EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 179767 NOTE:- CAPACETY SELECTED 4.63 / 85 x 100 = 5.54 TR.
LATENT HEAT (15% ACCOUNTED FOR DERATION AT 45°c AMBIANT).
People 2 Nos X 205 410
OUTSIDE AIR
CFM GR/LB BF FACTOR
161 7 0.12 0.67 91
501
Supply duct leakage loss
Safety
+ factor % 5.0 25
EFFECTIVE ROOM LATENT HEAT (ERLH) 526
EFFECTIVE ROOM TOTAL HEAT (ERTH) 180293
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
161 33 0.88 1.08 5064
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
161 7 0.88 0.68 676
HEAT SUB TOTAL 186033
Return duct HP Pump + Dehum. & Pipe 5.0 9302
heat gain & loss (%)
TR 16.28 GRAND TOTAL HEAT 195335