You are on page 1of 1

TRANSFOPOWER INDUSTRIES (PVT) LTD.

R&D DEPARTMENT
TECHNICAL DATA SHEET OF TRANSFORMER
Date: November 20, 2023
Customer FWO Ref # : TP-I-23-24-0243
SPECIFICATION
Rated kVA 1500 Basic Insulation Level LV LI 0 AC 3
Voltage Ratio 11000 Y / 400 D V (BIL) HV LI 95 AC 34
Frequency / Phases 50 Hz / 3 f + 2.5,5.0,7.5
Tapping Voltages (%)
Vector Group YNd 11 - 2.5,5.0,7.5
Type of Cooling KNAN HV Terminals 4
Insulation Class H LV Terminals 3
Ambient Temperature 48 0C Service Altitude Above Sea Level 1000 meter
Top Oil 50 0C Type of Tank Conservator
Temperature Rise at Rated kVA
Winding Average 60 0C Type Indoor /Outdoor

PERFORMANCE
No Load Losses at Principle Tap Position 1.900 kW
Load Losses at Principle Tap Position & Rated Current 19.00 kW
Impedance 6.00 %
Regulation at Unity Power Factor & Rated Current 1.44 %
Regulation at 0.8 Power Factor & Rated Current 4.61 %
Efficiency at Unity Power Factor & 100% Rated Current 98.63 %
Efficiency at Unity Power Factor & 50% Rated Current 99.12 %

COMPONENTS & ACCESSORIES


Off Circuit Tap Changer Oil Thermometer (with contacts) (Elmek, Turkey)
Oil Filling Hole and Plug Pressure Relief Valve (with contacts) (Elmek, Turkey)
Oil Level Indicator Double Float Buchholz Relay (Elmek, Turkey)
Oil Drain Valve Marshalling Box with IP 54
Oil Conservator
Silicagel Breather
Cooling Tubes
Lifting Lugs
Transport Eyes
Earthing Terminals
Bi Directional Roller Wheels
Rating & Diagram Plate (Stainless Steel)
Remarks :
1) Transformer shall be offered with Unused Synthetic Organic Esters in accordance with IEC-61099
2) Transformer shall be manufactured and tested as per IEC 60076 Standard.
3) Paint Colour will be RAL 7033

Total Mass of Oil = 845 kg (Approx.)


Total Mass of Transformer = 3560 kg (Approx.)

R&D DEPARTMENT