Building Type =

Length , l = 42.80 m
Width , w = 32.50 m
Purlin Spacing = 1.20 m
Bay spacing for centre = 8.000 m
Bay spacing for end = 3.100 m
Clear eave height , h = 2.00 m
Max. eave height = 4.00 m
Roof slope (θ) = 8.13 ˚

DEAD LOAD (DL)

Wt. of sheeting , purlins and sag rods = 25.00 Kg/m²

Dead Load (DL) FOR 8M centre span = 2.00 KN/m


Dead Load (DL) FOR 3.1 M
span(Gable End Span) = 0.39 KN/m

COLLATERAL LOAD
Collateral Load on Rafter = 100.00 Kg/m²
Load due to HVAC , Services , Fire Proofing . Solar Panel etc.
Dead Load (DL) FOR 7.667 M centre
span = 8.00 KN/m

Dead Load (DL) FOR 7.242 M


span(Gable End Span) = 1.55 KN/m

LIVE LOAD (LL)


Live load/unit area, roof = 75.00 Kg/m²

Dead Load (DL) FOR 7.667 M centre


span = 6.00 KN/m
Dead Load (DL) FOR 7.242 M
span(Gable End Span) = 1.16 KN/m

WIND LOAD (WL)


Basic wind speed (Vb) = 33 m/s
Design wind speed (Vz) = Vbxk1xk2xk3Xk4
where,
k1 = probability factor (risk coefficient)
= 1
k2 = terrain, height and structure size factor
= 1
k3 = topography factor
= 1
k4 = Cyclonic Factor
= 1
Vz = 33 m/s

Design wind pressure (pz) = 0.6xVz²


pz = 0.653 KN/m²

Design Wind Pressure , Pd = Pz X Kd X Ka X Kc


Wind Directionality Factor , Kd = 0.900 (Refer Clause 4.5.2.1 of NBC 2016) or Clause 7.2.1 of IS 875 - Part 3
Area Averaging Factor, Ka = 0.800 (Refer Clause 4.5.2.2 of NBC 2016) or Clause 7.2.2 of IS 875 - Part 3
Combination Factor , Kc = 0.900 (Refer Clause 4.5.3.3.13 of NBC 2016) or Clause 7.3.3.13 of IS 875 - Part 3
Kd X Ka X Kc = 0.648 > 0.7 NOT OK
Design Wind Pressure , Pd = 0.457 KN/m2

PRESURE COEFFICIENTS:~
Area of the face = 85.6 m2
Area of the opening = 0 + 0 + 0
= 0 m2
Percentage Area of the Opening = 0.00 %
Encloser condition of the building = FULLY ENCLOSED Enclosed 0.2
Internal pressure coeff.(Cpi) = 0.20 Partially Enclosed 0.5
Open 0.7
h/w = 0.062

l/w = 1.32
= 1<l/w<=3/2
External pressure coeff.(Cpe) : Table 4 Table 5 Table 4
Wind Angle
(ө) Coeff. For Wall Coeff. For Roof Coeff. For Wall
Left Right Left Right GABLE 1 GABLE 2
0 degree 0.70 0.20 -1.2000 -0.40 -0.50 0.50
90 degree -0.60 -0.60 -0.80 -0.60 0.70 -0.10
ROOF ARRANGEMENT WALL LOAD ARRANGEMENT

WIND LOAD DIAGRAMS:~

Wind Across the Ridge (With -Ve Cpi) (WL1) Wind Across the Ridge (With +Ve Cpi) KN/m
-1.00 -3.66 KN/m -0.20 -0.73KN/m -1.40 -5.123 KN/m -0.60 -2.20

KN/m KN/m KN/m KN/m


3.29 1.46 1.83 0.00
0.90 WL1 0.40 0.50 WL2 0.00

Wind Parallel to Ridge(With +Ve Cpi)


-1.00 -3.66 KN/m -0.80 -2.93 KN/m

KN/m KN/m
-2.93 -2.93
-0.80 WL3 -0.80

Wind Parallel to Ridge(With -Ve Cpi)


-0.60 -2.20 KN/m -0.40 -1.46 KN/m

KN/m KN/m
-1.46 0.00
-0.40 WL4 -0.40
Note:
1) Values within the circles are the UDL
2) -Ve value means, load applied
away from structure.

Wind Across the Ridge (With -Ve Cpi) Wind Across the Ridge (With +Ve Cpi)

WL1
KN/m KN/m WL2
-1.10 1.10

-0.30 0.30

Wind Parallel to Ridge(With +Ve Cpi) Wind Parallel to Ridge(With -Ve Cpi)

KN/m WL3 KN/m WL4


3.29 -1.10

0.90 -0.30