HEAT LOAD CALCULATIONS

JOB NAME: FLOOR HT. :- 18'


SPACE FOR: SWITCH ROOM F / C HT. :- Estimated By: PAVNEET
SIZE: FLOOR: SIXTH FLOOR
AREA: 538.2 Sq ft 9688 Cu ft ESTIMATE FOR : SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 113 75 75
(Sq ft) (Btu/h.sq ft) ROOM 80 50 68
N - Glass 0.0 12 0.56 0 DIFFERENCE 33 XXXX XXXX XXXX 7
NE - Glass 0.0 12 0.56 0
E - Glass 0.0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0.0 12 0.56 0 5 People X 10 CFM/Person 50
S - Glass 0.0 12 0.56 0 9688 Cu ft X 1 Air change per hour 161
SW - Glass 0.0 120 0.56 0 CFM VENTILATION 161
W - Glass 0.0 160 0.56 0
NW - Glass 0.0 120 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 1.00
Sky light 0 Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 56 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 21.12 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 7881 CFM
N - Wall 0.0 29 0.38 0 NOTES
NE - Wall 0.0 30 0.38 0 Occupancy = 5 Nos
E - Wall 0.0 38 0.38 0 Lighting = 1.5 W/Sq ft
SE - Wall 0.0 38 0.36 0 Eq. Load = 48 KW
S - Wall 0.0 36 0.38 0 Height = 18 FT

SW - Wall 0.0 34 0.38 0 Load Summary


W - Wall 0.0 32 0.38 0

NW - Wall 0.0 26 0.38 0 Summer Load:


Roof Sun 0 55 0.12 0 TR = 16.28 TR
Roof Shaded 31 0 DEHUMIDIFIED CFM = 7881 CFM 19.7030298

TRANS. GAIN EXCEPT WALLS & ROOF

ITEM Area Temp. diff. U

(Sq ft) (°F) (Btu/h.sq ft) COMPENSATED TR:


All Glass 0.0 33 1.13 0 TR = 19.15 TR
Partition 750 4 0.38 1140 DEHUMIDIFIED CFM = 7881 CFM
Ceiling 538 4 0.41 883

Floor 538.2 4 0.41 883 20TR - 10.TR 2W+1S


INTERNAL HEAT GAIN
People 2 Nos X 245 490
Light 807 W X 1.25 3.41 3441
Eq. Load 48000 WX 3.41 163680
170516 CHECK FIGURES
OUTSIDE AIR Btu/h/ Sq ft = 362.9
CFM °F BF FACTOR CFM / Sq ft = 14.64
161 33 0.12 1.08 691 Sq ft / TR = 33
ROOM SENSIBLE HEAT (RSH) 171207 CFM/ TR = 484
Supply duct Supply duct Heat gain from 0
heat gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 8560

EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 179767 NOTE:- CAPACETY SELECTED 4.63 / 85 x 100 = 5.54 TR.
LATENT HEAT (15% ACCOUNTED FOR DERATION AT 45°c AMBIANT).
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
161 7 0.12 0.67 91
501
Supply duct leakage loss
Safety
+ factor % 5.0 25
EFFECTIVE ROOM LATENT HEAT (ERLH) 526
EFFECTIVE ROOM TOTAL HEAT (ERTH) 180293
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
161 33 0.88 1.08 5064
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
161 7 0.88 0.68 676
HEAT SUB TOTAL 186033
Return duct HP Pump + Dehum. & Pipe 5.0 9302
heat gain & loss (%)
TR 16.28 GRAND TOTAL HEAT 195335