Zone Load Summary Escalera P2 32 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 12.73 Btu/hr-ft2
Time at Peak: 6/21 16:45:00
Floor Area per Capacity: 78.5807
Outside ft2/kBtu-hr
DB: 91.8 F Outdoor Air Percentage: 0.00 %
HR: 0.0205 lb/lb Airflow per Floor Area: 0.563215
WB: 81.0 F ft3/min-ft2
Airflow per Capacity: 531.094491
Zone ft3/min-ton
DB: 76.0 F Number of People: 2.0
HR: 0.0089 lb/lb
RH: 46.5 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 506 - 506 2.6
Other - Roof - 0 - 0 0.0
Ceiling - -123 - -123 -0.6
Glass - Conduction 2,088 - - 2,088 10.6
Glass - Solar - 13,687 - 13,687 69.7
Door - 68 - 68 0.3
Wall - 955 - 955 4.9
Below-grade Wall - 0 - 0 0.0
Partition - -246 - -246 -1.3
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -2,085 - -2,085 -10.6
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 386 - 1,232 1,618 8.2
Subtotal 2,473 12,762 1,232 16,468 83.9

Internal Gains
People 350 442 400 1,192 6.1
Lights 1,364 0 - 1,364 7.0
Return Air - Lights 0 - - 0 0.0
Equipment 682 0 0 682 3.5
Subtotal 2,397 442 400 3,239 16.5

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -78 - -78 -0.4
Grand Total 4,870 13,127 1,632 19,629 100.0
Zone Load Summary EscaleraTerraza 33 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 13.37 Btu/hr-ft2
Time at Peak: 6/21 17:15:00
Floor Area per Capacity: 74.8015 ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.00 %
DB: 91.2 F Airflow per Floor Area: 0.501885
HR: 0.0205 lb/lb ft3/min-ft2
WB: 80.9 F Airflow per Capacity: 450.501765
ft3/min-ton
Zone Number of People: 1.0
DB: 76.0 F
HR: 0.0099 lb/lb
RH: 51.6 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 169 - 169 3.3
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 374 - - 374 7.4
Glass - Solar - 541 - 541 10.7
Door - 124 - 124 2.4
Wall - 1,527 - 1,527 30.1
Below-grade Wall - 0 - 0 0.0
Partition - 0 - 0 0.0
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 180 - 180 3.5
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 349 - 1,056 1,405 27.7
Subtotal 723 2,541 1,056 4,320 85.0

Internal Gains
People 175 164 200 539 10.6
Lights 175 0 - 175 3.4
Return Air - Lights 0 - - 0 0.0
Equipment 87 0 0 87 1.7
Subtotal 437 164 200 801 15.8

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -41 - -41 -0.8
Grand Total 1,161 2,664 1,255 5,080 100.0
Zone Load Summary Ofic1 1 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 48.86 Btu/hr-ft2
Time at Peak: 6/21 10:15:00
Floor Area per Capacity: 20.4671 ft2/kBtu-hr
Outside Outdoor Air Percentage: 13.32 %
DB: 89.1 F Airflow per Floor Area: 1.583854
HR: 0.0205 lb/lb ft3/min-ft2
WB: 80.4 F Airflow per Capacity: 389.003141
ft3/min-ton
Zone Number of People: 3.0
DB: 74.9 F
HR: 0.0106 lb/lb
RH: 57.2 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 285 - 285 6.2
Glass - Conduction 137 - - 137 3.0
Glass - Solar - 751 - 751 16.4
Door - -16 - -16 -0.4
Wall - 36 - 36 0.8
Below-grade Wall - 0 - 0 0.0
Partition - 73 - 73 1.6
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - -132 - -132 -2.9
Other - Floor - 0 - 0 0.0
Infiltration 13 - 41 54 1.2
Subtotal 150 997 41 1,188 26.0

Internal Gains
People 525 233 600 1,358 29.7
Lights 352 0 - 352 7.7
Return Air - Lights 0 - - 0 0.0
Equipment 480 0 0 480 10.5
Subtotal 1,356 233 600 2,189 47.8

Systems
Zone Ventilation 287 - 936 1,223 26.7
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 287 0 936 1,223 26.7

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -25 - -25 -0.5
Grand Total 1,793 1,205 1,577 4,575 100.0
Zone Load Summary Ofic2 2 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 50.54 Btu/hr-ft2
Time at Peak: 6/21 10:15:00
Floor Area per Capacity: 19.7864 ft2/kBtu-hr
Outside Outdoor Air Percentage: 10.54 %
DB: 89.1 F Airflow per Floor Area: 1.858833
HR: 0.0205 lb/lb ft3/min-ft2
WB: 80.4 F Airflow per Capacity: 441.355359
ft3/min-ton
Zone Number of People: 3.0
DB: 75.0 F
HR: 0.0102 lb/lb
RH: 55.3 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 572 - 572 9.9
Glass - Conduction 215 - - 215 3.7
Glass - Solar - 1,241 - 1,241 21.5
Door - -45 - -45 -0.8
Wall - 212 - 212 3.7
Below-grade Wall - 0 - 0 0.0
Partition - -105 - -105 -1.8
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - -240 - -240 -4.2
Other - Floor - 0 - 0 0.0
Infiltration 36 - 120 156 2.7
Subtotal 250 1,635 120 2,006 34.8

Internal Gains
People 525 322 600 1,447 25.1
Lights 428 0 - 428 7.4
Return Air - Lights 0 - - 0 0.0
Equipment 584 0 0 584 10.1
Subtotal 1,537 322 600 2,458 42.7

Systems
Zone Ventilation 304 - 1,027 1,331 23.1
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 304 0 1,027 1,331 23.1

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -34 - -34 -0.6
Grand Total 2,090 1,923 1,747 5,761 100.0
Zone Load Summary Gerencia General 14 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 54.34 Btu/hr-ft2
Time at Peak: 12/21 10:30:00
Floor Area per Capacity: 18.4040
Outside ft2/kBtu-hr
DB: 85.8 F Outdoor Air Percentage: 4.25 %
HR: 0.0202 lb/lb Airflow per Floor Area: 2.361732
WB: 79.3 F ft3/min-ft2
Airflow per Capacity: 521.584517
Zone ft3/min-ton
DB: 75.0 F Number of People: 5.0
HR: 0.0093 lb/lb
RH: 50.3 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -2,635 - -2,635 -13.5
Glass - Conduction 1,711 - - 1,711 8.8
Glass - Solar - 16,633 - 16,633 85.3
Door - -204 - -204 -1.0
Wall - -647 - -647 -3.3
Below-grade Wall - 0 - 0 0.0
Partition - -821 - -821 -4.2
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -2,309 - -2,309 -11.8
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 82 - 394 476 2.4
Subtotal 1,793 10,017 394 12,205 62.6

Internal Gains
People 875 2,066 1,000 3,941 20.2
Lights 673 0 - 673 3.5
Return Air - Lights 0 - - 0 0.0
Equipment 918 0 0 918 4.7
Subtotal 2,467 2,066 1,000 5,533 28.4

Systems
Zone Ventilation 374 - 1,807 2,181 11.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 374 0 1,807 2,181 11.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -419 - -419 -2.1
Grand Total 4,634 11,664 3,201 19,500 100.0
Zone Load Summary Secretaría 13 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 23.81 Btu/hr-ft2
Time at Peak: 6/21 10:30:00
Floor Area per Capacity: 41.9983
Outside ft2/kBtu-hr
DB: 89.5 F Outdoor Air Percentage: 9.29 %
HR: 0.0205 lb/lb Airflow per Floor Area: 0.897835
WB: 80.5 F ft3/min-ft2
Airflow per Capacity: 452.491503
Zone ft3/min-ton
DB: 75.0 F Number of People: 2.0
HR: 0.0100 lb/lb
RH: 54.0 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -250 - -250 -5.6
Glass - Conduction 211 - - 211 4.7
Glass - Solar - 1,392 - 1,392 31.0
Door - 5 - 5 0.1
Wall - 105 - 105 2.3
Below-grade Wall - 0 - 0 0.0
Partition - 352 - 352 7.8
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -219 - -219 -4.9
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 22 - 75 97 2.2
Subtotal 233 1,385 75 1,693 37.7

Internal Gains
People 350 264 400 1,014 22.6
Lights 354 0 - 354 7.9
Return Air - Lights 0 - - 0 0.0
Equipment 483 0 0 483 10.7
Subtotal 1,187 264 400 1,852 41.2

Systems
Zone Ventilation 225 - 753 978 21.7
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 225 0 753 978 21.7

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -27 - -27 -0.6
Grand Total 1,645 1,623 1,228 4,495 100.0
Zone Load Summary Ofic3 3 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 52.42 Btu/hr-ft2
Time at Peak: 5/21 10:00:00
Floor Area per Capacity: 19.0765 ft2/kBtu-hr
Outside Outdoor Air Percentage: 10.49 %
DB: 88.6 F Airflow per Floor Area: 1.937504
HR: 0.0207 lb/lb ft3/min-ft2
WB: 80.5 F Airflow per Capacity: 443.530468
ft3/min-ton
Zone Number of People: 3.0
DB: 75.0 F
HR: 0.0102 lb/lb
RH: 55.4 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 175 - 175 3.0
Glass - Conduction 211 - - 211 3.7
Glass - Solar - 1,219 - 1,219 21.3
Door - -43 - -43 -0.7
Wall - 194 - 194 3.4
Below-grade Wall - 0 - 0 0.0
Partition - 363 - 363 6.3
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - -213 - -213 -3.7
Other - Floor - 0 - 0 0.0
Infiltration 33 - 118 151 2.6
Subtotal 244 1,696 118 2,057 35.9

Internal Gains
People 525 288 600 1,413 24.6
Lights 410 0 - 410 7.2
Return Air - Lights 0 - - 0 0.0
Equipment 560 0 0 560 9.8
Subtotal 1,495 288 600 2,383 41.6

Systems
Zone Ventilation 288 - 1,035 1,323 23.1
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 288 0 1,035 1,323 23.1

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -30 - -30 -0.5
Grand Total 2,027 1,953 1,752 5,733 100.0
Zone Load Summary Auditorio 4 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 207.76 Btu/hr-ft2
Time at Peak: 11/21 10:00:00
Floor Area per Capacity: 4.8133 ft2/kBtu-hr
Outside Outdoor Air Percentage: 13.95 %
DB: 87.0 F Airflow per Floor Area: 6.988771
HR: 0.0219 lb/lb ft3/min-ft2
WB: 81.3 F Airflow per Capacity: 403.671173
ft3/min-ton
Zone Number of People: 60.0
DB: 74.9 F
HR: 0.0106 lb/lb
RH: 57.5 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 3,748 - 3,748 5.5
Glass - Conduction 2,884 - - 2,884 4.2
Glass - Solar - 23,835 - 23,835 35.0
Door - -373 - -373 -0.5
Wall - 265 - 265 0.4
Below-grade Wall - 0 - 0 0.0
Partition - -1,302 - -1,302 -1.9
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - -1,823 - -1,823 -2.7
Other - Floor - 0 - 0 0.0
Infiltration 184 - 814 998 1.5
Subtotal 3,068 24,350 814 28,233 41.5

Internal Gains
People 9,450 1,977 6,300 17,727 26.1
Lights 1,039 0 - 1,039 1.5
Return Air - Lights 0 - - 0 0.0
Equipment 1,117 0 0 1,117 1.6
Subtotal 11,606 1,977 6,300 19,883 29.2

Systems
Zone Ventilation 3,749 - 16,604 20,353 29.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 3,749 0 16,604 20,353 29.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -441 - -441 -0.6
Grand Total 18,423 25,886 23,718 68,027 100.0
Zone Load Summary Escalera PB 11 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 32.15 Btu/hr-ft2
Time at Peak: 6/21 16:45:00
Floor Area per Capacity: 31.1012 ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.00 %
DB: 91.8 F Airflow per Floor Area: 1.443185
HR: 0.0205 lb/lb ft3/min-ft2
WB: 81.0 F Airflow per Capacity: 538.618128
ft3/min-ton
Zone Number of People: 2.0
DB: 76.0 F
HR: 0.0088 lb/lb
RH: 46.2 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 770 - 770 5.4
Glass - Conduction 1,536 - - 1,536 10.8
Glass - Solar - 9,346 - 9,346 66.0
Door - -261 - -261 -1.8
Wall - 650 - 650 4.6
Below-grade Wall - 0 - 0 0.0
Partition - -785 - -785 -5.5
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - -189 - -189 -1.3
Other - Floor - 0 - 0 0.0
Infiltration 189 - 604 792 5.6
Subtotal 1,725 9,530 604 11,859 83.7

Internal Gains
People 350 232 400 982 6.9
Lights 902 0 - 902 6.4
Return Air - Lights 0 - - 0 0.0
Equipment 451 0 0 451 3.2
Subtotal 1,703 232 400 2,335 16.5

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -31 - -31 -0.2
Grand Total 3,428 9,731 1,004 14,162 100.0
Zone Load Summary Servicios PB 7 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 70.84 Btu/hr-ft2
Time at Peak: 10/21 18:00:00
Floor Area per Capacity: 14.1171 ft2/kBtu-hr
Outside Outdoor Air Percentage: 2.40 %
DB: 90.3 F Airflow per Floor Area: 3.227056
HR: 0.0221 lb/lb ft3/min-ft2
WB: 82.3 F Airflow per Capacity: 546.680343
ft3/min-ton
Zone Number of People: 1.0
DB: 75.0 F
HR: 0.0103 lb/lb
RH: 55.9 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -3 - -3 -0.4
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - 45 - 45 4.9
Wall - 157 - 157 16.9
Below-grade Wall - 0 - 0 0.0
Partition - 69 - 69 7.4
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - -20 - -20 -2.1
Other - Floor - 0 - 0 0.0
Infiltration 16 - 54 70 7.5
Subtotal 16 248 54 318 34.2

Internal Gains
People 175 149 200 524 56.3
Lights 22 0 - 22 2.4
Return Air - Lights 0 - - 0 0.0
Equipment 13 0 0 13 1.4
Subtotal 211 149 200 559 60.1

Systems
Zone Ventilation 13 - 42 55 5.9
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 13 0 42 55 5.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 -0.3
Grand Total 240 394 296 930 100.0
Zone Load Summary Escalera P1 22 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 17.20 Btu/hr-ft2
Time at Peak: 6/21 16:45:00
Floor Area per Capacity: 58.1562 ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.00 %
DB: 91.8 F Airflow per Floor Area: 0.754763
HR: 0.0205 lb/lb ft3/min-ft2
WB: 81.0 F Airflow per Capacity: 526.730571
ft3/min-ton
Zone Number of People: 2.0
DB: 76.0 F
HR: 0.0089 lb/lb
RH: 46.8 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 880 - 880 4.9
Glass - Conduction 2,232 - - 2,232 12.5
Glass - Solar - 15,940 - 15,940 89.2
Door - -216 - -216 -1.2
Wall - 937 - 937 5.2
Below-grade Wall - 0 - 0 0.0
Partition - -1,595 - -1,595 -8.9
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -4,052 - -4,052 -22.7
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 396 - 1,258 1,654 9.3
Subtotal 2,628 11,894 1,258 15,779 88.3

Internal Gains
People 350 49 400 799 4.5
Lights 868 0 - 868 4.9
Return Air - Lights 0 - - 0 0.0
Equipment 434 0 0 434 2.4
Subtotal 1,653 49 400 2,102 11.8

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -20 - -20 -0.1
Grand Total 4,280 11,923 1,658 17,861 100.0
Zone Load Summary Sala de Reuniones 15 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 83.52 Btu/hr-ft2
Time at Peak: 12/21 10:30:00
Floor Area per Capacity: 11.9737 ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.81 %
DB: 85.8 F Airflow per Floor Area: 3.522174
HR: 0.0202 lb/lb ft3/min-ft2
WB: 79.3 F Airflow per Capacity: 506.080729
ft3/min-ton
Zone Number of People: 6.0
DB: 75.0 F
HR: 0.0094 lb/lb
RH: 51.0 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -2,452 - -2,452 -13.6
Glass - Conduction 1,583 - - 1,583 8.8
Glass - Solar - 18,281 - 18,281 101.1
Door - -366 - -366 -2.0
Wall - -1,035 - -1,035 -5.7
Below-grade Wall - 0 - 0 0.0
Partition - -1,201 - -1,201 -6.6
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -4,655 - -4,655 -25.7
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 77 - 366 443 2.5
Subtotal 1,660 8,573 366 10,600 58.6

Internal Gains
People 1,050 2,732 1,200 4,982 27.5
Lights 480 0 - 480 2.7
Return Air - Lights 0 - - 0 0.0
Equipment 369 0 0 369 2.0
Subtotal 1,900 2,732 1,200 5,832 32.2

Systems
Zone Ventilation 382 - 1,821 2,203 12.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 382 0 1,821 2,203 12.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -547 - -547 -3.0
Grand Total 3,942 10,757 3,387 18,087 100.0
Zone Load Summary Servicio P2 28 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 299.62 Btu/hr-ft2
Time at Peak: 9/21 18:30:00
Floor Area per Capacity: 3.3376 ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.27 %
DB: 90.9 F Airflow per Floor Area: 14.060742
HR: 0.0227 lb/lb ft3/min-ft2
WB: 83.0 F Airflow per Capacity: 563.143756
ft3/min-ton
Zone Number of People: 1.0
DB: 75.0 F
HR: 0.0101 lb/lb
RH: 54.8 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -100 - -100 -11.0
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -304 - -304 -33.6
Wall - 51 - 51 5.6
Below-grade Wall - 0 - 0 0.0
Partition - -621 - -621 -68.8
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -171 - -171 -19.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 17 - 57 74 8.2
Subtotal 17 -1,145 57 -1,071 -118.6

Internal Gains
People 175 1,590 200 1,965 217.6
Lights 3 0 - 3 0.3
Return Air - Lights 0 - - 0 0.0
Equipment 2 0 0 2 0.2
Subtotal 179 1,590 200 1,969 218.1

Systems
Zone Ventilation 2 - 5 7 0.7
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 2 0 5 7 0.7

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 -0.2
Grand Total 198 443 262 903 100.0
Zone Load Summary Servicio P1 18 COOLING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 40.74 Btu/hr-ft2
Time at Peak: 9/21 18:15:00
Floor Area per Capacity: 24.5485
Outside ft2/kBtu-hr
DB: 91.3 F Outdoor Air Percentage: 2.05 %
HR: 0.0227 lb/lb Airflow per Floor Area: 1.789549
WB: 83.1 F ft3/min-ft2
Airflow per Capacity: 527.169166
Zone ft3/min-ton
DB: 75.0 F Number of People: 1.0
HR: 0.0103 lb/lb
RH: 55.5 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -3 - -3 -0.3
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - 49 - 49 5.1
Wall - 135 - 135 14.0
Below-grade Wall - 0 - 0 0.0
Partition - 62 - 62 6.4
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -8 - -8 -0.8
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 18 - 57 74 7.7
Subtotal 18 235 57 309 32.0

Internal Gains
People 175 198 200 573 59.4
Lights 20 0 - 20 2.1
Return Air - Lights 0 - - 0 0.0
Equipment 12 0 0 12 1.3
Subtotal 207 198 200 605 62.8

Systems
Zone Ventilation 12 - 40 52 5.4
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 12 0 40 52 5.4

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - -2 - -2 -0.2
Grand Total 237 431 297 965 100.0
Zone Load Summary Escalera P2 32 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -0.02 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.00 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 2.0
Zone
DB: 68.0 F
HR: 0.0123 lb/lb
RH: 84.2 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -197 - -197 590.2
Other - Roof - 0 - 0 0.0
Ceiling - -6 - -6 19.5
Glass - Conduction -200 - - -200 601.4
Glass - Solar - 0 - 0 0.0
Door - -8 - -8 24.6
Wall - -84 - -84 251.0
Below-grade Wall - 0 - 0 0.0
Partition - -67 - -67 201.8
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 128 - 128 -383.3
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 34 - 362 396 -1,189.2
Subtotal -166 -234 362 -39 116.0

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 5 - 5 -16.0
Grand Total -166 -229 362 -33 100.0
Zone Load Summary EscaleraTerraza 33 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.05 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: 21251.3410
Outside ft2/kBtu-hr
DB: 69.4 F Outdoor Air Percentage: 0.00 %
HR: 0.0156 lb/lb Airflow per Floor Area: 0.000000
WB: 69.4 F ft3/min-ft2
Airflow per Capacity: 0.000000
Zone ft3/min-ton
DB: 68.0 F Number of People: 1.0
HR: 0.0138 lb/lb
RH: 94.4 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - -100 - -100 -557.3
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 16 - - 16 88.5
Glass - Solar - 0 - 0 0.0
Door - -17 - -17 -93.5
Wall - -102 - -102 -572.5
Below-grade Wall - 0 - 0 0.0
Partition - 0 - 0 0.0
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 7 - 7 38.7
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 31 - 180 211 1,181.3
Subtotal 47 -212 180 15 85.3

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 3 - 3 14.7
Grand Total 47 -209 180 18 100.0
Zone Load Summary Ofic1 1 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.03 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: 30494.3700
Outside ft2/kBtu-hr
DB: 69.4 F Outdoor Air Percentage: 13.32 %
HR: 0.0156 lb/lb Airflow per Floor Area: 0.000000
WB: 69.4 F ft3/min-ft2
Airflow per Capacity: 0.000000
Zone ft3/min-ton
DB: 70.0 F Number of People: 3.0
HR: 0.0129 lb/lb
RH: 82.0 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -28 - -28 -911.1
Glass - Conduction -14 - - -14 -444.4
Glass - Solar - 0 - 0 0.0
Door - -8 - -8 -255.6
Wall - -6 - -6 -200.0
Below-grade Wall - 0 - 0 0.0
Partition - -38 - -38 -1,244.4
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 15 - 15 503.3
Other - Floor - 0 - 0 0.0
Infiltration -1 - 12 11 361.1
Subtotal -14 -65 12 -67 -2,191.1

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -3 - 73 69 2,253.3
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -3 0 73 69 2,253.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 1 - 1 37.8
Grand Total -18 -64 84 3 100.0
Zone Load Summary Ofic2 2 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.05 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: 20124.7639
Outside ft2/kBtu-hr
DB: 69.4 F Outdoor Air Percentage: 10.54 %
HR: 0.0156 lb/lb Airflow per Floor Area: 0.000000
WB: 69.4 F ft3/min-ft2
Airflow per Capacity: 0.000000
Zone ft3/min-ton
DB: 70.0 F Number of People: 3.0
HR: 0.0130 lb/lb
RH: 82.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -62 - -62 -1,096.4
Glass - Conduction -22 - - -22 -391.6
Glass - Solar - 0 - 0 0.0
Door - -8 - -8 -138.6
Wall - -21 - -21 -367.5
Below-grade Wall - 0 - 0 0.0
Partition - -11 - -11 -198.8
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 18 - 18 309.0
Other - Floor - 0 - 0 0.0
Infiltration -2 - 32 30 530.1
Subtotal -24 -85 32 -77 -1,353.6

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -4 - 85 81 1,425.3
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -4 0 85 81 1,425.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 2 - 2 28.3
Grand Total -28 -83 117 6 100.0
Zone Load Summary Gerencia General 14 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -0.04 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.25 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 5.0
Zone
DB: 70.0 F
HR: 0.0122 lb/lb
RH: 77.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -126 - -126 823.7
Glass - Conduction -175 - - -175 1,142.9
Glass - Solar - 0 - 0 0.0
Door - -4 - -4 24.6
Wall - -32 - -32 212.1
Below-grade Wall - 0 - 0 0.0
Partition - 3 - 3 -20.3
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 25 - 25 -163.8
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -5 - 127 122 -795.5
Subtotal -180 -134 127 -187 1,223.4

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -7 - 175 168 -1,096.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -7 0 175 168 -1,096.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 4 - 4 -27.2
Grand Total -187 -130 301 -15 100.0
Zone Load Summary Secretaría 13 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -0.06 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 9.29 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 2.0
Zone
DB: 70.0 F
HR: 0.0119 lb/lb
RH: 76.2 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -46 - -46 419.8
Glass - Conduction -21 - - -21 188.3
Glass - Solar - 0 - 0 0.0
Door - -9 - -9 80.2
Wall - -10 - -10 92.6
Below-grade Wall - 0 - 0 0.0
Partition - -63 - -63 574.1
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 16 - 16 -149.1
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -1 - 27 26 -234.6
Subtotal -22 -112 27 -107 971.3

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -4 - 98 95 -855.6
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -4 0 98 95 -855.6

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 2 - 2 -15.7
Grand Total -26 -111 125 -11 100.0
Zone Load Summary Ofic3 3 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.08 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: 12094.5790
Outside ft2/kBtu-hr
DB: 69.4 F Outdoor Air Percentage: 10.49 %
HR: 0.0156 lb/lb Airflow per Floor Area: 0.000000
WB: 69.4 F ft3/min-ft2
Airflow per Capacity: 0.000000
Zone ft3/min-ton
DB: 70.0 F Number of People: 3.0
HR: 0.0133 lb/lb
RH: 84.8 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -16 - -16 -177.4
Glass - Conduction -23 - - -23 -249.1
Glass - Solar - 0 - 0 0.0
Door - -9 - -9 -94.3
Wall - -20 - -20 -222.6
Below-grade Wall - 0 - 0 0.0
Partition - -32 - -32 -358.5
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 16 - 16 173.6
Other - Floor - 0 - 0 0.0
Infiltration -1 - 26 25 277.4
Subtotal -24 -61 26 -59 -650.9

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -4 - 71 67 736.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -4 0 71 67 736.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 1 - 1 14.7
Grand Total -28 -60 97 9 100.0
Zone Load Summary Auditorio 4 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.08 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: 12846.4027
Outside ft2/kBtu-hr
DB: 69.4 F Outdoor Air Percentage: 13.95 %
HR: 0.0156 lb/lb Airflow per Floor Area: 0.064711
WB: 69.4 F ft3/min-ft2
Airflow per Capacity: 9975.635543
Zone ft3/min-ton
DB: 70.0 F Number of People: 60.0
HR: 0.0130 lb/lb
RH: 83.0 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -51 - -51 -200.8
Glass - Conduction -319 - - -319 -1,253.0
Glass - Solar - 0 - 0 0.0
Door - -8 - -8 -32.1
Wall - -78 - -78 -306.6
Below-grade Wall - 0 - 0 0.0
Partition - 7 - 7 28.9
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 60 - 60 233.6
Other - Floor - 0 - 0 0.0
Infiltration -10 - 191 182 712.9
Subtotal -329 -71 191 -208 -817.1

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -12 - 240 228 893.7
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -12 0 240 228 893.7

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 6 - 6 23.4
Grand Total -341 -65 431 25 100.0
Zone Load Summary Escalera PB 11 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.00 Btu/hr-ft2
Time at Peak: null
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.00 %
DB: null F Airflow per Floor Area: 0.000000
HR: null lb/lb ft3/min-ft2
WB: null F Airflow per Capacity: null ft3/min-ton
Number of People: 2.0
Zone
DB: null F
HR: null lb/lb
RH: null %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - - - 0 -
Other - Roof - - - 0 -
Ceiling - - - 0 -
Glass - Conduction - - - 0 -
Glass - Solar - - - 0 -
Door - - - 0 -
Wall - - - 0 -
Below-grade Wall - - - 0 -
Partition - - - 0 -
Other - Wall - - - 0 -
Exterior Floor - - - 0 -
Interior Floor - - - 0 -
Slab - - - 0 -
Other - Floor - - - 0 -
Infiltration - - - 0 -
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 -
Lights - - - 0 -
Return Air - Lights - - - 0 -
Equipment - - - 0 -
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation - - - 0 -
Transfer Air - - - 0 -
DOAS Direct to Zone - - - 0 -
Return Air - Other 0 - - 0 -
Power Generation Equipment - - - 0 -
Refrigeration - - - 0 -
Water Use Equipment - - - 0 -
HVAC Equipment Loss - - - 0 -
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 -
Time Delay Correction - 0 - 0 -
Grand Total 0 0 0 0 -
Zone Load Summary Servicios PB 7 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -0.23 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 2.40 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0119 lb/lb
RH: 75.7 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -1 - -1 44.4
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -12 - -12 377.8
Wall - -8 - -8 255.6
Below-grade Wall - 0 - 0 0.0
Partition - -16 - -16 511.1
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 2 - 2 -74.4
Other - Floor - 0 - 0 0.0
Infiltration -1 - 18 17 -556.7
Subtotal -1 -34 18 -17 557.8

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -0 - 14 14 -443.3
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -0 0 14 14 -443.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 -14.4
Grand Total -1 -34 32 -3 100.0
Zone Load Summary Escalera P1 22 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: 0.02 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: 52395.5138
Outside ft2/kBtu-hr
DB: 69.4 F Outdoor Air Percentage: 0.00 %
HR: 0.0156 lb/lb Airflow per Floor Area: 0.000000
WB: 69.4 F ft3/min-ft2
Airflow per Capacity: 0.000000
Zone ft3/min-ton
DB: 68.0 F Number of People: 2.0
HR: 0.0142 lb/lb
RH: 96.4 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -93 - -93 -471.6
Glass - Conduction -237 - - -237 -1,194.5
Glass - Solar - 0 - 0 0.0
Door - 27 - 27 136.1
Wall - -102 - -102 -516.4
Below-grade Wall - 0 - 0 0.0
Partition - 88 - 88 444.6
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 136 - 136 688.5
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 36 - 163 198 1,001.2
Subtotal -201 56 163 17 88.0

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 0 - 0 0 0.0
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 0 0 0.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 2 - 2 12.0
Grand Total -201 58 163 20 100.0
Zone Load Summary Sala de Reuniones 15 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -0.14 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 4.81 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 6.0
Zone
DB: 70.0 F
HR: 0.0117 lb/lb
RH: 74.8 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -92 - -92 304.3
Glass - Conduction -165 - - -165 546.4
Glass - Solar - 0 - 0 0.0
Door - -6 - -6 20.4
Wall - -27 - -27 89.4
Below-grade Wall - 0 - 0 0.0
Partition - -9 - -9 29.4
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 20 - 20 -65.4
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -5 - 135 130 -431.1
Subtotal -170 -114 135 -149 493.3

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -4 - 119 115 -381.7
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -4 0 119 115 -381.7

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 4 - 4 -11.7
Grand Total -174 -111 254 -30 100.0
Zone Load Summary Servicio P2 28 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -9.95 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 0.27 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0090 lb/lb
RH: 57.9 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -9 - -9 30.7
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -19 - -19 62.6
Wall - -8 - -8 26.2
Below-grade Wall - 0 - 0 0.0
Partition - -28 - -28 92.2
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - -0 - -0 1.1
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -1 - 31 31 -101.9
Subtotal -1 -64 31 -33 110.8

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 0 - 3 3 -9.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 0 0 3 3 -9.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 -1.6
Grand Total -1 -63 34 -30 100.0
Zone Load Summary Servicio P1 18 HEATING

CONDITIONS AT TIME OF PEAK ENGINEERING CHECKS


Capacity per Floor Area: -0.44 Btu/hr-ft2
Time at Peak: 2/21 24:00:00
Floor Area per Capacity: null ft2/kBtu-hr
Outside Outdoor Air Percentage: 2.05 %
DB: 69.4 F Airflow per Floor Area: 0.000000
HR: 0.0156 lb/lb ft3/min-ft2
WB: 69.4 F Airflow per Capacity: null ft3/min-ton
Number of People: 1.0
Zone
DB: 70.0 F
HR: 0.0109 lb/lb
RH: 69.5 %

Instant Sensible [Btu/hr] Delayed Sensible [Btu/hr] Latent [Btu/hr] Total [Btu/hr] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -5 - -5 48.9
Glass - Conduction 0 - - 0 0.0
Glass - Solar - 0 - 0 0.0
Door - -15 - -15 143.3
Wall - -9 - -9 81.4
Below-grade Wall - 0 - 0 0.0
Partition - -21 - -21 202.0
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 2 - 2 -14.3
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration -1 - 22 22 -207.8
Subtotal -1 -48 22 -27 253.4

Internal Gains
People 0 0 0 0 0.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation -0 - 16 16 -148.2
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal -0 0 16 16 -148.2

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 1 - 1 -5.2
Grand Total -1 -48 38 -10 100.0