Project : TATA MEMORIAL CENTRE

Aganampudi, Visakhapatnam

Project Consultants : CRN Architects, Chennai


Client : HINDUSTAN CONSTRUCTION COMPANY
Structural Consultants : Narnindi Consulting Engineers
Title : Design data for Sky Light -4

I ATRIUM - 4 GEOMETRICAL DESIGN DATA


Length of the Atrium = 8.55 M

Width of the Atrium = 7.20 M

F.D.L. To F.F.L. = 0.60 M


F.F.L. Level = 82.50 M
Terrace Level = 98.45 M

Eaves Height from F.D.L. = 16.55 M

Roof Slope = 17 Deg


Maximum Spacing of Purlins (North & South) = 1.20 M
Maximum Spacing of Purlins (East & West) = 1.154 M

II DESIGN LOADS
1 DEAD LOAD :

Roofing Sheet density as per Manufacturer's


= 1200.00 Kg/Cu.M
data sheet (Tuflite Top Seam)

Sheet thickness = 12.00 mm


Self weight of roofing sheet = 14.40 Kg/Sq.M

Design weight of roofing sheet including


= 20.00 Kg/Sq.M
accessories

= 0.20 Kn/Sq.M

Dead Load on North & South side Roofs = 0.240 Kn/M


Dead Load on East & West side Roofs = 0.231 Kn/M

IS:875- 2003 (Part 2) Table - 2, S.No


2 LIVE LOAD : = 0.75 Kn/Sq.M
Access not provided except for mainte

ii) Sloping roof with slope greater than 10


degrees For roof membrane sheets or purlins-
= 0.61 Kn/Sq.M
0.75 kN/mZ less 0.02 kN/m for every degree
increase in slope over 10 degrees

Live Load on North & South side Roofs = 0.732 Kn/M


Live Load on East & West side Roofs = 0.704 Kn/M
Design Data Ncoen Page 1
3 WIND LOAD : as per IS 875 Part-3, 2015

a Basic Wind Speed (Vb) = 50 m/sec

As per IS:875 -2015 - Basic wind speed Map of


= 180 KMPH
India

b Design Wind Speed (Vz) = Vb x K1 x K2 x K3 x K4

K1 = 1.08 As per IS:875 -2015, part 3 , Table 1, Sl.No. (iv)

As per IS:875 -2015, part 3 , Table 2, Terrain Cat


K2 = 1.0562
Height 16.55m

K3 = 1.0 As per IS:875 -2015, part 3 , Clause 6.3.3.1

K4 = 1.30 As per IS:875 -2015, part 3 , Clause 6.3.4, for Ho

Design Wind Speed (Vz) = 50 x 1.08 x 1.0562 x 1.00 x


= 74.15 m/Sec

c Wind Pressure Pz = 0.6 Vz2


= 3298.50997 N/Sq.m
= 3.30 Kn/Sq.m

d Design Wind Pressure Pd = Kd Ka Kc Pz

As per IS:875 -2015, part 3 , 7.2.1 Wind direction


Kd = 1.0
for the Cyclone affected regions

As per IS:875 -2015, part 3 , Table 4, Sl.No.3, Cla


Ka = 0.8
(b)

Kc = 0.9 As per IS:875 -2015, part 3 , Clause 7.3.3.13

Design Wind Pressure Pd 1.00 0.8 0.9 3.30 2.375 Kn/Sq.m

EXTERNAL PRESSURE CO-EFFICIENTS FOR ROOFS As per IS:875 -2015, part 3 , Table 6

Building
h/w = 2.299 3/2 £ h/w £ 6
& Roof

Wind flowing from West to east


EF (Wind ward) GH (Lee Ward)
Wind Perpendicular to Ridge 0 deg -0.77 -0.6
North
E G 7.2M (W
Design Data Ncoen Page 2
E G

8.55m
West
F H

South
10 Deg 20 Deg for 17 Deg
EF -0.7 -0.8
FOR 1 DEG -0.01 -0.77
GH -0.6 -0.6 -0.6
EG -0.8 -0.8 -0.8
FH -0.8 -0.8 -0.8

Hipped Slope M, N for 0 deg Incidence -0.8


-0.8

Hipped Slope M, N for 90 deg Incidence -0.77


0.6

Wind flowing from North to South

Building
h/w (h/l) = 1.936 3/2 £ h/w £ 6
& Roof

EF (Wind ward) GH (Lee Ward)


Wind Perpendicular to Ridge 0 deg -0.77 -0.6
North
E G 7.2M

West 8.55m (W)


F H

10 Deg 20 Deg for 17 Deg South


EF -0.7 -0.8
FOR 1 DEG -0.01 -0.77
GH -0.6 -0.6 -0.6
EG -0.8 -0.8 -0.8
FH -0.8 -0.8 -0.8

Hipped Slope M, N for 0 deg Incidence -0.8


-0.8

Design Data Ncoen Page 3


Hipped Slope M, N for 90 deg Incidence -0.77
-0.6
Internal pressure co-efficient as per Clause 7.3.2.2 ± 0.7

NET CO-EFFICIENTS FOR ROOF Wind flowing from West to east


Perpendicular to ridge with internal pressure
Wind Ward (West) = -0.77 - 0.7 = -1.47
Lee Ward (East) = -0.6 - 0.7 = -1.30

Perpendicular to ridge with internal suction


Wind Ward (West) = -0.77 - -0.7 = -0.07
Lee Ward (East) = -0.6 - -0.7 = 0.10

Parallel to ridge with internal pressure


Wind Ward (West) = -0.8 - 0.7 = -1.50
Lee Ward (East) = -0.8 - 0.7 = -1.50

Parallel to ridge with internal suction


Wind Ward (West) = -0.8 - -0.7 = -0.10
Lee Ward (East) = -0.8 - -0.7 = -0.10

Hipped Slope M, N for 0 deg Incidence


Perpendicular to ridge with internal pressure
North = -0.8 - -0.7 = -0.1
South = -0.8 - -0.7 = -0.1

Perpendicular to ridge with internal Suction


North = -0.77 - 0.7 = -1.47
South = -0.6 - 0.7 = -1.3

Hipped Slope M, N for 90 deg Incidence


Perpendicular to ridge with internal pressure
North = -0.8 - -0.7 = -0.1
South = -0.8 - -0.7 = -0.10

Perpendicular to ridge with internal Suction


North = -0.77 - 0.7 = -1.47
South = -0.6 - 0.7 = -1.30

Design Data Ncoen Page 4


NET CO-EFFICIENTS FOR ROOF Wind flowing from North to South
Perpendicular to ridge with internal pressure
wind ward (North) = -0.77 - 0.7 = -1.47
Lee Ward (South) = -0.6 - 0.7 = -1.30

Perpendicular to ridge with internal suction


wind ward (North) = -0.77 - -0.7 = -0.07
Lee Ward (South) = -0.6 - -0.7 = 0.10

Parallel to ridge with internal pressure


wind ward (North) = -0.8 - 0.7 = -1.50
Lee Ward (South) = -0.8 - 0.7 = -1.50

Parallel to ridge with internal suction


wind ward (North) = -0.8 - -0.7 = -0.10
Lee Ward (South) = -0.8 - -0.7 = -0.10

Hipped Slope M, N for 0 deg Incidence


Perpendicular to ridge with internal pressure
West = -0.8 - -0.7 = -0.10
East = -0.8 - -0.7 = -0.10

Perpendicular to ridge with internal Suction


West = -0.77 - 0.7 = -1.47
East = 0.6 - 0.7 = -0.10

Hipped Slope M, N for 90 deg Incidence


Perpendicular to ridge with internal pressure
West = -0.8 - -0.7 = -0.1
East = -0.8 - -0.7 = -0.10

Perpendicular to ridge with internal Suction


West = -0.77 - 0.7 = -1.47
East = 0.6 - 0.7 = -0.10
MAXIMUM PURLIN SPACINGS
FOR "N" & "S" = 1.200 M
FOR "E" & "W" = 1.154 M

Net Pressure Wind flowing from West to East

Perpendicular with Internal pressure Pd x Net co-efficient x spacing of purlin


wind ward (West) = -4.03 Kn/Rmt
Lee Ward (East) = -3.56 Kn/Rmt
Design Data Ncoen Page 5
Perpendicular with Internal Suction
Wind ward (West) = -0.19 Kn/Rmt
Lee Ward (East) = 0.27 Kn/Rmt

Parallel with Internal pressure


wind ward (West) = -4.11 Kn/Rmt
Lee Ward (East) = -4.11 Kn/Rmt

Parallel with Internal Suction


Wind ward (West) = -0.27 Kn/Rmt
Lee Ward (East) = -0.27 Kn/Rmt

Hipped Slope M, N for 0 deg Incidence


Perpendicular to ridge with internal pressure 20% LESS
North = -0.28 Kn/Rmt -0.228 Kn/Rmt
South = -0.28 Kn/Rmt -0.228 Kn/Rmt

Perpendicular to ridge with internal Suction


North = -4.19 Kn/Rmt -3.351 Kn/Rmt
South = -0.28 Kn/Rmt -0.228 Kn/Rmt

Hipped Slope M, N for 90 deg Incidence


Perpendicular to ridge with internal pressure
North = -0.28 Kn/Rmt -0.228 Kn/Rmt
South = -0.28 Kn/Rmt -0.228 Kn/Rmt

Perpendicular to ridge with internal Suction


North = -4.19 Kn/Rmt -3.351 Kn/Rmt
South = -0.28 Kn/Rmt -0.228 Kn/Rmt

Net Pressure Wind flowing from North to South

Perpendicular with Internal pressure


wind ward (North) = -4.19 Kn/Rmt
Lee Ward (South) = -3.70 Kn/Rmt

Perpendicular with Internal Suction


wind ward (North) = -0.20 Kn/Rmt
Lee Ward (South) = 0.28 Kn/Rmt

Parallel with Internal pressure


wind ward (North) = -4.27 Kn/Rmt
Lee Ward (South) = -4.27 Kn/Rmt

Design Data Ncoen Page 6


Parallel with Internal Suction
wind ward (North) = -0.28 Kn/Rmt
Lee Ward (South) = -0.28 Kn/Rmt

Hipped Slope M, N for 0 deg Incidence


Perpendicular to ridge with internal pressure 20% LESS
West = -0.27 Kn/Rmt -0.219 Kn/Rmt
East = -0.27 Kn/Rmt -0.219 Kn/Rmt

Perpendicular to ridge with internal Suction


West = -4.03 Kn/Rmt -3.223 Kn/Rmt
East = -3.56 Kn/Rmt -2.85 Kn/Rmt

Hipped Slope M, N for 90 deg Incidence


Perpendicular to ridge with internal pressure
West = -0.27 Kn/Rmt -0.219 Kn/Rmt
East = -0.27 Kn/Rmt -0.219 Kn/Rmt

Perpendicular to ridge with internal Suction


West = -4.03 Kn/Rmt -3.223 Kn/Rmt
East = -3.56 Kn/Rmt -2.85 Kn/Rmt

Design Data Ncoen Page 7


t 2) Table - 2, S.No. 1-(i) b -
ed except for maintenance

Design Data Ncoen Page 8


Table 1, Sl.No. (iv)

Table 2, Terrain Category - 2,

Clause 6.3.4, for Hospital Building

1.30

7.2.1 Wind directionality Factor


ns

Table 4, Sl.No.3, Clause 7.2.2.1

Building Height Ratio


& Roof Angle 17 Deg

North
7.2M (Width)
Design Data Ncoen Page 9
East

South 0 90
E -0.77 -0.8
F -0.77 -0.8
G -0.6 -0.8
H -0.6 -0.8

M,N WIND WARD -0.8 0 DEG


LEE WARD -0.8
Wind Ward
Lee Ward M,N WIND WARD -0.77 90 DEG

Wind Ward LEE WARD -0.6


Lee Ward

Building Height Ratio


& Roof Angle 17 Deg

North
7.2M

East

South 0 90
E -0.77 -0.8
F -0.77 -0.8
G -0.6 -0.8
H -0.6 -0.8
M,N WIND WARD -0.8 0 DEG
LEE WARD -0.8
Wind Ward
Lee Ward M,N WIND WARD -0.77 90 DEG

Design Data Ncoen Page 10


Wind Ward LEE WARD -0.6
Lee Ward

Design Data Ncoen Page 11


Resolving Forces

Gy Gx
-4.007 -0.421
-3.543 -0.372
Design Data Ncoen Page 12
-0.191 -0.020
0.273 0.029

-4.088 -0.430
-4.088 -0.430

-0.273 -0.029
-0.273 -0.029

-0.227 -0.024
-0.227 -0.024

-3.333 -0.350
-0.227 -0.024

-0.227 -0.024
-0.227 -0.024

-3.333 -0.350
-0.227 -0.024

Resolving Forces

Gy Gx
-4.166 -0.438
-3.685 -0.387

-0.198 -0.021
0.283 0.030

-4.251 -0.447
-4.251 -0.447

Design Data Ncoen Page 13


-0.283 -0.030
-0.283 -0.030

-0.218 -0.023
-0.218 -0.023

-3.205 -0.337
-2.835 -0.298

-0.218 -0.023
-0.218 -0.023

-3.205 -0.337
-2.835 -0.298

Design Data Ncoen Page 14