29
4E Typical Shear Wall Height-to-Width Ratio
for Shear Walls Designed for Force Transfer
Around Openings ............................................... 29
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 1
DESIGNER
FLOWCHART
1.1 Flowchart 2
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
2 DESIGNER FLOWCHART
1.1 Flowchart
Design Capacity
No
Applicable Load
Effect
Yes
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 3
GENERAL 2
DESIGN
REQUIREMENTS
2.1 General 4
2.2 Terminology 4
2.3 Notation 6
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
4 GENERAL DESIGN REQUIREMENTS
2.1 General
2.1.1 Scope struction (ANSI/AWC NDS) and provisions of this
document.
The provisions of this document cover materials, 2.1.2.2 Strength Design: Load and resistance factor
design and construction of wood members, fasteners, design (LRFD) of wood structures shall be in accord-
and assemblies to resist wind and seismic forces. ance with the National Design Specification (NDS) for
Wood Construction (ANSI/AWC NDS) and provisions
2.1.2 Design Methods of this document.
2.2 Terminology
ALLOWABLE STRESS DESIGN. A method of pro- based material bonded together with a waterproof adhe-
portioning structural members and their connections sive.
such that stresses do not exceed specified allowable
DIAPHRAGM. A roof, floor, or other membrane
stresses when the structure is subjected to appropriate
bracing system acting to transmit lateral forces to the
load combinations (also called working stress design).
vertical resisting elements. When the term “dia-
ASD REDUCTION FACTOR. A factor to reduce phragm” is used, it includes horizontal bracing systems.
nominal strength to an allowable stress design level.
DIAPHRAGM, BLOCKED. A diaphragm in which
BOUNDARY ELEMENT. Diaphragm and shear wall all adjacent panel edges are fastened to either common
boundary members to which sheathing transfers forces. framing members or common blocking.
Boundary elements include chords and collectors at
DIAPHRAGM BOUNDARY. A location where shear
diaphragm and shear wall perimeters, interior openings,
is transferred into or out of the diaphragm sheathing.
discontinuities, and re-entrant corners.
Transfer is either to a boundary element or to another
CHORD. A boundary element perpendicular to the force-resisting element.
applied load that resists axial stresses due to the in-
DIAPHRAGM, UNBLOCKED. A diaphragm that
duced moment.
has fasteners at boundaries and supporting members
COLLECTOR. A diaphragm or shear wall boundary only. Blocking between supporting structural members
element parallel to the applied load that collects and at panel edges is not included.
transfers diaphragm shear forces to the vertical force-
FIBERBOARD. A fibrous, homogeneous panel made
resisting elements or distributes forces within the dia-
from lignocellulosic fibers (usually wood or cane) and
phragm or shear wall.
having a density of less than 31 pounds per cubic foot
COMPOSITE PANELS. A wood structural panel but more than 10 pounds per cubic foot.
comprised of wood veneer and reconstituted wood-
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 5
FORCE TRANSFER SHEAR WALL. A shear wall PLYWOOD. A wood structural panel comprised of
with openings in the wall that has been specifically de- plies of wood veneer arranged in cross-aligned layers.
signed and detailed for force transfer around the open- The plies are bonded with an adhesive that cures on
ings. application of heat and pressure.
HARDBOARD. A fibrous-felted, homogeneous panel RE UIRED STRENGTH. Strength of a member, 2
made from lignocellulosic fibers consolidated under cross section, or connection re uired to resist factored
heat and pressure in a hot press to a density not less loads or related internal moments and forces.
than 31 pounds per cubic foot.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
6 GENERAL DESIGN REQUIREMENTS
2.3 otation
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 7
MEMBERS AND
CONNECTIONS 3
3.1 Framing 8
3.2 Sheathing 8
3.3 Connections 10
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
8 MEMBERS AND CONNECTIONS
3.1 Framing
3.1.1 Wall Framing Table 3.1.1.1 Wall Stud Repetitive Member
Factors
In addition to gravity loads, wall framing shall be
designed to resist induced wind and seismic forces. St Si e S te F cto
The framing shall be designed using the methods refer- 2x 1. 0
enced in 2.1.2.1 for allowable stress design (ASD) and 2x 1.3
2.1.2.2 for strength design (LRFD). 2x 1.2
2x10 1.20
3.1.1.1 Wall Stud Bending Strength and Stiffness 2x12 1.1
Design alue Increase: The reference bending design
value, Fb, for sawn lumber wood studs resisting out-of-
3.1.2 Floor Framing
plane wind loads shall be permitted to be multiplied by
the repetitive member factors in Table 3.1.1.1, in lieu of
the NDS repetitive member factor, Cr 1.1 . The bend- In addition to gravity loads, floor framing shall be
designed to resist induced wind and seismic forces. The
ing stiffness, EI, for sawn lumber studs shall be permit-
ted to be multiplied by the repetitive member factors in framing shall be designed using the methods referenced
in 2.1.2.1 for allowable stress design (ASD) and 2.1.2.2
Table 3.1.1.1 for the purposes of calculating out-of-
for strength design (LRFD).
plane deflection under wind load. The repetitive mem-
ber factors in Table 3.1.1.1 apply when studs are de-
signed for bending strength and stiffness, spaced no 3.1.3 Roof Framing
more than 2 on center, covered on the inside with a
minimum of 1/2 gypsum wallboard, attached in ac- In addition to gravity loads, roof framing shall be
cordance with minimum building code re uirements designed to resist induced wind and seismic forces. The
and sheathed on the exterior with a minimum of 3/ framing shall be designed using the methods referenced
(nominal) wood structural panel sheathing with all pan- in 2.1.2.1 for allowable stress design (ASD) and 2.1.2.2
el joints occurring over studs or blocking and attached for strength design (LRFD).
using a minimum of d common nails spaced a maxi-
mum of on center at panel edges and 12 on center at
intermediate framing members.
3.2 Sheathing
3.2.1 Wall Sheathing factored uniform load capacities to be used for wind
design shall be determined by multiplying the nominal
Exterior wall sheathing and its fasteners shall be uniform load capacities in Table 3.2.1 by a resistance
capable of resisting and transferring wind loads to the factor, b , of 0. . Sheathing used in shear wall assem-
wall framing. aximum spans and nominal uniform blies to resist lateral forces shall be designed in accord-
load capacities for wall sheathing materials are given in ance with .3. Walls sheathed with wood structural
Table 3.2.1. The ASD allowable uniform load capaci- panel sheathing or siding that are designed to resist up-
ties to be used for wind design shall be determined by lift from wind, or combined shear and uplift from wind
dividing the nominal uniform load capacities in Table shall be in accordance with . .
3.2.1 by an ASD reduction factor of 1. . The LRFD
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 9
Table 3.2.1 ominal niform oad apacities psf for Wall Sheathing Resisting ut of lane
Wind oads1
Strength Axis6
Perpendicular to Supports Parallel to Supports
Minimum Maximum Actual Stud Spacing Maximum Actual Stud Spacing
Sheathing Type4 Span Rating or Grade Thickness Stud (in.) Stud (in.)
(in.) Spacing 12 16 24 Spacing 12 16 24
(in.) (in.)
3
Nominal Uniform Nominal Uniform
Loads (psf) Loads (psf)
Wood Structural Panels 24/0 3/8 24 425 240 105 24 90 50 303
(Sheathing Grades, C-C, 24/16 7/16 24 540 305 135 24 110 60 353
C-D, C-C Plugged,
1. Nominal capacities shall be adjusted in accordance with Section 3.2.1 to determine ASD uniform load capacity and LRFD uniform resistances.
2. Unless otherwise noted, tabulated values are based on the lesser of nominal values for either OSB or plywood with 3 or more plies.
3. Tabulated values are based on the lesser of nominal values for either OSB or plywood with 4 or more plies.
4. Wood structural panels shall conform to the requirements for its type in DOC PS 1 or PS 2. Particleboard sheathing shall conform to ANSI A208.1. Hardboard
panel and siding shall conform to the requirements of ANSI/CPA A135.6. Cellulosic fiberboard sheathing shall conform to ASTM C 208.
5. Tabulated values are for maximum bending loads from wind. Loads are limited by bending or shear stress assuming a 2-span continuous condition. Where
panels are continuous over 3 or more spans the tabulated values shall be permitted to be increased in accordance with the ASD/LRFD Manual for Engineered
Wood Construction.
6. Strength axis is defined as the axis parallel to the face and back orientation of the flakes or the grain (veneer), which is generally the long panel direction, unless
otherwise marked.
3.2.2 Floor Sheathing load capacities for roof sheathing materials are given in
Table 3.2.2. The ASD allowable uniform load capaci-
Floor sheathing shall be capable of resisting and ties to be used for wind design shall be determined by
transferring gravity loads to the floor framing. Sheath- dividing the nominal uniform load capacities in Table
ing used in diaphragm assemblies to resist lateral forces 3.2.2 by an ASD reduction factor of 1. . The LRFD
shall be designed in accordance with .2. factored uniform load capacities to be used for wind
design shall be determined by multiplying the nominal
3.2.3 Roof Sheathing uniform load capacities in Table 3.2.2 by a resistance
factor, b , of 0. . Sheathing used in diaphragm as-
Roof sheathing and its fasteners shall be capable of semblies to resist lateral forces shall be designed in ac-
resisting and transferring wind and gravity loads to the cordance with .2.
roof framing. aximum spans and nominal uniform
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
10 MEMBERS AND CONNECTIONS
Table 3.2.2 ominal niform oad apacities psf for Roof Sheathing Resisting ut of lane Wind
oads1 2
Sheathing Type5 Span Rating Minimum Strength Axis7 Applied Strength Axis7 Applied
or Grade Thickness Perpendicular to Supports Parallel to Supports
(in.)
Rafter/Truss Spacing (in.) Rafter/Truss Spacing (in.)
12 16 19.2 24 32 48 12 16 24
Nominal Uniform Loads (psf) Nominal Uniform Loads (psf)
Wood Structural Panels 24/0 3/8 425 240 165 105 - - 90 50 303
(Sheathing Grades, C-C, 24/16 7/16 540 305 210 135 - - 110 60 353
C-D, C-C Plugged, OSB) 32/16 15/32 625 355 245 155 90 - 155 90 453
40/20 19/32 955 595 415 265 150 - 255 145 753
48/24 23/32 11603 8403 6153 3953 2203 1003 4553 2553 1153
Wood Structural Panels 16 o.c. 19/32 705 395 275 175 100 - 170 95 503
(Single Floor Grades, 20 o.c. 19/32 815 455 320 205 115 - 235 135 703
Underlayment, C-C Plugged) 24 o.c. 23/32 11603 6703 4653 3003 1703 - 4403 2503 1103
32 o.c. 7/8 13954 10004 6954 4454 2504 1104 11604 6554 2904
48 o.c. 1-1/8 17904 12954 10604 8054 4554 2004 17904 11454 5104
1. Nominal capacities shall be adjusted in accordance with Section 3.2.3 to determine ASD uniform load capacity and LRFD uniform resistances.
2. Unless otherwise noted, tabulated values are based on the lesser of nominal values for either OSB or plywood with 3 or more plies.
3. Tabulated values are based on the lesser of nominal values for either OSB or plywood with 4 or more plies.
4. Tabulated values are based on the lesser of nominal values for either OSB or plywood with 5 or more plies.
5. Wood structural panels shall conform to the requirements for its type in DOC PS 1 or PS 2.
6. Tabulated values are for maximum bending loads from wind. Loads are limited by bending or shear stress assuming a 2-span continuous condition. Where
panels are continuous over 3 or more spans, the tabulated values shall be permitted to be increased in accordance with the ASD/LRFD Manual for Engineered
Wood Construction.
7. Strength axis is defined as the axis parallel to the face and back orientation of the flakes or the grain (veneer), which is generally the long panel direction, unless
otherwise marked.
3.3 onnections
Connections resisting induced wind and seismic
forces shall be designed in accordance with the meth-
ods referenced in 2.1.2.1 for allowable stress design
(ASD) and 2.1.2.2 for strength design (LRFD).
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 11
3. .2 esign Re uirements
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
12 MEMBERS AND CONNECTIONS
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 13
LATERAL
FORCE-
RESISTING 4
SYSTEMS
4.1 General 14
4.2 Wood-Frame Diaphragms 15
4.3 Wood-Frame Shear Walls 25
4.4 Wood Structural Panels Designed
to Resist Combined Shear and Uplift
from Wind 39
Table 4.2.4 Maximum Diaphragm Aspect Ratios ...................16
Tables 4.2A-D Nominal Unit Shear Capacities for Wood-
Frame Diaphragms .......................................21 – 24
Table 4.3.3.2 Unblocked Shear Wall Adjustment Factor, Cub ..26
Table 4.3.3.5 Shear Capacity Adjustment Factor, Co ................28
Table 4.3.4 Maximum Shear Wall Aspect Ratios ....................28
Tables 4.3A-D Nominal Unit Shear Capacities for Wood-
Frame Shear Walls .........................................35 – 38
Table 4.4.1 Nominal Uplift Capacity of 7/16" Wood
Structural Panel Sheathing or Siding–Combined
Shear and Uplift .....................................................43
Table 4.4.1.6 Maximum Shear Wall Aspect Ratios ....................43
Table 4.4.2 Nominal Uplift Capacity of 3/8" Wood Structural
Panel Sheathing or Siding–Uplift Only ................44
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
14 LATERAL FORCE-RESISTING SYSTEMS
4.1 General
4.1.1 Design Requirements 4.1.5 Wood Members and Systems
Resisting Seismic Forces Contributed by
The proportioning, design, and detailing of engi- Masonry and Concrete Walls
neered wood systems, members, and connections in
lateral force-resisting systems shall be in accordance Wood-frame shear walls, wood-frame diaphragms,
with the reference documents in 2.1.2 and provisions in trusses, and other wood members and systems shall not
this chapter. A continuous load path, or paths, with ad- be used to resist seismic forces contributed by masonry
equate strength and stiffness shall be provided to trans- or concrete walls in structures over one story in height.
fer all forces from the point of application to the final
point of resistance. Exceptions:
1. Wood floor and roof members shall be permit-
4.1.2 Shear Capacity ted to be used in diaphragms and horizontal
trusses to resist horizontal seismic forces con-
Nominal shear capacities of diaphragms and shear tributed by masonry or concrete walls provided
walls are provided for reference assemblies in Tables such forces do not result in torsional force dis-
4.2A, 4.2B, 4.2C, and 4.2D and Tables 4.3A, 4.3B, tribution through the diaphragm or truss.
4.3C, and 4.3D, respectively. Alternatively, shear ca- 2. Vertical wood structural panel sheathed shear
pacity of diaphragms and shear walls shall be permitted walls shall be permitted to be used to provide
to be calculated by principles of mechanics using val- resistance to seismic forces contributed by ma-
ues of fastener strength and sheathing shear capacity. sonry or concrete walls in two-story structures,
provided the following requirements are met:
4.1.3 Deformation Requirements a. Story-to-story wall heights shall not exceed
12'.
b. Diaphragms shall not be considered to
Deformation of connections within and between transmit lateral forces by torsional force
structural elements shall be considered in design such distribution or cantilever past the outermost
that the deformation of each element and connection supporting shear wall.
comprising the lateral force-resisting system is compat- c. Combined deflections of diaphragms and
ible with the deformations of the other lateral force- shear walls shall not permit design story drift
resisting elements and connections and with the overall of supported masonry or concrete walls to
system. exceed the allowable story drift in accord-
ance with Section 12.12.1 of ASCE 7.
4.1.4 Boundary Elements d. Wood structural panel diaphragms shall be
blocked diaphragms.
Shear wall and diaphragm boundary elements shall e. Wood structural panel shear walls shall be
be provided to transfer the design tension and compres- blocked shear walls and, for the lower sto-
sion forces. Diaphragm and shear wall sheathing shall ry, the sheathing shall have a minimum
not be used to splice boundary elements. Diaphragm nominal panel thickness of 15/32".
chords and collectors shall be placed in, or in contact f. There shall be no out-of-plane horizontal
with, the plane of the diaphragm framing unless it can offsets between the first and second stories
be demonstrated that the moments, shears, and deflec- of wood structural panel shear walls.
tions, considering eccentricities resulting from other
configurations, can be tolerated without exceeding the 4.1.5.1 Anchorage of Concrete or Masonry Struc-
framing capacity and drift limits. tural Walls to Diaphragms: In Seismic Design Catego-
ries C, D, E, or F, diaphragms shall be provided with
continuous ties or struts between diaphragm chords to
distribute concrete or masonry structural wall anchor-
age forces in accordance with Section 12.11.2 of ASCE
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 15
7 into the diaphragms. Subdiaphragms shall be permit- 4.1.6 Wood Members and Systems
ted to be used to transmit the anchorage forces to the Resisting Seismic Forces from Other
main continuous cross-ties. The maximum length-to- Concrete or Masonry Construction
width ratio of the structural subdiaphragm shall be
2.5:1. Connections and anchorages capable of resisting Wood members and systems shall be permitted to
the prescribed forces shall be provided between the di- be used where designed to resist seismic forces from
aphragm and the attached components. concrete, or masonry components other than walls, in-
4.1.5.1.1 Anchorage shall not be accomplished by cluding but not limited to: chimneys, fireplaces, con-
use of nails subject to withdrawal or toe-nails nor shall crete or masonry veneers, and concrete floors.
wood ledgers or framing be used in cross-grain bending
or cross-grain tension.
4.1.5.1.2 The diaphragm sheathing shall not be
4.1.7 Toe-Nailed Connections
4
considered effective as providing the ties or struts re- In seismic design categories D, E, and F, the capac-
quired by this section. ity of toe-nailed connections shall not be used when
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
16 LATERAL FORCE-RESISTING SYSTEMS
Alternatively, for wood structural panel dia- ments of the story below. It shall be permitted to ideal-
phragms, deflection shall be permitted to be calculated ize a diaphragm as rigid when the computed maximum
using a rational analysis where apparent shear stiffness in-plane deflection of the diaphragm itself under lateral
accounts for panel shear deformation and non-linear load is less than or equal to two times the average de-
nail slip in the sheathing-to-framing connection. flection of adjoining vertical elements of the lateral
force-resisting system of the associated story under
4.2.3 Unit Shear Capacities equivalent tributary lateral load.
When a diaphragm is not idealized as rigid or flexi-
Tabulated nominal unit shear capacities for seismic ble, the diaphragm shear forces shall be distributed to
design are provided in Column A of Tables 4.2A, 4.2B, the vertical resisting elements using a semi-rigid dia-
4.2C, and 4.2D; and for wind design in Column B of phragm analysis based on the relative stiffnesses of the
Tables 4.2A, 4.2B, 4.2C, and 4.2D. The ASD allowable diaphragm and the vertical resisting elements account-
unit shear capacity shall be determined by dividing the ing for both shear and flexural deformations. In lieu of
tabulated nominal unit shear capacity, modified by ap- using a semi-rigid diaphragm analysis for distribution
plicable footnotes, by the ASD reduction factor of 2.0. of story shear forces, it shall be permitted to use an en-
The LRFD factored unit resistance shall be determined veloped analysis whereby distribution of horizontal
by multiplying the tabulated nominal unit shear capacity, diaphragm shear to each vertical resisting element is the
modified by applicable footnotes, by a resistance factor, larger of the shear forces resulting from analyses where
D, of 0.80. No further increases shall be permitted.
the diaphragm is idealized as flexible and the dia-
phragm is idealized as rigid.
4.2.4 Diaphragm Aspect Ratios 4.2.5.1 Torsional Irregularity: Structures with
wood-frame diaphragms modeled as semi-rigid or ide-
Size and shape of diaphragms shall be limited to alized as rigid shall be considered as torsionally irregu-
the aspect ratios in Table 4.2.4. lar under seismic load when the maximum story drift,
computed from seismic design forces including acci-
dental torsion, at one end of the structure is more than
Table 4.2.4 Maximum Diaphragm Aspect
1.2 times the average of the story drifts at the two ends
Ratios of the structure. Where a torsional irregularity exists in
(Horizontal or Sloped structures assigned to Seismic Design Category B, C,
Diaphragms) D, E, or F, diaphragms shall meet all of the following
requirements:
Diaphragm Maximum
1. The diaphragm conforms to 4.2.7.1, 4.2.7.2, or
Sheathing Type L/W Ratio 4.2.7.3.
Wood structural panel, unblocked 3:1 2. The L/W ratio is not greater than 1.5:1 when
Wood structural panel, blocked 4:1 sheathed in conformance with 4.2.7.1 or not
Single-layer straight lumber sheathing 2:1 greater than 1:1 when sheathed in conformance
Single-layer diagonal lumber sheathing 3:1 with 4.2.7.2 or 4.2.7.3.
Double-layer diagonal lumber sheathing 4:1 3. The maximum story drift at each edge of the
structure shall not exceed the ASCE 7 allowa-
4.2.5 Horizontal Distribution of Shear ble story drift when subject to seismic design
forces including torsion, and accidental torsion.
The distribution of shear to vertical resisting ele-
ments shall be based on an analysis where the dia- 4.2.5.2 Open Front Structures: For resistance to
phragm is modeled as semi-rigid, idealized as flexible, seismic loads, wood-frame diaphragms in open front
or idealized as rigid. When a diaphragm is idealized as structures shall comply with all of the following re-
flexible, the diaphragm shear forces shall be distributed quirements:
to the vertical resisting elements based on tributary ar- 1. The diaphragm conforms to 4.2.7.1, 4.2.7.2, or
ea. When a diaphragm is idealized as rigid, the dia- 4.2.7.3.
phragm shear forces shall be distributed based on the 2. The L′/W′ ratio (as shown in Figure 4A (a
relative lateral stiffnesses of the vertical-resisting ele- through d)) is not greater than 1.5:1 when
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 17
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
18 LATERAL FORCE-RESISTING SYSTEMS
4.2.6.3 Fasteners: Sheathing shall be attached to el edges shall be 6" on center. Nails along in-
framing members using nails or other approved fasten- termediate framing members and blocking for
ers alone, or in combination with adhesives. Nails shall panels shall be the same size as installed at the
be driven with the head of the nail flush with the sur- panel edges. Maximum nail spacing shall be 6"
face of the sheathing. Other approved fasteners shall be on center when support spacing of 48" on cen-
driven as required for proper installation of that fasten- ter is specified and 12" on center for closer
er. support spacings.
3. The width of the nailed face of framing mem-
4.2.7 Diaphragm Assemblies bers and blocking shall be 2" nominal or great-
er at adjoining panel edges except that a 3"
nominal or greater width at adjoining panel
4.2.7.1 Wood Structural Panel Diaphragms: Dia-
edges and staggered nailing at all panel edges
phragms sheathed with wood structural panel sheathing
are required where:
shall be permitted to be used to resist seismic and wind
a. Nail spacing of 2-1/2" on center or less at
forces. Wood structural panel sheathing used for dia-
adjoining panel edges is specified, or
phragms that are part of the lateral force-resisting sys-
b. 10d common nails having penetration in-
tem shall be applied directly to the framing members to framing members and blocking of
and blocking. more than 1-1/2" are specified at 3" on
Exception: Wood structural panel sheathing in a center or less at adjoining panel edges.
diaphragm is permitted to be fastened over solid 4. Wood structural panels shall conform to the
lumber planking or laminated decking provided requirements for their type in DOC PS1 or PS2.
the following requirements are met:
1. Panel edges do not coincide with joints in the 4.2.7.1.2 High Load Blocked Diaphragms: All
lumber planking or laminated decking. joints in sheathing shall occur over and be fastened to
2. Adjacent panel edges parallel to the planks or common framing members or common blocking. The
decking are fastened to a common member. size and spacing of fasteners at wood-frame diaphragm
3. The planking or decking shall be of sufficient boundaries and panel edges shall be as prescribed in
thickness to satisfy minimum fastener penetra- Table 4.2B and Figure 4B. The diaphragms shall be
tion in framing members and blocking as re- constructed as follows:
quired in Table 4.2A. 1. Panels shall not be less than 4' x 8' except at
4. Diaphragm aspect ratio (L/W) does not exceed boundaries and changes in framing where min-
that for a blocked wood structural panel dia- imum panel dimension shall be 24" unless all
phragm (4:1). edges of the undersized panels are supported by
5. Diaphragm forces are transferred from wood and fastened to framing members or blocking.
structural panel sheathing to diaphragm bound- 2. Nails shall be located at least 3/8" from panel
ary elements through planking or decking or by edges but not less than distances shown in Fig-
other methods. ure 4B. Maximum nail spacing at panel edges
shall be 6" on center. Nails along intermediate
4.2.7.1.1 Blocked Diaphragms: Where diaphragms framing members for panels shall be the same
are designated as blocked, all joints in sheathing shall size as installed at the panel edges. Maximum
occur over and be fastened to common framing mem- nail spacing shall be 6" on center when support
bers or common blocking. The size and spacing of fas- spacing of greater than 32" on center is speci-
teners at wood-frame diaphragm boundaries and panel fied. Maximum nail spacing shall be 12" on
edges shall be as prescribed in Table 4.2A. The dia- center for specified support spacing of 32" on
phragm shall be constructed as follows: center or less.
1. Panels shall not be less than 4' x 8' except at 3. In diaphragm boundary members, lines of fas-
boundaries and changes in framing where min- teners shall be equally spaced and fasteners
imum panel dimension shall be 24" unless all within each line shall be staggered where spac-
edges of the undersized panels are supported by ing is 3" on center or less.
and fastened to framing members or blocking. 4. The depth of framing members and blocking
2. Nails shall be located at least 3/8" from the into which the nail penetrates shall be 3" nomi-
edges of panels. Maximum nail spacing at pan- nal or greater.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 19
5. The width of the nailed face of framing mem- ports are not less than 3" nominal (2-½" thick) in width
bers and blocking at boundaries and adjoining or 4" nominal (3-½" deep) in depth.
panel edges shall be 3" nominal or greater. The 4.2.7.3 Diaphragms Diagonally Sheathed with
width of the nailed face not located at bounda- Double-Layer of Lumber: Double diagonally sheathed
ries or adjoining panel edges shall be 2" nomi- lumber diaphragms shall be permitted to be used to re-
nal or greater. sist seismic and wind forces. Double diagonally
6. Wood structural panels shall conform to the re- sheathed lumber diaphragms shall be constructed of
quirements for their type in DOC PS1 or PS2. two layers of diagonal sheathing boards laid perpendic-
ular to each other on the same face of the supporting
4.2.7.1.3 Unblocked Diaphragms: Where dia- members. Each chord shall be considered as a beam
phragms are designated as unblocked, the diaphragms with uniform load per foot equal to 50% of the unit
shall be constructed as specified in 4.2.7.1.1, except shear due to diaphragm action. The load shall be as- 4
that blocking between supporting structural members at sumed as acting normal to the chord in the plane of the
panel edges shall not be required. The size and spacing diaphragm in either direction. Nailing of diagonally
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
20 LATERAL FORCE-RESISTING SYSTEMS
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
Table 4.2A Nominal Unit Shear Capacities for Wood-Frame Diaphragms
Blocked Wood Structural Panel Diaphragms1,2,3,4,5
A B
SEISMIC WIND
Nail Spacing (in.) at diaphragm
boundaries (all cases), at continuous
Nail Spacing (in.) at diaphragm boundaries (all cases), at continuous panel edges parallel to load panel edges parallel to load (Cases 3 &
(Cases 3 & 4), and at all panel edges (Cases 5 & 6) 4), and at all panel edges (Cases 5 & 6)
Minimum 6 4 2-1/2 2 6 4 2-1/2 2
Minimum
Nominal Width Nail Spacing (in.) at other panel edges
Fastener Minimum
of Nailed Face Nail Spacing (in.) at other panel edges (Cases 1, 2, 3, & 4) (Cases 1, 2, 3, & 4)
Penetration in Nominal
Sheathing Common at Adjoining 6 6 4 3 6 6 4 3
Framing Panel
Grade Nail Size Panel Edges vs Ga vs Ga vs Ga vs Ga vw vw vw vw
Member or Thickness
and (plf) (kips/in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (plf) (plf) (plf)
Blocking (in.)
Boundaries
(in.)
(in.) OSB PLY OSB PLY OSB PLY OSB PLY
2 370 15 12 500 8.5 7.5 750 12 10 840 20 15 520 700 1050 1175
6d 1-1/4 5/16
3 420 12 9.5 560 7.0 6.0 840 9.5 8.5 950 17 13 590 785 1175 1330
2 540 14 11 720 9.0 7.5 1060 13 10 1200 21 15 755 1010 1485 1680
Structural I 8d 1-3/8 3/8
3 600 12 10 800 7.5 6.5 1200 10 9.0 1350 18 13 840 1120 1680 1890
2 640 24 17 850 15 12 1280 20 15 1460 31 21 895 1190 1790 2045
10d 1-1/2 15/32
3 720 20 15 960 12 9.5 1440 16 13 1640 26 18 1010 1345 2015 2295
2 340 15 10 450 9.0 7.0 670 13 9.5 760 21 13 475 630 940 1065
5/16
3 380 12 9.0 500 7.0 6.0 760 10 8.0 860 17 12 530 700 1065 1205
6d 1-1/4
2 370 13 9.5 500 7.0 6.0 750 10 8.0 840 18 12 520 700 1050 1175
3/8
3 420 10 8.0 560 5.5 5.0 840 8.5 7.0 950 14 10 590 785 1175 1330
2 480 15 11 640 9.5 7.5 960 13 9.5 1090 21 13 670 895 1345 1525
3/8
3 540 12 9.5 720 7.5 6.0 1080 11 8.5 1220 18 12 755 1010 1510 1710
Sheathing
2 510 14 10 680 8.5 7.0 1010 12 9.5 1150 20 13 715 950 1415 1610
and 8d 1-3/8 7/16
3 570 11 9.0 760 7.0 6.0 1140 10 8.0 1290 17 12 800 1065 1595 1805
Single-Floor
2 540 13 9.5 720 7.5 6.5 1060 11 8.5 1200 19 13 755 1010 1485 1680
15/32
3 600 10 8.5 800 6.0 5.5 1200 9.0 7.5 1350 15 11 840 1120 1680 1890
2 580 25 15 770 15 11 1150 21 14 1310 33 18 810 1080 1610 1835
15/32
3 650 21 14 860 12 9.5 1300 17 12 1470 28 16 910 1205 1820 2060
10d 1-1/2
2 640 21 14 850 13 9.5 1280 18 12 1460 28 17 895 1190 1790 2045
19/32
1. Nominal unit shear capacities shall be adjusted in accordance with 4.2.3 to determine Cases 1&3:Continuous Cases 2&4: Continuous Cases 5&6: Continuous
ASD allowable unit shear capacity and LRFD factored unit resistance. For general Panel Joints Perpendicular Panel Joints Parallel to Panel Joints Perpen-
con tr ction re irement ee 4.2. . For pecific re irement ee 4.2. . for woo to Framing Framing dicular and Parallel to
structural panel diaphragms. See Appendix A for common nail dimensions. Framing
2. For pecie an gra e of framing other than o g a Fir arch or So thern ine
reduced nominal unit shear capacities shall be determined by multiplying the Long Panel Direction
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC
ta ate nomina nit hear capacity y the Specific Gravity tment Factor Perpendicular to Supports
0. G where G Specific Gravity of the framing m er from the NDS (Table
2. . . he Specific Gravity tment Factor ha not e greater than .
. pparent hear tiffne va e Ga are a e on nai ip in framing with moi t re
content e than or e a to at time of fa rication an pane tiffne va e
for diaphragms constructed with either OSB or 3-ply plywood panels. When 4-ply
or p y p ywoo pane or compo ite pane are e Ga va e ha e permitte Long Panel Direction
to be multiplied by 1.2. Parallel to Supportsa
4. here moi t re content of the framing i greater than at time of fa rication
Ga va e ha e m tip ie y 0. .
5. Diaphragm resistance depends on the direction of continuous panel joints with respect
to the oa ing irection an irection of framing mem er an i in epen ent of
the panel orientation.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
(a) Panel span rating for out-of-plane loads may be lower than the span rating with the long panel direction perpendicular to supports
(See Section 3.2.2 and Section 3.2.3)
21
2.4. For pecie an gra e of framing other than o g a Fir arch or So thern ine
reduced nominal unit shear capacities shall be determined by multiplying the Long Panel Direction
ta ate nomina nit hear capacity y the Specific Gravity tment Factor Perpendicular to Supports
0. G where G Specific Gravity of the framing m er from the NDS (Table
2. . . he Specific Gravity tment Factor ha not e greater than .
. pparent hear tiffne va e Ga are a e on nai ip in framing with moi t re
content e than or e a to at time of fa rication an pane tiffne va e
for diaphragms constructed with either OSB or 3-ply plywood panels. When 4-ply
or p y p ywoo pane or compo ite pane are e Ga va e ha e permitte
Long Panel Direction
to be multiplied by 1.2.
Parallel to Supportsa
4. here moi t re content of the framing i greater than at time of fa rication
Ga va e ha e m tip ie y 0. .
5. Diaphragm resistance depends on the direction of continuous panel joints with respect
to the oa ing irection an irection of framing mem er an i in epen ent of
the panel orientation.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
(a) Panel span rating for out-of-plane loads may be lower than the span rating with the long panel direction perpendicular to supports
(See Section 3.2.2 and Section 3.2.3)
Table 4.2C Nominal Unit Shear Capacities for Wood-Frame Diaphragms
Unblocked Wood Structural Panel Diaphragms1,2,3,4,5
A B
SEISMIC WIND
Minimum 6 in. Nail Spacing at
Minimum Minimum Nominal Width 6 in. Nail Spacing at diaphragm boundaries diaphragm boundaries and
Fastener Nominal of Nailed Face at and supported panel edges supported panel edges
Common
Sheathing Grade Penetration Panel Supported Cases
Nail Size Edges and Case 1 Cases 2,3,4,5,6 Case 1
in Framing Thickness 2,3,4,5,6
(in.) (in.) Boundaries
(in.) vs Ga vs Ga vw vw
(plf) (kips/in.) (plf) (kips/in.) (plf) (plf)
OSB PLY OSB PLY
2 330 9.0 7.0 250 6.0 4.5 460 350
6d 1-1/4 5/16
3 370 7.0 6.0 280 4.5 4.0 520 390
2 480 8.5 7.0 360 6.0 4.5 670 505
Structural I 8d 1-3/8 3/8
3 530 7.5 6.0 400 5.0 4.0 740 560
2 570 14 10 430 9.5 7.0 800 600
10d 1-1/2 15/32
3 640 12 9.0 480 8.0 6.0 895 670
2 300 9.0 6.5 220 6.0 4.0 420 310
5/16
3 340 7.0 5.5 250 5.0 3.5 475 350
6d 1-1/4
2 330 7.5 5.5 250 5.0 4.0 460 350
3/8
3 370 6.0 4.5 280 4.0 3.0 520 390
2 430 9.0 6.5 320 6.0 4.5 600 450
3/8
3 480 7.5 5.5 360 5.0 3.5 670 505
Sheathing and 2 460 8.5 6.0 340 5.5 4.0 645 475
8d 1-3/8 7/16
Single-Floor 3 510 7.0 5.5 380 4.5 3.5 715 530
2 480 7.5 5.5 360 5.0 4.0 670 505
15/32
3 530 6.5 5.0 400 4.0 3.5 740 560
2 510 15 9.0 380 10 6.0 715 530
15/32
3 580 12 8.0 430 8.0 5.5 810 600
1. Nominal unit shear capacities shall be adjusted in accordance with 4.2.3 to de- Cases 1&3:Continuous Cases 2&4: Continuous Cases 5&6: Continuous
termine ASD allowable unit shear capacity and LRFD factored unit resistance. Panel Joints Perpendicular Panel Joints Parallel to Panel Joints Perpen-
For genera con tr ction re irement ee 4.2. . For pecific re irement to Framing Framing dicular and Parallel to
ee 4.2. . for woo tr ct ra pane iaphragm . See ppen i for common Framing
nail dimensions.
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC
2. For species and grades of framing other than Douglas-Fir-Larch or Southern Long Panel Direction
ine re ce nomina nit hear capacitie ha e etermine y m tip ying Perpendicular to Supports
the ta ate nomina nit hear capacity y the Specific Gravity tment
Factor 0. G where G Specific Gravity of the framing m er from
the NDS a e 2. . . he Specific Gravity tment Factor ha not
be greater than 1.
. pparent hear tiffne va e Ga are a e on nai ip in framing with
moisture content less than or equal to 19% at time of fabrication and panel Long Panel Direction
tiffne va e for iaphragm con tr cte with either S or p y p ywoo Parallel to Supportsa
pane . hen 4 p y or p y p ywoo pane or compo ite pane are e Ga
va e ha e permitte to e m tip ie y .2.
4. Where moisture content of the framing is greater than 19% at time of fabrica-
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
tion Ga va e ha e m tip ie y 0. .
5. Diaphragm resistance depends on the direction of continuous panel joints
with re pect to the oa ing irection an irection of framing mem er an i (a) Panel span rating for out-of-plane loads may be lower than the span rating with the long panel direction perpendicular to supports
independent of the panel orientation.
23
1. Nominal unit shear capacities shall be adjusted in accordance with 4.2.3 to determine ASD allowable unit shear capacity and LRFD factored unit resistance. For general construction requirements see 4.2.6. For
pecific re irement ee 4.2. .2 for iaphragm iagona y heathe with a ing e ayer of m er ee 4.2. . for iaphragm iagona y heathe with a o e ayer of m er an ee 4.2. .4 for iaphragm
horizontally sheathed with a single-layer of lumber. See Appendix A for common and box nail dimensions.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 25
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
26 LATERAL FORCE-RESISTING SYSTEMS
b = Nominal unit shear capacity (lbs/ft) from Kmin = minimum ratio of s1/Ga1 or s2/Ga2
Table 4.3.3.2 Unblocked Shear Wall sc = Combined nominal unit shear capacity of
Adjustment Factor, Cub two-sided shear wall for seismic design,
lbs/ft
4.3.3.3.2 Nominal unit shear capacities for shear
Nail Spacing (in.) walls sheathed with dissimilar materials on the same
Stud Spacing (in.)
side of the wall are not cumulative. For shear walls
Supported Intermediate sheathed with dissimilar materials on opposite sides,
Edges Framing 12 16 20 24 the combined nominal unit shear capacity, sc or wc,
6 6 1.0 0.8 0.6 0.5 shall be either two times the smaller nominal unit
shear capacity or the larger nominal unit shear capaci-
6 12 0.8 0.6 0.5 0.4 ty, whichever is greater.
4.3.3.3 Summing Shear Capacities: For shear Exception: For wind design, the combined
walls sheathed with the same construction and materi- nominal unit shear capacity, wc, of shear
als on opposite sides of the same wall, the combined walls sheathed with a combination of wood
nominal unit shear capacity, sc or wc, shall be permit- structural panels, hardboard panel siding, or
ted to be taken as twice the nominal unit shear capaci- structural fiberboard on one side and gypsum
ty for an equivalent shear wall sheathed on one side. wallboard on the opposite side shall equal the
4.3.3.3.1 For seismic design of shear walls sum of the sheathing capacities of each side.
sheathed with the same construction and materials on
opposite sides of a shear wall, the shear wall deflection 4.3.3.4 Shear Walls in a Line: The provisions of
shall be calculated using the combined apparent shear this section are limited to shear distribution to individ-
wall shear stiffness, Gac and the combined nominal ual shear walls in a shear wall line where the individu-
unit shear capacity, sc, using the following equations: al shear walls have the same materials and construc-
tion.
sc KminGac (4.3-4)
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 27
4.3.3.4.1 Shear distribution to individual shear Ltot = total length of a perforated shear wall in-
walls in a shear wall line shall provide the same calcu- cluding the lengths of perforated shear wall
lated deflection, sw, in each shear wall. segments and the lengths of segments con-
taining openings, ft
Exceptions:
1. Where nominal shear capacities of all Ao = total area of openings in the perforated
wood structural panel shear walls with aspect shear wall where individual opening areas
ratios (h/bs) greater than 2:1 are multiplied by are calculated as the opening width times
2bs/h for design, shear distribution to individ- the clear opening height, ft2. Where sheath-
ual full-height wall segments shall be permit- ing is not applied to framing above or below
4
ted to be taken as proportional to the shear the opening, these areas shall be included
capacities of individual full height wall seg- in the total area of openings. Where the
ments used in design. Where multiplied by opening height is less than h/3, an opening
2bs/h, the nominal shear capacities need not height of h/3 shall be used
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
28 LATERAL FORCE-RESISTING SYSTEMS
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 29
Figure 4C Typical Shear Wall Height-to-Width 4.3.5.2 Force-transfer Shear Walls: Where shear
Ratio for Perforated Shear Walls walls with openings are designed for force transfer
around the openings, the aspect ratio limitations of
4.3.4.4 shall apply as illustrated in Figure 4E. Design
for force transfer shall be based on a rational analysis.
The following limitations shall apply:
1. The length of each wall pier shall not be less
than 2'.
2. A full-height wall segment shall be located at
each end of a force-transfer shear wall.
3. Where out-of-plane offsets occur, portions of
the wall on each side of the offset shall be 4
considered as separate force-transfer shear
walls.
4. Collectors for shear transfer shall be provided
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
30 LATERAL FORCE-RESISTING SYSTEMS
capacity of perforated shear walls sheathed with wood between members. When fasteners connecting the two
structural panel sheathing on one side and gypsum framing members are spaced less than 4" in center,
wallboard on the opposite side shall be permitted to be they shall be staggered.
determined in accordance with Section 4.3.3.3.2. The 4.3.6.1.2 Tension and Compression Chords: Ten-
following limitations shall apply: sion force, T, and a compression force, C, resulting
1. A perforated shear wall segment shall be lo- from shear wall overturning forces at each story level
cated at each end of a perforated shear wall. shall be calculated in accordance with the following:
Openings shall be permitted to occur beyond
the ends of the perforated shear wall, provided T C h (4.3-7)
the lengths of such openings are not included where:
in the length of the perforated shear wall.
2. The aspect ratio limitations of Section 4.3.4.3 C = compression force, lbs
shall apply. h = shear wall height, ft
3. The nominal unit shear capacity for a single-
sided wall shall not exceed 1,740 plf for seis- T = tension force, lbs
mic or 2,435 plf for wind as given in Table = induced unit shear, lbs/ft
4.3A. The nominal unit shear capacity for a
double-sided wall shall not exceed 2,435 plf 4.3.6.1.3 Tension and Compression Chords of Per-
for wind. forated Shear Walls: Each end of each perforated shear
4. Where out-of-plane offsets occur, portions of wall shall be designed for a tension force, T, and a
the wall on each side of the offset shall be
compression force, C. Each end of each perforated
considered as separate perforated shear walls.
shear wall segment shall be designed for a compres-
5. Collectors for shear transfer shall be provided
sion force, C, in each segment. For perforated shear
through the full length of the perforated shear
walls, the values for T and C resulting from shear wall
wall.
overturning at each story level shall be calculated in
6. A perforated shear wall shall have uniform
top-of-wall and bottom-of-wall elevations. accordance with the following:
Perforated shear walls not having uniform ele- Vh
vations shall be designed by other methods. T C (4.3-8)
7. Perforated shear wall height, h, shall not ex-
Co Li
ceed 20'.
where:
4.3.6 Construction Requirements
Co = shear capacity adjustment factor from Table
4.3.6.1 Framing Requirements: All framing mem- 4.3.3.5
bers and blocking used for shear wall construction V = induced shear force in perforated shear
shall be 2" nominal or greater. Where shear walls are wall, lbs
designed as blocked, all joints in sheathing shall occur
over and be fastened to common framing members or Li = sum of perforated shear wall segment
common blocking. Shear wall boundary elements, lengths Li , ft. Lengths of perforated shear
such as end posts, shall be provided to transmit the wall segments with aspect ratios greater
design tension and compression forces. Shear wall than 2:1 shall be adjusted in accordance
sheathing shall not be used to splice boundary ele- with 4.3.4.3.
ments. End posts (studs or columns) shall be framed to
provide full end bearing. 4.3.6.2 Sheathing: Shear walls shall be sheathed
4.3.6.1.1 Common Framing Member: Where a with approved materials attached directly to the fram-
common framing member is required at adjoining ing members, and blocking where required, except as
panel edges, two framing members that are at least 2" permitted in 4.3.7.2. Details on sheathing types and
in nominal thickness shall be permitted provided they thicknesses for commonly used shear wall assemblies
are fastened together with fasteners designed in ac- are provided in 4.3.7 and Tables 4.3A, 4.3B, 4.3C, and
cordance with the NDS to transfer the induced shear 4.3D.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 31
4.3.6.3 Fasteners: Sheathing shall be attached to slot length not to exceed 1-3/4", provided a standard
framing members using nails or other approved fas- cut washer (see Appendix A) is placed between the
teners. Nails shall be driven with the head of the nail plate washer and the nut. The plate washer shall ex-
flush with the surface of the sheathing. Other approved tend to within 1/2" of the edge of the bottom plate on
fasteners shall be driven as required for proper instal- the side(s) with sheathing or other material with nomi-
lation of that fastener. See Appendix A for common, nal unit shear capacity greater than 400 plf for wind or
box, and sinker nail dimensions. seismic.
4.3.6.3.1 Adhesives: Adhesive attachment of shear
wall sheathing shall not be used alone, or in combina- Exception: Standard cut washers shall be
tion with mechanical fasteners. permitted to be used where anchor bolts are
designed to resist shear only and the follow-
Exception: Approved adhesive attachment ing requirements are met: 4
systems shall be permitted for wind and a. The shear wall is designed in accordance with
seismic design in Seismic Design Categories provisions of 4.3.5.1 with required uplift an-
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
32 LATERAL FORCE-RESISTING SYSTEMS
ted to be calculated in accordance with Shear walls sheathed with wood structural panel
Section 4.3.2.2. sheathing over gypsum wallboard or gypsum sheath-
b. The strength of the unblocked wood struc- ing board shall be permitted to be used to resist seis-
tural panel shear wall is determined in ac- mic and wind forces. The size and spacing of fasteners
cordance with Section 4.3.3.2, and at shear wall boundaries and panel edges shall be as
c. Specified nail spacing at supported edges provided in Table 4.3B. The shear wall shall be con-
is no closer than 6" o.c. structed in accordance with Section 4.3.7.1.
4.3.7.3 Particleboard Shear Walls: Shear walls
2. Nails shall be located at least 3/8" from the sheathed with particleboard sheathing shall be permit-
panel edges. Maximum nail spacing at panel ted to be used to resist wind forces and seismic forces
edges shall be 6" on center. in Seismic Design Categories A, B, and C. The size
3. Nails along intermediate framing members and spacing of fasteners at shear wall boundaries and
shall be the same size as nails specified for panel edges shall be as provided in Table 4.3A. The
panel edge nailing. At intermediate framing shear wall shall be constructed as follows:
members, the maximum nail spacing shall be 1. Panels shall not be less than 4' x 8', except at
6" on center. boundaries and changes in framing. All edges
of all panels shall be supported by and fas-
Exception: Where panels are thicker tened to framing members or blocking.
than 7/16" (nominal) or studs are spaced 2. Nails shall be located at least 3/8" from the
less than 24" on center, the maximum panel edges. Maximum nail spacing at panel
nail spacing shall be 12" on center. edges shall be 6" on center.
3. Nails along intermediate framing members
4. The width of the nailed face of framing mem- shall be the same size as nails specified for
bers and blocking shall be 2" nominal or panel edge nailing. At intermediate framing
greater. members, the maximum nail spacing shall be
5. Where any of the following conditions occur, 6" on center.
the width of the nailed face of a common
framing member or blocking at adjoining pan- Exception: Where panels are thicker
el edges shall be 3" nominal or greater and than 3/8" (nominal) or studs are spaced
nailing shall be staggered at all panel edges:
less than 24" on center, the maximum
a. Nail spacing of 2" on center at adjoining
nail spacing shall be 12" on center.
panel edges is specified, or
b. 10d common nails having penetration into
4. The width of the nailed face of framing mem-
framing members and blocking of more
bers and blocking shall be 2" nominal or
than 1-1/2" are specified at 3" on center,
greater.
or less at adjoining panel edges, or
5. Where any of the following conditions occur,
c. The nominal unit shear capacity on either
the width of the nailed face of a common
side of the shear wall exceeds 700 plf in
framing member or blocking at adjoining pan-
Seismic Design Category D, E, or F.
el edges shall be 3" nominal or greater and
nailing shall be staggered at all panel edges:
In lieu of a single common framing member,
a. Nail spacing of 2" on center at adjoining
two framing members that are at least 2" in panel edges is specified, or
nominal thickness shall be permitted where b. 10d common nails having penetration into
designed in accordance with 4.3.6.1.1. framing members and blocking of more
than 1-1/2" are specified at 3" on center,
6. Maximum stud spacing shall be 24" on center. or less at adjoining panel edges.
7. Wood structural panels shall conform to the
requirements for its type in DOC PS 1 or PS 2. In lieu of a single common framing member,
two framing members that are at least 2" in
4.3.7.2 Shear Walls using Wood Structural Panels
nominal thickness shall be permitted where
over Gypsum Wallboard or Gypsum Sheathing Board: designed in accordance with 4.3.6.1.1.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 33
6. Maximum stud spacing shall be 24" on center. be applied parallel or perpendicular to studs. Gypsum
7. Particleboard shall conform to ANSI A208.1. wallboard shall conform to ASTM C 1396 and shall be
4.3.7.4 Structural Fiberboard Shear Walls: Shear installed in accordance with ASTM C 840. Gypsum
walls sheathed with fiberboard sheathing shall be per- base for veneer plaster shall conform to ASTM C 1396
mitted to be used to resist wind forces and seismic and shall be installed in accordance with ASTM C
forces in Seismic Design Categories A, B, and C. The 844. Water-resistant gypsum backing board shall con-
size and spacing of fasteners at shear wall boundaries form to ASTM C 1396 and shall be installed in ac-
and panel edges shall be as provided in Table 4.3A. cordance with ASTM C 840.
The shear wall shall be constructed as follows: 4.3.7.5.2 Gypsum Sheathing Board: Four-foot-
1. Panels shall not be less than 4' x 8', except at wide pieces of gypsum sheathing board shall be ap-
boundaries and changes in framing. All edges plied parallel or perpendicular to studs. Two-foot-wide
of all panels shall be supported by and fas- pieces of gypsum sheathing board shall be applied 4
tened to framing members or blocking. perpendicular to the studs. Gypsum sheathing board
2. Nails shall be located at least 3/4" from edges shall conform to ASTM C 1396 and shall be installed
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
34 LATERAL FORCE-RESISTING SYSTEMS
sheathed lumber shear walls shall be in accordance Nailing of horizontally sheathed lumber shear walls
with Table 4.3D. shall be in accordance with Table 4.3D.
4.3.7.8 Shear Walls Horizontally Sheathed with 4.3.7.9 Shear Walls Sheathed with Vertical Board
Single-Layer of Lumber: Horizontally sheathed lum- Siding: Vertical board siding shear walls shall be per-
ber shear walls shall be permitted to be used to resist mitted to be used to resist wind forces and seismic
wind forces and seismic forces in Seismic Design Cat- forces in Seismic Design Categories A, B, and C. Ver-
egories A, B, and C. Horizontally sheathed lumber tical board siding shear walls shall be constructed of
shear walls shall be constructed of minimum 1" thick minimum 1" thick nominal sheathing boards applied
nominal sheathing boards applied perpendicular to the directly to studs and blocking. Nailing of vertical
supports. End joints in adjacent boards shall be sepa- board siding shear walls shall be in accordance with
rated by at least one stud space and there shall be at Table 4.3D.
least two boards between joints on the same support.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
Table 4.3A Nominal Unit Shear Capacities for Wood-Frame Shear Walls1,3,6,7
Wood-based Panels4
A B
Minimun SEISMIC WIND
Minimum Fastener Panel Edge Fastener
Nominal Penetration Fastener Panel Edge Fastener Spacing (in.)
Sheathing Spacing (in.)
Panel in Framing Type & Size
Material 6 4 3 2 6 4 3 2
Thickness Member or
(in.) vs Ga vs Ga vs Ga vs Ga vw vw vw vw
Blocking
(in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (plf) (plf) (plf)
Nail (common or
OSB PLY OSB PLY OSB PLY OSB PLY
galvanized box)
ood 5/16 1-1/4 6d 400 13 10 600 18 13 780 23 16 1020 35 22 560 840 1090 1430
Structural
3/82 460 19 14 720 24 17 920 30 20 1220 43 24 645 1010 1290 1710
Panel -
Structural I4 5 7/162 1-3/8 8d 510 16 13 790 21 16 1010 27 19 1340 40 24 715 1105 1415 1875
15/32 560 14 11 860 18 14 1100 24 17 1460 37 23 785 1205 1540 2045
15/32 1-1/2 10d 680 22 16 1020 29 20 1330 36 22 1740 51 28 950 1430 1860 2435
5/16 360 13 9.5 540 18 12 700 24 14 900 37 18 505 755 980 1260
1-1/4 6d
3/8 400 11 8.5 600 15 11 780 20 13 1020 32 17 560 840 1090 1430
ood 3/82 440 17 12 640 25 15 820 31 17 1060 45 20 615 895 1150 1485
Structural
7/162 1-3/8 8d 480 15 11 700 22 14 900 28 17 1170 42 21 670 980 1260 1640
Panel
Sheathing4 5 15/32 520 13 10 760 19 13 980 25 15 1280 39 20 730 1065 1370 1790
15/32 620 22 14 920 30 17 1200 37 19 1540 52 23 870 1290 1680 2155
1-1/2 10d
19/32 680 19 13 1020 26 16 1330 33 18 1740 48 22 950 1430 1860 2435
Nail (galvanized casing)
Pl ood
Siding 5/16 1-1/4 6d 280 13 420 16 550 17 720 21 390 590 770 1010
3/8 1-3/8 8d 320 16 480 18 620 20 820 22 450 670 870 1150
Nail (common or
Particle oard galvanized box)
Sheathing - 3/8 6d 240 15 360 17 460 19 600 22 335 505 645 840
25/32 340 4.0 460 5.0 520 5.5 475 645 730
1-3/4 long 3/8 head
1. Nominal unit shear capacities shall be adjusted in accordance with 4.3.3 to determine ASD allowable unit shear capacity and LRFD factored unit resistance. For general construction requirements see 4.3.6. For
pecific re irement ee 4. . . for woo tr ct ra pane hear wa 4. . .2 for partic e oar hear wa an 4. . . for fi er oar hear wa . See ppen i for common an o nai imen ion .
2. Shear are permitte to e increa e to va e hown for 2 inch nomina heathing with ame nai ing provi e a t are pace a ma im m of inche on center or pane are app ie with ong
dimension across studs.
. For pecie an gra e of framing other than o g a Fir arch or So thern ine re ce nomina nit hear capacitie ha e etermine y m tip ying the ta ate nomina nit hear capacity y the
Specific Gravity tment Factor 0. G where G Specific Gravity of the framing m er from the S a e 2. . . he Specific Gravity tment Factor ha not e greater than .
4. pparent hear tiffne va e Ga are a e on nai ip in framing with moi t re content e than or e a to at time of fa rication an pane tiffne va e for hear wa con tr cte with either S
or p y p ywoo pane . hen 4 p y or p y p ywoo pane or compo ite pane are e Ga va e ha e permitte to e m tip ie y .2.
. here moi t re content of the framing i greater than at time of fa rication Ga va e ha e m tip ie y 0. .
. here pane are app ie on oth face of a hear wa an nai pacing i e than on center on either i e pane oint ha e off et to fa on ifferent framing mem er a hown e ow. ternative y the
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
width of the nailed face of framing members shall be 3" nominal or greater at adjoining panel edges and nails at all panel edges shall be staggered.
. Ga vani e nai ha e hot ippe or t m e .
35
Table 4.3B Nominal Unit Shear Capacities for Wood-Frame Shear Walls1,2,5,6
Wood Structural Panels Applied over 1/2" or 5/8" Gypsum Wallboard or Gypsum Sheathing Board
A B
Minimum SEISMIC WIND
Minimum Panel Edge Fastener Spacing
Fastener Panel Edge Fastener Spacing (in.)
Nominal (in.)
Sheathing Penetration in
Panel Fastener Type & Size 6 4 3 2 6 4 3 2
Material Framing
Thickness vs Ga vs Ga vs Ga vs Ga vw vw vw vw
Member or
(in.)
Blocking (in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (kips/in.) (plf) (plf) (plf) (plf)
Nail (common or
OSB PLY OSB PLY OSB PLY OSB PLY
galvanized box)
Wood Structural
Panels - 5/16 1-1/4 8d 400 13 10 600 18 13 780 23 16 1020 35 22 560 840 1090 1430
Structural I3,4
3/8, 7/16,
1-3/8 10d 560 14 11 860 18 14 1100 24 17 1460 37 23 785 1205 1540 2045
15/32
5/16 360 13 9.5 540 18 12 700 24 14 900 37 18 505 755 980 1260
Wood Structural 1-1/4 8d
3/8 400 11 8.5 600 15 11 780 20 13 1020 32 17 560 840 1090 1430
Panels -
3/8, 7/16,
Sheathing3,4 1-3/8 10d 520 13 10 760 19 13 980 25 15 1280 39 20 730 1065 1370 1790
15/32
Nail (galvanized casing)
Plywood Siding 5/16 1-1/4 8d (2-1/2" x0.113") 280 13 420 16 550 17 720 21 390 590 770 1010
3/8 1-3/8 10d (3"x0.128") 320 16 480 18 620 20 820 22 450 670 870 1150
1. Nominal unit shear capacities shall be adjusted in accordance with 4.3.3 to determine ASD allowable unit shear capacity and LRFD factored unit resistance. For general construction requirements see 4.3.6. For
pecific re irement ee 4. . . for woo tr ct ra pane hear wa . See ppen i for common an o nai imen ion .
2. For pecie an gra e of framing other than o g a Fir arch or So thern ine re ce nomina nit hear capacitie ha e etermine y m tip ying the ta ate nomina nit hear capacity y the
Specific Gravity tment Factor 0. G where G Specific Gravity of the framing m er from the NDS a e 2. . . he Specific Gravity tment Factor ha not e greater than .
. pparent hear tiffne va e Ga are a e on nai ip in framing with moi t re content e than or e a to at time of fa rication an pane tiffne va e for hear wa con tr cte with either S
or p y p ywoo pane . hen 4 p y or p y p ywoo pane or compo ite pane are e Ga va e for p ywoo ha e permitte to e m tip ie y .2.
4. here moi t re content of the framing i greater than at time of fa rication Ga va e ha e m tip ie y 0. .
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
Table 4.3C Nominal Unit Shear Capacities for Wood-Frame Shear Walls1
Base ply--6d cooler (0.092 x 1-7/8 long, 1/4 head) or allboard nail (0.0915
5/8 Base 9
x 1-7/8 long, 19/64 head) or 0.120 nail x 1-3/4 long, min 3/8 head
(0.0915 x 1-7/8 long, 19/64 head) or 0.120 nail x 1-3/4 long, min 3/8 head
Gypsum lath, plain or 3/8 lath and 0.092 x 1-1/8 long, 19/64 head, gypsum allboard blued nail or 0.120 nail
5 16 unblocked 200 5.5 200
perforated 1/2 plaster x1-1/4 long, min 3/8 head
Expanded metal or
o en ire lath and
7/8 0.120 nail x 1- long, 7/16 head 6 16 unblocked 360 9.0 360
Portland cement
plaster
1. Nominal unit shear capacities shall be adjusted in accordance with 4.3.3 to determine ASD allowable unit shear capacity and LRFD factored unit resistance. For general construction requirements see 4.3.6. For
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
pecific re irement ee 4. . .4.
2. ype S or rywa crew ha conform to re irement of S 002.
. here two n m er are given for ma im m fa tener e ge pacing the fir t n m er enote fa tener pacing at the e ge an the econ n m er enote fa tener pacing a ong interme iate framing mem-
37
bers.
4
Table 4.3D Nominal Unit Shear Capacities for Wood-Frame Shear Walls1
1. Nominal unit shear capacities shall be adjusted in accordance with 4.3.3 to determine ASD allowable unit shear capacity and LRFD factored unit resistance. For general construction requirements see 4.3.6. For
pecific re irement ee 4. . . thro gh 4. . . . See ppen i for common an o nai imen ion .
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 39
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
40 LATERAL FORCE-RESISTING SYSTEMS
backing the horizontal joint shall be permit- from wind forces, they shall be in accordance with
ted to be used to resist both uplift and shear at Section . .1, except that panels with a minimum
sheathing splices over studs provided the fol- nominal panel thickness of 3/ shall be permitted
lowing conditions are met (see Figure I): when installed with the strength axis parallel to the
a. Sheathing tension splices shall be made studs. The ASD allowable unit uplift shall be deter-
from the same thickness and grade as the mined by dividing the tabulated nominal uplift capaci-
shear wall sheathing. ty in Table . .2, modified by applicable footnotes, by
b. Edges of sheathing shall be nailed to the ASD reduction factor of 2.0. The LRFD factored
sheathing tension splices using the same uplift resistance shall be determined by multiplying
nail size and spacing as the sheathing or the tabulated nominal unit uplift capacity in Table
siding nails at the bottom plate. . .2, modified by applicable footnotes, by a re-
sistance factor, , of 0. .
4.4.2 Wood Structural Panels Designed to
Resist Only Uplift from Wind
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 41
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
42 LATERAL FORCE-RESISTING SYSTEMS
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 43
Table 4.4.1 Nominal Uplift Capacity of 7/16" (Nominal) Minimum Wood Structural Panel
Sheathing or Siding When Used for Both Shear Walls and Wind Uplift Simultaneously
over Framing with a Specific Gravity of 0.42 or Greater 1
Table 4.4.1.6 Maximum Anchor Bolt Spacing (inches) for Combined Shear and Wind Uplift1,2
No in Unit
S e C p cit
N i p No in Up i t C p cit p
Si e G .
G .
d 3
0 0 2 3 3 32 2 2 1 .2 1 - -
common
(0.131 x 00 3 2 3 3 32 2 2 1 .2 1 - -
2-1/2 ) 0 1 3 32 2 2 2 2 1 .2 1 .2 1 - -
0 02 2 2 1 .2 1 .2 1 .2 1 1 - - - -
10d 3
0 0 2 3 3 32 2 2 1 .2 1 1 1
common
(0.1 x 00 3 2 3 3 32 2 2 1 .2 1 - -
3 ) 0 00 2 2 2 1 .2 1 .2 1 .2 1 1 - - -
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
44 LATERAL FORCE-RESISTING SYSTEMS
Table 4.4.2 Nominal Uplift Capacity of 3/8" (Nominal) Minimum Wood Structural Panel Sheathing
or Siding When Used for Wind Uplift Only over Framing with a Specific Gravity of 0.42
or Greater 1
1. Nominal unit uplift capacities shall be adjusted in accordance with 4.4.2 to determine ASD allowable unit uplift capacity and LRFD factored unit resistance.
Anchors shall be installed in accordance with this section. See Appendix A for common nail dimensions.
2. Where framing has a specific gravity of 0.49 or greater, uplift values in table 4.4.2 shall be permitted to be multiplied by 1.08.
3. The tabulated uplift values are applicable to 3/8" (nominal) minimum OSB panels or plywood with species of plies having a specific gravity of 0.49 or greater.
For plywood with other species, multiply the tabulated uplift values by 0.90.
4. Wood structural panels shall overlap the top member of the double top plate and bottom plate by 1-1/2" and a single row of fasteners shall be placed ¾" from
the panel edge.
5. Wood structural panels shall overlap the top member of the double top plate and bottom plate by 1-1/2". Rows of fasteners shall be ½" apart with a minimum
edge distance of ½". Each row shall have nails at the specified spacing.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 45
APPENDIX A
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
46 APPENDIX A
Table Table
A1 Standard
A1 Common,
Standard Box,
Common, and
Box, andSinker Nails
Sinker Nails 1
1
L
L
D diameter
H H
L length
D D head diameter
Common or Box Sinker
Penn ei t
T pe
L 2 2-1/ 2-1/2 3 3-1/ 3-1/2 -1/2 -1/2
Common D 0.113 0.113 0.131 0.1 0.1 0.1 2 0.1 2 0.20 0.22 0.2 0.2 3
0.2 0.2 0.2 1 0.312 0.312 0.3 0. 0 0. 3 0. 0. 0. 31
L 2 2-1/ 2-1/2 3 3-1/ 3-1/2 -1/2 - -
Box D 0.0 0.0 0.113 0.12 0.12 0.13 0.1 0.1 0.1 2 - -
0.2 0.2 0.2 0.312 0.312 0.3 0.3 0.3 0. 0 - -
L 1- / 2-1/ 2-3/ 2- / 3-1/ 3-1/ 3-3/ -1/ -3/ - -3/
Sinker D 0.0 2 0.0 0.113 0.12 0.13 0.1 0.1 0.1 2 0.20 - 0.2
0.23 0.2 0 0.2 0.2 1 0.312 0.3 0.3 0. 0 0. 3 - 0.
. o erance pecifie in S F . ypica hape of common o an in er nai hown. See S F for other nai type .
1.
1
Dimensions of Standard Cut Washers
A B C
Nominal
Washer Si e nside Diameter (in.) Outside Diameter (in.) Thickness (in.)
(in.) Basic Basic Basic
3/8 0.438 1.000 0.083
1/2 0.562 1.375 0.109
5/8 0.688 1.750 0.134
3/4 0.812 2.000 0.148
7/8 0.938 2.250 0.165
1 1.062 2.500 0.165
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
SPECIAL DESIGN PROVISIONS FOR WIND AND SEISMIC 47
REFERENCES
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
48 REFERENCES
References
1. ASD/LRFD Manual for Engineered Wood Construc- 13. S 44 04 20 0 Stan ar Specification for
tion, American Wood Council, Leesburg, VA, 2012 Application of Gypsum Base to Receive Gypsum Ve-
neer Plaster, ASTM, West Conshohocken, PA, 2010.
2. ANSI/ASME B18.21.1-2009, Washers: Helical
Spring-Lock, Tooth Lock, and Plain Washers (Inch 14. S 4 2 Stan ar Specification for eta
Series), American Society of Mechanical Engineers, Lath, ASTM, West Conshohocken, PA, 2012.
New York, NY, 2009.
15. S 2 a Stan ar Specification for p-
3. S S 20 ationa e ign Specifica- plication of Portland Cement-Based Plaster, ASTM,
tion (NDS) for Wood Construction, American Wood West Conshohocken, PA, 2013.
Council, Leesburg, VA, 2014.
16. S 002 0 20 Stan ar Specification
4. ANSI A208.1-2009, Particleboard Standard, ANSI, for Steel Self-Piercing Tapping Screws for the Ap-
New York, NY, 2009. plication of Gypsum Panel Products or Metal Plaster
Bases to Wood Studs or Steel Studs, ASTM, West
5. ANSI/CPA A135.6 Engineered Wood Siding, Com-
Conshohocken, PA, 2013.
posite Panel Association, Gaithersburg, MD, 2012.
17. S 0 2 0 20 Stan ar Specification
6. S Stan ar Specification
for Woven Wire Plaster Base, ASTM, West Con-
for Gypsum Board, ASTM, West Conshohocken,
shohocken, PA, 2011.
PA, 2013.
18. S 0 Stan ar Specification for n ta -
7. ASCE/SEI Standard 7-10 Minimum Design Loads for
lation of Lathing and Furring to Receive Interior and
Buildings and Other Structures, American Society of
Exterior Portland Cement-Based Plaster, ASTM, West
Civil Engineers, Reston, VA, 2010.
Conshohocken, PA, 2013.
8. S 2 2 0 Stan ar Specification for
19. S 2 0 a Stan ar Specification for p-
Gypsum Plasters, ASTM, West Conshohocken, PA,
plication of Exterior Gypsum Panel Products for Use
2010.
as Sheathing, ASTM, West Conshohocken, PA, 2013.
9. S 0 2 Stan ar Specification for ort an
20. S F Stan ar Specification for riven
Cement, ASTM, West Conshohocken, PA, 2012.
Fasteners: Nails, Spikes, and Staples, ASTM, West
10. S 20 2 Stan ar Specification for e - Conshohocken, PA, 2013.
lulosic Fiber Insulating Board, ASTM, West Con-
21. PS 1-09 (Structural Plywood), United States Depart-
shohocken, PA, 2012.
ment of Commerce, National Institute of Standards
11. S 40 Stan ar Specification for pp ica- and Technology, Gaithersburg, MD, 2009.
tion and Finishing of Gypsum Board, ASTM, West
22. PS 2-10 Performance Standard for Wood-Based
Conshohocken, PA, 2013.
Structural Use Panels, United States Department
12. S 4 0 20 Stan ar Specification for of Commerce, National Institute of Standards and
Installation of Interior Lathing and Furring, ASTM, Technology, Gaithersburg, MD, 2011.
West Conshohocken, PA, 2013.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
AMERICAN WOOD COUNCIL
American Wood Council
AWC Mission Statement
To increase the use of wood by assuring the broad
regulatory acceptance of wood products, developing
design tools and guidelines for wood construction,
and influencing the development of public policies
affecting the use and manufacture of wood products.
Copyright © American Wood Council. Downloaded/printed pursuant to License Agreement. No reproduction or transfer authorized.
ISBN 978-1-940383-04-0