Professional Documents
Culture Documents
DR= 25 °F
OUTSIDE CONDITION
SUMMER
A Dry Bulb Temperature to= 113 °F ti=
B Wet Bulb Temperature 66 °F
C Relative Humidity
D Humidity Ratio 21 grains/lb
WINTER
A Dry Bulb Temperature 41 °F
ROOF TYPE: Roof with Suspended Ceiling and with Total Resistance of 4.480 hr-ft² °F/Btu may classified as
Roof Number 5 ( from ASHRAE GRP 158 2nd Edition Table 8.4 Roof Classification for Use with Table 8.2A) See Appendix A, page
CLTDt= 68 °F, Considering Roof Number 5 ( from ASHRAE GRP 158 2nd Edition Table 8.2A Cooling Load Temperature Di
CALCULATION TABLE -1
Sensible Heat gain For Exposed Roofs
qsr = Ur x Ar x CLTDrc- Eqn.1
PACU Net Area (Ar) U CLTDrc qsr
Factor
ZONE ROOM NAME ft2 Btu/hr.ft2.oF oF Btu/hr
1 Office Area 14,170.92 0.223 86.5 273,349.96
2 IT Room 96.84 0.223 86.5 1,868.00
Elevator Lobby 1 290.52 0.223 86.5 5,603.99
3
Elevator Lobby 2 204.44 0.223 86.5 3,943.55
Total Sensible Heat Gain Through Exposed Roofs 284,765.49
( from ASHRAE GRP 158 2nd Edition Table 8.5 Thrmal Properties and Code number Layers for Wall and Roof (see Appendix A, p
WALL TYPE: Walls and Principal material Code and Secondary wall gypsum board with the Total Resistance of 5.01 ft2hr F may
Wall Number 10 (form ASHRAE GRP 158 2nd Edition Table 8.6A Wall Types, Mass Located Inside Insulation, for Use with Table 8
CLTDt = for Wall No.10 at 1600 H (from ASHRAE GRP 2ndEdition Table 8.3A Cooling Load Temperature Difference
for Calculating Cooling Load from Sunlit Walls – 24 °N Latitude, July) (see Appendix A, page A.8
Direction N E S W
CLTDт 16 34 14 17
CALCULATION TABLE-3
Sensible Heat Gain For Glass
qsgc = Ug x Ag x CLTDgc – Eqn 6
Wall Net Area U
PACU
Facing (Ag) Factor
ZONE ROOM NAME ft2 Btu/hr.ft2.oF
1 Office Area N 988 0.67
E 33 0.67
S 988 0.67
W 387 0.67
2 IT Room - - -
3 Elevator Lobby 1 - - -
4 Elevator Lobby 2 - - -
Total Sensible (Transmission Heat Gain for the glass) Heat Gain For Exposed Walls
In an effort to reduce the number of tables, the CLTD/CLF method discussed in the 1989 Handbook of Fundamentals and its pr
in conjunction with maximum Solar Heat Gain Factors (SHGF) to predict solar cooling loads. Solar cooling loads obtained with t
of solar cooling load profiles dueto different latitudes, months and other factors. In order to more closely approximate cooling
fenestration, a new term Solar Cooling Load (SCL) is introduced.
The cooling load per square foot of unshaded fenestration due to solar radiation transmitted through and absorbed by the glas
Direction N E S W
SCL 36 42 29 152
CALCULATION TABLE-4
Solar Heat Gain for Glass
qsg = Asg x SCsg x SCLsg -Eqn.8
(from ASHRAE GRP 158 2nd Edition Table 8.5 Thermal Properties and Code number of Layers for Wall and Roof)
(see Appendix A, page A.12)
Calculating for Sensible heat gain for partition walls,
qsp= Up x Ap x TDp
qsp= U (Btu/hr-ft²-°F) x A(ft²) x TDp(°F) = Btu/hr– Eqn. (9)
Substituting the values to Calculate Table - 5 using Eqn. (9):
(Next Page)
CALCULATION TABLE -5
Sensible Heat Gain For Partition Floor
qsp = Up x Ap x TDp – Eqn. 9
Net Area U-VALUE (Up) TDp qspf
PACU
(Ap)
ZONE ROOM NAME ft2 Btu/hr.ft2.°F °F Btu/hr
1 Office Area 1275 0.272 13 4,508.61
2 IT Room 200 0.272 13 707.68
Elevator Lobby 1 665 0.272 13 2,351.33
3
Elevator Lobby 2 454 0.272 13 1,605.98
Total Sensible Heat Gain through Partition 9,173.60
3. Internal Loads
Internal Heat Gains
The component of the space cooling load is the heat that originates within the space. Typical sources of internal heat gain are p
lights, cooking processes and other heat-generating equipment, such as motors, appliances and office equipment.
The people inside the space contribute both sensible and latent heat. Lighting contributes only sensible heat to the space
,heat and latent heat (as in the case for a coffee maker). Infiltration generally contributes both sensible and latent heat to the s
while equipment in the space may contribute only sensible heat (as in the case for a computer) or both sensible
where:
qsl= Cooling Load due to lighting, Btu/hr
3.41= Conversion factor, Btu/hr-W
Watts = Total wattage of lighting fixture, watts
Since there is no lighting fixture given during this design stage, it was assumed that lighting load is equal to 2watt
Fu= Use factor, fraction of Watts in use
=1
Fs = Special allowance factor (Ballast factor in the case of fluorescent and metal halide fixtures)
= 1.2 (Recommended value for general applications)
CLF = Cooling load factor, (equal to “1” since cooling system operates when lights are ON)
Calculating for heat gain due to internal lightings,
qsl= 3.41 x Watts x Fu x Fs x CLF – Eqn. (11)
qsl= 3.41(Btu/hr-W) x Watts x Fu x Fs = Btu/hr
CALCULATION TABLE -6
Heat Gain due to Internal Lightings
qsl = 3.41 x Watts x Fu x Fs x CLF – Eqn 11
Net Lighting
PACU Area (A) Watts/Ft2 Btu/hr-W Power,Watts
ZONE ROOM ft2
1 Office Area 14,170.92 2 3.41 28,341.84
2 IT Room 96.84 2 3.41 193.68
Elevator Lobby 1 290.52 2 3.41 581.04
3
Elevator Lobby 2 204.44 2 3.41 408.88
Total Heat Gain due to Internal Lightings
CALCULATION TABLE -7
Sensible Heat Gain Of People
qspe = qspe’ x NP x CLF – Eqn 12
Net Area Number of Heat Gain CLF
PACU
(A) People Per Person
ZONE ROOM NAME ft2 (NP) BTU/hr
1 Office Area 14,170.92 99 250 1
2 IT Room 96.84 6 250 1
Elevator Lobby 1 290.52 9 250 1
3
Elevator Lobby 2 204.44 6 250 1
Total Sensible Heat Gain Of People
CALCULATION TABLE -8
Latent Heat Gain Of People
qlpe = qlpe’ x NP x CLF – Eqn 13
Nmber Heat Gain
PACU Net Area people Per Person CLF
(A) (NP) BTU/hr
ZONE ROOM NAME ft2
1 Office Area 14,170.92 99 200 1
2 IT Room 96.84 6 200 1
Elevator Lobby 1 290.52 9 200 1
3
Elevator Lobby 2 204.44 6 200 1
Total Latent Heat Gain Of People
CALCULATION TABLE-9
Sensible Heat Gain due to Appliances and Equipment
qse = 3.41 x Eqpt. Watts x CLF – Eqn 14
Airflow = Quantity of air infiltrating the space, ft³/min(Follow the same formula of Eqn. 16 and apply the correspond
Airflow = ACH x Space Volume ÷ 60 - Eqn. (16)
ΔWi = Dgrains of water/lb of dry air
= (Wo - Wi) = 21 – 65
= 44 grains of water/lb of dry air (Using Psychometric Chart to determine the
humidity ratio for both outdoor and indoor conditions)
Outside Design Temperatures: (Summer)
Dry Bulb Temperature = 113°F
Wet Bulb Temperature = 66°F
Inside Design Temperatures: (Summer)
Dry Bulb = 75°F
Relative Humidity= 50%
The result will be:
Wo = 21 grains of water/lb of dry air
Wi = 65 grains of water/lb of dry air
Applying the value from Eqn. (16) and the corresponding Difference of humidity ratios,
Then, Calculating for Latent heat gain due to infiltration,
qli= 0.7 x Airflow x Δwi, -Eqn. (17)
qli= 0.7(Btu-min-lb/hr-ft³-gr) x Airflow(ft³/min) x ΔWi(grains/lb) = Btu/hr
Substituting the values to Calculate Table 11 using Eqn. (17):
5. Miscellaneous Load
Miscellaneous Heat Gains
Other sources of heat gain within the HVAC System are fan, driven by an electric motor, and located in conditioned airstream,
it adds heat to the air. The author justifiably introduces a safety factor of 3 % to the total coil cooling load of this project to
compensate fans and ducts heat gains.
CALCULATION TABLE –A
Summary of Cooling Loads, Btu/hr
Sensible Heat
Item No. Load Description Loads (Btu/Hr) Loads (Btu/Hr)
1 Conduction through Roofs 284,765
2 Conduction through Walls 11,736
3 Conduction through Glass 52,169
4 Solar Radiation through Glass 73,435
5 Conduction through Partitions 9,174
6 Heat Gain for Lights 120,818
7 Heat Gain for People 30,000
8 Heat Gain for Equipment 111,506
9 Heat Gain for Infiltration 29,808
Total Space Cooling Loads
10 Ventilation 95,418
Total Coil Cooling Loads
Safety Factor and Miscellaneous (3%)
Grand Total Coil Cooling Loads
The term sensible heat ratio refers to the ratio obtained from dividing the room sensible heat gain by the total heat gain (sensib
SHR = ________Sensible Heat Gain_______ - Eqn. (20)
Sensible Heat Gain + Latent Heat Gain
Substituting the values for each Zone to Calculate Table C Eqn. 20:
CALCULATION TABLE -C
Sensible Heat Ratio
Sensible Heat Latent Heat Total Cooling
Load (Btu/Hr) Load (Btu/Hr) Loads (Btu/Hr)
with Safety with Safety with Safety SENSIBLE
PACU Factor 3% Factor 3% Factor HEAT RATIO
ZONE ROOM NAME
1 Office Area 784,442 105,326 889,768 0.88
2 IT Room 26,468 5,194 31,662 0.84
Elevator Lobby 1 19,271 6,590 25,861 0.75
3
Elevator Lobby 2 13,214 4,410 17,624 0.75
9. Supply Airflow
To determine the supply airflow, the following equation must be used:
Supply Airflow = Sensible Heat Gain n
1.08 x (Indoor Air DB – Supply Air DB) - Eqn. (21)
where: Supply Airflow = The total quantity of air required to offset the space sensible heat gain, cfm
1.08 = Product of air density and specific heat at standard condition, Btu-min/hr-ft³-°F
Indoor Air DB = Design space dry-bulb temperature, °F = 75 °F
Supply Air DB = Supply air dry-bulb temperature, °F = Tc + Tf
Where : Tc = Coil Leaving Temp = 55 °F (Normal)
Tf = Temp. rise across draw-thru fan
= 2.2 °F (from table D.3 Air Temp. Rise Due to Fans, of ASHRAE GRP 158 2nd Edition. Assume Fan static Pressur
= Supply Air Temperature = 55 + 2.2 = 57.2°F
Indoor Air DB - Supply Air DB = 75 – 57.2 = 17.8 °F
Substituting the values for each Zone to Calculate Table D - Eqn. (21)
CALCULATION TABLE -C
Supply Airflow, cfm
Supply Airflow= Sensible Heat Gain/ 1.08 x (Indoor Air db- Supply Air db)
Sensible Indoor Supply Temp. Diff Supply
PACU Heat Load Factor air DB Air DB (ΔT) °F Airflow
ZONE ROOM NAME Btu/hr cfm
1 Office Area 784,442 1.08 75 57.2 17.8 40,805.34
2 IT Room 26,468 1.08 75 57.2 17.8 1,376.80
Elevator Lobby 1 19,271 1.08 75 57.2 17.8 1,002.46
3
Elevator Lobby 2 13,214 1.08 75 57.2 17.8 687.37
Total Sen. Ht. Load 843,395 Total Supply Airflow 43,871.96
PACU-1 & 2 Cooling Coil Load Calculation Solving for Mixed Air Properties from:
TOTAL COOLING COIL LOAD:
QCC= m (h3-h4) m1h1 + m2h2 = m3h3
Where:
m = 60 x cfm/ v4 m1t1 + m2t2 = m3t3
= 60 x 21,936 cfm
14.16702 cu. Ft. / lb m1w1+ m2w2 = m3w3
= 92,903.09 lb/hr
h4 at pt. 4 = 23.6156 Btu/lb Solving for m1:
m1 = 60 x cfm1/v1
= 60 x 1,163 cfm
15.62363 cu. Ft./lb
= 4,466.31 lb/hr
75 °F 23.89 °C
62.5 °F 16.94 °C
50 %
65 grains/lb
72 °F 22.22 °C
Codenumber of Layers for Wall and Roof (see Appendix A, page A.3)
or Calculating Cooling Load from Flat Roofs- 24°Nlatitude, Julay
THERMAL CODE NO.
RESISTANCE
0.33 A0
0.08
0.06
0.00
0.76
2.56 C20
0.69 E0
4.48 hr-ft² °F/Btu
0.22 Btu/hr-f² °F
CLTDwc qsw
oF Btu/hr
34.5 4,544
52.5 230
32.5 4,280
35.5 1,834
35.5 848
-
-
11,736
x A, page A.9)
CLTDgc qsgc
oF Btu/hr
32.5 21,508.65
32.5 716.95
32.5 21,508.65
32.5 8,434.76
- -
- -
- -
52,169
n many ways to light. Both can pass through transparent materials such as glass.
ntrolled by installing venetian blinds, curtains or drapes.
ok of Fundamentals and its previous editions used Cooling Load Factors (CLFs)
cooling loads obtained with this method do not recognize the significant variation
e closely approximate cooling loads due to solar radiation transmitted through
qgs
Btu/hr
20,980.19
815.9
16,900.71
34,738.44
-
-
-
73,435.24
nsfer of heat through the separating section must be considered. The heat transfer rate is given by:
CODE NO.
E0
E1
C7
E1
E0
hr-ft2 °F/Btu
Btu/hr-ft2 F
Btu/hr
24,750.00
1,500.00
2,250.00
1,500.00
30,000.00
qlp
Btu/hr
19,800.00
1,200.00
1,800.00
1,200.00
24,000
CLF qse
Btu/hr
1 96,645.67
1 14,860.10
- -
- -
111,505.77
r Ventilation)
Airflow ΔWv qlv
(ft3/min) (grains/ (Btu/hr)
lb)
1980 44 60,984.00
120 44 3,696.00
135 44 4,158.00
90 44 2,772.00
71,610.00
ed in conditioned airstream,
ing load of this project to
71,610 167,028
936,811
28,104
964,915
by the total heat gain (sensible plus latent) and is defined as follows:
on. Assume Fan static Pressure of 4” and Fan and motor Combined efficiency of 65%) (see Appendix A, page A.16)
1 psi = 27.7076 in.of water
1 psi = 6895 Pa
1 psi = 2.03602 inch of mercury
1 Bar = 14.5038 psi
1 Bar = 100 kPa
40805.3
DESIGNATION
vator Lobby 2
Grand Total
Load
Btu/hr
889,768
31,662
25,861
17,624
964,915