AKD,NURSE STATION

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : SECOND Area : AKD & NURSE STATION System No. : 1
Floor Area 1432 Sq Ft Ceiling Ht 10 Ft Volume = 14320 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 128 23 0.81 2385 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 16 People X 0 CFM/Person 5.00
S - Glass 58 12 0.81 564 1432 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 166
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4022
No. of Rows = 0
N - Wall 444 19 0.36 3037 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 477
SE - Wall 33 0.36 0
S - Wall 240 31 0.36 2678
SW - Wall 29 0.36 0
W - Wall 270 27 0.36 2624
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 16 persons
ITEM Area Temp. diff. U FRESH AIR 477
(Sq ft) (°F) (Btu/h.sq ft) Light 2148 watt
All Glass 186 28 0.55 2864 Equipment 2148 watt
Glass Partition 88 23 0.55 1113
Partition 668 23 0.3 4609
Partition 23 0.35 0
Ceiling 27 23 0.45 279
Floor 131 23 0.45 1356
INTERNAL HEAT GAIN
People 16 Nos X 230 3680
Light 2148 W X 1.25 3.412 9161
Eq. Load 2148 W 3.412 28339
ROOM SENSIBLE HEAT (RSH) 62690
Supply duct heat Supply duct Heat gain from 2 1254
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 3135


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
477 28 0.12 1.08 1732
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 68811
LATENT HEAT
People 16 Nos X 120 1920
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
477 81.7 0.12 0.68 3182
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 5102
Supply duct leakage loss + Safety factor % 5.0 255
EFFECTIVE ROOM LATENT HEAT (ERLH) 5357
EFFECTIVE ROOM TOTAL HEAT (ERTH) 74168
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 477
477 28 0.88 1.08 12702 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 9.37
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 78.5 Monsoon TR= 9.42
477 81.7 0.88 0.68 23336 CFM / Sq ft = 2.81 Deh. CFM= 4022
HEAT SUB TOTAL 110207 Sq ft / TR = 153 CFM(ACPH)= 17
Return duct heat HP Pump + Dehum. & Pipe 2.0 2204
gain & leak. loss + loss (%) CFM/ TR = 429
Selected TR = 9.4
TONS 9.37 GRAND TOTAL HEAT 112411 Selected CFM= 4050
AKD,NURSE STATION
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 128 11 0.81 1140 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 16 People X 0 CFM/Person 5
S - Glass 58 11 0.81 517 1432 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 166
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3797
No. of Rows = 0
N - Wall 444 9 0.36 1439 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 477
SE - Wall 0 23 0.36 0
S - Wall 240 21 0.36 1814
SW - Wall 0 19 0.36 0
W - Wall 270 17 0.36 1652
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 186 26 0.5500 2660
Glass Partition 88 21 0.55 1016
Partition glass-NAC 668 21 0.30 4208
Partition wall-NAC 0 10 0.35 0
Ceiling 27 10 0.45 122
Floor 131 10 0.45 590
INTERNAL HEAT GAIN
People 16.0 Nos X 230 3680
Light 2148.0 W X 1.25 3.412 9129
Eq. Load 2148.0 WX 3.412 28339
ROOM SENSIBLE HEAT (RSH) 56306
Supply duct heat Supply duct Heat gain from 2 4223
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 2815
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
477 26 0.12 1.08 1608
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 64953
LATENT HEAT
People 16 Nos X 120 1920
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
477 99 0.12 0.68 3856
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 5776
EFFECTIVE ROOM TOTAL HEAT (ERTH) 70729
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
477 26 0.88 1.08 11795
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
477 99 0.88 0.68 28278
HEAT SUB TOTAL 110802
Return duct heat HP Pump + Dehum. & Pipe 2.0 2216
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 9.42 TR
TONS 9.42 TOTAL HEAT 113018
PASSAGE

GREEN AIR ROOM TYPE 3 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : SECOND Area : PASSAGE System No. : 1
Floor Area 120 Sq Ft Ceiling Ht 10 Ft Volume = 1200 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 23 0.81 0 DIFFERENCE 24 XXXX XXXX XXXX 72.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 1 People X 0 CFM/Person 7.00
S - Glass 29 12 0.81 282 120 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 14
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 215
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 40
SE - Wall 33 0.36 0
S - Wall 108 31 0.36 1205
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 1 persons
ITEM Area Temp. diff. U FRESH AIR 40
(Sq ft) (°F) (Btu/h.sq ft) Light 180 watt
All Glass 29 24 0.55 383 Equipment 180 watt
Glass Partition 19 0.55 0
Partition 64 19 0.3 365
Partition 19 0.35 0
Ceiling 19 0.45 0
Floor 28 19 0.45 239
INTERNAL HEAT GAIN
People 1 Nos X 230 230
Light 180 W X 1.25 3.412 768
Eq. Load 180 W 3.412 614
ROOM SENSIBLE HEAT (RSH) 4086
Supply duct heat Supply duct Heat gain from 2 82
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 204


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
40 24 0.12 1.08 124
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 4496
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
40 72.7 0.12 0.68 237
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 357
Supply duct leakage loss + Safety factor % 5.0 18
EFFECTIVE ROOM LATENT HEAT (ERLH) 375
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4872
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 40
40 24 0.88 1.08 912 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.64
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 64.0 Monsoon TR= 0.65
40 72.7 0.88 0.68 1740 CFM / Sq ft = 1.79 Deh. CFM= 215
HEAT SUB TOTAL 7524 Sq ft / TR = 188 CFM(ACPH)= 11
Return duct heat HP Pump + Dehum. & Pipe 2.0 150
gain & leak. loss + loss (%) CFM/ TR = 336
Selected TR = 0.7
TONS 0.64 GRAND TOTAL HEAT 7675 Selected CFM= 250
PASSAGE
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 0 11 0.81 0 DIFFERENCE 22 XXXX XXXX XXXX 90
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 1 People X 0 CFM/Person 7
S - Glass 29 11 0.81 258 120 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 14
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.91
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 193
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 40
SE - Wall 0 23 0.36 0
S - Wall 108 21 0.36 816
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 29 22 0.5500 351
Glass Partition 0 17 0.55 0
Partition glass-NAC 64 17 0.30 326
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 28 10 0.45 126
INTERNAL HEAT GAIN
People 1.0 Nos X 230 230
Light 180.0 W X 1.25 3.412 765
Eq. Load 180.0 WX 3.412 614
ROOM SENSIBLE HEAT (RSH) 3487
Supply duct heat Supply duct Heat gain from 5 262
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 174
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
40 22 0.12 1.08 114
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 4037
LATENT HEAT
People 1 Nos X 120 120
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
40 90 0.12 0.68 294
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 414
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4451
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
40 22 0.88 1.08 836
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
40 90 0.88 0.68 2154
HEAT SUB TOTAL 7442
Return duct heat HP Pump + Dehum. & Pipe 5.0 372
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.65 TR
TONS 0.65 TOTAL HEAT 7814
TFA-SINGLE UNIT

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : SECOND Area : TFA-SINGLE UNITS System No. : 1
Floor Area 1678 Sq Ft Ceiling Ht 10 Ft Volume = 16780 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 76 23 0.81 1416 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 53 People X 0 CFM/Person 5.00
S - Glass 35 12 0.81 340 1678 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 366
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.88
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4347
No. of Rows = 0
N - Wall 276 19 0.36 1888 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 559
SE - Wall 33 0.36 0
S - Wall 239 31 0.36 2667
SW - Wall 29 0.36 0
W - Wall 178 27 0.36 1730
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 53 persons
ITEM Area Temp. diff. U FRESH AIR 559
(Sq ft) (°F) (Btu/h.sq ft) Light 2517 watt
All Glass 111 28 0.55 1709 Equipment 2517 watt
Glass Partition 23 0.55 0
Partition 576 23 0.3 3974
Partition 23 0.35 0
Ceiling 81 23 0.45 838
Floor 50 23 0.45 518
INTERNAL HEAT GAIN
People 53 Nos X 230 12190
Light 2517 W X 1.25 3.412 10735
Eq. Load 2517 W 3.412 29598
ROOM SENSIBLE HEAT (RSH) 67604
Supply duct heat Supply duct Heat gain from 2 1352
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 3380


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
559 28 0.12 1.08 2030
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 74366
LATENT HEAT
People 53 Nos X 120 6360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
559 81.7 0.12 0.68 3729
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 10089
Supply duct leakage loss + Safety factor % 5.0 504
EFFECTIVE ROOM LATENT HEAT (ERLH) 10593
EFFECTIVE ROOM TOTAL HEAT (ERTH) 84959
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 559
559 28 0.88 1.08 14885 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 10.81
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 77.3 Monsoon TR= 11.11
559 81.7 0.88 0.68 27345 CFM / Sq ft = 2.59 Deh. CFM= 4347
HEAT SUB TOTAL 127189 Sq ft / TR = 155 CFM(ACPH)= 16
Return duct heat HP Pump + Dehum. & Pipe 2.0 2544
gain & leak. loss + loss (%) CFM/ TR = 402
Selected TR = 11.1
TONS 10.81 GRAND TOTAL HEAT 129733 Selected CFM= 4350
TFA-SINGLE UNIT
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 76 11 0.81 677 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 53 People X 0 CFM/Person 5
S - Glass 35 11 0.81 312 1678 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 366
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.87
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4258
No. of Rows = 0
N - Wall 276 9 0.36 894 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 559
SE - Wall 0 23 0.36 0
S - Wall 239 21 0.36 1807
SW - Wall 0 19 0.36 0
W - Wall 178 17 0.36 1089
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 111 26 0.5500 1587
Glass Partition 0 21 0.55 0
Partition glass-NAC 576 21 0.30 3629
Partition wall-NAC 0 10 0.35 0
Ceiling 81 10 0.45 365
Floor 50 10 0.45 225
INTERNAL HEAT GAIN
People 53.0 Nos X 230 12190
Light 2517.0 W X 1.25 3.412 10697
Eq. Load 2517.0 WX 3.412 29598
ROOM SENSIBLE HEAT (RSH) 63070
Supply duct heat Supply duct Heat gain from 2 4730
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 3154
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
559 26 0.12 1.08 1885
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 72839
LATENT HEAT
People 53 Nos X 120 6360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
559 99 0.12 0.68 4519
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 10879
EFFECTIVE ROOM TOTAL HEAT (ERTH) 83717
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
559 26 0.88 1.08 13821
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
559 99 0.88 0.68 33136
HEAT SUB TOTAL 130674
Return duct heat HP Pump + Dehum. & Pipe 2.0 2613
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 11.11 TR
TONS 11.11 TOTAL HEAT 133288
CORRIDOR

GREEN AIR ROOM TYPE 3 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : SECOND Area : CORRIDOR System No. : 1
Floor Area 2381 Sq Ft Ceiling Ht 10 Ft Volume = 23810 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 58 23 0.81 1081 DIFFERENCE 24 XXXX XXXX XXXX 72.7
NE - Glass 12 0.81 0
E -GLASS 58 12 0.81 564 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 50 People X 0 CFM/Person 7.00
S - Glass 151 12 0.81 1468 2381 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 493
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.87
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3449
No. of Rows = 0
N - Wall 201 19 0.36 1375 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 222 33 0.36 2637 'Min. cfm reqd. = 794
SE - Wall 33 0.36 0
S - Wall 493 31 0.36 5502
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 50 persons
ITEM Area Temp. diff. U FRESH AIR 794
(Sq ft) (°F) (Btu/h.sq ft) Light 3572 watt
All Glass 267 24 0.55 3524 Equipment 3572 watt
Glass Partition 354 19 0.55 3699
Partition 1027 19 0.3 5854
Partition 19 0.35 0
Ceiling 19 0.45 0
Floor 55 19 0.45 470
INTERNAL HEAT GAIN
People 50 Nos X 230 11500
Light 3572 W X 1.25 3.412 15232
Eq. Load 3572 W 3.412 12186
ROOM SENSIBLE HEAT (RSH) 65092
Supply duct heat Supply duct Heat gain from 2 1302
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 3255


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
794 24 0.12 1.08 2469
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 72117
LATENT HEAT
People 50 Nos X 120 6000
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
794 72.7 0.12 0.68 4708
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 10708
Supply duct leakage loss + Safety factor % 5.0 535
EFFECTIVE ROOM LATENT HEAT (ERLH) 11244
EFFECTIVE ROOM TOTAL HEAT (ERTH) 83361
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 794
794 24 0.88 1.08 18103 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 11.56
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 58.3 Monsoon TR= 12.28
794 72.7 0.88 0.68 34527 CFM / Sq ft = 1.45 Deh. CFM= 3449
HEAT SUB TOTAL 135992 Sq ft / TR = 206 CFM(ACPH)= 9
Return duct heat HP Pump + Dehum. & Pipe 2.0 2720
gain & leak. loss + loss (%) CFM/ TR = 298
Selected TR = 12.3
TONS 11.56 GRAND TOTAL HEAT 138712 Selected CFM= 3450
CORRIDOR
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 58 11 0.81 517 DIFFERENCE 22 XXXX XXXX XXXX 90
NE - Glass 0 11 0.81 0
E - Glass 58 11 0.81 517 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 50 People X 0 CFM/Person 7
S - Glass 151 11 0.81 1345 2381 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 493
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.85
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3309
No. of Rows = 0
N - Wall 201 9 0.36 651 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 222 23 0.36 1838 'Min. cfm reqd. = 794
SE - Wall 0 23 0.36 0
S - Wall 493 21 0.36 3727
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 267 22 0.5500 3231
Glass Partition 354 17 0.55 3310
Partition glass-NAC 1027 17 0.30 5238
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 55 10 0.45 248
INTERNAL HEAT GAIN
People 50.0 Nos X 230 11500
Light 3571.5 W X 1.25 3.412 15179
Eq. Load 3571.5 WX 3.412 12186
ROOM SENSIBLE HEAT (RSH) 59486
Supply duct heat Supply duct Heat gain from 5 4461
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 2974
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
794 22 0.12 1.08 2263
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 69185
LATENT HEAT
People 50 Nos X 120 6000
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
794 90 0.12 0.68 5829
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 11829
EFFECTIVE ROOM TOTAL HEAT (ERTH) 81013
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
794 22 0.88 1.08 16595
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
794 90 0.88 0.68 42744
HEAT SUB TOTAL 140352
Return duct heat HP Pump + Dehum. & Pipe 5.0 7018
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 12.28 TR
TONS 12.28 TOTAL HEAT 147369
SHANNAYA HOSPITAL AC LOAD SUMMERY - GROUND FLOOR

MAINTAIN MAINTAIN MAINTAIN


SL.NO. FLOOR LOCATION AREA Dehumidified AC Load OCCUPANCY ROOM ROOM RELATIVE FRESH AIR LIGHTING EQ. LOAD UNIT TYPE
(Sqft) CFM (TR) HEIGHT TEMP IN HUMIDITY CFM LOAD W/SQ.FT
(FT) (F) IN (%) W/SQ.FT.

1 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 AHU
2 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 CASSETTE
3 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 HI WALL
4 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 HI WALL
5 FIRST AKD & NURSE STATION 1432 4050 9.4 16 10.0 72 55 477 1.5 1.5 HI WALL