Space Loads (From HAP)

Indoor Design Conditions Outdoor Design Conditions sensible load


Space Name
DB WB h DB WB h (Btu/hr)
78 64.9 29.9 89 73 36.5 30000
ace Loads (From HAP) Fan Heat and Total Cooling Coil
Ventialtion Air
Ventilation Load Duct Heat gain Load (BTU/hr)
Flow (cfm) (Btu/hr)
Latent load sensible load Latent load
(Btu/hr) (Btu/hr) (Btu/hr)
12000 423 5022 7533 2609 57163
Cooling Coil On Conditions (or) mixed air
Total Cooling Total Cooling FCU Discharge Supply Air conditions
Coil Sensible Coil Latent Load Temperature Flow (cfm)
Load (BTU/hr) (BTU/hr) (Deg F)
DB Enthalphy DP

37630 19533 55 1208 81.9 32.2 59.8


tions (or) mixed air Cooling Coil off Conditions Avialble Heat transfer
surface coefficient
area
HR RH (%) DB Enthalphy DP HR

0.0110 95.0 53.0 21.7 52.1 0.0083 40 10.5

`
Based on available coil Chilled Chilled
properties , Maximum water water
supply return
off coil enthalphy temp temp

-0.9990062112 40 50