Job : Comparison

Location : Mumbai
Space : Zone 2 BY ANUBHAVSAXENA
Unit in Ft. : W Length Area F/C Height Volume 16 Hours
Size : 0 0 269.19 10.76 2896 4.00pm Date :
Clean Room Class : NIL Out Side DB deg.F WB deg.F Drange %RH DP GR/LB
Filtration : 10 Micron Summer 96 83 32 60 0 92
Pressure Gradient : NIL Monsoon 85 82 88 162
Lighting Load : 0.9 Watts / Sq.ft. Room 71.58 61 55 0 64
Occupancy : 5 Nos. T : 24.42 32 Gr/Lb : 28
Equipment Load : 0.0 KW VENTILATION:
CFM / Person : 15 5 People 15 CFM/Per 75
Correction Factor : 12 269.19 Sq.ft. 10.76 HT. x 1 48
Coil By Pass Factor. : 0.1 Row Deep Coil. 4 Select : 75
Fresh Air Changes/Hr.: 1 Effective Room Sensible Heat Factor ( ERSHF ) :
Weight OF Wall: 60
Heatload for(summmer/monsoon) summer
Room Air Changes/Hr.: 1 48 CFM 9284 Effective Room Sensible Heat
= 0.90
Glasses Area In Sun Gain / Temp. 'U'Factor Heat 10355 Effective Room Total Heat
Sq.ft. In Deg. F Btu / Hr. Apparatus Dew Point. :( A.D.P.) Indicated = 54
Glass W 0.00 163 0.30 0 Selected = 61
Glass E 0.00 12 0.30 0 Dehumidified Rise =
Glass N 26.90 23 0.70 433 (1-B.F.) x (RM.TEMP- A.D.P.)
Glass S 26.90 12 0.70 226 0.90 x 10.58 = 9.522
Glass NW 0.00 138 0.30 0
Glass SW 0.00 85 0.30 0 Dehumidified CFM = 9284 (E.R.S.H.)
Glass NE 0.00 12 0.30 0 1.08 x 9.52 (Deh. Rise)
Glass SE 0.00 12 0.30 0

Walls Eq.Temp. Dehum. CFM = 903


Diff. : Supply Air CFM = 903
Wall W 176.44 37 0.28 1834
Wall E 0.00 30 0.28 0 Coil By Pass CFM = 0
Wall N 182.00 22 0.28 1121 CFM / Sq.ft. = 3.4
Wall S 182.00 35 0.28 1784 Sq.ft. / TR = 234
Wall NW 0.00 24 0.16 0 ROOM LATENT GAIN :
Wall SW 0.00 44 0.16 0 Infiltration 28 gr/lb 0.68 200
Wall NE 0.00 24 0.16 0 People 5 NO. X 175 Gain/Person 700
Wall SE 0.00 30 0.16 0 Steam Lb/Hr. X 1080 0
Roof SUN 269.19 40 0.09 0 Vap.Trans. 0 0.01 28 gr/lb 0
Roof SHA 0.00 20 0.40 0 Permeation Load
All Glass 53.80 29 0.47 744 ROOM LATENT HEAT SUBTOTAL: 900
Partition 0.00 19 0.30 0 Supply Duct Leackage Loss & Safty Factor : 5% 45
PartitionGl. 0.00 19.42 0.30 0 Out.Air 75 28 0.1 B.F. 0.68 126
Ceiling 0.00 19.42 0.02 0 EFFECTIVE ROOM LATENT HEAT : 1071
Floor 0.00 19.42 0.38 0 EFFECTIVE ROOM TOTAL HEAT : 10355
People 5 No. X 270 Gain/Person. 1350 Out Side Air Heat : T x (1 - B.F.) x Factor = BTU / Hr.
Eqp Load 0.00 No. X 3410 Gain/KW 0 Sensible 75 24.42 T 0.90 1.08 1780
Lights 247.65 Watts X 1 X 3.40 842 Latent 75 28 gr/lb 0.90 0.68 1285
Appliance 0.00 Watts X 3.40 0 GRAND TOTAL HEAT SUBTOTAL : 13420
Product Load Safety Factor : 0.03 403
ROOM SENSIBLE HEAT SUBTOTAL : 8334 Roof Sun 32 0 0
Supply Duct Heat Gain : 2% 0 0 0
Safety Factor : 5% Roof SHA 8 0 0
Fan Heat Gain : 5% 417 Ceiling 19.42 0 0
Out.Air 75 24.42 0.10 B.F. 1.08 198 GRAND TOTAL HEAT : 13823
Infiltration 335
EFFECTIVE ROOM SENSIBLE HEAT : 9284 LOAD TR : 1.2
ROOM SENSIBLE HEAT FACTOR : 0.90
GRAND ROOM SENSIBLE HEAT FACTOR : 0.67