You are on page 1of 2

10:14:26 472092812.

xls 04/24/2020

DEFGFFFFFFFFF
CONTRACT TITLE ?
COLD DRAFTS - BSRIA AG 7/95

CONTRACT No. ?
.

Rev. 0
CALCULATION FOR: ?
TWO WAY DIFFUSER AT ROOM CENTRE, DOUBLE GLAZING.

Tai 22.0 (DEG C)


Tao -4.0 (DEG C)
Rsi 0.12 (W/SQM K)
N 6.0 (AC/HR)
DESIGN TERMINAL VELOCITY Vt 0.25 (M/S)
ROOM LENGTH (INT) 6.000 (M)
ROOM WIDTH (EXP) 4.000 (M)
WALL HEIGHT 2.750 (M)
WALL U VALUE 0.45 (W/SQM K)
WINDOW HEIGHT 2.000 (M)
WINDOW LENGTH 4.000 (M)
WINDOW U VALUE 2.70 (W/SQM K)

FLOOR AREA 24.0 (SQM)


WALL AREA 3.00 (SQM)
WINDOW AREA 8.00 (SQM)

Q= 597 (W)
q= 25 (W/SQM)
% GLAZING fg = 72.7 (%)
SURFACE TEMPERATURE tc = 16.9 (DEG C)
SUPPLY AIR TEMPEARTURE ts = 26.5 (DEG C)
DT( ts - tc) = 9.7 (DEG C)
qmax = 54 (W/SQM)
Kv = 0.86
MEAN ROOM AIR VELOCITY Vm = 0.17 (M/S)
CORRECTED MEAN AIR VELOCITY Vi = 0.15 (M/S)

VELOCITY CHECK > 0.25 m/s OK


VELOCITY CHECK < 0.10 m/s OK
qmax>q = OK
10:14:26 472092812.xls 04/24/2020

DEFGFFFFFFFFF
CONTRACT TITLE ?
COLD DRAFTS - BSRIA AG 7/95

CONTRACT No. ?
.

Rev. 0
CALCULATION FOR: ?
ONE WAY DIFFUSER AT ROOM EDGE, DOUBLE GLAZING.

Tai 22.0 (DEG C)


Tao -4.0 (DEG C)
Rsi 0.12 (W/SQM K)
N 6.0 (AC/HR)
DESIGN TERMINAL VELOCITY Vt 0.25 (M/S)
ROOM LENGTH (INT) 6.000 (M)
ROOM WIDTH (EXP) 4.000 (M)
WALL HEIGHT 2.750 (M)
WALL U VALUE 0.45 (W/SQM K)
WINDOW HEIGHT 2.000 (M)
WINDOW LENGTH 4.000 (M)
WINDOW U VALUE 2.50 (W/SQM K)

FLOOR AREA 24.0 (SQM)


WALL AREA 3.00 (SQM)
WINDOW AREA 8.00 (SQM)

Q= 555 (W)
q= 23 (W/SQM)
% GLAZING fg = 72.7 (%)
SURFACE TEMPERATURE tc = 17.3 (DEG C)
SUPPLY AIR TEMPEARTURE ts = 26.2 (DEG C)
DT( ts - tc) = 8.9 (DEG C)
qmax = 57 (W/SQM)
Kv = 0.63
MEAN ROOM AIR VELOCITY Vm = 0.17 (M/S)
CORRECTED MEAN AIR VELOCITY Vi = 0.11 (M/S)

VELOCITY CHECK > 0.25 m/s OK


VELOCITY CHECK < 0.10 m/s OK
qmax>q = OK

You might also like