You are on page 1of 3

TECHNICAL SELECTION Page 1 / 3

HED BASIC 0051


Software version: ELCA World 1.3.3.0
Database version: 1.4.1.0
User: Ortega Cuauhtemoc
Print data: 25/02/2020 11:19

INDOOR UNIT

GENERAL DATA
Model HED BASIC 0051
Version BASIC
Frame F02
Primary circuit type Direct expansion air
No. Circuits N° 1
Refrigerant R410A
UNIT DESCRIPTION [General descriptions and images of Split air conditioners for telecommunication shelters
the range, not specific to the choice of model]

MAIN CIRCUIT

DESIGN CONDITIONS
Dry bulb temperature °C 27.0
Relative humidity % 50
Altitude m 2250
Air flow rate m³/h 2450
ESP External Static Pressure Pa 0
Outdoor air temperature °C 35.0

PERFORMANCE AT DESIGNED CONDITIONS


Total cooling capacity gross kW 8.90
Sensible cooling capacity gross kW 7.58
Net cooling capacity kW 8.56
Net sensible cooling capacity kW 7.23
SHR 0.85
EER total kW/kW 2.75
Leaving air temperature °C 14.9
Leaving air relative humidity % 99

FANS

EVAPORATOR FANS
Fans type EC BASIC 48VDC
Quantity N° 2
Power Input kW 0.34
Air flow rate m³/h 2450
Available static pressure Pa 267

ACCESSORIES

ELECTRICAL HEATER
Heater description EH TLC 3,4 230/1/50
Quantity N° 1
Steps N° 1
Elettrical power abs. kW 3.40
Max absorbed current (FLA) A 14.8
Power supply V/ph/Hz 230/1/50

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.3.0
TECHNICAL SELECTION Page 2 / 3

HED BASIC 0051


Software version: ELCA World 1.3.3.0
Database version: 1.4.1.0
User: Ortega Cuauhtemoc
Print data: 25/02/2020 11:19

NOISE DATA
Spectrum Hz 63 125 250 500 1000 2000 4000 8000 Tot
dB dB dB dB dB dB dB dB dB(A)
Sound Power 3 3 3 3 3 3 3 3 3
Sound Pressure - - - - - - - - -
Distance m 1.0

Note
Average sound pressure level, at 1.0 m distance, unit in a free field on a reflective surface
Note according to ISO3744. Non-binding value obtained from the sound power level.

WEIGHT & DIMENSIONS


A mm 1236
B mm 1110
H mm 405
Weight kg 107

ELECTRICAL DATA (refer to indoor unit)


Power supply V/ph/Hz 230/1/50 48V DC
Max Electrical power absorbed (FLI) kW 3.40 0.76
Max absorbed current (FLA) A 14.8 13.4
Max inrush current (SA) A 14.8 13.4
Power input (OI) kW 3.40 0.34

OUTDOOR UNIT

GENERAL DATA
Code HCAT 0051

CONDENSER FANS
Fans Type AXIAL
Quantity N° 2
Fans power input kW 0.13
Air flow for fan m³/h 3600
Static pressure Pa 0

COMPRESSORS
Compressor type SCROLL
Compressors nr. N° 1
Compressors power absorption kW 2.77

NOISE DATA
Spectrum Hz 63 125 250 500 1000 2000 4000 8000 Tot
dB dB dB dB dB dB dB dB dB(A)
Sound Power 74 73 72 70 68 63 55 50 70
Sound Pressure 60 59 58 56 54 49 41 36 56
Distance m 1.0

Note
Average sound pressure level, at 1.0 m distance, unit in a free field on a reflective surface
Note according to ISO3744. Non-binding value obtained from the sound power level.

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.3.0
TECHNICAL SELECTION Page 3 / 3

HED BASIC 0051


Software version: ELCA World 1.3.3.0
Database version: 1.4.1.0
User: Ortega Cuauhtemoc
Print data: 25/02/2020 11:19

WEIGHT & DIMENSIONS


Dimension A mm 900
Dimension B mm 370
Dimension H mm 990
Weight kg 102

ELECTRICAL DATA (refer to outdoor unit)


Power supply V/ph/Hz 400/3+N/50
Max eletrical power absorbed (FLI) kW 4.43
Max absorbed current (FLA) A 14.8
Max inrush current (SA) A 48.7
Power input (OI) kW 3.40

The performance shown are obtained from theoretical calculations and tolerances will apply.
Rpt.version: 1.0.3.0