System Load Summary AHU 00 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 2910.000 l/s
Time at Peak: 4/21 15:00:00
Ventilation: 20.760 l/s
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 17.82 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 42.530174 l/s-kW
Return: 23.9 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 9,187 - 9,187 13.4
Glass - Conduction 3,081 - - 3,081 4.5
Glass - Solar - 1,032 - 1,032 1.5
Door - 936 - 936 1.4
Wall - 3,925 - 3,925 5.7
Below-grade Wall - 0 - 0 0.0
Partition - 2,179 - 2,179 3.2
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 1,380 - 244 1,625 2.4
Subtotal 4,461 17,258 244 21,964 32.1

Internal Gains
People 9,384 504 12,563 22,451 32.8
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 9,384 504 12,563 22,451 32.8

Systems
Zone Ventilation 9,600 - 1,540 11,140 16.3
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 4,830 - - 4,830 7.1
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 14,430 0 1,540 15,969 23.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 8,038 - 8,038 11.7
Grand Total 28,275 25,800 14,346 68,422 100.0
System Load Summary AHU 04 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 2290.000 l/s
Time at Peak: 4/21 15:00:00
Ventilation: 20.760 l/s
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 22.66 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 39.143419 l/s-kW
Return: 23.9 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - -2,167 - -2,167 -3.7
Glass - Conduction 3,420 - - 3,420 5.8
Glass - Solar - 9,004 - 9,004 15.4
Door - -33 - -33 -0.1
Wall - 1,164 - 1,164 2.0
Below-grade Wall - 0 - 0 0.0
Partition - -1,249 - -1,249 -2.1
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 1,417 - 209 1,626 2.8
Subtotal 4,837 6,719 209 11,765 20.1

Internal Gains
People 9,384 3,289 12,563 25,236 43.1
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 9,384 3,289 12,563 25,236 43.1

Systems
Zone Ventilation 9,603 - 1,172 10,774 18.4
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 3,796 - - 3,796 6.5
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 13,399 0 1,172 14,571 24.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 6,932 - 6,932 11.8
Grand Total 27,620 16,940 13,943 58,503 100.0
System Load Summary AHU 03 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 2810.000 l/s
Time at Peak: 4/21 15:00:00
Ventilation: 20.760 l/s
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 18.47 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 42.143864 l/s-kW
Return: 23.9 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 7,601 - 7,601 11.4
Glass - Conduction 3,391 - - 3,391 5.1
Glass - Solar - 1,363 - 1,363 2.0
Door - 200 - 200 0.3
Wall - 3,785 - 3,785 5.7
Below-grade Wall - 0 - 0 0.0
Partition - 1,946 - 1,946 2.9
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 1,373 - 227 1,600 2.4
Subtotal 4,764 14,896 227 19,887 29.8

Internal Gains
People 9,384 738 12,563 22,685 34.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 9,384 738 12,563 22,685 34.0

Systems
Zone Ventilation 9,601 - 1,392 10,993 16.5
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 4,658 - - 4,658 7.0
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 14,259 0 1,392 15,651 23.5

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 8,454 - 8,454 12.7
Grand Total 28,406 24,088 14,182 66,676 100.0
System Load Summary AHU 01 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 2210.000 l/s
Time at Peak: 4/21 15:00:00
Ventilation: 20.760 l/s
Outside
DB: 0.5 C
HR: 27.8300 kg/kg
ENGINEERING CHECKS
WB: 35.1 C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 23.43 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 38.706984 l/s-kW
Return: 23.9 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 3,184 - - 3,184 5.6
Glass - Solar - 4,579 - 4,579 8.0
Door - 19 - 19 0.0
Wall - 2,084 - 2,084 3.6
Below-grade Wall - 0 - 0 0.0
Partition - -287 - -287 -0.5
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 1,405 - 177 1,582 2.8
Subtotal 4,590 6,395 177 11,162 19.5

Internal Gains
People 9,384 1,828 12,563 23,775 41.6
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 9,384 1,828 12,563 23,775 41.6

Systems
Zone Ventilation 9,605 - 933 10,538 18.5
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 3,673 - - 3,673 6.4
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 13,277 0 933 14,211 24.9

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 7,948 - 7,948 13.9
Grand Total 27,251 16,171 13,673 57,096 100.0
System Load Summary AHU 02 COOLING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 3200.000 l/s
Time at Peak: 4/21 10:00:00
Ventilation: 20.760 l/s
Outside
DB: 0.5 C
HR: 27.4100 kg/kg
ENGINEERING CHECKS
WB: 33.3 C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 16.22 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 45.243588 l/s-kW
Return: 23.9 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 12.8 C
Fan Heat TD: 1.3 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - 0 - 0 0.0
Other - Roof - 0 - 0 0.0
Ceiling - 0 - 0 0.0
Glass - Conduction 3,555 - - 3,555 5.0
Glass - Solar - 0 - 0 0.0
Door - 673 - 673 1.0
Wall - 11,085 - 11,085 15.7
Below-grade Wall - 0 - 0 0.0
Partition - 9,378 - 9,378 13.3
Other - Wall - 0 - 0 0.0
Exterior Floor - 0 - 0 0.0
Interior Floor - 0 - 0 0.0
Slab - 0 - 0 0.0
Other - Floor - 0 - 0 0.0
Infiltration 1,001 - 223 1,225 1.7
Subtotal 4,557 21,136 223 25,916 36.6

Internal Gains
People 9,384 0 12,563 21,947 31.0
Lights 0 0 - 0 0.0
Return Air - Lights 0 - - 0 0.0
Equipment 0 0 0 0 0.0
Subtotal 9,384 0 12,563 21,947 31.0

Systems
Zone Ventilation 7,382 - 1,692 9,074 12.8
Transfer Air 0 - 0 0 0.0
DOAS Direct to Zone 0 - 0 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 5,306 - - 5,306 7.5
Power Generation Equipment 0 0 - 0 0.0
Refrigeration 0 - 0 0 0.0
Water Use Equipment 0 - 0 0 0.0
HVAC Equipment Loss 0 0 - 0 0.0
Subtotal 12,687 0 1,692 14,379 20.3

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 8,486 - 8,486 12.0
Grand Total 26,628 29,622 14,478 70,728 100.0
System Load Summary AHU 00 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 l/s
Time at Peak: null
Ventilation: null l/s
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 17.82 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 0.000000 l/s-kW
Return: 0.0 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 631,812 - 400,500,608 401,132,420 100.0
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 631,812 0 400,500,608 401,132,420 100.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 631,812 0 400,500,608 401,132,420 100.0
System Load Summary AHU 04 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 l/s
Time at Peak: null
Ventilation: null l/s
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 22.66 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 0.000000 l/s-kW
Return: 0.0 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 631,749 - 400,460,573 401,092,322 100.0
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 631,749 0 400,460,573 401,092,322 100.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 631,749 0 400,460,573 401,092,322 100.0
System Load Summary AHU 03 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 l/s
Time at Peak: null
Ventilation: null l/s
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 18.47 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 0.000000 l/s-kW
Return: 0.0 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 631,749 - 400,460,573 401,092,322 100.0
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 631,749 0 400,460,573 401,092,322 100.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 631,749 0 400,460,573 401,092,322 100.0
System Load Summary AHU 01 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 l/s
Time at Peak: null
Ventilation: null l/s
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 23.43 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 0.000000 l/s-kW
Return: 0.0 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 631,749 - 400,460,573 401,092,322 100.0
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 631,749 0 400,460,573 401,092,322 100.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 631,749 0 400,460,573 401,092,322 100.0
System Load Summary AHU 02 HEATING

CONDITIONS AT TIME OF PEAK AIRFLOWS


Main Fan: 0.000 l/s
Time at Peak: null
Ventilation: null l/s
Outside
DB: 0.0 C
HR: null kg/kg
ENGINEERING CHECKS
WB: null C Capacity per Floor Area: null W/m2
Floor Area per Capacity: 0.0000 m2/kW
Outdoor Air Percentage: 16.22 %
TEMPERATURES Airflow per Floor Area: null l/s-m2
Airflow per Capacity: 0.000000 l/s-kW
Return: 0.0 C Number of People: 171.6
Mixed Air: 0.0 C
Supply: 0.0 C
Fan Heat TD: 0.0 °C

Instant Sensible [W] Delayed Sensible [W] Latent [W] Total [W] Percent of Total [%]

Envelope
Roof - - - 0 0.0
Other - Roof - - - 0 0.0
Ceiling - - - 0 0.0
Glass - Conduction - - - 0 0.0
Glass - Solar - - - 0 0.0
Door - - - 0 0.0
Wall - - - 0 0.0
Below-grade Wall - - - 0 0.0
Partition - - - 0 0.0
Other - Wall - - - 0 0.0
Exterior Floor - - - 0 0.0
Interior Floor - - - 0 0.0
Slab - - - 0 0.0
Other - Floor - - - 0 0.0
Infiltration - - - 0 0.0
Subtotal 0 0 0 0 0.0

Internal Gains
People - - - 0 0.0
Lights - - - 0 0.0
Return Air - Lights - - - 0 0.0
Equipment - - - 0 0.0
Subtotal 0 0 0 0 0.0

Systems
Zone Ventilation 631,749 - 400,460,573 401,092,322 100.0
Transfer Air - - - 0 0.0
DOAS Direct to Zone - - - 0 0.0
Return Air - Other 0 - - 0 0.0
Supply Fan Heat 0 - - 0 0.0
Power Generation Equipment - - - 0 0.0
Refrigeration - - - 0 0.0
Water Use Equipment - - - 0 0.0
HVAC Equipment Loss - - - 0 0.0
Subtotal 631,749 0 400,460,573 401,092,322 100.0

Total
Sizing Factor Adjustment 0 - - 0 0.0
Time Delay Correction - 0 - 0 0.0
Grand Total 631,749 0 400,460,573 401,092,322 100.0