DESIGN CALCULATIONS

Job No. SV-0164 Building 01


Revision 00 As per CO.No. 00
NHÀ XƯỞNG XÂY SẴN C-1B-B11
LÔ C-1B-CN, KCN MỸ PHƯỚC 3, BẾN CÁT, BÌNH DƯƠNG

Project Name NHÀ XƯỞNG XÂY SẴN - GIAI ĐOẠN 3


Building Name FACTORY
The Total No. of pages in this document are:

Designed By PHV
Checked By NTH
Date 26/09/2019

Page 1
Table of Contents

Table of Contents ................................................................................................................................2


Roof Panel and Screw Calculation ........................................................................................3
Screw Calculation ...................................................................................................................8

Page 2
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

Roof Panel and Screws calculation

BUILDING GEOMETRY
Input Metric Imperial
Building Width 50.000 m 164.042 ft
Building Length 84.000 m 275.591 ft
Eave Height 7.700 m 25.262 ft
Roof Slope 1.0 X/10 5.711 º
Roof style GableRoofs

Interior Bay Spacing 7.000 m 22.966 ft


End Bay Spacing 7.000 m 22.966 ft
EW Column Spacing 5.000 m 16.404 ft
EW Column Height 10.200 m 33.465 ft

Purlin Spacing on Roof 1.500 m 4.921 ft


SW Girt Spacing 1.500 m 4.921 ft
EW Girt Spacing 1.500 m 4.921 ft

SW Canopy Spacing 7.000 m 22.966 ft


SW Canopy Width 1.500 m 4.921 ft
SW Canopy Height 5.000 m 16.404 ft
SW Canopy Purlin Spacing 1.300 m 4.265 ft

EW Canopy Spacing 5.700 m 18.701 ft


EW Canopy Width 4.500 m 14.764 ft
EW Canopy Height 5.000 m 16.404 ft
EW Canopy Purlin Spacing 1.300 m 4.265 ft

Height of hill or escarpment 0.000 m 0.000 ft

Wind Speed V 116 kph 72 mph

Wind Exposure B Urban & Suburban Area


Building Category II All others

Page 3
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

WIND LOAD CALCULATIONS (AS PER ASCE 7-05)

EAVE HEIGHT (M) 7.7


WIND SPEED V (KM/hour) 116
WIND SPEED V (m/s) 32.2
WIND EXPOSURE B
BAY SPACING (m) 7.00
qh=0.613.Kz.Kzt.Kd.V2.I
VELOCITY PRESSURE (N/m2) (6-15)
[ V in m/s]
VELOCITY PRESSURE (kN/m2) qh=0.48 (6-15)
THE VELOCITY
0.7 (Table 6-3)
PRESSURE EXPOSURE, (Kz)
THE TOPOGRAPHIC FACTOR, (Kzt) 1.00 (Figure 6-4)

THE WIND DIRECTIONALITY


0.85 (Table 6-4)
FACTOR, (Kd)

IMPORTANCE FACTOR, I 1.00 (TableE 6-1)


DESIGN PRESSURE, p (N/m2) p=qh[(GCpf)-(GCpi)]
ENCLOSURE CONDITION Enclosed
INTERNAL PRESSURE
±0.18 (Figure 6-5)
COEFFICIENT, (Gcpi)

Page 4
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

Page 5
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

Page 6
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

Wind uplift on roof = (GCp-GCpi)*qh = (-2.8-0.18)*0.48 = -1.43kN/m²; [(-): wind uplift]


compare to span 1.5m = 2.55kN/m² > 1.43kN/m² => Hence safe.
Other direction, we don’t check bending. It is allowed to bend in this direction.

Page 7
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

1. CALCULATION TENSION FORCE FOR SCREW:


MAX. TENSION FORCE AT EACH CONNECTION (1 SCREW):
F=A x qh x (Gcp – Gcpi)
WHERE:
A: AREA LOAD
A = 1.5 x 0.315 = 0.4725 (m2)
qh=0.48 (kN/m2)
Gcp = -2.8 (REFER FIGURE 6-11B, ASCE 7-05)
Gcpi = 0.18 (REFER FIGURE 6-5, ASCE 7-05)
 F = 0.4725 x 0.48 x (-2.8 – 0.18) = -0.676 kN ((-) WIND UPLIFT)
COMPARE WITH TECHNICAL INFORMATION => HENCE SAFE (REFER ATTACHED FILE
TECHNICAL INFORMATION)

Page 8
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

2. ALLOWABLE PULL-OUT STRENGTH FOR SCREW:

THE NOMINAL PULL-OUT STRENGTH (RESISTANCE) Pnot. SHALL BE CALCULATED AS FOLLOWS:


Pnot = 0.85 x tc x d x Fu2 (AISI. Eq. E4.4.1-1)
WHERE:
tc: PURLIN THICKNESS, tc = 0.15 (cm)
d: NOMINAL DIAMETER SCREW, d=0.55 (cm)

Page 9
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

Fu2: TENSILE STRENGTH OF MEMBER NOT IN CONTACT WITH SCREW HEAD OR WASHER (Fu2=55 Kn/cm 2;
OF CF)
 Pnot = 0.85 x 0.15 x 0.55 x 55 = 3.85 (Kn)
ALLOWABLE PULL-OUT STRENGTH FOR 1 SCREW: Pnot/Ω = 3.85/3 = 1.28 (kN) > T = 0.676
(kN)
Ω: SAFE FACTOR (PLEASE REFER AISI – SECTION E4)
=> HENCE SAFE

Page 10
DESIGN SHEET
Job No. SV-0164 Building No. 01 Co. No. 00
BW INDUSTRIAL DEVELOPMENT
Customer Rev. No. 00
JSC.
Description Designed By PHV
Checked By NTH

Date: …../…../……. Date: …../…../…….


Designer: Pham Hoang Vu Checker: Nguyen Thanh Huy

…………………………………………….. ……………………………………………..
(Signature) (Signature)

Date: …../…../…….
Approval:…Quach Tran Tuan…………………………………

……………………………………………..
(Signature)

Page 11