You are on page 1of 32

GOVERNMENT OF MADHYA PRADESH

Madhya Pradesh Water Resources Department

PROJECT: SIP AMBER MICRO IRRIGATION PROJECT

DESIGN OF PUMP HOUSE-2 (SALAROND)

SUBMITTED BY : VIJAY KUMAR MISHRA


PVT. CONSTRUCTION LTD.

SUB DIVISION OFFICER EXECUTIVE ENGINEER

WATER RESOURCES SUBDIVISION WATER RESOURCES DIVISION

NASRULLAHGANJ
SEHORE (M.P)
SEHORE, (M.P)
WATER RESOURCES DEPARTMENT
GOVERNMENT OF MADHYA PRADESH

Madhya Pradesh Water Resources Department

PROJECT: SIP AMBER MICRO IRRIGATION PROJECT

DESIGN OF CONTROL ROOM (PH-2)

SUBMITTED BY : VIJAY KUMAR MISHRA


PVT. CONSTRUCTION LTD.

SUB DIVISION OFFICER EXECUTIVE ENGINEER


WATER RESOURCES
WATER RESOURCES DIVISION
SUBDIVISION
NASRULLAHGANJ SEHORE

SEHORE, (M.P) (M.P)


INDEX: DESIGN OF PUMP HOUSE-2 (SALAROND)

S.No Components

1 Load List

2 Wind Force Calculation

3 STAAD Input File

4 STAAD Output File

5 Design of Roof Level Beams

6 Design of EOT Level Beams

7 Design of T-Girder

8 Design of Tie Level Beams

10 Design of Inspection Gallery Slab

12 Design of Pump Floor Level Beams

13 Design of Pump Floor Slab

14 Design of Maintenance Bay slab

15 Design of Pipe Gallery Slab

16 Design of Substructure Level Beam-1

17 Design of Substructure Tie Beam-2

18 Design of Columns
19 Design of Footings

20 Deisgn of Raft Foundation (Corners)

21 Design of Raft Foundation (Centre)

21 Design of Side Wall-1

22 Design of Side Wall-2

23 Design of Side Wall-3

24 Design of Back Wall-1

25 Design of Back Wall-2

26 Design of Back Wall-3

27 Design of Partition Wall

28 Plate Stress Summary

29 Pump Load Documents

30 Soil Bearing Capacity Report


ABUTMENT LOAD CALCULATIONS

PROJECT: SIP KOLAR

1 Unit Weight of Concrete = 25 KN/m3

2 Depth of Top Slab = 0.4 m

3 Load Transferred from Aqueduct at Corner = 720 KN

4 Load Transferred from Aqueduct at centre = 100 KN

(Values obtained are from attached aqueduct STAAD File)

LIVE LOADS

2 Angle of Divergence Assumed = 28 *

3 Volume of Water/sec = 10 m3/sec

4 Velocity of water = 1.2 m/sec

5 Momentum Force =y*Q*v 117.72 KN

6 Load Component along Z (Fz) =y*Q*v*(1-cosO) 13.77 KN

7 Load Component along X (Fx) =y*Q*v*sinO 55.24 KN

8 Height of Supporting Wall = 2.5 m

9 Fz/ Unit length = 5.508 KN/m

10 Fx/Unit Length = 22.096 KN/m

For safer side calculation, Impact factor of 1.25 is considered

Fz/ Unit length = 6.885 KN/m

Fx/Unit Length = 27.62 KN/m

Velocity of water in stream = 7.2 m/sec

Water Current force =52*k*v*v 1.78 KN/m


SUMMARY SHEET FOR LOAD CALCULATIONS

NOTE: Values used for Calculations will be Mx/1.5, My/1.5. For main reinforcement calculation, LSM will be used & FOS of 1.5 will be used for reinf. Calculation. For
calculation of crackwidth, WSM will be used
1 Stresses are in N/mm2
2 Meq is calculated using clause: IS 456 Clause 41.4.2
3 Values obtained are from STAAD PRO.
4 Combinations for Primary forces have been developed on STAAD Pro as per IS 456. The values obtained are used for design.
BOTTOM RAFT
Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m Meq SY N/mm2 SXY N/mm2 Meq
439 20 1.042 -1.159 609.195 1271.545 161.17 0 0 0 1461.157
590 19 -0.678 2.739 1060.943 1191.053 173.552 0 0 0 1163.032
587 19 0.181 0.957 495.639 439.125 115.12 0 0 0 506.843
MAXIMUM BASE PRESSURE ON RAFT = 0.94 N/mm2
SETTLEMENT SUMMARY
Node L/C X-Trans mm Y-Trans mm Z-Trans mm Absolute mm X-Rotan rad Y-Rotan rad Z-Rotan rad
394 21 0 -1.024 0 1.024 0 0 0

ABUTMENT BASE SLAB


Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m Meq SY N/mm2 SXY N/mm2 Meq
89 10 -0.024 0.155 -329.768 -1669.164 639.386 -0.327 -0.77 0.306 2421.383
25 10 0.668 -0.071 107.88 253.427 -46.37 0.018 -0.187 0.169 280.703
103 10 -0.204 1.442 -152.045 -1262.12 307.147 0.122 -1.121 -0.046 332.72

ABUTMENT WALL
Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m Meq SY N/mm2 SXY N/mm2 Meq
184 15 0.157 0.048 -61.051 -5.72 -6.324 0.356 -0.25 -0.084 64.771
246 15 0 0.127 4.018 54.373 -2.41 -0.178 0.344 0.024 55.791
LOAD LIST: SEEP AMBER (PH2)
Dead Load
1 Masonry Load =0.23*3.0*16 11.04 KN/m
Assumed = 12 KN/m
2 Control room+ER slab thick = 0.3 m
Dead Load =25*0.3 7.5 Kn/m2
Assumed = 7.5 KN/m2
3 Maintenance Bay slab thick = 0.3 m
Dead Load = 7.5 KN/m2
Assumed = 7.5 KN/m2
4 Truss Load = 22.5 KN
(Manufacturer Data)
5 Dead load of EOT RAIL = 3 KN/m
(Manufactuer Data)
6 Pump Floor Slab = 7.5 KN/m2
7 Partition Brick Wall Load = 6 KN/m
PUMP LOAD
Data is Obtrained from Pump Manufacturer
Bare Weight of Pump = 6.907 T
Weight of Motor = 7 T
Weight of Water Column = 3.067 T
Dead Load of Pump = 13.907 T
Live Load of Pump = 16.974 T
3 Total Downward Dead Load = 136.428 KN
4 Number of bolts = 8
5 Total Downward Dead Load per Bolt = 17.054 KN
Live Loads on Pumps
Max Horizontal Thrust (Hor) = 26.772 T
6 Maximum Horizontal Thrust =26.772*9.81 262.633 KN
7 Number of bolts resisting thrust = 8
8 Horizontal thrust per bolt = 32.829 KN
Considering Impact factor as 1.25 = 41.036
Assumed = 42 KN
Weight of Pump Assumed as DL = 14.715 KN
9 Downward Live Load = 30.09 KN
10 Considering Impact Factor as 1.25 = 37.6125 KN
11 Load acting on each Bolt = 4.702 KN

Live Load
2 Live Floor Load on Maintenace bay = 12.5 KN/m2
3 Live Load on Approach Bay = 12.5 KN/m2
4 EOT Load =1.25*dry wt of pump 84.697 KN
5 Assumed = 200 KN
6 Moment on EOT = 100 KNm
7 Horizontal thrust on EOT = 10 KN
7 Live Load on Roof = 1 KN/m2
8 Shutter Load = 7.5 KN/m
9 Inspection Gallery = 3 KN/m2
Distribution Acoss Nodes (Live Load)
Floor Load = 0.75 KN/m2
SUB-STRUCTURE LOAD
WATER UPTO MWL
Hydrostatic Load
1 Unit weight of water = 9.81 Kn/m3
MWL = 304.5 m
FRL = 304.5 m
Bottom raft lev = 293.5 m
Height of tank upto MWL = 11 m
Hydrostatic load upto MWL (Max) = 9.81 * 11 107.91 Kn/m2
Weight of Water = 108 KN/m2
SOIL LOAD

2 Angle of friction = 30 *
Coeff. Of active earth pressure = 0.33
Unit Weight of Saturated soil = 20 KN/m3
Height = 6 m
Saturarated Weight at Raft Level =Ysat*H 120 KN/m2
Active Pressure on Walls =(Ysat-9.81)*H 61.14 KN/m2
Weight of water on bottom raft
3 Height of water upto MWL = 11 m
Load acting on bottom raft = 107.91 KN/m2
ASSUMED = 130 KN/m2
1 EQ Analysis is done on STAAD, Considering structure to be in Zone 3
2 Wind load,Hydrodyanimic calculation is shown on a separate sheet
SUMMARY SHEET FOR LOAD CALCULATIONS

NOTE: Values used for Calculations will be Mx/1.5, My/1.5. For main reinforcement calculation, LSM will be used & FOS of 1.5 will be used for
reinf. Calculation. For calculation of crackwidth, WSM will be used
1 Stresses are in N/mm2
2 Meq is calculated using clause: IS 456 Clause 41.4.2
3 Values obtained are from STAAD PRO.
4 Combinations for Primary forces have been developed on STAAD Pro as per IS 456. The values obtained are used for design.
BOTTOM RAFT (Corner)
Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
3216 18 -1.067 0.236 346.045 528.232 13.456 0 0 0 MY
2812 68 -0.096 0.885 469.03 251.711 10.327 0 0 0 MX
3216 21 -1.067 0.236 346.045 528.232 13.456 0 0 0 SQY
MAXIMUM BASE PRESSURE ON RAFT = 0.28 N/mm2
SETTLEMENT SUMMARY
Node L/C X-Trans mm Y-Trans mm Z-Trans mm Absolute mm X-Rotan rad Y-Rotan rad Z-Rotan rad
346 18 0 -2.479 0 2.479 0 0 0

BOTTOM RAFT (Centre)


Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
5336 21 0.457 -0.008 91.46 173.832 6.851 0 0 0 MY
2803 65 0.02 0.454 142.06 37.714 2.887 0 0 0 MX
3218 18 -0.569 -0.032 65.35 167.54 7.143 0 0 0 SQY

SW+BW: RL: 293.5 TO 296.00


Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
3231 24 -0.011 -0.132 22.853 174.006 0.222 -0.138 -0.407 0.128
3230 24 0.029 -0.014 27.015 109.152 3.579 -0.082 -0.239 0.011
3231 26 -0.057 -0.419 7.985 53.345 -4.464 -0.34 -1.189 -0.015
SW+BW: RL: 296.00 TO 303.00
Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
3453 127 0.056 0.141 0.138 -24.705 -8.145 0.035 0.058 -0.165
3614 18 -0.052 -0.072 12.11 21.878 8.753 -0.02 -0.153 -0.003
3447 18 -0.072 0.148 9.736 14.513 -7.969 -0.024 -0.088 -0.162

SW+BW: RL: 303.00 TO 306.50


Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
3386 65 0.313 0.659 41.03 175.689 71.265 -0.712 -0.457 -0.381
3386 65 0.313 0.659 41.03 175.689 71.265 -0.712 -0.457 -0.381
3386 65 0.313 0.659 41.03 175.689 71.265 -0.712 -0.457 -0.381

PUMP FLOOR SLAB: RL: 306.50


Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
4559 94 -0.142 -0.158 -6.845 -34.668 6.162 0 0 0
4855 18 -0.24 -0.007 33.911 6.186 0.039 0 0 0
4568 25 -0.04 0.366 10.797 22.346 5.68 0 0 0

PARTITION WALL
Plate L/C SQX N/mm2 SQY N/mm2 MX kN-m/m MY kN-m/m MXY kN-m/m SX N/mm2 SY N/mm2 SXY N/mm2
1324 139 -0.033 -0.023 -3.174 -10.923 -3.432 -0.409 -2.292 -0.512
770 32 0.041 0.002 4.809 6.629 3.645 -0.03 -1.311 -0.789
1856 33 0.026 0.158 1.606 8.45 1.589 -0.259 -0.355 0.263
Design of RAFT (CORNER)

Grade of concrete M 30 N/mm2

Grade of Steel Fe 500 N/mm2

Max BM of the raft in Top along Shorter direction (Mx +ve) 352.15 kN-m/m

Max BM of the raft in bottom along Shorter direction (Mx -ve) 352.15 kN-m/m

Max BM of the raft in top along Longer direction (My +ve) 312.69 kN-m/m

Max BM of the raft in bottom Longer direction (My -ve) 312.69 kN-m/m

Maximum Shear stress acting 0n the raft = 0.71 N/mm^2

Shear Force acting at the base of Raft Vu = 569 kN

Thickness of Raft required for Max. Moment

= 352.16x1000000x 1.5/(0.1338 x 30x1000) = 363 mm

Provide wall thickness of = 800 mm

Effecetive depth @ bottom = 750 mm

Area of steel (X Direction)

Diameter of bar provided = 20 mm

Effective depth of wall = 800-40-20/2 = d,eff = 750 mm

Mu/bd2= 352.16 x 1.5 x 1000000/(1000 x750^2)= 0.94

% of steel required pt,req = 0.225 %

Ast required = 0.225 x 1000 x 750 /100 Ast,req = 1687.5 mm2

Cl:8.1
of IS Minimum percentage of steel required pt,min = 0.24 %
3370
(part- Min Area of steel required on each face = 0.24/100/2x1000x800 960 mm2/m
2):200
9
Provide 20 mm dia tor steel at a spacing = 150 mm c/c

Area of steel provided = Ast,prov = 2094.4 mm2/m

percentage of steel provided = 0.279 %

OK

Area of steel (z Direction)

Diameter of bar provided = 20 mm

Effective depth of wall = 800-50-20/2 = 740 mm

Mu/bd2= 312.69 x 1.5 x 1000000/(1000 x740^2)= 0.86

% of steel required 0.205 %

Ast required=0.205 x 1000 x 740 /100= 1517 mm2

Cl:8.1
of IS Minimum percentage of steel required = 0.24 %
3370
(part- Min Area of steel required on each face = 0.24/100/2x1000x800 960 mm2/m
2):200
9
Provide 20 mm dia tor steel at a spacing = 100 mm c/c

Area of steel provided = 3141.6 mm2/m

percentage of steel provided = 0.425 %

OK

Check for shear

Max. Factored Shear Stress on the wall = 1.067 N/mm2

Shear Type : Punching

Percentage of steel provided = 0.425 %

Allowable shear stress = 0.464 N/mm2

Punching Shear Stress = 1.369 N/mm2

Hence safe
Check for Base Pressure

Base pressure (from staad) = 0.280 N/mm2

Load case . LC: 18 (Settlement)

Allowable base pressure

= 1.12 N/mm2

Safe

Check for settlement

settlement from staad = 0.112 mm

Node No. 5 LC: 18 (Settlement)

Permissible settlement (Ref. IS 1904 Table 1) = 12 mm

Safe
Design of RAFT (CENTRE)

Grade of concrete M 30 N/mm2

Grade of Steel Fe 500 N/mm2

Max BM of the raft in Top along Shorter direction (Mx +ve) 115.89 kN-m/m

Max BM of the raft in bottom along Shorter direction (Mx -ve) 115.89 kN-m/m

Max BM of the raft in top along Longer direction (My +ve) 94.71 kN-m/m

Max BM of the raft in bottom Longer direction (My -ve) 94.71 kN-m/m

Maximum Shear stress acting 0n the raft = 0.38 N/mm^2

Shear Force acting at the base of Raft Vu = 228 kN

Thickness of Raft required for Max. Moment

= 115.89x1000000x 1.5/(0.1338 x 30x1000) = 208 mm

Provide wall thickness of = 600 mm

Effecetive depth @ bottom = 552 mm

Area of steel (X Direction)

Diameter of bar provided = 16 mm

Effective depth of wall = 600-40-16/2 = d,eff = 552 mm

Mu/bd2= 115.89 x 1.5 x 1000000/(1000 x552^2)= 0.57

% of steel required pt,req = 0.134 %

Ast required = 0.134 x 1000 x 552 /100 Ast,req = 739.68 mm2

Cl:8.1
of IS Minimum percentage of steel required pt,min = 0.24 %
3370
(part- Min Area of steel required on each face = 0.24/100/2x1000x600 720 mm2/m
2):200
9
Provide 16 mm dia tor steel at a spacing = 250 mm c/c

Area of steel provided = Ast,prov = 804.3 mm2/m

percentage of steel provided = 0.146 %

OK

Area of steel (z Direction)

Diameter of bar provided = 16 mm

Effective depth of wall = 600-50-16/2 = 542 mm

Mu/bd2= 94.71 x 1.5 x 1000000/(1000 x542^2)= 0.48

% of steel required 0.113 %

Ast required=0.113 x 1000 x 542 /100= 612.46 mm2

Cl:8.1
of IS Minimum percentage of steel required = 0.24 %
3370
(part- Min Area of steel required on each face = 0.24/100/2x1000x600 720 mm2/m
2):200
9
Provide 16 mm dia tor steel at a spacing = 250 mm c/c

Area of steel provided = 804.3 mm2/m

percentage of steel provided = 0.148 %

OK

Area of Steel (X direction)

Diameter of bar provided = 16 mm

Effective depth of wall = 600-50-16/2 = d,eff = 542 mm

Mu/bd2= 94.71 x 1.5 x 1000000/(1000 x542^2)= 0.48

% of steel required pt,req = 0.113 %

Ast required=0.113 x 1000 x 542 /100 Ast,req = 612.46 mm2


Cl:8.1
of IS Minimum percentage of steel required pt,min = 0.24 %
3370
(part- Min Area of steel required on each face = 0.24/100/2x1000x600 720 mm2/m
2):200
9
Provide 16 mm dia tor steel at a spacing = 250 mm c/c

Area of steel provided = Ast,prov = 804.3 mm2/m

percentage of steel provided = 0.148 %

OK

Area of steel (Y direction)

Diameter of bar provided = 16 mm

Effective depth of wall = 600-50-16/2 = d,eff = 542 mm

Mu/bd2= 94.71 x 1.5 x 1000000/(1000 x542^2)= 0.48

% of steel required pt,req = 0.113 %

Ast required=0.113 x 1000 x 542 /100 Ast,req = 612.46 mm2

Cl:8.1
of IS Minimum percentage of steel required pt,min = 0.24 %
3370
(part- Min Area of steel required on each face = 0.24/100/2x1000x600 720 mm2/m
2):200
9
Provide 16 mm dia tor steel at a spacing = 250 mm c/c

Area of steel provided = Ast,prov = 804.3 mm2/m

percentage of steel provided = 0.148 %

OK

Check for shear

Max. Factored Shear Stress on the wall = 0.569 N/mm2

Percentage of steel provided = 0.148 %

Allowable shear stress = 0.292 N/mm2


Unsafe

Hence Haunch reinforcements need to be provided

Vu = 341.4 KN

Shear resisted by Concrete =Tc*b*d 175.05 KN

Vsu =Vu-Tc*b*d 166.35 KN

Providing bars of dia = 12 mm

Ast =Vsu/0.87fy 460.74 mm2

Spacing = 245.344446 mm

Provide 12mm haunch steel @ 150mm C/C

Check for Base Pressure

Base pressure (from staad) = 0.280 N/mm2

Load case . LC: 18 (Settlement)

Allowable base pressure

= 1.12 N/mm2

Safe

Check for settlement

settlement from staad = 0.112 mm

Node No. 5 LC: 18 (Settlement)

Permissible settlement (Ref. IS 1904 Table 1) = 12 mm

Safe
WALL (RL:293.50 TO 296.00)

Grade of concrete M 30

Grade of Steel Fe 500

Max. Vertical BM acting on the wall/m water face,My = 116.00 kN-m/m

Max. Horizontal BM acting on the wall/m water face,Mx = 18.01 kN-m/m

Max. Vertical BM acting on the wall/m Soil face ,My = 116.00 kN-m/m

Max. Horizontal BM acting on the wall/m Soil face ,Mx = 18.01 kN-m/m

Maximum Shear stress acting an the wall = 0.279 N/mm^2

Shear Force acting at the base of wall Vu = 223.47 kN

Thickness of wall required for Max. Moment

= 116.01x1000000x 1.5/(0.1338 x 30x1000) = 208 mm

Provide wall thickness at Bottom = 600 mm

Provide wall thickness at Top= 600 mm

Effecetive depth @ bottom = 550 mm

Area of Vertical steel required on water face

Diameter of bar provided = 20 mm

Effective depth of wall = 600-40-20/2 = d,eff = 550 mm

Mu/bd2= 116.01 x 1.5 x 1000000/(1000 x550^2)= 0.58

% of steel required pt,req = 0.137 %

Ast required = 0.137 x 1000 x 550 /100 Ast,req = 753.5 mm2


Cl:
Minimum percentage of steel required pt,min = 0.24 %
8.
1
of
IS
33
70
(p
Cl:
8.
1
of Min Area of steel required on each face = 0.24/100/2x1000x600 720 mm2/m
IS
33 Provide 20 mm dia tor steel at a spacing = 200 mm c/c
70
(p Area of steel provided = Ast,prov = 1570.8 mm2/m
art
-
2): percentage of steel provided = 0.286 %
20
09 Area of Horizontal steel required on water face

Total Area of steel required for Axial tension = (Ast of Axial tension + Ast of Bending)

Ast, due to Axial Tension = T/(2 * 0.87*Fy) Ast, for Axial = 917.24 mm2/m

Diameter of bar provided = 16 mm

Effective depth of wall = 600-40-16- 16/2 = 536 mm

Mu/bd2= 18.01 x 1.5 x 1000000/(1000 x536^2)= 0.09

% of steel required 0.021 %

Ast required=0.021 x 1000 x 536 /100= 112.56 mm2

Total Area of steel required 1029.80 mm2


Cl:
Minimum percentage of steel required = 0.24 %
8.
1
of Min Area of steel required on each face = 0.24/100/2x1000x600 720 mm2/m
IS
33 Provide 16 mm dia tor steel at a spacing = 180 mm c/c
70
(p Area of steel provided = 1117.0 mm2/m
art
-
2): percentage of steel provided = 0.208 %
20
09

Check for shear

Max. Factored Shear Stress on the wall = 0.419 N/mm2

Percentage of steel provided = 0.286 %


Allowable shear stress = 0.391 N/mm2

Unsafe

Hence Shear reinforcements need to be provided

Vu = 335.20 KN

Shear Force resisted by concrete =Tc*b*d 215.232 KN

Hence stirrups need to be providedMax((Vu-Tc*b*d) 119.97 KN

Area of Stirupps =Vu*1000/0.87f 275.789 mm2

Providing bars of dia = 12 mm

Spacing = 409.879 mm

Hence 12 mm dia bars @ 150mm c/c are provided


WALL (RL:296.00 TO 303.00)

Grade of concrete M 30

Grade of Steel Fe 500

Max. Vertical BM acting on the wall/m water face,My = 16.47 kN-m/m

Max. Horizontal BM acting on the wall/m water face,Mx = 8.07 kN-m/m

Max. Vertical BM acting on the wall/m Soil face ,My = 16.47 kN-m/m

Max. Horizontal BM acting on the wall/m Soil face ,Mx = 8.07 kN-m/m

Maximum Shear stress acting an the wall = 0.099 N/mm^2

Shear Force acting at the base of wall Vu = 78.93 kN

Thickness of wall required for Max. Moment

= 16.47x1000000x 1.5/(0.1338 x 30x1000) = 78 mm

Provide wall thickness at Bottom = 500 mm

Provide wall thickness at Top= 500 mm

Effecetive depth @ bottom = 452 mm

Area of Vertical steel required on water face

Diameter of bar provided = 16 mm

Effective depth of wall = 500-40-16/2 = d,eff = 452 mm

Mu/bd2= 16.47 x 1.5 x 1000000/(1000 x452^2)= 0.12

% of steel required pt,req = 0.028 %

Ast required = 0.028 x 1000 x 452 /100 Ast,req = 126.56 mm2


Cl:
8. Minimum percentage of steel required pt,min = 0.24 %
1
of Min Area of steel required on each face = 0.24/100/2x1000x500 600 mm2/m
IS
33 Provide 16 mm dia tor steel at a spacing = 200 mm c/c
70
(p Area of steel provided = Ast,prov = 1005.3 mm2/m
art
-
2): percentage of steel provided = 0.222 %
20
09
Area of Horizontal steel required on water face

Total Area of steel required for Axial tension = (Ast of Axial tension + Ast of Bending)

Ast, due to Axial Tension = T/(2 * 0.87*Fy) Ast, for Axial = 917.24 mm2/m

Diameter of bar provided = 16 mm

Effective depth of wall = 500-40-16- 16/2 = 436 mm

Mu/bd2= 8.08 x 1.5 x 1000000/(1000 x436^2)= 0.06

% of steel required 0.014 %

Ast required=0.014 x 1000 x 436 /100= 61.04 mm2

Total Area of steel required 978.28 mm2


Cl:
8. Minimum percentage of steel required = 0.24 %
1
of Min Area of steel required on each face = 0.24/100/2x1000x500 600 mm2/m
IS
33 Provide 16 mm dia tor steel at a spacing = 200 mm c/c
70
(p Area of steel provided = 1005.3 mm2/m
art
-
2): percentage of steel provided = 0.231 %
20
09
Check for shear

Max. Factored Shear Stress on the wall = 0.148 N/mm2

Percentage of steel provided = 0.231 %

Allowable shear stress = 0.356 N/mm2

OK
WALL (RL:303.00 TO 306.50)

Grade of concrete M 30

Grade of Steel Fe 500

Max. Vertical BM acting on the wall/m water face,My = 117.13 kN-m/m

Max. Horizontal BM acting on the wall/m water face,Mx = 27.35 kN-m/m

Max. Vertical BM acting on the wall/m Soil face ,My = 117.13 kN-m/m

Max. Horizontal BM acting on the wall/m Soil face ,Mx = 27.35 kN-m/m

Maximum Shear stress acting an the wall = 0.439 N/mm^2

Shear Force acting at the base of wall Vu = 197.70 kN

Thickness of wall required for Max. Moment

= 117.13x1000000x 1.5/(0.1338 x 30x1000) = 209 mm

Provide wall thickness at Bottom = 450 mm

Provide wall thickness at Top= 450 mm

Effecetive depth @ bottom = 400 mm

Area of Vertical steel required on water face

Diameter of bar provided = 20 mm

Effective depth of wall = 450-40-20/2 = d,eff = 400 mm

Mu/bd2= 117.13 x 1.5 x 1000000/(1000 x400^2)= 1.1

% of steel required pt,req = 0.265 %

Ast required = 0.265 x 1000 x 400 /100 Ast,req = 1060 mm2


Cl:
Minimum percentage of steel required pt,min = 0.24 %
8.
1
of
IS
33
70
(p
Cl:
8.
1
of Min Area of steel required on each face = 0.24/100/2x1000x450 540 mm2/m
IS
33 Provide 20 mm dia tor steel at a spacing = 200 mm c/c
70
(p Area of steel provided = Ast,prov = 1570.8 mm2/m
art
-
2): percentage of steel provided = 0.393 %
20
09 Area of Horizontal steel required on water face

Total Area of steel required for Axial tension = (Ast of Axial tension + Ast of Bending)

Ast, due to Axial Tension = T/(2 * 0.87*Fy) Ast, for Axial = 917.24 mm2/m

Diameter of bar provided = 16 mm

Effective depth of wall = 450-40-16- 16/2 = 386 mm

Mu/bd2= 27.36 x 1.5 x 1000000/(1000 x386^2)= 0.28

% of steel required 0.065 %

Ast required=0.065 x 1000 x 386 /100= 250.9 mm2

Total Area of steel required 1168.14 mm2


Cl:
Minimum percentage of steel required = 0.24 %
8.
1
of Min Area of steel required on each face = 0.24/100/2x1000x450 540 mm2/m
IS
33 Provide 16 mm dia tor steel at a spacing = 200 mm c/c
70
(p Area of steel provided = 1005.3 mm2/m
art
-
2): percentage of steel provided = 0.260 %
20
09

Check for shear

Max. Factored Shear Stress on the wall = 0.659 N/mm2

Percentage of steel provided = 0.393 %


Allowable shear stress = 0.449 N/mm2

Unsafe

Hence Shear reinforcements need to be provided

Vu = 296.55 KN

Shear Force resisted by concrete =Tc*b*d 179.524 KN

Hence stirrups need to be providedMax((Vu-Tc*b*d) 117.03 KN

Area of Stirupps =Vu*1000/0.87f 269.025 mm2

Providing bars of dia = 12 mm

Spacing = 420.184 mm

Hence 12 mm dia bars @ 150mm c/c are provided


Design of Pump Floor Slab:

Grade of concrete M 30 N/mm2

Grade of Steel Fe 500 N/mm2

Max BM at Corners (Mx) 23.11 kN-m/m

Max BM At Corners (My) 23.11 kN-m/m

Max BM at centre (Mx) 22.61 kN-m/m

Max BM at centre (My) 22.61 kN-m/m

Maximum Shear stress acting 0n the Slab = 0.24 N/mm^2

Shear Force acting at the base of Slab Vu = 73 kN

Thickness of Slab required for Max. Moment

= 23.12x1000000x 1.5/(0.1338 x 30x1000) = 93 mm

Provide thickness of = 300 mm

Effecetive depth @ bottom = 252 mm

Area of steel (X Direction)

Diameter of bar provided = 16 mm

Effective depth of wall = 300-40-16/2 = d,eff = 252 mm

Mu/bd2= 23.12 x 1.5 x 1000000/(1000 x252^2)= 0.55

% of steel required pt,req = 0.129 %

Ast required = 0.129 x 1000 x 252 /100 Ast,req = 325.08 mm2


Cl:8.1 of IS
Minimum percentage of steel required pt,min = 0.24 %
3370 (part-
2):2009
Min Area of steel required on each face = 0.24/100/2x1000x300 360 mm2/m

Provide 16 mm dia tor steel at a spacing = 150 mm c/c


Area of steel provided = Ast,prov = 1340.4 mm2/m

percentage of steel provided = 0.532 %

OK

Area of steel (z Direction)

Diameter of bar provided = 16 mm

Effective depth of wall = 300-50-16/2 = 242 mm

Mu/bd2= 22.61 x 1.5 x 1000000/(1000 x242^2)= 0.58

% of steel required 0.137 %

Ast required=0.137 x 1000 x 242 /100= 331.54 mm2


Cl:8.1 of IS
Minimum percentage of steel required = 0.24 %
3370 (part-
2):2009
Min Area of steel required on each face = 0.24/100/2x1000x300 360 mm2/m

Provide 16 mm dia tor steel at a spacing = 150 mm c/c

Area of steel provided = 1340.4 mm2/m

percentage of steel provided = 0.554 %

OK

Check for shear

Max. Factored Shear Stress on the slab = 0.366 N/mm2

Percentage of steel provided = 0.554 %

Allowable shear stress = 0.518 N/mm2

OK
WALL (RL:293.50 TO 306.50)

Grade of concrete M 30

Grade of Steel Fe 500

Max. Vertical BM acting on the wall/m water face,My = 7.28 kN-m/m

Max. Horizontal BM acting on the wall/m water face,Mx = 3.21 kN-m/m

Max. Vertical BM acting on the wall/m Soil face ,My = 7.28 kN-m/m

Max. Horizontal BM acting on the wall/m Soil face ,Mx = 3.21 kN-m/m

Maximum Shear stress acting an the wall = 0.105 N/mm^2

Shear Force acting at the base of wall Vu = 84.27 kN

Thickness of wall required for Max. Moment

= 7.29x1000000x 1.5/(0.1338 x 30x1000) = 52 mm

Provide wall thickness at Bottom = 300 mm

Provide wall thickness at Top= 300 mm

Effecetive depth @ bottom = 254 mm

Area of Vertical steel required on water face

Diameter of bar provided = 12 mm

Effective depth of wall = 300-40-12/2 = d,eff = 254 mm

Mu/bd2= 7.29 x 1.5 x 1000000/(1000 x254^2)= 0.17

% of steel required pt,req = 0.039 %

Ast required = 0.039 x 1000 x 254 /100 Ast,req = 99.06 mm2


Cl:
Minimum percentage of steel required pt,min = 0.24 %
8.
1
of
IS
33
70
(p
Cl:
8.
1
of Min Area of steel required on each face = 0.24/100/2x1000x300 360 mm2/m
IS
33 Provide 12 mm dia tor steel at a spacing = 250 mm c/c
70
(p Area of steel provided = Ast,prov = 452.4 mm2/m
art
-
2): percentage of steel provided = 0.178 %
20
09 Area of Horizontal steel required on water face

Total Area of steel required for Axial tension = (Ast of Axial tension + Ast of Bending)

Ast, due to Axial Tension = T/(2 * 0.87*Fy) Ast, for Axial = 917.24 mm2/m

Diameter of bar provided = 12 mm

Effective depth of wall = 300-40-16- 12/2 = 238 mm

Mu/bd2= 3.21 x 1.5 x 1000000/(1000 x238^2)= 0.08

% of steel required 0.018 %

Ast required=0.018 x 1000 x 238 /100= 42.84 mm2

Total Area of steel required 960.08 mm2


Cl:
Minimum percentage of steel required = 0.24 %
8.
1
of Min Area of steel required on each face = 0.24/100/2x1000x300 360 mm2/m
IS
33 Provide 12 mm dia tor steel at a spacing = 200 mm c/c
70
(p Area of steel provided = 565.5 mm2/m
art
-
2): percentage of steel provided = 0.238 %
20
09

Check for shear

Max. Factored Shear Stress on the wall = 0.158 N/mm2

Percentage of steel provided = 0.399 %


Allowable shear stress = 0.452 N/mm2

OK

You might also like