Air System Sizing Summary for Security office

Project Name: VIP SIA PROJECT 07/29/2020


Prepared by: ZFP 03:07PM

Air System Information


Air System Name Security office Number of zones 1
Equipment Class UNDEF Floor Area 6.0 m²
Air System Type SZCAV Location Phnom Penh, Cambodia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.6 kW Load occurs at Aug 1600
Sensible coil load 0.3 kW OA DB / WB 36.4 / 28.3 °C
Coil L/s at Aug 1600 30 L/s Entering DB / WB 26.2 / 21.1 °C
Max block L/s 30 L/s Leaving DB / WB 16.5 / 16.1 °C
Sum of peak zone L/s 30 L/s Coil ADP 15.4 °C
Sensible heat ratio 0.621 Bypass Factor 0.100
m²/kW 10.6 Resulting RH 65 %
W/m² 93.9 Design supply temp. 14.4 °C
Water flow @ 5.6 °K rise 0.02 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 30 L/s Fan motor BHP 0.01 BHP
Standard L/s 30 L/s Fan motor kW 0.01 kW
Actual max L/(s-m²) 5.01 L/(s-m²) Fan static 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s 4 L/s L/s/person 4.30 L/s/person
L/(s-m²) 0.72 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 2


Space Design Load Summary for Security office
Project Name: VIP SIA PROJECT 07/29/2020
Prepared by: ZFP 03:07PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Security Office '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.4 °C / 28.3 °C HEATING OA DB / WB 18.9 °C / 12.9 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 6 m² 45 - 6 m² 9 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 6 m² 0 - 6 m² 0 -
Partitions 40 m² 0 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 113 W 109 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 60 W 59 - 0 0 -
People 1 63 35 0 0 0
Infiltration - 35 59 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 31 9 0% 0 0
>> Total Zone Loads - 343 104 - 9 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Security Office '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 6 0.681 - 45 - 9

Hourly Analysis Program v4.90 Page 2 of 2